This document is a Trane Rental Services product catalog for Voyager Packaged DX Air Conditioning units, detailing comprehensive technical specifications for multiple air conditioning models ranging from 25 to 80 tons. The catalog covers various configurations including electric heat, hot gas reheat, and multiple refrigerant circuit options, with models designed for different airflow requirements and operating conditions ranging from 0°F to 115°F. Key features across models include variable frequency drive (VFD) fans, economizer controls, BACnet interface capabilities, electric reheat options, and compliance with environmental and safety standards.

The catalog provides extensive technical data for each model, including electrical specifications, airflow characteristics, cooling capacities, heating performance, sound levels, and operating clearances. Models are categorized by size (25, 35, 50, and 80 tons) and include variants with different electrical configurations, such as CSDX (standard), RSDX (rental), and CSHX (high static) units. Each model listing includes detailed tables covering general data, electrical parameters, airflow specifications, dimensions, weights, cooling capacities at various ambient temperatures, and sound data, enabling precise selection for specific rental and temporary cooling requirements.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Trane Rental Services Packaged DX Air Conditioning

June 2024 TEMP-PRC001A-EN

Product Catalog

Introduction Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

Important Environmental Concerns Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.

Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

The three types of advisories are defined as follows:

WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

NOTICE Indicates a situation that could result in equipment or property-damage only accidents.

WARNING

Proper Field Wiring and Grounding Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

©2024 Trane TEMP-PRC001A-EN

Introduction Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks All trademarks referenced in this document are the trademarks of their respective owners.

Revision History Added General Data, Electrical Data, Features, Airflow Data, Dimensions and Weights Data, Operating Clearance, Fan Curve, Gross Cooling Capacities, and Unit Drawing for RSDX0025F7AA-AK, RSDX0035F6AB-AF, RSDX0050F6AA-AJ, RSHX0035F4AA-AO, and RSHX0050F4AA-AJ.

WARNING

Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury.

Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

• Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.

• When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.

• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC

FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY

RATED FOR INTENDED VOLTAGE.

WARNING

Follow EHS Policies!

Failure to follow instructions below could result in death or serious injury.

• All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.

• Non-Trane personnel should always follow local regulations.

TEMP-PRC001A-EN 3

Table of Contents

4 TEMP-PRC001A-EN

Overview

Application Considerations Ventilation Controls Dehumidification/Reheat Modulating Hot Gas Reheat Flexible Rental Duct Additional Considerations

Quick Equipment Overview

Voyager™ with Electric Heat Model: CSDX0025F3 Model: CSDX0025F4DE-EB Model: CSDX0025F4ED-GL Model: CSDX0025F5 Model: RSDX0025F7AA-AK Model: CSDX0035F0 Model: CSDX0035F6 Model: RSDX0035F6AB-AF Model: CSDX0050F0 Model: CSDX0050F4 Model: CSDX0050F6 Model: RSDX0050F6AA-AJ Model: CSHX0035F3 Model: CSHX0035F4 Model: RSHX0035F4AA-AO Model: CSHX0050F3 Model: CSHX0050F4 Model: RSHX0050F4AA-AJ Model: RSHX0080

TEMP-PRC001A-EN 5

Overview This catalog should be only be used as a reference for Trane Rental Services Voyager™ air conditioners to determine size limitations, available power, or lifting requirements. Verify the following with Trane Rental Services:

• Dimensions/weights and control options for the specific rental unit before equipment is shipped to a job site.

• Confirm adequate power is available for each Voyager unit.

• If additional information is required, reference the product catalog and/or installation manual.

Contact Trane Rental Services 24/7 for availability of all equipment (including: flex duct, electrical cable, transformers, etc.) prior to obtaining a purchase order from the customer. Equipment is available on a first-come, first-served basis, and can be reserved for three days with a signed Rental Agreement.

Application Considerations Ventilation Economizing

Most standard units (CSDX) are equipped with a 0 to 100 percent dry bulb controlled economizer (see “Quick Equipment Overview,” p. 8). A return duct inlet must be left open and a manual damper should be used when introducing fresh air to a machine without an economizer.

100% Outside Air

• Standard units (CSDX) nominally operate to the standard 400 cfm/ton, and can only achieve a

15°F to 25°F temperature differential across the coil, while maintaining a usable external static pressure.

• When the outdoor ambient temperature is high, units cannot provide the discharge air temperatures required to maintain a space at comfortable temperatures.

• High static units (CSHX and RSHX) are nominally designed to provide 200 cfm/ton at a much higher external static pressure.

• They are able to achieve 25°F to 35°F temperature differential across the cooling coil (dependent on latent load).

• This makes them more suitable to maintain typical space temperatures at a relatively high ambient temperature.

Controls Setpoint

Adjust the CSDX and CSHX setpoint using the unit mounted return air sensor or the provided remote sensor included with a 50 foot lead wire.

Adjust the RSHX0080 setpoint using the unit mounted return air sensor or the supply air sensor with an onboard PLC control.

Another option is to use a remote wireless thermostat. Place this inside the space, up to 100 feet away from the unit.

Communications If BACnet® or LonTalk® is required on *SDX and *SHX units, contact Trane Rental Services.

RSHX0080 units do not include a remote communications option and are local control only.

Airflow

• 25 ton F3 and F5 units do not have a VFD or an electronic method to modulate cfm.

• 25 ton F4 and F7 feature VFD for VAV/static pressure reset applications.

• 35 to 50 tons F0-F6 feature a VFD for VAV/static pressure reset applications.

• The default static pressure setpoint programmed into the VFD corresponds to the pressure differential between fan discharge pressure and atmospheric pressure.

Note: Trane Rental Services models are configured as constant volume with fan speed adjustment performed with an on-board setpoint. If VAV mode is required, contact Trane Rental Services.

• 35 to 50 tons high static units are not suitable for VAV/static reset or to achieve a wide variety of airflows. If a cfm setpoint is programmed, the fan speed will modulate to maintain that cfm, regardless of static pressure. Only the cfm setting can be changed.

6 TEMP-PRC001A-EN

Application Considerations Dehumidification/Reheat All rental packaged units can operate in electric reheat mode (except CSDX0025F5, RSDX0035F6 and RSDX0050F6) see “Quick Equipment Overview,” p. 8. This operating mode includes compressors, fans, and a portion of the electric heat in the unit. This allows the cooling coil to continue condensing moisture out of the supply air, while reheating it to minimize the amount of overcooling of the conditioned space.

Modulating Hot Gas Reheat

• 35 and 50 tons F6 DX units include hot gas reheat.

• The colder the air, the less moisture it contains. With hot gas reheat, hot refrigerant gas leaving the compressor is diverted to a hot gas reheat coil. The cold air leaving the DX coil is reheated to an acceptable temperature and returned as dehumidified air to the facility space.

• Modulating hot gas reheat helps maintain both temperature and humidity levels in cooling mode, while reducing unit operating costs and saving energy.

• Standard modulating hot gas reheat requires a call for cooling to initiate. If there is no call for cooling, and a need for dehumidification, use another electric reheat.

Flexible Rental Duct Rental duct is not insulated and can gain/lose heat along duct path. When planning the job, consider the length and path of flexible duct. For high static units, excess duct lengths across hot blacktops or roofing can have a negative impact on cooling ability.

The recommended maximum duct lengths for units do not take into consideration existing duct systems.

If connecting flex duct to customer duct for additional distribution, consider the specified static pressure needed to push air through. Add this to the friction losses through the flexible duct to determine the total amount of external static pressure required.

Important: If running return ducts on a high static unit, rental duct is collapsible and may cinch closed if put under high enough negative pressure.

If collapsing return duct occurs, see the following options:

• Straighten the duct path by pulling duct taut and secure with wire or twine with provided nylon tabs and grommets.

• For turns, consider using hard elbows (not provided).

• Introduce fresh air to reduce the negative pressure in the return section of the unit.

Additional Considerations For additional information and specific unit considerations, contact Trane Rental Services.

TEMP-PRC001A-EN 7

8 TEMP-PRC001A-EN

Quick Equipment Overview

Heat Size and Type Electric Re-heat

Hot Gas Reheat

Economizer (0-100% Dry Bulb Control)

VFD with VAV Operation

VFD with Constant Volume Operation

Zone Temperature Input Selector

CSDX0025F3 54 kW - Electric Yes No Yes No No Yes

CSDX0025F4 72 kW - Electric Yes No No Yes Yes Yes

CSDX0025F5 200 MBH - Gas No No No No No Yes

RSDX0025F7 72 kW - Electric Yes No No Yes Yes Yes

CSDX0035F0 90 kW - Electric Yes No Yes Yes No No

CSDX0035F6 90 kW - Electric Yes Yes Yes Yes Yes Yes

RSDX0035F6 90 kW - Electric No Yes Yes Yes Yes Yes

CSDX0050F0 108 kW - Electric Yes No Yes Yes No No

CSDX0050F4 108 kW - Electric Yes No Yes Yes Yes Yes

CSDX0050F6 108 kW - Electric Yes Yes Yes Yes Yes Yes

RSDX0050F6 108 kW - Electric No Yes Yes Yes Yes Yes

CSHX0035F3 90 kW - Electric Yes No No No Yes No

CSHX0035F4 90 kW - Electric Yes No Yes No Yes Yes

RSHX0035F4 90 kW - Electric Yes No Yes No Yes Yes

CSHX0050F3 108 kW - Electric Yes No No No Yes No

CSHX0050F4 108 kW - Electric Yes No Yes No Yes Yes

RSHX0050F4 108 kW - Electric Yes No Yes No Yes Yes

RSHX0080F0 162 kW - Electric Yes No No No Yes Yes

Voyager™ with Electric Heat Model: CSDX0025F3 Features

• 0 to 100 percent Economizer, Dry Bulb Control

• Constant Volume Fan with Field Adjustable Sheave

• Hinged Service Access

• Electric Heat with Reheat Option

• Phase and Under/Over Voltage Protection

• Series 16 Cam Type Electrical Connections

• Unit Mounted Thermostat with Remote Option

• Trane BACnet® Control Interface RS-485 MS/TP and Remote Monitoring Available Upon Request

• Clogged Filter Switch Kit

• Hot Gas Bypass

• Manual Supply Air Dampers

• Two Stage Cooling and Heating

• Low Ambient Operation Down to 0°F

• ReliaTel™ Trane Controls

Table 1. General data - CSDX0025F3

Labels Value Nominal Cooling Tons(a) 25

Heating Capacity 54 kW

Refrigerant R-410A

Number of Refrigerant Circuits 2

Number of Compressors 2

Ambient Operating Conditions 0°F – 115°F

(a) Design Conditions: 95°F Ambient, 80°F EDB, 71°F EWB, 400 CFM/Ton.

Table 2. Electrical data – circuit breaker style disconnect - CSDX0025F3

Labels Value Number of Electrical Circuits 1

Voltage 460V 3 Phase

Frequency 60 Hz

Wire Connection Type Series 16 Cam Type Connections or Hardwire (Maximum 350 MCM)

SCCR 5000 A

Minimum Circuit Ampacity (MCA) 101 A

Maximum Overcurrent Protection (MOP) 125 A

Cooling Only FLA 54 A

Heating Only FLA 78.9 A

Electric Reheat (27 kW Electric Heat + All Cooling) FLA 87.9 A

TEMP-PRC001A-EN 9

Table 3. Airflow data - CSDX0025F3

Labels Value Supply Motor 7.5 HP

Nominal CFM 10,000

Minimum/Maximum CFM 7,000 – 11,000

Maximum ESP at Nominal CFM 0.75 in.

Supply Air Connection Qty/Size (2) 20 in.

Return Air Connection Qty/Size (2) 20 in.

Merv-7 Throwaway Filter Qty/Size (6) 20 in. x 20 in. x 2 in.

Maximum Supply/Return Duct Run at Minimum CFM 175 ft.

Maximum Supply/Return Duct Run at Maximum CFM 50 ft.

Table 4. Dimensions and weights - CSDX0025F3

Labels Value Length 14 ft. 8.4 in.

Width 8 ft. 6 in.

Height 5 ft. 10 in.

Shipping Weight 4,700 lbs

Fork Pocket Dimensions 9.25 in. x 5.25 in. x 8 ft.

Center to Center Distance of Fork Pockets 63.25 in.

Notes:

• Lifting Device: Forklift or crane.

• Confirm all dimensions and weights with TRS turnkey facility because this data might not match what is listed in this document.

• For additional installation information, see RT-SVX25*-EN.

Table 5. Operating clearances - CSDX0025F3

Labels Value Condenser Coil End 4 ft. 0 in.

Economizer End (if equipped) 5 ft. 8 in.

Front (Control Panel) 5 ft. 0 in.

Back (Supply/Return Duct Connections) 3 ft. 0 in.

Top No Obstructions

Note: Operating clearances are provided based on single machine, above ground. For multiple unit or pit operation, contact Trane Rental Services.

10 TEMP-PRC001A-EN

Table 6. External static pressure – CSDX0025F3

External Static Pressure (in H2O)

CFM

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4

CFM

ESP

Subtraction (in

H2O)

54 kW Heat 7000 - - - - - - - - 7000 0.10

7500 - - - - - - - - 892 7500 0.11

8000 - - - - - - - - 891 911 8000 0.13

8500 - - - - - - - - 895 913 932 8500 0.14

9000 - - - - - - - 887 904 921 938 955 9000 0.15

9500 - - - - - - 882 889 915 932 949 965 981 9500 0.16

10000 - - - - - - 896 912 929 945 10000 0.18

10500 - - - - 891 908 - - 10500 0.19

11000 - - 885 - - - - - 11000 0.22

Notes:

1. Assumes 2-inch MERV 7 filters (factory provided).

2. Subtract 0.01 inch from ESPs if using 2-inch MERV 13 filters (customer provided).

Table 7. Fan data – CSDX0025F3

Turns Open

Sheave Adjustment 6 5 4 3 2 1

Fan RPM 806 844 882 920 958 994

TEMP-PRC001A-EN 11

Table 8. Gross cooling capacities – CSDX0025F3

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 85 95 105

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.4 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1 80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 272.1 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0 85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7 90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2

75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7 80 263.5 262.1 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3 85 270.1 270.1 295.0 264.3 322.1 207.6 250.9 250.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7 90 285.1 285.1 292.4 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7

75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8 80 268.4 266.9 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0 85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9 90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 282.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6

10000

75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9 80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8 85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4 90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4

11000

75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.1 80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5 85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8 90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 115 120 125

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8 - - - - 236.0 85.9 80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7 - - - - 236.2 125.8 85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3 - - - - 236.6 165.5 90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7 - - - - 233.8 204.9

75 223.7 209.8 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 244.8 91.5 - - 227.8 148.2 236.9 87.5 80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1 - - 228.0 193.2 237.3 133.1 85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4 - - 227.6 227.1 238.0 178.6 90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3 - - 231.1 231.1 238.0 223.4

75 226.8 221.7 249.1 164.3 257.8 96.3 214.5 213.9 234.7 159.8 245.1 92.1 - - 229.5 156.9 - - 80 230.0 227.3 249.1 214.9 258.8 148.2 220.4 220.4 234.8 210.7 246.2 144.0 - - 229.6 207.4 - - 85 242.4 239.8 248.5 248.1 259.6 199.7 231.9 231.9 234.3 233.9 247.0 195.5 - - 229.1 228.7 - - 90 252.9 251.0 253.0 253.0 259.8 250.6 241.7 241.7 241.8 241.8 247.3 245.5 - - 233.9 233.9 - -

10000

75 229.3 223.8 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7 - - 80 235.2 232.2 250.9 229.1 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7 - - 85 247.3 244.8 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.6 230.3 230.3 230.4 230.4 - - 90 256.6 255.0 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2 - -

11000

75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1 - - - - 80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.2 224.1 224.1 - - - - 85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5 - - - - 90 258.7 258.7 258.8 258.8 264.9 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7 - - - -

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total Gross Capacity.

3. SHC = Sensible Heat Capacity.

12 TEMP-PRC001A-EN

Unit Drawings – CSDX0025F3

Table 9. Electric heating performance – CSDX0025F3

CFM Temp Rise (°F) 7000 24.0

8000 21.0

9000 19.0

10000 17.0

11000 15.5

Table 10. Sound data – CSDX0025F3

Sound Path (Hz) 63 125 250 500 1K 2K 4K 8K Ducted Discharge (dB) 95 88 79 80 80 80 80 74

Ducted Inlet (dB) 93 84 79 70 70 71 71 67

Outdoor Noise (dB) 102 89 93 94 92 87 83 75

TEMP-PRC001A-EN 13

Model: CSDX0025F4DE-EB Features

• Hot Gas Bypass

• Incoming/Outgoing Power Daisy Chain Capable

• Phase and Under/Over Voltage Protection

• ReliaTel™ Trane Controls

• Hinged Service Access

• Electric Heat with Reheat Option

• Series 16 Cam Type Electrical Connections

• Low Ambient Down to 0°F

• Two Stage Cooling and Heating

• Unit Mounted Thermostat with Remote Option

• Blower VFD with across the Line Bypass and Speed Adjustment Potentiometer

(VAV Mode Available Upon Request)

• Trane BACnet® Control Interface RS-485 MS/TP (Remote Monitoring Available Upon Request)

• Clogged Filter Switch

Table 11. General data – CSDX0025F4DE-EB

Labels Value Nominal Cooling Tons(a) 25

Heating Capacity 72 kW

Refrigerant R-410A

Number of Refrigerant Circuits 2

Number of Compressors 2

Ambient Operating Conditions 0°F – 115°F

(a) Design Conditions: 95°F Ambient, 80°F EDB, 71°F EWB, 400 CFM/Ton.

Table 12. Electrical data – circuit breaker style disconnect – CSDX0025F4DE-EB

Labels Value Number of Electrical Circuits 1

Voltage 460V 3 Phase

Frequency 60 Hz

Wire Connection Type Series 16 Cam Type Only

SCCR 5000 A

Minimum Circuit Ampacity (MCA) 110.9 A

Maximum Overcurrent Protection (MOP) 125 A

Cooling Only FLA 48.9 A

Heating Only FLA 101.5 A

Electric Reheat (36 kW Electric Heat + All Cooling) FLA 94.1 A

14 TEMP-PRC001A-EN

Table 13. Airflow data – CSDX0025F4DE-EB

Labels Value Supply Motor 7.5 HP

Nominal CFM 10,000

Minimum/Maximum CFM 7,000 – 11,000

Maximum ESP at Nominal CFM 1.25 in.

Supply Air Connection Qty/Size (2) 20 in.

Return Air Connection Qty/Size (2) 20 in.

Merv-7 Throwaway Filter Qty/Size (8) 20 in. x 25 in. x 2 in.

Maximum Supply/Return Duct Run at Minimum CFM 350 ft.

Maximum Supply/Return Duct Run at Maximum CFM 75 ft.

Table 14. Dimensions and weights – CSDX0025F4DE-EB

Labels Value Length 10 ft. 11.5 in.

Width 7 ft. 11.625 in.

Height 5 ft. 4.125 in.

Shipping Weight 3,790 lbs

Fork Pocket Dimensions 7.625 in. x 2.625 in.

Center to Center Distance of Fork Pockets 32 in.

Notes:

• Lifting Device: Forklift or crane.

• Confirm all dimensions and weights with TRS turnkey facility because this data might not match what is listed in this document.

• For additional installation information, see RT-SVX25*-EN.

Table 15. Operating clearances – CSDX0025F4DE-EB

Labels Value Ends 4 ft.

Front (Control Panel) 5 ft.

Back (Supply/Return Duct Connections) 3 ft.

Top No Obstructions

Note: Operating clearances are provided based on single machine, above ground. For multiple unit or pit operation, contact Trane Rental Services.

TEMP-PRC001A-EN 15

Figure 1. Fan curve – CSDX0025F4DE-EB

16 TEMP-PRC001A-EN

Table 16. Gross cooling capacities – CSDX0025F4DE-EB

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 85 95 105

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.4 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1 80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 272.1 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0 85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7 90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2

75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7 80 263.5 262.1 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3 85 270.1 270.1 295.0 264.3 322.1 207.6 250.9 250.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7 90 285.1 285.1 292.4 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7

75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8 80 268.4 266.9 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0 85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9 90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 282.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6

10000

75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9 80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8 85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4 90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4

11000

75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.1 80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5 85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8 90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 115 120 125

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8 - - - - 236.0 85.9 80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7 - - - - 236.2 125.8 85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3 - - - - 236.6 165.5 90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7 - - - - 233.8 204.9

75 223.7 209.8 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 244.8 91.5 - - 227.8 148.2 236.9 87.5 80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1 - - 228.0 193.2 237.3 133.1 85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4 - - 227.6 227.1 238.0 178.6 90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3 - - 231.1 231.1 238.0 223.4

75 226.8 221.7 249.1 164.3 257.8 96.3 214.5 213.9 234.7 159.8 245.1 92.1 - - 229.5 156.9 - - 80 230.0 227.3 249.1 214.9 258.8 148.2 220.4 220.4 234.8 210.7 246.2 144.0 - - 229.6 207.4 - - 85 242.4 239.8 248.5 248.1 259.6 199.7 231.9 231.9 234.3 233.9 247.0 195.5 - - 229.1 228.7 - - 90 252.9 251.0 253.0 253.0 259.8 250.6 241.7 241.7 241.8 241.8 247.3 245.5 - - 233.9 233.9 - -

10000

75 229.3 223.8 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7 - - 80 235.2 232.2 250.9 229.1 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7 - - 85 247.3 244.8 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.6 230.3 230.3 230.4 230.4 - - 90 256.6 255.0 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2 - -

11000

75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1 - - - - 80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.2 224.1 224.1 - - - - 85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5 - - - - 90 258.7 258.7 258.8 258.8 264.9 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7 - - - -

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total Gross Capacity.

TEMP-PRC001A-EN 17

Unit Drawings – CSDX0025F4DE-EB

Table 17. Electric heating performance – CSDX0025F4DE-EB

CFM Temp Rise (°F) 7000 32.4

8000 28.3

9000 25.2

10000 22.7

11000 20.6

Table 18. Sound data – CSDX0025F4DE-EB

Sound Path (Hz) 63 125 250 500 1K 2K 4K 8K Ducted Discharge (dB) 94 88 78 80 79 79 79 74

Ducted Inlet (dB) 92 84 78 74 69 71 71 66

18 TEMP-PRC001A-EN

Model: CSDX0025F4ED-GL Features

• Hot Gas Bypass

• Series 16 Cam Type Electrical Connections

• Incoming/Outgoing Power Daisy Chain Capable

• Phase and Under/Over Voltage Protection

• ReliaTel™ Trane Controls

• Hinged Service Access

• Electric Heat with Reheat Option

• Low Ambient Down to 0°F

• Four Stage Cooling and Two Stage Heating

• Unit Mounted Thermostat with Remote Option

• Blower VFD with Line Bypass and Speed Adjustment Potentiometer

(VAV Mode Available Upon Request)

• Trane BACnet® Control Interface RS-485 MS/TP (Remote Monitoring Available Upon Request)

• Clogged Filter Switch

Table 19. General data – CSDX0025F4ED-GL

Labels Value Nominal Cooling Tons(a) 25

Heating Capacity 72 kW

Refrigerant R-410A

Refrigerant Charge(Ckt1/Ckt2) 11.8lbs/10.6lbs

Number of Refrigerant Circuits 2

Number of Compressors 2

Ambient Operating Conditions 0°F – 115°F

(a) Design Conditions: 95°F Ambient, 80°F EDB, 71°F EWB, 400 CFM/Ton.

Table 20. Electrical data – circuit breaker style disconnect – CSDX0025F4ED-GL

Labels Value Number of Electrical Circuits 1

Voltage 460V 3 Phase

Frequency 60 Hz

Wire Connection Type Series 16 Cam Type Only

SCCR 5000 A

Minimum Circuit Ampacity (MCA) 111.8 A

Maximum Overcurrent Protection (MOP) 125 A

Cooling Only FLA 50.7 A

Heating Only FLA 101.4 A

Reheat (36kW Electric Heat + All Cooling) FLA 95.9 A

TEMP-PRC001A-EN 19

Table 21. Airflow data – CSDX0025F4ED-GL

Labels Value Supply Motor 7.5 HP

Nominal CFM 10,000

Minimum/Maximum CFM 7,000 – 11,000

Maximum ESP at Nominal CFM 1.25 in.

Supply Air Connection Qty/Size (2) 20 in.

Return Air Connection Qty/Size (2) 20 in.

Merv-8 Throwaway Filter Qty/Size (12) 20 in. x 20 in. x 2 in.

Maximum Supply/Return Duct Run at 7000 CFM 650 ft.

Maximum Supply/Return Duct Run at 10,000 CFM 125 ft.

Table 22. Dimensions and weights – CSDX0025F4ED-GL

Labels Value Length 11 ft. 0.25 in.

Width 8 ft. 0.25 in.

Height 6 ft. 3.25 in.

Shipping Weight 3,700 lbs.

Fork Pocket Dimensions 7.625 in. x 3.625 in.

Center to Center Distance of Fork Pockets 32 in.

Notes:

• Lifting Device: Forklift or crane.

• Confirm all dimensions and weights with TRS turnkey facility because this data might not match what is listed in this document.

• For additional installation information, see RT-SVX25*-EN.

Table 23. Operating clearances – CSDX0025F4ED-GL

Labels Value Sides 48 in.

Front (Control Panel) 60 in.

Back (Supply/Return) 18 in.

Top No obstructions

Note: Operating clearances are provided based on single machine, above ground. For multiple unit or pit operation, contact Trane Rental Services.

20 TEMP-PRC001A-EN

Figure 2. Fan curve – CSDX0025F4ED-GL

Table 24. Electric heating performance – CSDX0025F4ED-GL

CFM Temp Rise (°F) 7000 32.4

8000 28.3

9000 25.2

10000 22.7

11000 20.6

Table 25. Sound data – CSDX0025F4ED-GL

CSDX0025F4ED-GL Sound Data

Sound Path (Hz) 63 125 250 500 1K 2K 4K 8K Ducted Discharge (dB) 94 88 78 80 79 79 79 74

Ducted Inlet (dB) 92 84 78 74 69 71 71 66

TEMP-PRC001A-EN 21

Table 26. Gross cooling capacities – CSDX0025F4ED-GL

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 85 95 105

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 265.0 218.8 289.1 175.7 308.5 103.5 251.6 209.8 273.9 168.5 292.2 98.3 237.1 200.1 257.7 160.6 274.8 92.5 80 272.6 243.7 290.1 213.7 312.6 162.9 259.1 233.6 275.1 205.1 296.2 156.0 244.6 222.8 259.1 195.8 278.8 148.4 85 282.6 263.5 295.9 241.5 316.7 204.5 268.8 252.4 280.9 231.7 300.2 196.1 254.0 240.6 264.8 221.2 282.7 187.1 90 293.9 279.9 304.6 263.0 320.8 234.9 279.7 268.1 289.2 252.2 304.2 225.4 264.4 255.6 272.9 240.8 286.7 215.3

75 273.3 229.9 295.7 185.4 324.1 111.8 259.1 220.1 279.8 177.5 306.4 105.9 243.9 209.7 262.8 168.9 287.8 99.3 80 281.8 255.9 298.0 224.7 324.2 172.6 267.6 245.0 282.2 215.4 306.7 165.0 252.3 233.5 265.5 205.3 288.3 156.6 85 292.5 276.6 304.7 253.7 324.2 215.6 278.0 264.7 288.9 243.1 307.0 206.4 262.5 252.2 272.1 231.9 288.7 196.7 90 304.5 293.8 314.1 276.0 329.2 247.0 289.5 281.2 298.1 264.5 311.9 236.8 273.5 268.0 281.0 252.4 293.6 225.9

75 280.1 239.6 301.0 193.8 327.8 118.7 265.2 229.1 284.3 185.2 309.4 112.0 249.3 218.0 266.6 175.8 290.0 104.7 80 289.6 266.7 304.4 234.4 329.1 181.0 274.7 255.1 288.0 224.3 310.9 172.6 258.7 242.8 270.5 213.5 291.7 163.6 85 301.1 288.3 312.1 264.4 330.3 225.2 285.9 275.7 295.6 253.1 312.3 215.4 269.6 262.5 278.1 241.2 293.3 204.9 90 313.7 306.3 322.3 287.7 336.3 257.8 297.9 293.0 305.5 275.5 318.3 246.8 281.2 279.0 287.7 262.6 299.2 235.1

10000

75 285.6 247.9 304.9 200.8 330.2 124.2 270.0 236.7 287.4 191.4 311.0 116.8 253.3 224.8 269.0 181.3 290.9 108.7 80 296.1 276.1 309.5 242.7 332.6 188.0 280.4 263.8 292.3 231.9 313.7 178.9 263.6 250.7 274.1 220.3 293.7 169.1 85 308.3 298.6 318.2 273.8 335.0 233.5 292.3 285.3 300.9 261.7 316.3 222.9 275.3 271.3 282.6 249.0 296.6 211.7 90 321.4 317.4 329.1 298.0 342.0 267.1 305.0 303.3 311.6 285.0 323.2 255.4 287.5 287.5 293.0 271.4 303.4 243.0

11000

75 289.7 254.9 307.3 206.5 331.1 128.3 273.3 243.0 289.2 196.3 311.2 120.2 255.9 230.3 270.0 185.5 291.5 111.3 80 301.1 284.2 313.2 249.6 334.7 193.7 284.7 271.1 295.2 238.0 315.1 183.8 267.2 257.3 276.3 225.8 294.4 173.2 85 314.1 307.6 322.8 281.8 338.3 240.4 297.4 293.5 304.8 269.0 318.9 229.1 279.6 278.8 285.8 255.6 298.4 217.1 90 327.9 327.1 334.5 306.9 346.3 275.1 310.7 310.7 316.3 293.2 326.8 262.7 292.5 292.5 297.0 278.8 306.2 249.5

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 115 120 125

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 221.7 189.7 240.4 152.0 256.4 85.9 213.6 184.3 231.5 147.5 246.8 82.4 205.2 178.7 222.2 142.8 237.0 78.7 80 229.1 211.3 242.1 185.8 260.3 140.1 220.9 205.2 233.2 180.5 250.7 135.7 212.6 199.1 224.1 175.1 240.8 131.1 85 238.2 228.2 247.7 210.1 264.2 177.4 229.9 221.7 238.8 204.3 254.6 172.3 221.4 215.1 229.6 198.2 244.7 167.0 90 248.2 242.4 255.6 228.7 268.1 204.4 239.7 235.5 246.5 222.4 258.4 198.7 230.9 228.5 237.2 215.9 248.5 192.8

75 227.7 198.6 244.9 159.6 268.2 92.0 219.2 192.8 235.5 154.6 258.0 88.1 210.5 186.8 225.9 149.6 247.5 84.0 80 236.1 221.2 247.7 194.6 268.8 147.6 227.6 214.8 238.5 189.0 258.7 142.8 218.8 208.3 229.0 183.2 248.4 137.9 85 245.9 239.0 254.3 220.0 269.5 186.2 237.3 232.2 245.0 213.8 259.5 180.8 228.4 225.2 235.5 207.4 249.2 175.1 90 256.5 254.0 262.9 239.5 274.3 214.3 247.7 246.8 253.5 232.9 264.3 208.2 238.5 238.5 243.9 226.0 254.0 202.0

75 232.4 206.1 247.9 165.7 269.7 96.6 223.5 200.0 238.2 160.5 259.1 92.4 214.4 193.6 228.2 155.0 248.3 87.9 80 241.7 229.8 252.0 202.0 271.5 153.8 232.8 223.0 242.4 196.0 261.0 148.6 223.7 216.1 232.5 189.9 250.3 143.3 85 252.3 248.5 259.5 228.5 273.4 193.7 243.3 241.3 249.9 221.9 263.0 187.8 234.1 233.9 240.0 215.2 252.4 181.8 90 263.5 263.5 268.9 249.0 279.2 222.8 254.3 254.3 259.1 241.9 268.8 216.4 244.8 244.8 249.1 234.7 258.1 209.8

10000

75 235.6 212.3 249.6 170.5 269.8 99.9 226.4 205.7 239.5 164.9 260.5 95.3 217.0 199.0 229.2 159.1 249.2 90.5 80 245.9 237.0 254.9 208.1 272.8 158.6 236.7 229.9 244.9 201.7 262.0 153.1 227.2 222.6 234.6 195.2 250.9 147.4 85 257.3 256.6 263.3 235.7 275.9 199.7 247.9 247.9 253.3 228.7 265.1 193.5 238.3 238.3 243.1 221.6 254.1 187.1 90 269.1 269.1 273.5 257.1 282.7 229.9 259.5 259.5 263.4 249.6 271.9 223.2 249.6 249.6 253.0 242.0 260.9 216.2

11000

75 237.5 217.0 249.9 174.0 271.0 101.8 228.0 210.1 240.5 167.9 261.3 96.8 218.1 203.0 229.8 161.7 252.3 91.6 80 248.8 242.8 256.3 212.8 274.0 162.0 239.2 235.3 246.0 206.1 263.6 156.1 229.3 227.7 235.4 199.2 253.4 150.1 85 260.9 260.9 265.8 241.4 277.0 204.4 251.2 251.2 255.4 234.1 265.9 197.9 241.2 241.2 244.8 226.6 254.5 191.1 90 273.3 273.3 276.7 263.8 284.7 235.7 263.3 263.3 266.2 256.0 273.6 228.5 253.1 253.1 255.4 248.0 262.2 221.2

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total Gross Capacity.

22 TEMP-PRC001A-EN

Unit Drawings – CSDX0025F4ED-GL

TEMP-PRC001A-EN 23

Model: CSDX0025F5 Features

• Incoming/Outgoing Power Daisy Chain Capable

• Constant Volume Fan with Field Adjustable Sheave

• Hinged Service Access

• Phase and Under/Over Voltage Protection

• Series 16 Cam Type Electrical Connections

• Unit Mounted Thermostat with Remote Option

• Trane BACnet® Control Interface RS-485 MS/TP and Remote Monitoring Available Upon Request

• Clogged Filter Switch Kit

• Hot Gas Bypass

• Manual Supply Air Dampers

• Two Stage Cooling and Heating

• Low Ambient Operation Down to 0°F

Table 27. General data – CSDX0025F5

Labels Value Nominal Cooling Tons(a) 25

Heating Capacity (Input/Output)(b) (c) 250/200 Mbh

Refrigerant R-410A

Number of Refrigerant Circuits 2

Number of Compressors 2

Ambient Operating Conditions 0°F – 115°F

(a) Design Conditions: 95°F Ambient, 80°F EDB, 71°F EWB, 400 CFM/Ton.

(b) Gas Heat – Machine will come with factory fitted gas valve to orifice plate only. Trane does not provide any gas piping, fittings, regulators required to connect to machine.

When gas heat is utilized, Trane start-up is required.

(c) Unit will ship from Trane ready to operate with Natural Gas. LP Kit available for field installation only. Unit must be returned to NG prior to returning the machine to TRS.

Table 28. Electrical data – circuit breaker style disconnect – CSDX0025F5

Labels Value Number of Electrical Circuits 1

Voltage 460V 3 Phase

Frequency 60 Hz

Wire Connection Type Series 16 Cam Type Only

SCCR 5000 A

Minimum Circuit Ampacity (MCA) 58.65 A

Maximum Overcurrent Protection (MOP) 70 A

Cooling Only FLA 54 A

Heating Only FLA 11.8 A

24 TEMP-PRC001A-EN

Table 29. Airflow data – CSDX0025F5

Labels Value Supply Motor 7.5 HP

Nominal CFM 10,000

Minimum/Maximum CFM 7,000 – 11,000

Maximum ESP at Nominal CFM 0.5 in.

Supply Air Connection Qty/Size (2) 20 in.

Return Air Connection Qty/Size (2) 20 in.

Merv-7 Throwaway Filter Qty/Size (8) 20 in. x 25 in. x 2 in.

Maximum Supply/Return Duct Run at Minimum CFM 175 ft.

Maximum Supply/Return Duct Run at Maximum CFM 50 ft.

Table 30. Dimensions and weights – CSDX0025F5

Labels Value Length 10 ft. 11.5 in.

Width 8 ft. 0 in.

Height 5 ft. 1.25 in.

Shipping Weight 3,600 lbs

Fork Pocket Dimensions 7.625 in. x 2.625 in.

Center to Center Distance of Fork Pockets 32 in.

Notes:

• Lifting Device: Forklift or crane.

• Confirm all dimensions and weights with TRS turnkey facility because this data might not match what is listed in this document.

• For additional installation information, see RT-SVX26*-EN.

Table 31. Operating clearances – CSDX0025F5

Labels Value Ends 4 ft.

Front (Control Panel) 5 ft.

Back (Supply/Return Duct Connections) 3 ft.

Top No Obstructions

Note: Operating clearances are provided based on single machine, above ground. For multiple unit or pit operation, contact Trane Rental Services.

TEMP-PRC001A-EN 25

Table 32. External static pressure – CSDX0025F5

External Static Pressure (Inches of Water) cfm

0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp 7.5-hp Standard Motor and Drive

7000 694 3.19 716 3.38 738 3.58 760 3.79 783 4.01

7500 704 3.57 725 3.76 746 3.94 767 4.15 787 4.36 807 4.57

8000 716 3.99 737 4.19 757 4.39 777 4.59 797 4.80 816 5.02 835 5.24

8500 705 4.16 728 4.42 750 4.67 770 4.89 790 5.11 808 5.30 827 5.53 846 5.75 864 5.98

9000 717 4.63 740 4.86 763 5.14 785 5.43 804 5.66 823 5.89 841 6.12 859 6.34 877 6.57

9500 752 5.38 777 5.68 799 5.97 818 6.23 838 6.50 856 6.76 874 7.00

10000 791 6.27 814 6.56 834 6.86 854 7.16 872 7.43

10500 828 7.23 850 7.55 869 7.80

11000 867 8.33

External Static Pressure (Inches of Water) cfm

1.10 1.20 1.30 1.40 1.50 rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp 7.5-hp Standard Motor and Drive

7000 805 4.24 827 4.74 849 4.69 869 4.91

7500 828 4.82 850 5.06 871 5.31

8000 853 5.46 873 5.72

10000

10500

11000

Notes:

1. Fan motor heat (MBh) = 3.15 x Fan bhp.

2. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

26 TEMP-PRC001A-EN

Table 33. Gross cooling capacities – CSDX0025F5

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 85 95 105

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.4 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1 80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 272.1 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0 85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7 90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2

75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7 80 263.5 262.1 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3 85 270.1 270.1 295.0 264.3 322.1 207.6 250.9 250.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7 90 285.1 285.1 292.4 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7

75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8 80 268.4 266.9 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0 85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9 90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 282.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6

10000

75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9 80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8 85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4 90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4

11000

75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.1 80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5 85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8 90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 115 120 125

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8 - - - - 236.0 85.9 80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7 - - - - 236.2 125.8 85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3 - - - - 236.6 165.5 90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7 - - - - 233.8 204.9

75 223.7 209.8 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 244.8 91.5 - - 227.8 148.2 236.9 87.5 80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1 - - 228.0 193.2 237.3 133.1 85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4 - - 227.6 227.1 238.0 178.6 90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3 - - 231.1 231.1 238.0 223.4

75 226.8 221.7 249.1 164.3 257.8 96.3 214.5 213.9 234.7 159.8 245.1 92.1 - - 229.5 156.9 - - 80 230.0 227.3 249.1 214.9 258.8 148.2 220.4 220.4 234.8 210.7 246.2 144.0 - - 229.6 207.4 - - 85 242.4 239.8 248.5 248.1 259.6 199.7 231.9 231.9 234.3 233.9 247.0 195.5 - - 229.1 228.7 - - 90 252.9 251.0 253.0 253.0 259.8 250.6 241.7 241.7 241.8 241.8 247.3 245.5 - - 233.9 233.9 - -

10000

75 229.3 223.8 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7 - - 80 235.2 232.2 250.9 229.1 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7 - - 85 247.3 244.8 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.6 230.3 230.3 230.4 230.4 - - 90 256.6 255.0 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2 - -

11000

75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1 - - - - 80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.2 224.1 224.1 - - - - 85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5 - - - - 90 258.7 258.7 258.8 258.8 264.9 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7 - - - -

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total Gross Capacity.

TEMP-PRC001A-EN 27

Unit Drawings – CSDX0025F5

Table 34. Gas heating performance – CSDX0025F5

CFM Temp Rise (°F) 7000 26.3

8000 23.0

9000 20.5

10000 18.4

11000 16.8

Table 35. Sound data – CSDX0025F5

Sound Path (Hz) 63 125 250 500 1K 2K 4K 8K Ducted Discharge (dB) 94 88 78 80 79 79 79 74

Ducted Inlet (dB) 92 84 78 74 69 71 71 66

Outdoor Noise (dB) 102 89 93 94 92 87 83 75

BACK

FRONT RIGHT

LEFT

59.75

28 TEMP-PRC001A-EN

Model: RSDX0025F7AA-AK Features

• Two Direct Drive Plenum Fans

• Series 16 Cam Type Electrical Connections

• Phase and Under/Over Voltage Protection

• Symbio 700 Trane Controls

• Hinged Service Access

• Electric Heat with Reheat Option

• Low Ambient Down to 0°F

• Four Stage Cooling and Two Stage Heating

• Unit Mounted Thermostat with Remote Option

• Variable Speed Evaporator Fans with EC motors

• Trane BACnet® Control Interface RS-485 MS/TP (Remote Monitoring Available Upon Request)

• Clogged Filter Switch

• RA Humidity Sensor for Dehumidification Electric Reheat

Table 36. General data – RSDX0025F7AA-AK

Labels Value Nominal Cooling Tons(a) 25

Heating Capacity 72 kW

Refrigerant R-410A

Refrigerant Charge 38.0 lbs

Number of Refrigerant Circuits 1

Number of Compressors 2

Ambient Operating Conditions 0°F – 125°F

(a) Design Conditions: 95°F Ambient, 80°F EDB, 71°F EWB, 400 CFM/Ton.

Table 37. Electrical data – circuit breaker style disconnect – RSDX0025F7AA-AK

Labels Value Number of Electrical Circuits 1

Voltage 460V 3 Phase

Frequency 60 Hz

Wire Connection Type Series 16 Cam Type Only

SCCR 65 kA

Minimum Circuit Ampacity (MCA) 147 A

Maximum Overcurrent Protection (MOP) 150 A

Cooling Only FLA 54.3 A

Heating + Aux Electric Heat FLA 144.8 A

Reheat (72kW Electric Heat + All Cooling) FLA 99.5 A

TEMP-PRC001A-EN 29

Table 38. Airflow data – RSDX0025F7AA-AK

Labels Value Supply Motor 7.5 HP

Nominal CFM 10,000

Minimum/Maximum CFM 7,500 – 12,000

Maximum ESP at Nominal CFM 1.70 in.

Supply Air Connection Qty/Size (2) 20 in.

Return Air Connection Qty/Size (2) 20 in.

Merv-8 Throwaway Filter Qty/Size (4) 20 in. x 24 in. x 2 in. and (4) 20 in. x 30 in. x 2 in.

Maximum Supply/Return Duct Run at 7500 CFM 500 ft.

Maximum Supply/Return Duct Run at 12,000 CFM 150 ft.

Table 39. Dimensions and weights – RSDX0025F7AA-AK

Labels Value Length 11 ft. 6 in.

Width 8 ft. 5 in.

Height 8 ft. 6 in.

Shipping Weight 4,900 lbs

Fork Pocket Dimensions 7.625 in. x 3.625 in.

Center to Center Distance of Fork Pockets 3 ft. 2 in.

Note: Lifting Device: Forklift or crane.

Table 40. Operating clearances – RSDX0025F7AA-AK

Labels Value Front (Control Panel) 60 in.

Back Side 36 in.

Left Side (Supply/Return) 68 in.

Right Side (Power Connection) 48 in.

Top No obstructions

Note: Operating clearances are provided based on single machine, above ground. For multiple unit or pit operation, contact Trane Rental Services.

30 TEMP-PRC001A-EN

Figure 3. Fan curve – RSDX0025F7AA-AK

Table 41. Electric heating performance – RSDX0025F7AA-AK

CFM Temp Rise (°F) 7500 30.35

9000 25.29

10000 22.76

11000 20.69

12000 18.97

Table 42. Sound data – RSDX0025F7AA-AK

Octave Center Frequency (Hz) 63 125 250 500 1K 2K 4K 8K Overall dBA 94 90 92 91 88 84 81 75 93

TEMP-PRC001A-EN 31

Table 43. Gross cooling capacities – RSDX0025F7AA-AK

Airflow cfm

Ent DB (°F)

Ambient Temperature (°F) 85 95 105

Entering Wet Bulb 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 247.4 201.9 273.9 155.7 301.5 107.9 233.5 194.4 258.6 148.2 284.3 100.4 218.8 186.5 242.5 140.4 266.0 92.7 80 250.4 238.1 275.3 193.8 303.1 146.3 237.0 230.3 260.1 186.3 286.4 138.9 222.9 222.1 244.0 178.5 268.8 131.3 85 260.5 260.5 276.6 231.8 304.4 184.4 248.4 248.4 261.7 224.4 288.0 177.1 235.4 235.4 245.9 216.7 270.5 169.5 90 274.9 274.9 280.0 267.7 305.4 222.4 262.5 262.5 265.6 260 289.1 215.2 249.2 249.2 250.6 250.6 271.7 207.6

75 255.6 222.5 281.6 167.6 308.2 111.2 241.2 214.9 265.7 160 290.4 103.8 225.8 207.0 248.8 152.1 271.5 96.0 80 261.5 261.5 283.1 212.5 310.7 156.6 248.1 248.1 267.3 204.9 293.4 149.1 234.5 234.5 250.5 197.0 275.0 141.4 85 276.3 276.3 285.7 257.7 312.3 201.6 263.1 263.1 270.3 250.3 295.1 194.2 249.1…