Y1DA--528A6-24-612 Connect PIVs to Fire Alarm System

Closed Solicitation Posted

Solicitation number
36C24226B0016
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 2, is soliciting construction services for installation, testing, and commissioning work to connect Post Indicator Valves (PIVs) to the fire alarm system at Bath VA Medical Center in Bath, New York. The project requires contractors to add system supervision and protection for 22 building-adjacent PIVs through radio-linked control relays, update the fire alarm system in Building 78 (Community Living Center) from a single zone to 11 zones, install voice alarm capabilities, and provide bollard protection for the valves. Key requirements include utilizing NICET-certified technicians with New York State Security and Fire Alarm Systems Installer's licenses, ensuring compliance with NFPA standards (1, 4, 13, 70, 72, and 101) and UFC standards, integrating with the existing Johnson Controls/Honeywell Verifire fire alarm system, and conducting 100% fire alarm system testing with government presence along with a 24-hour battery test prior to final commissioning. The solicitation indicates that evaluation will consider contractor qualifications, technical approach, and compliance with fire safety standards and federal acquisition regulations, including Buy American requirements. The Request for Information (RFI) deadline was December 9, 2025, at 4:00 PM EST, and sealed bids are due on December 22, 2025, at 12:30 PM EST for a virtual bid opening at 1:00 PM EST that same day.

This is a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside procurement with an estimated cost range of $250,000 to $500,000, with Johnson Controls identified as the current service contractor for the Bath VA facility. The project encompasses work across multiple buildings on the VA Medical Center campus, with a 180-calendar day performance period from the Notice to Proceed. Bidders must be registered in SAM.gov, verified as SDVOSB or VOSB in VetBiz.gov, and are classified under NAICS code 238210 (Electrical Contractors and Other Wiring Installation Contractors). Offerors are required to submit a bid bond, acknowledge all amendments, provide a Buy American Certification, submit a Limitations on Subcontracting certification, include an EMR rating, and potentially provide financial capability documentation such as a bank letter or Dun and Bradstreet report. The place of performance is Bath VA Medical Center, 76 Veterans Avenue, Bath, New York 14810, with work to be performed at this active patient care facility requiring careful coordination with nursing staff and the Bath Fire Department.

Notice text

2 versions

Update #2 · Latest ·

Project No. 528A6-24-612 Connect PIV s to Fire Alarm System

Bath VA Medical Center 76 Veterans Avenue Bath, NY 14810

The general scope of this project is for installation, testing, and commissioning services to add post indicator valve (PIV) system supervision and protection and update the fire zones and add voice alarms in building 78.

Existing Conditions

Post indicator valves (PIV s) previously installed with new station water system currently require manual inspection/supervision and system supervision will be added. These 22 valves are building adjacent and will be linked via radio to control relays in each building s fire alarm system. Most of these buildings are aging brick structures on grounds with many legacy underground systems around them. This makes wire/conduit trenches and internal wiring routing challenging. Changing conditions over time necessitate protecting some valves from equipment and vehicle impacts.

Building 78, the Community Living Center (CLC) is the onsite nursing home at the VA Medical Center (VAMC) located in Bath, New York. The current fire alarm system, 1 zone for building, does not support the current fire practice of 11 zones, 9 of which are living spaces, one for attic, one for crawlspace. This structure has been more recently remodeled, so has relatively easier structural access however is also a working patient nursing facility so work needs to be well planned and coordinated with nursing staff.

Current station fire system uses Johnson Controls/Honeywell Verifire programming and compon

Update #1 ·

Project No. 528A6-24-612

Connect PIV s to Fire Alarm System

Construction Services Statement of Work

Page 2 of 3

Bath VA Medical Center 76 Veterans Avenue Bath, NY 14810

The general scope of this project is for installation, testing, and commissioning services to add post indicator valve (PIV) system supervision and protection and update the fire zones and add voice alarms in building 78.

Existing Conditions

Post indicator valves (PIV s) previously installed with new station water system currently require manual inspection/supervision and system supervision will be added. These 22 valves are building adjacent and will be linked via radio to control relays in each building s fire alarm system. Most of these buildings are aging brick structures on grounds with many legacy underground systems around them. This makes wire/conduit trenches and internal wiring routing challenging. Changing conditions over time necessitate protecting some valves from equipment and vehicle impacts.

Building 78, the Community Living Center (CLC) is the onsite nursing home at the VA Medical Center (VAMC) located in Bath, New York. The current fire alarm system, 1 zone for building, does not support the current fire practice of 11 zones, 9 of which are living spaces, one for attic, one for crawlspace. This structure has been more recently remodeled, so has relatively easier structural access however is also a working patient nursing facility so work needs to be well planned and coordinated with nursing staff.

Current station fire system uses Johnson Controls/Honeywell Verifire programming and components.

Construction will include, but is not limited to:

Post Indicator Valve (PIV) bollard protection.

Removal, including underground portions, of existing bollards to be replaced.

Preparation of new bollard locations including survey for locations and conflicting underground utilities.

Installation of bollard protection.

Return of surrounding areas to project specified and/or previous conditions.

Some of these locations involve asphalt and concrete surfaces.

Support of post project documentation.

Installation and integration of post indicator valves (PIV) to fire control panel systems

Supply, installation and configuration of Potter radio switch and supporting communication equipment.

Connection to signaling line circuits (SLC) of Johnson Controls (JCI)/Honeywell fire alarm systems, to include wall penetrations, fire conduit, and panel installation.

This will include penetration and sealing of masonry walls.

Configuration and programming of existing station wide Johnson Controls Verifire based systems for new equipment.

Support of post project documentation.

Installation and integration of zone voice alarms into building 78 the community living center residence. Reconfiguration of single fire zone into 11, with 9 living areas

Supply, install, wire, and connect new fire control panels.

Supply, install, wire, and connect new annunciators.

Configure and program fire alarm system for new zoning and equipment in all panels and monitoring locations.

Ensure conditions around new equipment are restored similar to existing.

Support of post project documentation.

Safety Measures:

Review and incorporate risk assessment and interim life safety plans and measures into safety and construction planning.

Pre Construction Risk Analysis (PCRA) by VA

Interim Life Safety Measures (ILSM) by VA

Generate and follow a safety plan and incorporate risk and life safety assessments.

The Contractor shall supply:

All the materials, tools, labor, and supervision to complete this project as required on the contract drawings and in the specifications.

JCI/Honeywell Verifire software is required

JCI/Honeywell hardware is required

Potter Signalink hardware and software is required.

Contractor will adhere strictly to the plans and specifications unless directed otherwise by the CO in writing.

Contractor shall have 180 days from the Notice to Proceed to complete all work.

Communications and Standards

All contract direction, changes, financials, and contract performance are the responsibility of the VAMC Contracting Officer (CO).

Contracting Officers Technical Representative (COR) is responsible for day-to-day operations in project and the primary point of contact (POC) for project.

Communications to/from VAMC,

Technical communications, submittals, RFI s, change orders

On site visits for construction and sub-contractors

Construction coordination

Site work coordination

Project is required to use the Autodesk Construction Cloud Build Platform (ACC)

Bath VAMC will provide licensing, permissions, and online training for this cloud-based tool at no cost to contractors.

Contractor required to actively use Build on ACC for project documentation and coordination.

ACC is used for submittals, requests for information, project communications and documentation.

No contract financial information on ACC

No personal identification information on ACC.

Project must, at a minimum, be in accordance with

All federal, state, and local building and safety codes MUST be followed.

All work is to be completed as shown on the contract documents drawings and specifications unless otherwise directed by the facility/CO in writing.

Industry Construction Standards

National Fire Protection Association (NFPA),

Underwriters Laboratory,

International Building Code IBC 2003,

National Electric Code (NEC),

VA Information Security Handbook 6500.6, etc.

The C&A Information Technology requirements do not apply, and a Security Accreditation Package is not required.

VA supplies

Access and coordination with Bath VAMC station utilities and site

Licensing, permissions, and online training for Autodesk Construction Cloud Build (ACC).

Location on station, north of railroad tracks, for staging area, trailers, parking

Files

Show all 11

Notice history

Notice Type Posted
This notice Latest solicitation Solicitation
Y1DA--528A6-24-612 Connect PIVs to Fire Alarm System Original Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
Y1DA--Project620-22-110 Replace and Upgrade Fire alarm System at Montrose VAMC Department of Veterans Affairs Franklin D. Roosevelt VA Medical Center Montrose, New York 10548, United States · NAICS 238210 Veterans Integrated Service Network 2 Service-Disabled Veteran-Owned Small Business
Z1DA--Project # 528A6-26-607 Replace Flooring for Rm. 140 B76 | Bath VAMC NAICS 236220 Veterans Integrated Service Network 2 No set-aside
Z1DA--Upgrade Fire Alarm System Construction 676-22-110 Tomah, Wisconsin 54660, United States · NAICS 238210 Veterans Integrated Service Network 12 Service-Disabled Veteran-Owned Small Business
C1DA--NRM A/E- 528A7-27-112 Fire Alarm Panel Upgrade Department of Veterans Affairs Syracuse VA Medical Center Syracuse, New York 13210, United States · NAICS 541330 Veterans Integrated Service Network 2 No set-aside
Y1DA--NRM-CONST 528-CSI-102 Urology Equipment Site Prep | FY27 NRM Buffalo, New York 14215, United States · NAICS 236220 Veterans Integrated Service Network 2 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors