YTPM 25-0005 Repair ATCALS B5505- Asbestos Containing Material Survey.pdf
PDF 3 MB Posted
- Attached to
- SABER IDIQ Westover Air Reserve Base
- Solicitation number
- FA6606-26-R-0008
About this file
This is an Asbestos Containing Material (ACM) Survey Report for Building 5505 at Westover Air Reserve Base in Chicopee, Massachusetts, prepared by the U.S. Army Corps of Engineers Louisville District in August 2025. The survey was conducted on July 30, 2025, by EPA-accredited Asbestos Building Inspector and Management Planner Christian Elslager to support a planned renovation of the 1,214-square-foot, one-story masonry block building constructed in 1963. The inspector identified and sampled fifteen homogeneous areas (HAs) throughout the building's interior finishes, which included roofing materials, flooring, ceiling tiles, drywall, vinyl cove bases, caulks, and various adhesive materials. Laboratory analysis using polarized light microscopy (PLM) conducted by EMSL Analytical Laboratories identified asbestos in only one sample: HA-06, consisting of 12"x12" green vinyl composite tile with black mastic, which tested positive for 3% chrysotile in both the tile and mastic components. The remaining fourteen HAs tested negative for asbestos.
Prior to renovation of Building 5505, the identified asbestos-containing vinyl composite tile and mastic must be removed in accordance with Army Regulation 200-1, the U.S. Army Center for Public Works Technical Bulletin 420-70-8, USACE Engineer Pamphlet 1110-1-22, and all applicable federal, state, and local regulations. The report notes that in Massachusetts, a licensed asbestos project designer must design the abatement, a licensed asbestos abatement contractor must perform the work, and a licensed monitoring company must oversee the process. The survey was performed using AHERA protocols and EPA guidance, with all samples analyzed at an NVLAP-accredited laboratory. The report recommends that any additional suspect ACM discovered during future work be sampled and tested prior to renovation or demolition activities.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos Containing Material Survey Report Westover Air Reserve Base, Building 5505 AUGUST 2025
CHICOPEE, MA FINAL
PAGE i
DRAFT
ASBESTOS CONTAINING MATERIAL
SURVEY REPORT
WESTOVER AIR RESERVE BASE
BUILDING 5505
150 RADAR HILL ROAD
CHICOPEE, MA
Prepared For:
Westover ARB – Engineering Division 975 Patriot Avenue, Chicopee, MA 01022
Prepared By:
U.S. Army Corps of Engineers – Louisville District Engineering Division – Environmental Branch
600 Dr. Martin Luther King, Jr. Place Louisville, Kentucky 40202-2232
AUGUST 2025
PAGE ii
EXECUTIVE SUMMARY
The U.S. Army Corps of Engineers (USACE) Louisville District performed an Asbestos Containing Material (ACM) Survey at Building 5505, located on Radar Hill Road within the western portion of Westover Air Reserve Base (WARB) in Chicopee, MA. The ACM Survey was performed on 30 July 2025, and involved identification, assessment, and sampling of newly identified ACM and the preparation of this comprehensive ACM Survey report. The work was performed for the WARB Engineering Division to support a planned renovation of Building 5505. The work was performed by United States Environmental Protection Agency (USEPA) accredited Asbestos Building Inspector and USEPA accredited Asbestos Management Planner Christian Elslager, in accordance with the following regulations and standards:
• Army Regulation (AR) 200-1, “Environmental Protection and Enhancement,” dated 13 December 2007;
• AR 420-1, “Army Facilities Management,” dated 12 February 2008;
• Asbestos Hazard Emergency Response Act (AHERA) protocols published in
40 Code of Federal Regulations (CFR) Part 763, Subpart E, “Asbestos- Containing Materials in Schools”;
• USEPA Publication 700/B-92/001, “A Guide to Performing Re-inspections under the AHERA,” dated February 1992;
• U.S. Army Center for Public Works Technical Bulletin (PWTB) 420-70-8, “Installation Asbestos Management Program,” dated 23 March 1998; and
• USACE Engineer Pamphlet (EP) 1110-1-22, “Asbestos Surveys and Assessments – Standard Scope of Work,” dated 15 September 2000
The following is description of the inspected structure:
• Building 5505: Constructed in approximately 1963; 1,214 square feet (SF) footprint, one-story, masonry block construction, built slab-on-grade. The structure footprint is roughly “L” shaped with mechanical rooms occupying the southern portion of the building, a radio room occupying the northeast quarter of the building and the remainder consisting of offices and a restroom. Figure 1 (attached) depicts the structure footprint and sample locations. Interior finishes consisted of drywall, painted masonry, vinyl composite tile (VCT), carpet squares, sheet vinyl/linoleum, cellulose ceiling tile and bare concrete. Ethylene Propylene Diene Monomer (EPDM) flat roof.
The facility is located on the western portion of WARB, with Radar Hill Road adjoining to the south. The property slopes from north to south. A paved drive connects Building 5505 with the termination of Radar Hill Road to the west. A parking area occupies the portion of the property along the west side of Building 5505. A skeletal steel radar array was attached to the east side of Building 5505. The building vicinity consisted of grass-covered lawn.
PAGE iii
Homogeneous Areas
No previous Asbestos Inspections have been performed on Building 5505. The USACE inspector identified and sampled fifteen (15) separate Homogenous Areas (HA’s) during the 30 July 2025 ACM Survey. The identified HA’s were in good condition with relatively low exposure risk based on material characteristics (e.g. generally non-friable). The following is a summary of HA’s sampled:
• HA-01: Black Roofing Felt Paper
• HA-02: White EPDM Roofing Seam Sealant
• HA-03: EPDM Roofing with Foam Board and Felt Paper
• HA-04: Asphalt Tar on Roof Deck beneath EPDM Roofing
• HA-05: Brown Vinyl Cove Base with Yellow Glue
• HA-06: 12”X12” Green Vinyl Composite Tile with Black Mastic
• HA-07: White 2’X4’ Ceiling Tile
• HA-08: Drywall
• HA-09: Wood Patterned Linoleum
• HA-10: Tan Vinyl Cove Base with Yellow Glue
• HA-11: White Flexible Vinyl Tile with Black Mastic
• HA-12: White 2’X2’ Ceiling Tile
• HA-13: White Exterior Door Caulk
• HA-14: White Exterior Louver Hood Caulk
• HA-15: White Exterior Window Caulk
Throughout this report, Bold text indicates laboratory confirmed ACM.
Asbestos-Containing Materials
Only one of the HA’s sampled during the 30 July 2025 inspection was found to be ACM by laboratory analysis (HA-06 – 12”X12” Green VCT and Black Mastic). The samples were analyzed using polarized light microscopy (PLM) coupled with dispersion staining, as described in 40 CFR Part 763 and the National Emissions Standard for Hazardous Air Pollutants (NESHAPS), following EPA Method 600/R-93/116. The samples were analyzed at EMSL Analytical Laboratories (EMSL) under the NVLAP Lab Code 200188- 0 (Appendix C).
ACM may be present in additional areas not sampled or available to be sampled during the investigation, and it is recommended that an EPA AHERA accredited building inspector collect bulk samples of previously unsampled suspect ACM if encountered and have them tested and confirmed by recognized laboratory methods prior to any renovation and/or demolition of the buildings.
PAGE iv
Conclusions and Recommendations
All accessible areas of Building 5505 were inspected, and the current condition of ACM was assessed. One HA was indicated to be ACM (>1% asbestos) by laboratory analysis.
Prior to the proposed renovation of Building 5505, the affected ACM should be removed in accordance with Army Regulation(AR) 200-1, Environmental Protection and Enhancement, dated 13 December 2007; Department of the Army; U.S. Army Center for Public Works Technical Bulletin (PWTB) 420-70-8, Installation Asbestos Management Program, dated 23 Match 1998; Department of the Army, U.S. Army Corp of Engineers, Engineer Pamphlet (EP) 1110-1-22, Engineer and Design - Asbestos Survey and Assessments Standard Scope of Work, dated 15 September 2000; and applicable federal, state, and local regulations and standards.
TABLE OF CONTENTS
SECTION & TITLE PAGE NO.
TABLE OF CONTENTS
LISTS OF APPENDICES
APPENDICES
ACRONYMS AND ABBREVIATIONS
1.0 INTRODUCTION
1.1 Purpose of an Asbestos Containing Material Survey Report
1.2 ACM Definition
1.3 Regulated ACM
1.4 Abatement
2.0 ASBESTOS CONTAINING MATERIAL SURVEY APPROACH
3.0 SITE INFORMATION
3.1 Installation Name and Location
3.2 Facility Point of Contact
3.3 Inspection Information
3.4 Facility Building(s) Information
4.0 ASBESTOS SURVEY FINDINGS
4.1 Inspection and Sampling
5.0 CONCLUSIONS AND RECOMMENDATIONS
6.0 LIMITATIONS AND CERTIFICATIONS
7.0 POINTS OF CONTACT
LISTS OF APPENDICES
APPENDICES
Appendix A Asbestos Sample Analysis Summary Appendix B Laboratory Analytical Results and Chain-of-Custody Documentation Appendix C Laboratory Accreditations and Personnel Certifications Appendix D Sample Location Drawings Appendix E Photographic Documentation
ACRONYMS AND ABBREVIATIONS
ACM Asbestos Containing Material(s)
AHERA Asbestos Hazard Emergency Response Act
CFR Code of Federal Regulations
CMU Concrete Masonry Unit
EPA Environmental Protection Agency
HA Homogeneous Area
LF Linear Feet
NESHAP National Emissions Standards for Hazardous Air Pollutants
NVLAP National Voluntary Laboratory Accreditation Program
PLM Polarized Light Microscopy
PWTB Public Works Technical Bulletin
SF Square Feet
US United States
USACE United States Army Corps of Engineers
VCT Vinyl Composite Tile
MA Massachusetts
1.0 INTRODUCTION
The U.S. Army Corps of Engineers (USACE) Louisville District has performed this Asbestos Containing Material (ACM) Survey at Building 5505, located on Radar Hill Road within the western portion of Westover Air Reserve Base (WARB) in Chicopee, MA and is hereafter referred to as the “Property”. The purpose of this ACM Survey was identification, assessment, and sampling of suspect ACM and preparation of a comprehensive ACM Survey report. The ACM Survey was performed on 30 July 2025 by accredited inspector/management planner Christian Elslager. This effort is being conducted to support a planned renovation of the facility.
The following is description of the inspected structure:
• Building 5505: Constructed in approximately 1963; 1,214 square feet (SF) footprint, one-story, masonry block construction, built slab-on-grade. The structure footprint is roughly “L” shaped with mechanical rooms occupying the southern portion of the building, a radio room occupying the northeast quarter of the building and the remainder consisting of offices and a restroom. Figure 1 (attached) depicts the structure footprint and sample locations. Interior finishes consisted of drywall, painted masonry, vinyl composite tile (VCT), carpet squares, sheet vinyl/linoleum, cellulose ceiling tile and bare concrete. EPDM flat roof.
1.1 Purpose of an Asbestos Containing Material Survey Report
Westover ARB requires a comprehensive asbestos inspection of Building 5505 in preparation for a planned renovation. The intent of the ACM Survey is to evaluate the building for ACM that requires abatement prior to renovation.
There is a known link between the inhalation of asbestos fibers and various diseases such as asbestosis, mesothelioma, lung and other cancers. As a result, the Asbestos Hazard Emergency Response Act (AHERA), published in 40 Code of Federal Regulations (CFR) Part 763, Asbestos-Containing Materials In Schools, was enacted in 1986 and specifically to address asbestos in schools. An AHERA inspection requires an accredited inspector to visually inspect and assess the condition of all known or assumed asbestos-containing building materials, touch it to determine friability, and identify homogeneous areas of materials. There is no requirement for facility re-inspection for non-school buildings in AHERA. The National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 CFR Part 61 Subpart M enacted 1984 April 5, unless otherwise noted, require thorough inspections for asbestos in structures before renovation or demolition. Army regulation (AR) 200-1 dated 2007 December 12, Environmental Protection and Enhancement, Section 9.2 states “Army installations will perform an exposure assessment and risk assessment for all locations containing asbestos.”
1.2 ACM Definition
The United States Environmental Protection Agency (USEPA), per the Title 40 Code of Federal Regulations (CFR) Part 61, Subpart M, defines an ACM as a material that contains one percent (1%) or more asbestos using polarized light microscopy (PLM).
The confirmed or assumed ACM within each HA are to be categorized based on the friability of the material. The categories of regulated ACM are described as follows:
• Friable ACM – any material containing more than 1 percent asbestos, as determined by PLM analysis, and that can be crumbled, pulverized, or reduced to powder under hand pressure when dry.
• Category I non-friable ACM – packing material, gaskets, resilient floor covering (except vinyl sheet flooring products), and asphalt roofing products that contain greater than 1 percent asbestos.
• Category II non-friable ACM – any material, except for Category I Non-friable ACM, that contains greater than 1 percent asbestos and cannot be reduced to powder by hand pressure when dry.
1.3 Regulated ACM
According to USEPA’s National Emissions Standards for Hazardous Air Pollutants (NESHAP) regulation Asbestos-Containing Materials Guidance USEPA-340/1-90-018 (USEPA, December 1990) for building renovations and demolitions, ACM becomes regulated if the ACM is:
1. Friable
2. Category I non-friable ACM that is in poor condition and becomes friable
3. Category I or II non-friable ACM that will be or has been subjected to sanding, grinding, cutting and/or abrading
4. Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized and/or reduced to powder by the forces expected to act on the material in the course of demolition or building renovation operations. Further, Category II non-friable ACM (e.g., cement siding and transite board shingles) subjected to intense weather conditions such as thunderstorms, high winds and/or prolonged exposure to high heat and humidity may become "weathered" to a point where they become friable.
1.4 Abatement
According to NESHAP (40 CFR § 61.145), friable or potentially friable ACM that will be disturbed and/or has the potential to be disturbed during renovation must be removed.
A licensed asbestos inspector should be consulted prior to any renovation operations in a building or other structure containing ACM.
In Massachusetts (MA) regulated structures:
1. A MA-licensed asbestos project designer shall design the asbestos abatement.
2. A MA-licensed asbestos abatement contractor shall perform the abatement.
3. A MA-licensed company shall monitor the abatement.
2.0 ASBESTOS CONTAINING MATERIAL SURVEY APPROACH
The ACM Survey was performed in accordance with the AHERA protocols published in 40 CFR Part 763, “Asbestos-Containing Materials In Schools”; the U.S. Environmental Protection Agency (EPA) publication 700/B-92/001, “A Guide to Performing Re- Inspections under AHERA”, EPA Publication 700/B-92/001, dated 1992 February; and pursuant to the applicable requirements of the U.S. Army Center for Public Works Technical Bulletin No. 420-70-8, Installation Asbestos Management Program dated 1998 March. This ACM Survey was performed to prepare for a planned renovation of the building.
• Document Review - A review of previously completed asbestos inspection reports and/or abatement reports and information concerning facility construction, maintenance, and management history. No prior ACM Surveys have been performed on Building 5505; therefore, no document review was incorporated into this scope of work.
• Inspection - A facility walk-through and visual survey to inspect and assess ACMs.
Photographic documentation, located in Appendix E, was used to document the current condition of suspect ACM.
• Sampling – Samples were collected from suspect materials and submitted for laboratory analysis according to appropriate methods and procedures.
3.0 SITE INFORMATION
3.1 Installation Name and Location
Facility Name: Building 5505
Facility ID Number: 5505
Facility Address: 150 Radar Hill Road, WARB, Chicopee, MA 01022
3.2 Facility Point of Contact
Facility Point of Contact: Richard Colburn
Point of Contact Title: Chief of Design
Point of Contact Phone: (413) 557-2433
Point of Contact Email: richard.colburn.1@us.af.mil
3.3 Inspection Information
Inspector/Management Planner: Christian Elslager
Inspector License Number and Expiration Date of License EPA: Indiana Department of Environmental Management, Asbestos Inspector License #19A012555
Affiliation: U.S. Army Corps of Engineers, Louisville District (LRL)
Address: 600 Dr. Martin Luther King Jr. Place Louisville, KY 40201-0059
Phone Number: (502) 315-7083
Email: christian.j.elslager@usace.army.mil
Inspection Date(s): 30 July 2025 mailto:richard.colburn.1@us.af.mil mailto:christian.j.elslager@usace.army.mil
3.4 Facility Building(s) Information
Building 5505: Constructed in approximately 1963; 1,214 square feet (SF) footprint, one-story, masonry block construction, built slab-on-grade. The structure footprint is roughly “L” shaped with mechanical rooms occupying the southern portion of the building, a radio room occupying the northeast quarter of the building and the remainder consisting of offices and a restroom. Figure 1 (attached) depicts the structure footprint and sample locations. Interior finishes consisted of drywall, painted masonry, vinyl composite tile (VCT), carpet squares, sheet vinyl/linoleum, cellulose ceiling tile and bare concrete. EPDM flat roof.
4.0 ASBESTOS SURVEY FINDINGS
4.1 Inspection and Sampling
The USACE inspector identified and sampled fifteen (15) separate HA’s during the 30 July 2025 ACM Survey. The identified HA’s were in good condition with relatively low exposure risk based on material characteristics (e.g. generally non-friable). The following is a summary of HA’s sampled:
• HA-01: Black Roofing Felt Paper
• HA-02: White EPDM Roofing Seam Sealant
• HA-03: EPDM Roofing with Foam Board and Felt Paper
• HA-04: Asphalt Tar on Roof Deck beneath EPDM Roofing
• HA-05: Brown Vinyl Cove Base with Yellow Glue
• HA-06: 12”X12” Green Vinyl Composite Tile with Black Mastic
• HA-07: White 2’X4’ Ceiling Tile
• HA-08: Drywall
• HA-09: Wood Patterned Linoleum
• HA-10: Tan Vinyl Cove Base with Yellow Glue
• HA-11: White Flexible Vinyl Tile with Black Mastic
• HA-12: White 2’X2’ Ceiling Tile
• HA-13: White Exterior Door Caulk
• HA-14: White Exterior Louver Hood Caulk
• HA-15: White Exterior Window Caulk
Throughout this report, Bold text indicates laboratory confirmed ACM.
The United States Environmental Protection Agency (USEPA), per the Title 40 Code of Federal Regulations (CFR) Part 61, Subpart M, defines an ACM as a material that contains one percent (1%) or more asbestos using polarized light microscopy (PLM).
Laboratory results are provided in a Table in Appendix A and the Analytical Laboratory Report is attached in Appendix B. Sample location drawings are shown on Appendix D with Asbestos Containing Materials (ACMs) depicted with red text. The samples were analyzed using PLM coupled with dispersion staining, as described in 40 CFR Part 763 and the NESHAP, following EPA Method 600/R-93/116. The samples were analyzed at EMSL Analytical Laboratories (EMSL) under the NVLAP Lab Code 200188-0 (Appendix C).
5.0 CONCLUSIONS AND RECOMMENDATIONS
An ACM Survey was conducted at the Property. During the 30 July inspection, the USACE Louisville inspector identified fifteen (15) HAs. Asbestos was detected in only one (1) HA sampled: HA-06 – 12”X12” Green VCT w/ Black Mastic.
The remaining HAs are non-ACM and do not require corrective actions. Reasonable inspection methods and techniques were employed to perform the ACM Survey. ACM may be present in additional areas not sampled or available to be sampled during the investigation, and it is recommended that any suspect ACM found at a later date be tested and confirmed by recognized laboratory methods, and licensed EPA AHERA professional prior to any renovation and/or demolition of the building.
6.0 LIMITATIONS AND CERTIFICATIONS
This ACM Survey report was prepared by the USACE Louisville District for use Westover ARB. This report, and the supporting data, findings, conclusions, opinions, and recommendations it contains represent the result of USACE efforts within this environmental investigation work. Opinions and recommendations presented in this report apply to site conditions and features as they existed at the time of the site visit, and those reasonably foreseeable. They cannot necessarily apply to conditions and features of which USACE is unaware and has not had the opportunity to evaluate. The information presented in this report contains professional opinions based solely upon USACE’s visual observations, laboratory test data, and current regulatory requirements.
These conclusions are intended exclusively for the purpose stated herein, at the site indicated, and for the project indicated.
7.0 POINTS OF CONTACT
Please direct any questions to Christian Elslager or Shelton Poole, by phone at (502) 315-7083 or (502) 315-6290, respectively, or email at Christian.j.elslager@usace.army.mil or Shelton.M.Poole@usace.army.mil
08/19/2025
Christian Elslager Date Physical Scientist U.S. Army Corps of Engineers Louisville District
08/19/2025
Shelton Poole Date Environmental Branch Chief U.S. Army Corps of Engineers Louisville District mailto:Christian.j.elslager@usace.army.mil mailto:Shelton.M.Poole@usace.army.mil
APPENDICES
APPENDIX A
SAMPLE ANALYSIS SUMMARY
Appendix A- Asbestos Sample Analysis Summary
Homo-genous Area
(HA #)
Sample Number
Material Sample Location PLM Result
HA-01 1A Black Felt Flashing Roof, SE Corner, pipe penetration
NAD
HA-02 2A White Flexible Roof Seam Sealer
Roof, SE Corner, near E side
NAD
HA-03 3A EPDM Roofing, with Foam Board and Roofing Felt
Roof, SE Corner NAD
HA-04 4A Tar on Roof Deck under EPDM Roofing
Roof, SE Corner NAD
HA-05 5A Brown Vinyl Cove Base w/ Yellow Glue
Office 101-1, Closet NAD 5B Office 103-1, N Wall NAD 5C Office 103-1, S Wall NAD
HA-06 6A 12”x12” Green Vinyl Composite Tile w/ Black Mastic
Office 101-1, Closet 3% Chrysotile
(VCT), 3%
Chrysotile (Mastic)
HA-07 7A White 2’x4’ Ceiling Tile Office 100-1, W Side NAD 7B Office 103-1, N Side NAD 7C Office 103-1, S Side NAD
HA-08 8A Drywall Office 101-1, Closet NAD 8B Restroom, N Wall NAD 8C Office 103-1, S Wall NAD
HA-09 9A Wood Patterned Linoleum
Restroom, W Side NAD 9B Restroom, NE Corner NAD 9C Restroom, SE Corner NAD
HA-10 10A Tan Vinyl Cove Base w/ Yellow Glue
Restroom, N Wall NAD 10B Restroom, W Wall NAD 10C Restroom, E Wall NAD
HA-11 11A White Flexible Vinyl Floor Tile w/ Black Mastic
Office 108-1, NE Corner NAD 11B Office 108-1, SW Corner NAD 11C Office 108-1, Center NAD
HA-12 12A White 2’x2’ Ceiling Tile Office 108-1, SW Corner NAD 12B Office 108-1, NE Corner NAD
HA-13 13A White Exterior Door Caulk
W Exterior Mechanical Room Door
NAD
HA-14 14A White Exterior Louver Hood Caulk
W Wall Louver Hood NAD 14B S Wall Louver Hood NAD
HA-15 15A White Exterior Window Caulk
E Wall Center NAD
NAD = No Asbestos Detected by PLM NA/PS = Not Analyzed/Positive Stop NA = Not Applicable Bold = Positive for ACM
APPENDIX B
LAB ANALYSIS REPORT
EMSL Analytical, Inc.
6340 CastlePlace Dr. Indianapolis, IN 46250
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162510032EMSL Order:
Customer ID: USEL75
Customer PO:
Project ID:
Attention: Phone:Christian Elslager (502) 648-6770
Fax:US Corps Of Engineers
Received Date:600 Dr. Martin Luther King Jr Place 08/06/2025 10:07 AM
Analysis Date:Room 351 08/13/2025
Collected Date:Louisville, KY 40202
Project: US Army Reserves-Westover AFB
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1A
162510032-0001
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Felt Flashing, Black
HA: HA-1
2A
162510032-0002
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
White
Flexible,Roofing
Seam Sealer
HA: HA-2
3A-Roofing
162510032-0003
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
EPDM Roofing w/
Foam Board
HA: HA-3
3A-Foam Board
162510032-0003A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
EPDM Roofing w/
Foam Board
HA: HA-3
3A-Felt
162510032-0003B
None DetectedNon-fibrous (Other)5%Cellulose
Glass
95%
<1%
Gray/Black
Fibrous
Homogeneous
EPDM Roofing w/
Foam Board
HA: HA-3
4A
162510032-0004
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Black Tar on Roof
Deck
HA: HA-4
5A-Vinyl Cove Base
162510032-0005
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Brown Vinyl Cove
Base w/ yellow glue
HA: HA-5
5A-Glue
162510032-0005A
None DetectedNon-fibrous (Other)100%Tan/Yellow
Non-Fibrous
Homogeneous
Brown Vinyl Cove
Base w/ yellow glue
HA: HA-5
5B-Vinyl Cove Base
162510032-0006
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Brown Vinyl Cove
Base w/ yellow glue
HA: HA-5
5B-Glue
162510032-0006A
None DetectedNon-fibrous (Other)100%Tan/Yellow
Non-Fibrous
Homogeneous
Brown Vinyl Cove
Base w/ yellow glue
HA: HA-5
5C-Vinyl Cove Base
162510032-0007
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Brown Vinyl Cove
Base w/ yellow glue
HA: HA-5
5C-Glue
162510032-0007A
None DetectedNon-fibrous (Other)100%Tan/Yellow
Non-Fibrous
Homogeneous
Brown Vinyl Cove
Base w/ yellow glue
HA: HA-5
Initial report from: 08/13/2025 14:03:39
Page 1 of 4ASB_PLM_0008_0002 - 2.31 Printed: 8/13/2025 2:03 PM
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162510032EMSL Order:
Customer ID: USEL75
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
6A-Vinyl Composite Tile
162510032-0008
3% ChrysotileNon-fibrous (Other)97%Brown/Black
Non-Fibrous
Homogeneous
Green Vinyl
Composet Tile w/
Black Mastic
HA: HA-6
6A-Mastic
162510032-0008A
3% ChrysotileNon-fibrous (Other)97%Black
Non-Fibrous
Homogeneous
Green Vinyl
Composet Tile w/
Black Mastic
HA: HA-6
7A
162510032-0009
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
60%
20%
Gray/White
Fibrous
Homogeneous
2'x4' White Ceiling
Tile
HA: HA-7
7B
162510032-0010
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
60%
20%
Gray/White
Fibrous
Homogeneous
2'x4' White Ceiling
Tile
HA: HA-7
7C
162510032-0011
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
60%
20%
Gray/White
Fibrous
Homogeneous
2'x4' White Ceiling
Tile
HA: HA-7
8A
162510032-0012
None DetectedGypsum
Non-fibrous (Other)
60%
8%
Cellulose
Glass
30%
2%
Brown/White
Fibrous
Heterogeneous
Drywall
HA: HA-8
8B
162510032-0013
None DetectedGypsum
Non-fibrous (Other)
65%
5%
Cellulose30%Brown/White
Fibrous
Heterogeneous
Drywall
HA: HA-8
8C
162510032-0014
None DetectedGypsum
Non-fibrous (Other)
60%
5%
Cellulose35%Brown/White
Fibrous
Heterogeneous
Drywall
HA: HA-8
9A
162510032-0015
None DetectedNon-fibrous (Other)75%Cellulose25%Brown
Fibrous
Heterogeneous
Wood Pattern
Linoleum
HA: HA-9
9B
162510032-0016
None DetectedNon-fibrous (Other)75%Cellulose25%Brown
Fibrous
Heterogeneous
Wood Pattern
Linoleum
HA: HA-9
9C
162510032-0017
None DetectedNon-fibrous (Other)70%Cellulose30%Brown
Fibrous
Heterogeneous
Wood Pattern
Linoleum
HA: HA-9
10A-Vinyl Cove Base
162510032-0018
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Tan Vinyl Cove Base w/ yellow glue
HA: HA-10
10A-Glue
162510032-0018A
None DetectedNon-fibrous (Other)100%White/Yellow
Non-Fibrous
Homogeneous
Tan Vinyl Cove Base w/ yellow glue
HA: HA-10
10B-Vinyl Cove Base
162510032-0019
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Tan Vinyl Cove Base w/ yellow glue
HA: HA-10
10B-Glue
162510032-0019A
None DetectedNon-fibrous (Other)100%White/Yellow
Non-Fibrous
Homogeneous
Tan Vinyl Cove Base w/ yellow glue
Page 2 of 4ASB_PLM_0008_0002 - 2.31 Printed: 8/13/2025 2:03 PM
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162510032EMSL Order:
Customer ID: USEL75
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
HA: HA-10
10C-Vinyl Cove Base
162510032-0020
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Tan Vinyl Cove Base w/ yellow glue
HA: HA-10
10C-Glue
162510032-0020A
None DetectedNon-fibrous (Other)100%White/Yellow
Non-Fibrous
Homogeneous
Tan Vinyl Cove Base w/ yellow glue
HA: HA-10
11A-Vinyl Tile
162510032-0021
None DetectedNon-fibrous (Other)100%White/Blue
Non-Fibrous
Homogeneous
White Vinyl Tile w/
Black Mastic
HA: HA-11
11A-Mastic
162510032-0021A
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
White Vinyl Tile w/
Black Mastic
HA: HA-11
11B-Vinyl Tile
162510032-0022
None DetectedNon-fibrous (Other)100%White/Blue
Non-Fibrous
Homogeneous
White Vinyl Tile w/
Black Mastic
HA: HA-11
11B-Mastic
162510032-0022A
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
White Vinyl Tile w/
Black Mastic
HA: HA-11
11C-Vinyl Tile
162510032-0023
None DetectedNon-fibrous (Other)100%White/Blue
Non-Fibrous
Homogeneous
White Vinyl Tile w/
Black Mastic
HA: HA-11
11C-Mastic
162510032-0023A
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
White Vinyl Tile w/
Black Mastic
HA: HA-11
11C-Leveler
162510032-0023B
None DetectedQuartz
Non-fibrous (Other)
20%
80%
Gray
Non-Fibrous
Homogeneous
White Vinyl Tile w/
Black Mastic
HA: HA-11
12A
162510032-0024
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
60%
20%
Gray/White
Fibrous
Homogeneous
2'x2' White Ceiling
Tile
HA: HA-12
12B
162510032-0025
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
60%
20%
Gray/White
Fibrous
Homogeneous
2'x2' White Ceiling
Tile
HA: HA-12
13A
162510032-0026
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
White Door Caulk
Exterior
HA: HA-13
14A
162510032-0027
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
White Louver Caulk, Exterior
HA: HA-14
14B-Caulk
162510032-0028
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
White Louver Caulk, Exterior
HA: HA-14
Page 3 of 4ASB_PLM_0008_0002 - 2.31 Printed: 8/13/2025 2:03 PM
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162510032EMSL Order:
Customer ID: USEL75
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
14B-Foam
162510032-0028A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
White Louver Caulk, Exterior
HA: HA-14
15A
162510032-0029
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
White Window Caulk, Exterior
HA: HA-15
Analyst(s)
Hilary Jarvis (30)
Ross Matlock (13)
Asbestos Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN NVLAP Lab Code 200188-0, AZ0939, CA 2575, CO AL-15132, TX 300262, A2LA Accredited - Certificate #2845.25
Page 4 of 4ASB_PLM_0008_0002 - 2.31 Printed: 8/13/2025 2:03 PM
OrderID: 162510032
OrderID: 162510032
APPENDIX C
PERSONNEL AND LABORATORY CREDENTIALS
United States Department of Commerce National Institute of Standards and Technology
Certificate of Accreditation to ISO/IEC 17025:2017
NVLAP LAB CODE: 200188-0
EMSL Analytical, Inc.
Indianapolis, IN is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Asbestos Fiber Analysis
2025-04-01 through 2026-03-31
Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique on ISO/IEC 17025).
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017
For the National Voluntary Laboratory Accreditation Program
Effective
National Voluntary Laboratory Accreditation Program
2025-04-01 through 2026-03-31
EMSL Analytical, Inc.
6340 Castleplace Dr.
Indianapolis, IN 46250
Melissa Newkirk Phone: 317-803-2997
Email: mnewkirk@emsl.com http://www.emsl.com
ASBESTOS FIBER ANALYSIS NVLAP LAB CODE 200188-0
Bulk Asbestos Analysis
18/A01 EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples
18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials
Airborne Asbestos Analysis
18/A02 U.S. EPA's "Interim Transmission Electron Microscopy Analytical Methods-Mandatory and Nonmandatory-and Mandatory Section to Determine Completion of Response Actions" as found in 40 CFR, Part 763, Subpart E, Appendix A.
APPENDIX D
SAMPLE LOCATION FIGURE
Not To Scale
103-1 Office
104-1 Restroom
107-1 Radio Room
100-1 Office
108-1 RAWS Office
105-1 Mech
106-1 Mech
101-1
105-1 = Room # or Hallway 4A = Sample # and location – negative for asbestos
14A
12A
1A
6A
13A
15A
US Army Corps of Engineers Figure 1: Asbestos Sample Locations
Building 5505 Westover ARB Chicopee, MA
3A = Sample # and location – Asbestos containing
2A
3A 4A
5A 5C
5A 7B
7C
7A
8A
8C
8B
9C
9B
9A 10A
10C
10B
14B
12B
11A
11B
11C
APPENDIX E
SITE PHOTOS
Photo No.:
Date:
30 July 2025
Description:
Westover ARB: Bldg. 5505
Exterior view of Building 5505, facing northeast
Photo Direction: Facing Northwest
Photo No.:
Green 12”x12” Vinyl Composite Tile and Black Mastic located throughout radio room and central office area
2’x4’ White Ceiling Tile in central office area southwest
2’x2’ White Ceiling Tile in northwest office area
West
White Flexible Vinyl Floor Tile with Black Mastic located in northwest office area
Photo No.:
Drywall located throughout office areas and radio room
Wood Patterned Linoleum and Tan Vinyl Cove Base located in the Restroom
Photo No.:
Brown Vinyl Cove Base observed in central office areas
Southwest
Exterior White Caulk on louver hood.
North
Photo No.:
Exterior White Window Caulk
Southeast
Exterior White Door Caulk
Photo
| Table of Contents |
| Lists of Appendices |
| Appendices |
| Acronyms and abbreviations |
| 1.0 Introduction |
| 1.1 Purpose of an Asbestos Containing Material Survey Report |
| 1.2 ACM Definition |
| 1.3 Regulated ACM |
| 1.4 Abatement |
| 2.0 Asbestos Containing Material Survey Approach |
| 3.0 Site Information |
| 3.1 Installation Name and Location |
| 3.2 Facility Point of Contact |
| 3.3 Inspection Information |
| 3.4 Facility Building(s) Information |
| 4.0 Asbestos Survey Findings |
| 4.1 Inspection and Sampling |
| 5.0 Conclusions and Recommendations |
| 6.0 Limitations and Certifications |
| 7.0 Points of Contact |
| NVLAP Indianapolis.pdf |
| AccreditationCertificate2017 - 2025-03-17T150933.354 printed |
| AccreditationScope2017 - 2025-03-17T150938.231 printed |
| 2025-08-19T12:07:07-0400 | |
| ELSLAGER.CHRISTIAN.JAMES.1609969420 |
| 2025-08-19T13:43:28-0400 | |
| POOLE.SHELTON.M.1230563604 |
File details come from the government source that posted it. Updated .