About this file

214261_MECH-1

View the file

Other files

File Type Posted
A21_W91QVN19R01840001.pdf PDF
209625_TITLE.pdf PDF
214261_STRUCTURAL-1.pdf PDF
209625_ARCH-2.pdf PDF
209625_MECH-2.pdf PDF
A02_214261_CONST-OFFICE-FIRE-STATION-K16-256_MMTL-ARCH.xlsx XLSX spreadsheet
214261_TITLE_R1.pdf PDF
214261_CIVIL-1.pdf PDF
A02_209625_CONST-BAYS-FIRE-STATION-K16-256_MMTL-CIVIL.xlsx XLSX spreadsheet
214261_ELEC_1.pdf PDF
214261_ARCH-2.pdf PDF
A02_209625_CONST-BAYS-FIRE-STATION-K16-256_MMTL-MECH.xlsx XLSX spreadsheet
A02_209625_CONST-BAYS-FIRE-STATION-K16-256_MMTL-ARCH.xlsx XLSX spreadsheet
209625_STRUC-2.pdf PDF
214261_ELEC_3.pdf PDF
214261_CIVIL-2.pdf PDF
209625_ELEC.PDF PDF
209625_STRUC-1.pdf PDF
A02_214261_CONST-OFFICE-FIRE-STATION-K16-256_MMTL-MECH.xlsx XLSX spreadsheet
214261_ARCH-3.pdf PDF
214261_ARCH-1.pdf PDF
A02_209625_CONST-BAYS-FIRE-STATION-K16-256_MMTL-ELEC.xlsx XLSX spreadsheet
214261_STRUCTURAL-2.pdf PDF
214261_STRUCTURAL-3.pdf PDF
214261_ELEC_2.pdf PDF
A02_214261_CONST-OFFICE-FIRE-STATION-K16-256_MMTL-CIVIL.xlsx XLSX spreadsheet
214261_MECH-2.pdf PDF
209625_STRUC-3.pdf PDF
A02_214261_CONST-OFFICE-FIRE-STATION-K16-256_MMTL-STRU.xlsx XLSX spreadsheet
209625_ARCH-1.pdf PDF
A02_214261_CONST-OFFICE-FIRE-STATION-K16-256_MMTL-ELEC.xlsx XLSX spreadsheet
A02_209625_CONST-BAYS-FIRE-STATION-K16-256_MMTL-STRU.xlsx XLSX spreadsheet
A21_W91QVN19R0184.pdf PDF
209625_MECH-1.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

SYMBOLS AND ABBREVIATIONS

MECHANICAL MATERIAL INDICATIONS &

M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S

NTS

PD

Pa

OS&Y

OXY

OD

OAIL

OA

QT

PRV

PPM

POL

POC

PLMB

PH

PG

RT

RPM

RH

RDTR

RA

R12, R22

QTY

A B B R E V I A T I O N S

SBM

SAN

SA

SCH

FLOWMETER, ORIFICEBUTTERFLY

REFRIGERANT LIQUID

CHILLED WATER SUPPLY

CHILLED WATER RETURN

AIR COOLED CONDENSING UNIT

AIR CONDITION UNIT (S)

APPARATUS DEW POINT

AIR CONDITION (-ING,-ED)

CHILLED/HOT WATER RETURN

AMERICAN WIRE GAUGE

PRESSURE, BAROMETRIC

CUBIC METER PER HOUR

CHILLED/HOT WATER SUPPLY

CAPACITYCAP

CONNECTION

CONTINUE

COMPRESSOR

CUBIC METER

CPRSR

CONN

CONT

CU M

CHILLED WATER

CAST IRON PIPE

CIRCUIT

CLASSIFICATION

COOLING LOAD

COEFFICIENT

COUNTER CLOCKWISE

CLASS

CLG LOAD

COEF

CMH

CIP

CCW

CHW

CKT

ACV ALARM CHECK VALVE

AVERAGEAVG

BOILING POINT

CENTIGRADE

BAROMETER(-TRIC)

BRAKE HORSEPOWER

BP

BHP

C

BARO PR

AWG

BARO

ALUMINUM

ALTITUDE

AMBIENT

AIR HANDLING UNIT

AMPERE(AMP, AMPS)

APPROXIMATEAPPROX

ALT

AMB

AMP

AIR COND

ADP

AL

AHU

AIR COOLED

ACCU

ACLD

ACU

CHR

C/HWR

C/HWS

CHS

RL

D DRAIN

DIAMETER, INSIDE

ISOMETRIC

IRON PIPE SIZE

JOULE

THERMAL CONDUCTIVITY

KILOGRAM

KILOGRAM PER SQ. CENTIMETER (GAUGE)

KILOGRAM PER SQ. CENTIMETER

KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)

KILOCALORIE PER HOUR

EXPANSION JOINT

EXPLOSION PROOF

FIRE HOSE CABINET

FULL LOAD AMPERES

ENTERING WATER TEMP

EVAPORAT (-E,-ING,-ED,-OR)

EXTERNAL STATIC PRESSURE

FACE AREA OR FRESH AIRFA

FHC

FHY

FLA

FIRE HYDRANT

ESP

EXPJT

EWT

EVAP

EP

EQPT

ENT

EFF

EQUIPMENT

ENTERING

EFFICIENCY

KG/SQ CM

KG/SQ CM A

KG/SQ CM G

KG

KCAL/HR

J

K

ID

ISO

IPS

NO

N.O.

NIC

NPT

MPS

NC

N/A

N.C.

MAX

MIN

MPH

MM

NOT IN CONTRACT

NATIONAL TAPER PIPE (THREAD)

NUMBER

NORMALLY OPEN

MINIMUM OR MINUTE

METERS PER HOUR

METERS PER SECOND

NORMALLY CLOSED

NOISE CRITERIA

NOT APPLICABLE

MAXIMUM

MILLIMETER R

FEMALE PIPE THREAD

FUEL OIL

GALVANIZED STEEL

GAGE OR GAUGE

FIXTURE

FEED WATER PUMP

FACE VELOCITY

FLUSH VALVE

FREQUENCY

FIBERGLASS REINFORCED PLASTIC

HORIZONTAL

HOT WATER HEATER

HOT WATER

HOUR(S)

HORSEPOWER

MERCURY

HEAD

HOSE BIBB

HERTZ

GRAMS

FRPCWP CIRCULATING WATER PUMP

DIRECT EXPANSION

DRY PIPE VALVE

EQUIVALENT DIRECT RADIATION

ENTERING AIR TEMPERATURE

DOUBLE POLE DOUBLE THROW

DEWPOINT TEMPERATURE

DRY BULB TEMPERATURE

DECIBEL OR DRY BULB

DIESEL OILDO

ECON

ECC

EAT

EDR

DX

DPV

DPDT

DPT

ECONOMIZER

ECCENTRIC

o

DIFF

DIAG

DIA or

DIV

DBT

DB

DIFFERENCE

DIAGRAM

DIAMETER

DIVISION

DEGREE

HR

HORIZ

HWH

HW

HZ

HP

HG

HD

HB

GALVS

GA

GR

FXTR

FWP

FVEL

FV

CUBIC MILLIMETER

CLOCKWISE OR COLD WATER

COEFFICIENT, VALVE FLOWCv

CU MM

CW

PLUG VALVE

THREE WAY

FPT

FO

FREQ

GATE, ANGLE

GATE, GLOBE

GLOBE

GATE

CONTROL

KJ KILOJOULE

LH

LT

LWT

LPS

M

LL

LPD

LPH

LM

LAV

LAT

LBS

LG

KW

KWH

L

LATENT HEAT

LEAVING WATER TEMPERATURE

LITERS PER HOUR

LITERS PER SECOND

LAUNDRY TRAY

METERS

LIQUID LINE

LITERS PER DAY

LINEAR METER

LEAVING AIR TEMPERATURE

LAVATORY

POUNDS

LENGTH

KILOWATT

KILOWATT HOUR

LITERS

P

FLOWMETER, VENTURI

FLOW SWITCH

PRESSURE SWITCH

PRESSURE GAUGE AND COCK

PUMP (INDICATE USE)

STRAINER

STRAINER, BLOW OFF

KG/SM

KG/SM A

KG/SM G

PS

P

OFM

FS

VFM

KILOGRAM PER SQ. METER

KILOGRAM PER SQ. METER (ABSOLUTE)

KILOGRAM PER SQ. METER (GAUGE)

JACKET WATER RETURN

MEDIUM PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE

BOILER BLOW DOWN

PUMPED CONDENSATE

JACKET WATER SUPPLY

VACUUM PUMP DISCHARGE

FUEL OIL TANK VENT

CONDENSATE WATER SUPPLY

CONDENSATE WATER RETURN

MEDIUM TEMPERATURE HOT WATER SUPPLY

MEDIUM TEMPERATURE HOT WATER RETURN

LOW TEMPERATURE HOT WATER SUPPLY

LOW TEMPERATURE HOT WATER RETURN

PIPE TO BE REMOVED

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION

LPS

CONTROL AIR MAIN

air conditioning and refrigeration

RD

RS

(NAME)E

(NAME)

M

EXISTING PIPE

COMPRESSED AIR

VACUUM (AIR)

HWR

VAC

A

MTWS

MTWR

HWS

FOD FUEL OIL DRAIN

FOR

CS

CR

FOV

FOG

FOS FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL GAUGE

PC

VPD

MU

LPC

BBD

MAKE UP WATER

MPS

MPC

JWR

JWS

heating

PIPING

CHECK, SWINGSANITARY DRAIN

PITCH OR PIPE, UP(U), DOWN(D)

FLOOR SINK (200mm x 200mm)

PIPE SLEEVE WITH FIRE STOPPING

VENT THRU ROOF

BFP

valves : (for selective actuators)

PLAN

HOSE BIBB

AIR LINEA

BALL

ELEV.

BACKFLOW PREVENTER

PIPE SLEEVE

(NAME)

ACID

200mm x 200mm

SURFACE CLEANOUT

FLOOR CLEANOUT

FLOOR DRAIN

CHEMICAL SUPPLY PIPES

FUNNEL DRAIN, OPEN

FCO

FD

SCO

FLOOR OR GRADE

FLOOR OR GRADE

CONDENSATE DRAIN BELOW

CONDENSATE DRAIN ABOVE

ACID WASTE

GASG

CD

CD

AIR VENT, MANUAL

AIR VENT, AUTOMATIC

W/ MEASURING TAP

EXPANSION LOOP

EXPANSION JOINT

BALL JOINT

ANCHOR, MAIN

ANCHOR, INTERMEDIATE

ALIGNMENT GUIDE

AIR SEPARATOR

FLEXIBLE CONNECTOR

SQUARE HEAD BALANCING COCK

EJ

S

MV

AVV

CHECK, NON-SLAM

CONTROL, ELECTRIC-PNEUMATIC

CONTROL, PNEUMATIC-ELECTRIC

QUICK OPENING

PRESSURE REDUCING

NEEDLE

LOCK SHIELD

HOSE END DRAIN

SAFETY

RELIEF

SQUARE HEAD BALANCING COCK

QUICK CLOSING, FUSIBLE LINK

R

S

PE

EP

plumbing

COLD WATER

HOT WATER RETURN

HOT WATER SUPPLY

VENT

MOTOR ELECTRIC

DIAPHRAGM

valves, special duty :

SOLENOIDS

valve actuators

M

FDAD

QUANTITY

SANITARY

SUBMERSIBLE

SUPPLY AIR

SCHEDULE

RADIATOR

REFRIGERATION TON

REVOLUTIONS PER MINUTE

RELATIVE HUMIDITY

RETURN AIR

THERMAL RESISTANCE

REFRIGERANT (12, 22, ETC)

OUTSIDE AIR INTAKE LOUVER

PRESSURE DROP OR DIFFERENCE

PRESSURE REDUCING VALVE

PHASE (ELECTRIC)

PERCENT

PARTS PER MILLION

POINT OF CONNECTION

PLUMBING

PETROLEUM, OIL AND LUBRICANTS

QUART

OUTSIDE SCREW & YOKE

DIAMETER, OUTSIDE

PRESSURE GAGE

POLE

PASCAL

OXYGEN

ALARM CHECK VALVE

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

FIRE DEPARTMENT CONNECTION

PRE-ACTION VALVE

NOT TO SCALE

OUTSIDE AIR

(2-WAY SHOWN)

DRY-PIPE VALVE

VARIABLE AIR VOLUMEVAV

VENTILATION

PRESSURE, DYNAMIC(VELOCITY)

WATER-COOLED

WATER CLOSET

WATTHOUR OR WATER HEATER

WET BULB TEMPERATURE

WATERPROOF

WSHR

WCLD

WTRPRF

WH

WT

W/

WD

WC

WBT

WEIGHT

WITH

WASHER

WIDTH

VP

VOL

WB

W

VISC

VERT

VENT

VEL

VOLUME

WET BULB

WATT

VISCOSITY

VERTICAL

VELOCITY

MANUAL VOLUME DAMPER

SMOKE DAMPER (PROVIDE ACCESS DOOR)

PNEUMATIC OPERATED DAMPER

VLV

V

VAC

M

VALVE

VOLT

VACUUM

SPLITTER DAMPER

SD

AD

VD

grilles, registers and diffusers :

SG

SR

600/300

300x150

200mm NCD

FIGURE IS ON TOP

810mm x 400mm dampers

ELBOW, TURNED DOWN

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

TEE, OUTLET DOWN

TEE, SINGLE SWEEP

sprinkler

UNION, SCREWED

UNION, FLANGED

TEE, OUTLET UP

TEE

LATERAL

CONNECTION, BOTTOM

CONNECTION, TOP

ELBOW, TURNED UP

BUSHING

CAP

WELDED

FLANGED

SOLDERED

SCREWED BELL AND SPIGOT

SOLVENT CEMENT

SOUND ATTENUATOR

DETECTORS, FIRE AND/OR SMOKE

ELECTRIC MOTOR OPERATED DAMPER

FIRE DAMPER (PROVIDE ACCESS DOOR)

BACKDRAFT DAMPER

BDD

S

TRANSITION

TURNING VANES

SF

CHANGE OF ELEVATION, RISE(R), DOWN(D)

DUCT SECTION, NEGATIVE PRESS., FIRST

ACCESS DOOR, VERTICAL OR HORIZONTAL

COWL, (GOOSENECK) AND FLASHING

ACOUSTICAL LINING

FLEXIBLE DUCT

FLEXIBLE CONNECTIONFC

FIGURE IS ON TOP

R

AD

47.2

TG

94.4

UC 13mm

DG

500/300L

DUCT WORK

810mm x 400mm

810mm x 400mm

THERMOSTAT, ELECTRIC

TRAP, ELECTRIC (INDICATE TYPE)

fitting :

R

THERMOMETER

EXHAUST AIR GRILLE OR REGISTER, CEILING

DUCT SECTION, POSITIVE PRESS., FIRST

DIRECTION OF FLOW

SR

DIFFUSER, LINEAR

RETURN AIR GRILLE OR REGISTER, CEILING

CEILING DIFFUSER, SQUARE TYPE

CEILING DIFFUSER, ROUND TYPE (200mm

(600mm x 300mmH, 472 LPS)

UNDERCUT DOOR (13mm, 47.2 LPS)

DOOR GRILLE (300mmx150mmH)

NECK DIAMETER)

TRANSFER GRILLE ASSEMBLY

LOUVER, DOOR OR WALL

(500mmWx300mmH, 94.4 LPS)

RG

RR

SUPPLY AIR GRILLE OR REGISTER, SIDEWALL

EXHAUST AIR GRILLE OR REGISTER, CEILING

SUPPLY AIR GRILLE OR REGISTER, CEILING

ER

SG

EG

EXISTING WORK TO BE REMOVED.

POINT OF CONNECTION NEW TO EXISTING

OR END OF DEMOLITION WORK

EXISTING WORK TO REMAIN.(E)

(R) REMOVE EXIST WORK

STAINLESS STEELSTS

SEC

SF

SG SPECIFIC GRAVITY

SAFETY FACTOR

SECOND

SL

SLPD

SLPS

SLPH

SP

SM

SPEC

SPDT

SPECIFICATION

SQUARE METER

STATIC PRESSURE

SENSIBLE LOAD

SQ

SSF

SST

SSU

ST

STD

STL

STOR STORAGE

STAINLESS STEEL

SQUARE

STEAM

STANDARD

STEEL

SPR SPRINKLER

SH SENSIBLE HEAT

SAYBOLT SECONDS FUROL

SAYBOLT SECONDS UNIVERSAL

LPD, STANDARD CONDITIONS

LPS, STANDARD CONDITIONS

LPH, STANDARD CONDITIONS

SINGLE POLE DOUBLE THROW

SYM

TD

TEMP

THK

THERM

TONS

TSTAT

SYMBOL

TEMPERATURE

THERMOMETER

THICKNESS

THERMOSTAT

UH

UR

UNIT HEATER

URINAL

TYP TYPICAL

HEAT TRANSFER COEFFICIENT

TEMPERATURE DIFFERENCE

TONS OF REFRIGERATION

SUCT SUCTION

C

A

B

S E T

ID

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

CHONG, ST

214621

M-2

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

GENERAL NOTES & SCOPE OF WORK

SCOPE OF WORK

CONTRUCTION WORK(L-WORK)

HVAC SYSTEM

SPRINKLER WORK

PLUMBING WORK

1. INSTALL WET TYPE SPRINKLER SYSTEM AND ASSOCIATED PIPING, AS INDICATED ON PLANS

15.

14.

13.

12.

11.

10.

9.

8.

7.

6.

5.

4.

3.

2.

1.

PIPING SYSTEMS SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS

AND FLUSHED UNTIL ALL WATER BEING FLUSHED IS CLEAR AS TAP WATER.

ALL AIR DUCT DIMENSION SHOWN ARE INDICATED AS ACTUAL INSIDE DIMENSIONS.

DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.

TO SMACNA STATIC PRESSURE CLASS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS

ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING

OF SEAL CLASS C.

CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE

THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO

THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY

THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH

THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.

IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER'S

REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR

LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE

SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.

NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.

ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.

ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND

CONTRACTING OFFICER'S APPROVAL.

AND SHALL BE VERIFIED AT THE JOB SITE.

THIS CONTRACTOR.

GENERAL NOTES

PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.

ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED SHALL BE

ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES

SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.

SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY

FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR

ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE

CONTRACTING OFFICER FOR APPROVAL.

THE EXIST DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT

IF THE EXIST DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION, REMOVE

THE EXIST DUCTWORK AND PIPING ELEVATION/LOCATION.

PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST COORDINATE WITH

CONNECTION TO FUNCTION AS ORIGINALLY INTENDED.

CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPEC.

ALL GAS METERS, REGULATORS, GAS LEAK DETECTOR AND GAS PIPING SHALL BE INSTALLED

IN ACCORDANCE WITH LOCAL CODES AND CITY GAS COMPANY'S RECOMMENDATIONS.

1. INSTALL OUTDOOR & INDOOR SPLIT SYSTEM HEAT PUMP UNITS, OUTSIDE AIR UNIT, PIPING, CONC PAD

2. INSTALL GAS FIRED HOT WATER BOILER, FLUE VENT, COMBUSTION AIR INTAKE, GAS LEAK DETECTION CONTROL PANEL, GAS GONG, GAS LEAK DETECTOR, SHUT UP VALVE, GAS METER CABINET, GAS METER, GAS REGULATOR, VALVE CABINET

HOT WATER CIRC. PUMP, AIR SEPARATOR, EXPANSION TANK, CONC. PAD, ASSOCIATED PIPING AND ACCESSORIES.

4. INSTALL EXHAUST FANS ASSPCIATED DUCTWORKS, BACKFLOW PREVENTER & PRESSURE REDUCING STATION

AS INDICATED ON PLANS.

AS INDICATED ON PLANS.

1. INSTALL GAS FIRED DOMESTIC HOT WATER HEATER, FLUE VENT, COMBUSTION AIR INTAKE, DOMESTIC HOT WATER CIRC. PUMP, DOMESTIC HOT WATER RECIRC PUMP, CONC PAD, ASSOCIATED PIPING AND ACCESSORIES AS INDICATED ON PLAN.

3. INSTALL SEWER, VENT PIPING, FLOOR DRAIN, FLOOR CLEANOUT AND ACCESSORIES INDICATED ON PLANS.

4. INSTALL ELECTRIC WATER COOLER, EMERGENCY SHOWER AND EYEWASH, DOMESTIC HOT WATER STORAGE TANK, EXPANSION TANK, ASSOCIATED PIPING AND ACCESSORIES AS INDICATED ON PLANS.

5. INSTALL PLUMBING FIXTURES, ASSOCIATED PIPING AND ACCESORIES AS INDICATED ON PLANS.

O.A INTAKE LOUVER W/BIRDSCREEN AND MOTORIZED DAMPER, HOT WATER PIPING, INSULATION AND ACCESSORIES.

ACCESSORIES AS INDICATED ON PLANS.

2. INSTALL HOT AND COLD WATER PIPING INCLUDING VALVES, HOSS BIBBS, WATER HAMMER ARRESTS, INSULATION AND

3. INSTALL ELECTRIC WALL HEATERS, ELECTRIC UNIT HEATERS, RANG HOOD, UNIT HEATERS, SPLIT AIR CONDITIONING UNIT, DUCTWORKS, DIFFUSERS, CONTROL, PIPING, DUCTWORKS AND ACCESSORIES AS INDICATED ON PLANS.

GAS FILTER, AUTOMATIC SHUT OFF VALVE, HVAC PIPING W/INSULATION, CONC PAD AND GAS PIPING AS INDICATED ON PLANS.

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-3

208/ 1/ 60 R-410A

AS PER MANUFACTURER RECOMMENDATIONS.

3 SIMILAR TO LG MULTI V 5 MODEL ARUM121BTE5 OR APPROVED EQUAL.

129,000114,000

REFRIGERANT

TYPE

R-410A

HEATING CAPACITY SHALL BE BASED ON 8 DEG C

INDOOR HEAT PUMP UNITS 321MULTI V 5 HEAT PUMP1

T Y P EITEM NO SERVICE

RATED HEATING CAP.

(BTU/H)

REMARKSQTY.

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT

OHPU

ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE INSTALLED AS PER MANUFACTURER RECOMMENDATIONS.

COOLING CAPACITY SHALL BE BASED ON 35 DEG C2

1NOTES :

(BTU/H)

RATED COOLING CAP.

TYPE

REFRIGERANT

HEATING CAPACITY SHALL BE BASED ON 8 DEG C

COOLING CAP.

(BTU/H)

NOTES : 1

2 COOLING CAPACITY SHALL BE BASED ON 35 DEG C

ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE INSTALLED

HPU

INDOOR SPLIT SYSTEM HEAT PUMP UNIT

QTY. REMARKS

POWER INPUT

(W)

VOLT/PH/HZ

(BTU/H)

HEATING CAP. CFM

SERVICEITEM NO T Y P E

1 1 2

COMPRESSOR

HSS DC SCROLL

TYPE

3208/ 1/ 60 R-410A 2

HPU

2 1

ELECTRICAL

MOP(A) MCA(A)

40 30.9

QTY

FAN

TYPE

PROPELLER

QTY

(H/M/L)

VOLT/PH/HZ

208/ 3/ 60

208/ 1/ 60 R-410A

HPU

1 1

208/ 1/ 60 R-410A

HPU

3 1

21,50019,100 57

208/ 1/ 60

417/381/348

R-410A

HPU

2-WAY CEILING CASSETTE TYPE

6,1005,500 30

208/ 1/ 60

265/247/212

R-410A

HPU

4-WAY CEILING CASSETTE TYPE

8,5007,500 30

208/ 1/ 60

265/247/212

R-410A

HPU

4-WAY CEILING CASSETTE TYPE

10,9009,600 30283/265/2514-WAY CEILING CASSETTE TYPE

(BTU/H) (BTU/H)

COOLING CAP

VOLT/PH/HZ REMARKS

(CFM)

HEATING CAP AIR FLOW RATE ELECTRICAL DATA

2 664/519/519 16948,100 46,115

TYPE

CEILING EMBEDDED TYPE

TYPE

REFRIGERANT

R-410A

MCA MOP

151.5

AS PER MANUFACTURER RECOMMENDATIONS

ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE INSTALLED

HEATING CAPACITY SHALL BE BASED ON 8 DEG C

COOLlNG CAPACITY SHALL BE BASED ON 35 DEG C SIMILAR TO LG MODEL ARNU483BRZ4 OR APPROVED EQUAL. 1 2 3

1 2 3

OUTSIDE AIR UNIT

ITEM NO Q'TY

OAU

208/ 1/ 60

ELECTRICAL DATA

MCA MOP

0.84

0.25

0.25

0.25

5 8SIMILAR TO LG MULTIV MODEL ARNU183TSA4 OR APPROVED EQUAL.

9SIMILAR TO LG MULTIV MODEL ARNU053TRC4 OR APPROVED EQUAL.

10SIMILAR TO LG MULTIV MODEL ARNU073TRC4 OR APPROVED EQUAL.

SIMILAR TO LG MULTIV MODEL ARNU093TRC4 OR APPROVED EQUAL.

CHIEF SUITE

MEDICAL SUPPLY STORAGE

OFFICE/SHIFT LEADER OFFICE/DISPATCH

PHYSICAL TRAINING RM

4 SIMILAR TO LG MULTIV MODEL ARNU073TUC4 OR APPROVED EQUAL.

SIMILAR TO LG MULTIV MODEL ARNU123TRC4 OR APPROVED EQUAL.

SIMILAR TO LG MULTIV MODEL ARNU153TQC4 OR APPROVED EQUAL.

1-WAY CEILING CASSETTE TYPE 8,5007,500 40290/258/226 0.23

13,60012,300 30307/283/2474-WAY CEILING CASSETTE TYPE 0.25

17,10015,400 30388/353/3284-WAY CEILING CASSETTE TYPE 0.25

NOTES :

OHPU

1 206,000184,000 R-410AINDOOR HEAT PUMP UNITS 421MULTI V 5 HEAT PUMP HSS DC SCROLL80 57.9 2 PROPELLER 2208/ 3/ 60

4 SIMILAR TO LG MULTI V 5 MODEL ARUM192BTE5 OR APPROVED EQUAL.

208/ 1/ 60 R-410A

HPU

1 115 2 1127,30024,200 33600/530/4594-WAY CEILING CASSETTE TYPE 0.19

POWER PLUG-IN CODE 12

SIMILAR TO LG MULTIV MODEL ARNU243TPC4 OR APPROVED EQUAL.

SIMILAR TO LG MULTIV MODEL ARNU283TPC4 OR APPROVED EQUAL.3

SIMILAR TO LG MODEL ARNU963B8Z4 OR APPROVED EQUAL. 4

DORMS

FIRE INSPECTORS

CORRIDORS

KIT/DINING DAYROOM

M E C H A N I C A L E Q U I P M E N T S C H E D U L E-1

EQUIPMENT SCHEDULE - 1

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

NOTE :

PREFABRICATED ROOF CURB.4

FANS

ITEM NO Q'TY SERVICE TYPE REMARKS

HP(Pa)(LPS)

RPM

ESPAIR CAP

VOLT/PH/HZ

FAN MOTOR

W/DISCONNECT SWITCH

BIRD SCREENW/BACKDRAFT DAMPER 3

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-4

DAY ROOM

(MM)

750Wx450D

TYPE

W/BACKDRAFT DAMPER

HOOD VENTED TYPE

STAINLESS STEEL

115/1/60

LIGHTING(75W)WASHABLE FILTER1 2 BUILT-IN CONTROL SWITCH3

RANGE HOODS

Q'TYITEM NO

FAN MOTORFAN

CAPACITY

(LPS)

75.5

SERVICE

2.0 AMPS 1

VOLT/PH/HZPOWER

HOOD SIZE

32 &

REMARKS

PROVIDE UNIT MTD. DISCONNECT SWITCH.EUH

POWER(KW)

HEATING ELEMENT CAP

VOLT/PH/HZ

208/1/60

REMARKS

TYPE

SERVICEQTY

NO

ELECTRIC UNIT HEATER

HORIZONTAL

T Y P E

DISCHARGE

ITEM FAN CAPACITY

165.2 1/100 208/1/601,600

RPM HP VOLT/PH/HZAIR CAP.(LPS)

ELECTRIC WALL HEATERS

ITEM NO QTY SERVICE T Y P E

WALL MTD

ELEMENT CAPACITY

120/ 1/ 601,500

TOTAL

VOLT/PH/HZ

REMARKS

(WATTS) AMPERAGE

12.5

UNITS SHALL BE PROVIDED WITH DISCONNECT

SWITCH AND INTEGRAL THERMOSTAT.

TOILET RM AND DRYING RM

1 CEMENT LINED

TYPE

STEEL ROUND HORIZONTAL

T Y P E

DOMESTIC HOT WATER STORAGE TANK

NO

ITEM

DT

QTY.SERVICE (DIAxOVERALL

TANK SIZE

LENGTH) (LIT.)

TANK CAP. REMARKS

DOMESTIC H.W

SYSTEM

915 DIA x 1,800 LONG1,136

EF

1 62.3 1,750 120/1/60 2 31

WALL MOUNTED TYPE,

DIRECT DRIVEN, CENTRIFUGAL FAN

1,230 1/4EXHAUST AIR FAN FOR MECH RM

EF

1 62.3 1,320 120/1/60 2 31

ROOF MOUNTED TYPE,

DIRECT DRIVEN, CENTRIFUGAL FAN

1/4

EXHAUST AIR FAN FOR MECH TOILET, SHOWER

LAUNDRY AND JC

EF

1 62.3 1,550 120/1/60 2 31

DIRECT DRIVEN, CENTRIFUGAL FAN

1/40

EXHAUST AIR FAN FOR FIRE INSPECTORS

AND DORM 35

EF

1 62.3 1,750 120/1/60 2 31

ROOF MOUNTED TYPE,

DIRECT DRIVEN, CENTRIFUGAL FAN

1/4

EXHAUST AIR FAN FOR FIRE INSPECTORS

AND DORM 700 4

EF

1 62.3 1,050 120/1/60 2 31

WALL MOUNTED TYPE,

DIRECT DRIVEN, CENTRIFUGAL FANSTORAGE

EXHAUST AIR FAN FOR MEDICAL SUPPLY

35 1/100

IN-LINE TYPE

RH KIT/DINING

BF

1 62.3 120/1/60 2 31

DIRECT DRIVEN, CENTRIFUGAL FAN

70EXHAUST AIR FAN FOR LAUNDRY

IN-LINE TYPE

0.72AMPS

MECH RM

M E C H A N I C A L E Q U I P M E N T S C H E D U L E-2

EH

EES

D E S C R I P T I O N

EMERGENCY SHOWER AND EYEWASH

Q'TY

ITEM

NO

ENCON MODEL NO. 01052155 OR APPROVED EQUAL.

A SILENCING SWITCH, AND A FLASHING STROBE LIGHT FOR EACH EES.

WATER FLOW-INITATED ALARM TO INCLUDE A LOCAL AUDIBLE SIGNAL DEVICE,

INLET WATER = 1-1/4"(32mm), 20GPM (1.3LPS)

EYE WASH HEAD AND SPRAY, SHOWER OPERATED BY

BRASSTOKE ASSEMBLY WITH TWIN AREATED

200mm DIAMETER SHOWER HEAD CHROME PLATED

UNIT SHALL BE COMPLETELY SELF CONTAINED. (32)

PULL CHAIN AND EYE WASH BY PUSH HANDLE,

- DISPLAYS RED BLINKING ALARM LIGHT WHEN ACTIVATED.

- TO INCLUDE INTERMITTENT PULSING SOUND WHEN

ACTIVATED, LOCAL RESET BUTTON TO SILENCE THE

AUDIBLE ALARM.

- UNIT SHALL BE FACTORY INSULATED.

EQUIPMENT SCHEDULE - 2

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-5

PER MANUFACTURER RECOMMENDATIONS.

ALL AC UNITS REFRIGERANT PIPING SHALL BE INSTALLED 1 CAPACITY SHALL BE BASED ON 35 DEG C

5 INDOOR EVAPORATOR UNIT CARRIER MODEL 40MVC-009 AND

OUTDOOR UNIT CARRIER MODEL 38MVC-009 OR APPROVED EQUAL.

N O T E :

SPLIT AIR CONDITIONING UNIT

QTY. REMARKS

CONDENSER FAN

VOLT/PH/HZ

POWERPOWER QTY

OUTDOOR UNIT

POWER VOLT/PH/HZ

QTY

(KW)

COOLING CAP

(LPS)

INDOOR EVAPORATOR UNIT

COMPRESSORSERVICEITEM NO T Y P E

AIR CAP.

SHALL BE PROVIDED WITH LOW AMBIENT KIT.3

EFFICIENCY

MIN.

(SEER)

PACKAGED SPLIT AIR COOLED TYPE

ACU

1 153.4

2.70

(0.75 TON)

1.10 FLA 35 DC 1 7.5 RLA

40.0 LRA

1 115/1/600.6 FLA 13.0

HIGH WALL DUCT FREE SPLIT COOLING SYSTEM

WITH REMOTE ELECTRONIC CONTROLLER.

21 43 5COMM RM

ITEM

NO

PUMPS

DOMESTIC HOT WATER

CIRC. PUMP

P

Q'TY

PIPE MOUNTED IN-LINE, DIRECT DRIVE

CENTRIFUGAL TYPE

SERVICE TYPE

0.19 41.8 1/4 115/1/60 1,725

(LPS)

CAPACITY

(KPa)

HEAD

HP VOLT/PH/HZ

MOTOR

RPM REMARKS

DOMESTIC HOT WATER

RECIRC. PUMP

P

PIPE MOUNTED IN-LINE, DIRECT DRIVE

CENTRIFUGAL TYPE

0.62 77.5 1/2 115/1/60 1,725

EXPANSION TANK

Q'TY

ET

SERVICE TYPE

ACCEPTANCE VOL.

(LITS)

REMARKS

PRESSURE(KPa)

WORKINGITEM

NO

206.8DIAPHRAGM TYPE

HEATING WATER

SYSTEM

ELECTRIC WATER COOLER

DESCRIPTIONQ'TYITEM NO

MODEL : HALSEY TAYLER HTHB-HVRGRN8BL-WF OR APPROVED EQUAL.

STANDARD 1010.

EITHER PUSH PADS ONE OF THE TWO AND BUILT-IN PRESSURE REGULATOR. MECHANICALLY AIR

COOLED WITH AIR COOLED CONDENSER & COMPRESSOR SHALL CONFORM TO ADA/ARI

BI-LEVEL WALL MOUNTED TYPE, BUBBLER SHALL BE ACTIVATED BY DEPRESSING

POWER : 10 AMPS, 115 V, 1 PH, 60 HZ.

CAPACITY : 30.3 LPH, 32.2 DEG C TO 10 DEG C.

EWC

M E C H A N I C A L E Q U I P M E N T S C H E D U L E-3

TYPEITEM NO SERVICE

Q'TY

HEAT

RECOVERY

ELEC. POWER

SUPPLY

TEMP RISE

TEMP

REMARKS

EFFICIENCY

CASCADE

SYSTEM2

DWH BLDG. DOMESTIC

HOT WATER SYSTEM

CMHkW

OUTPUT

GROSS

CMH

GAS

INPUT

VOLT/PH/HZFLA ? ?

2,882.8112 29.14 120/1/60 60.0 16.7 97.0

CSA CERTIFY PRODUCT OR APPROVED EQAL.

NAVIEN CONDENSING WATER HEATER MODEL NPE-240S X 2EA,

CIRC. PUMP

P

CENTRIFUGAL TYPE

3.5 150 208/3/60 1,800

HOT WATER BASE MOUNTED END SUCTION

PRESSURE (KPa)

MAX WORKING

AIR SEPARATOR

ITEM NO Q'TY

AS

PIPE SIZE

TYPESERVICE

INLET

REMARKS

OUTLET

206.965 DIAPIPE MOUNTED 65 DIA W/ BUILT-IN STRAINERHOT WATER SYSTEM

ET

1 206.884DIAPHRAGM TYPE

DOMESTIC WATER

SYSTEM

CMH

B

ITEM NO

BLDG. HEATING SYSTEM1

SERVICEQ'TY TYPE

VOLT/PH/HZ

120/1/60

ELEC. POWER

12.86

GAS

INPUT

kW

OUTPUT

GROSS

FLA ?

SUPPLY

80.0

WATER TEMP

kPa

WORKING

PRESS REMARKS

92.0

EFFICIENCY

CASCADE

SYSTEM

206.85

CSA CERTIFY PRODUCT, ASME CERTIFY PRODUCT OR APPROVED EQAL.

NAVIEN CONDENSING BOILER MODEL NCB-210 X 3EA,

GAS FIRED HOT WATER BOILER

GAS FIRED DOMESTIC HOT WATER HEATER

EQUIPMENT SCHEDULE - 3

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

LADDER

TRUCK

OPER

SUV

EWC

UP

UP

JC SHOWER

FIRE

ENGINE

OPER

SUV

FIRE

ENGINE

EH

EH

EUH

300x200

200x150 x

200x100

200x150

EF

EG-2, 150x150

7LPS(TYPE OF 5)

EG-2, 150x150

35LPS(TYPE OF 3)

EF

35LPS(TYPE OF 3)

EG-2, 150x150

40LPS

EG-2, 200x200 250x150

EF

O .A

AND MOTORIZED DAMPER

LOUVER W/BIRDSCREEN

260x260 O.A INTAKE

BACKDRAFT DAMPER

WALL CAP WITH

BF

BOOSTER FAN

150 DIA.

AND MOTORIZED DAMPER

LOUVER W/BIRDSCREEN

300x300 O.A INTAKE 200x150

(OUTDOOR UNIT)

AIR CONDITIONING UNIT

ACU

CONC. PAD

ACU

S

A

25 20

E

E

32 40 25

CONN, TO EXIST COLD WATER LINE

SEE CIV. DWG.

80 32

65 40

P DOMESTIC HOT WATER

CIRC. PUMP

INTAKE (W/ WIRE MESH)

150mmDIA COMBUSTION AIR

DOMESTIC HOT WATER

RE-CIRC. PUMP

P

STORAGE TANK

DOMESTIC HOT WATERDT

DWH

CONC. PAD

CONC. PAD

MOUNTED ON CEILING

GAS LEAK DETECTOR

150mm FLUE VENT

UP THRU ROOF SEE DETAIL

AUTOMATIC SHUT OFF VALVE

G

M

G

SEE CIV. DWG.

CONN, TO GAS LINE

GAS ALARM GONG

GAS LEAK DETECTION CONTROL PANEL

GAS FILTER

GAS REGULATOR

VALVE CABINET

GAS METER

GAS METER CABINET

SHUT UP VALVE

P

3CIRC. PUMP

HOT WATER

AS

AIR SEPARATOR

ET

EXPANSION TANK

E

ET

EXPANSION TANK

BACKFLOW PREVENTER &

PRESSURE REDUCING STATION

200mm FLUE VENT

UP THRU ROOF SEE DETAIL

200mmDIA COMBUSTION AIR

INTAKE (W/ WIRE MESH)

65 65

B

HEATING BOILER

GAS FIRED HOT WATER

HOT HEATER

GAS FIRED DOMESTIC

ROOM

FIRE INSPECTORS

102103104

DORM DORM DORM

CORRIDOR-2

TRAINING RM

PHYSICAL

STAIR-2

COMM RM

SHOWER

TOILET

WOMEN

JC

LAUNDRY

MEN TOILET

SHOWER

MECH RM

STORAGE

SUPPLY

MEDICAL

STAIR-1

142 101

APPARATUS-2

SCALE : 1 / 100

NEW 1ST FL HVAC PLAN - 1

- SCALE : 1 / 50 M-6

200DIA

200DIA

FROM SECOND FLOOR

RISERS TO & FROM

65 HWS/HWR PIPE

SEE

ENLARGED MECH ROOM PLAN

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC SYSTEM.

OF EQUIPMENTS, DUCTWORKS AND PIPING IN FIELD(TYP)

PRIOR TO EQUIPMENTS, DUCTWORKS AND PIPING INSTALLATION.

NEW 1ST FL HVAC PLAN-1, ENLARGED

MECH ROOM PLAN, CO/NITROGEN AND

NOTES

S W

M6

M6

M6

M M

T

OUT OF CONTRACT

TV

VDVD

VD

VD

VD

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

DN DN

EF

350x250 EXHAUST DUCT

RISER FROM FIRST FLOOR

EG-2

150x150

35LPS

V.D

V.D

200x100

200x100

200x150

300x150300x200

300x150

200x150 x

35LPS(TYPE OF 2)

EG-2, 150x150

115LPS

RG-1, 250x250

(TYP)

VOLUME DAMPER

115LPS

EG-1, 250x250

125LPS

EG-1, 250x250

VD

180LPS

EG-2, 350x350

EF

RISER FROM FIRST FLOOR

250x150 EXHAUST DUCT

200x150

RH

300x150

V D

125LPS

RG-1, 250x250

VD VD

EH

EH

FROM SECOND FLOOR

RISERS TO & FROM

65 HWS/HWR PIPE

TOILET

OFFICE

OFFICE

LEADER

SHIFT

DISPATCH

SHOWER

TOILET

CORRIDOR-3

DAYROOM

KITCHEN/DINING

CHIEF SUITE

STAIR-2

STAIR-1

APPARATUS

(BELOW)

SCALE : 1 / 100

NEW 2ND FL HVAC PLAN - 2

M-7

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC SYSTEM.

OF EQUIPMENTS, DUCTWORKS AND PIPING IN FIELD(TYP)

PRIOR TO EQUIPMENTS, DUCTWORKS AND PIPING INSTALLATION.

NEW 2ND FL HVAC PLAN-2 AND NOTES

M7

M M

M M

OUT OF CONTRACT

V.D

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

LADDER

TRUCK

OPER

SUV

UP

UP

JC

FIRE

ENGINE

OPER

SUV

APPARATUS

FIRE

ENGINE

O .A

MD

OAU

AND MOTORIZED DAMPER

LOUVER W/BIRDSCREEN

600x300 O.A INTAKE

150x100

V.D

200x150200x200250x200 150x100150x100

150x100 150x100 x x

100x100

V.D

V.D

V.D

V.D

44.4LPS(TYPE OF 5)

CD, 100DIA.

33.3LPS(TYPE OF 2)

CD, 75DIA.

ROOM

FIRE INSPECTORS

102103104

DORM DORM DORM

CORRIDOR-2

TRAINING RM

PHYSICAL

COMM RM

MECH RM

STORAGE

SUPPLY

MEDICAL

STAIR-1

SHOWER

JC

LAUNDRY

MEN TOILET

SHOWER

TOILET

WOMEN

APPARATUS-2

STAIR-2

SCALE : 1 / 100

NEW 1ST FL HVAC PLAN - 3

M-8

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF DUCTWORKS IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DUCTWORK.

PRIOR TO DUCTWORK INSTALLATION.

NEW 1ST FL HVAC PLAN-3 AND NOTES

M8

M M

T

OUT OF CONTRACT

V.D

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

DN DN

TOILET

MEN

MD

150x100

100x100 200x150 x 0 200x150

150x100

250x200200x150

150x100100x100

VD

VD

VD

VD VD

VD

VD

AND MOTORIZED DAMPER

LOUVER W/BIRDSCREEN

600x300 O.A INTAKE

OAU

58.3LPS(TYPE OF 4)

CD, 100DIA.

38.8LPS(TYPE OF 2)

CD, 75DIA.

TOILET

OFFICE

OFFICE

LEADER

SHIFT

DISPATCH

SHOWER

TOILET

CORRIDOR-3

DAYROOM

KITCHEN/DINING

CHIEF SUITE

STAIR-2

STAIR-1

APPARATUS

(BELOW)

SCALE : 1 / 100

NEW 2ND FL HVAC PLAN - 4

M-9

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF DUCTWORKS IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DUCTWORK.

PRIOR TO DUCTWORK INSTALLATION.

NEW 2ND FL HVAC PLAN-4 AND NOTES

M9

M M

M M

OUT OF CONTRACT

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

LADDER

TRUCK

OPER

SUV

UP

UP

JC

STAIR-1

STAIR-2

FIRE

ENGINE

OPER

SUV

FIRE

ENGINE

O .A

40mm CONDENSATE DRAIN

HPUHPUHPUHPU

OAU

HPU

HPU

OHPU

OHPU

HPU

RG: O 12.7

RL: O 6.35

RG: O 12.7

RL: O 6.35

RG: O 12.7

RL: O 6.35RL: O 9.52

RG: O 19.05

RL: O 9.52

RG: O 15.88

RG: O 15.88

RL: O 9.52

RG: O 12.7

RL: O 6.35 RL: O 9.52

RG: O 15.88

RL: O 9.52

RG: O 15.88

RG: O 28.58

RL: O 12.7

RG: O 28.58

RL: O 15.88

RL: O 6.35

RG: O 12.7

D: O32

D: O25

D: O25

D: O25

D: O25

RL: O 6.35

RG: O 12.7

RG: O 12.7

RL: O 6.35

ROOM

FIRE INSPECTORS

102103104

DORM DORM DORM

CORRIDOR-2

TRAINING RM

PHYSICAL

COMM RM

MECH RM

STORAGE

SUPPLY

MEDICAL

STAIR-1

SHOWER

JC

LAUNDRY

MEN TOILET

SHOWER

TOILET

WOMEN

APPARATUS-2

STAIR-2

SCALE : 1 / 100M10

NEW 1ST FL HVAC PLAN - 5

T

TTT

T

T

T

M-10

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF HEAT PUMP SYSTEM IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HEATPUMP SYSTEM.

PRIOR TO HEATPUMP SYSTEM INSTALLATION.

NEW 1ST FL HVAC PLAN-5 AND NOTES

13 10 10 10

M M

T

OUT OF CONTRACT

DORMITORY OF NEW FIRE STATION, K16

CONSTRUCT BUILDING FOR OFFICES AND

214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M1
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M2
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M3
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M4
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M5
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M6
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M7
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M8
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M9
214621_CONSTRUCT BUILDING FOR OFFICES AND DORMITORY OF NEW FIRE STATION, K16_M10