A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
DESCRIPTION OF CONTROL COMPONENTS
TO BE CONNECTED BY THE ELECTRICAL CONTRACTOR)
(TO BE SUPPLIED AND INSTALLED BY THE MECHANICAL CONTRACTOR,
MV-H
HF
HF
T
HOA
4. INLET/ OUTLET DAMPERS
MOTORIZED DAMPER IS IN THE CLOSED POSITION.
T THERMOSTAT
IN THE SEQUENCE OF OPERATIONS.
WALL OR UNIT MOUNTED ADJUSTABLE THERMOSTAT AS NOTED
: 120 VAC
HEATING MOTORIZED CONTROL VALVE
WITH SPRING RETURN OPEN UPON POWER INTERRUPTION.
ELECTRIC PROPORTIONAL TYPE, NORMALLY OPEN
INPUT VOLTAGE
STROKE
: 120 VAC
: 160°C
ACTUATOR
MOTORIZED VOLUME DAMPER
MD
TM
SPRING RETURN CLOSED ON POWER INTERRUPTION.
ELECTRIC PROPORTIONAL TYPE, NORMALLY CLOSED WITH
3 CFM/SQFT AT 1"WC.
MOTORIZED DAMPERS ARE TO BE LOW LEAKAGE TYPE,
TIMER CONTROLLER
REVERSE ACTING THERMOSTAT
IN THE SEQUENCE OF OPERATIONS.
WALL OR UNIT MOUNTED ADJUSTABLE THERMOSTAT AS NOTED
RSTAT
THRUHRE
STARTER
ON/OFF SWITCH
WALL MOUNTED
HOSE REEL
EXHAUST FAN
DAMPER
LOW LEAKAGE
@ 1" wg)
(3 CFM/SQ FT
CB
CONTROL BOX FAN SPEED CONTROLLER
: 120 VAC
CB
FOR BOTH CEILING FANS.
MANUFACTURER SUPPLIED WALL MOUNTED SPEED CONTROL BOX
6. SAFETIES
7. EMERGENCY SHUT DOWN BUTTON
THERMOSTAT
WALL MOUNTED
ON/OFF SWITCH
WALL MOUNTED
MV-H
HOA
STARTER
2. CONTROL
3. HOA STARTER
A.
5. POWER FAILURE
A.
A.
A.
THE EXHAUST FAN SHALL BE PROVIDED WITH A HOA SELECTOR STARTER.
C. AUTO :
B. OFF :
A. HAND :
TO OPEN WHEN EITHER OR BOTH BURNERS ARE ACTIVE.
ON THE HEATING WATER BOILER AND THE DOMESTIC HOT WATER BURNERS
THE INLET MOTORIZED DAMPER IS TO BE HARD WIRED TO THE BURNER
AND THE CONTROL DAMPER SHALL CLOSE.
UPON SIGNAL FROM THE FIRE ALARM PANEL THE EXHAUST FAN SHALL DISABLE
CONTROL DAMPER SHALL CLOSE.
UPON SIGNAL FROM THE ESB THE EXHAUST FAN SHALL DISABLE AND THE
SHALL BE CONTROLLED VIA WALL MOUNTED THERMOSTAT.
WITH THE H-O-A SWITCH IN AUTO POSITION THE EXHAUST FAN
WITH THE H-O-A SWITCH IN OFF POSITION THE FAN SHALL STOP.
SHALL ACTIVATE AND RUN CONTINUOUSLY.
WITH THE H-O-A SWITCH IN HAND POSITION, THE EXHAUST FAN
1. GENERAL
TAIL PIPE EXHAUST SYSTEM FOR GARAGES.
OPERATIONS.
WITH MANUFACTURER CONTROL SYSTEMS TO PERFORM THIS SEQUENCE OF
CONTRACTOR SHALL INSTALL ALL HARDWARE, SOFTWARE AND COORDINATE
B.
A.
NOT TO SCALE
THE FAN IS DEACTIVATED.
THE MOTORIZED DAMPER SHALL OPEN WHEN FAN IS OPERATING AND CLOSE WHEN
WALL MOUNTED ON AND OFF SWITCH SHALL ACTIVATE FAN AND DEACTIVATE FAN.
3. HOA STARTER
THE EXHAUST FAN SHALL BE PROVIDED WITH A HOA SELECTOR STARTER.
C. AUTO :
B. OFF :
A. HAND :
SHALL BE CONTROLLED VIA ON/OFF SWITCH.
WITH THE H-O-A SWITCH IN AUTO POSITION THE EXHAUST FAN
WITH THE H-O-A SWITCH IN OFF POSITION THE FAN SHALL STOP.
SHALL ACTIVATE AND RUN CONTINUOUSLY.
WITH THE H-O-A SWITCH IN HAND POSITION, THE EXHAUST FAN
5. SAFETIES
A.
AND THE CONTROL DAMPER SHALL CLOSE.
UPON SIGNAL FROM THE FIRE ALARM PANEL THE EXHAUST FAN SHALL DISABLE
6. EMERGENCY SHUT DOWN BUTTON
CONTROL DAMPER SHALL CLOSE.
UPON SIGNAL FROM THE ESB THE EXHAUST FAN SHALL DISABLE AND THEA.
1. GENERAL
MOUNTED ON WALL.
BY A VARIABLE SPEED WITH SUMMER-WINTER CHANGEOVER CONTROLLER
FANS ARE USED AS HEAT DESTRATIFICATION FANS AND ARE CONTROLLED
SHALL BE PROPORTIONAL-INTEGRAL (PI) CONTROL.
OPERATIONS. UNLESS OTHERWISE NOTED ALL MODULATING CONTROL
WITH MANUFACTURER CONTROL SYSTEMS TO PERFORM THIS SEQUENCE OF
CONTRACTOR SHALL INSTALL ALL HARDWARE, SOFTWARE AND COORDINATE
2. CONTROL
A. BOTH FANS SHALL OPERATE IN TANDEM WITH A SINGLE SPEED CONTROLLER.
4. POWER FAILURE
A.
EXHAUST SYSTEM (HRE-1, 2)
TRUCK EXHAUST HOSE REEL
EXHAUST HOSE
SYMBOL DESCRIPTION
INPUT VOLTAGE
VOLTAGE
STROKE
: 120 VAC
: 160°
ADJUSTABLE
TIME SETTING
INPUT VOLTAGE
: 30 MIN. INCURMENTS
: SEE SEQUENCE OF OPERATIONS
M
EMERGENCY SHUTDOWN
CONTACT FROM
UH
UH
HF
TRUCK EXHAUST HOSE REEL EXHAUST SYSTEM (HRE-1)
HEAT DESTRATIFICATION FAN (HF-1)
M-7
NOT TO SCALE-
1 HEAT DESTRATIFICATION FAN
NOT TO SCALE-
2 UNIT HEATER CONTROL
HEAT DESTRATIFICATION FAN AND
UNIT HEATER CONTROL
1. GENERAL
RUNNING FIRE TRUCKS.
EXHAUST FAN IS USE FOR APPARATUS BAY EXHAUST WHEN
TO PERFORM THIS SEQUENCE OF OPERATIONS.
AND COORDINATE WITH MANUFACTURER CONTROL SYSTEMS
CONTRACTOR SHALL INSTALL ALL HARDWARE, SOFTWARE
2. CONTROL
ARE BELOW 50 PPM (ADJUSTABLE).
(ADJUSTABLE). FAN SHALL DEACTIVATE WHEN CO LEVELS
OPEN WHEN THE CO SENSOR LEVELS ARE ABOVE 60 PPM
FAN SHALL ACTIVATE AND MOTORIZED DAMPERS SHALL
3. HOA STARTER
B.OFF:
A.HAND:
SELECTOR STARTER.
THE EXHAUST FAN SHALL BE PROVIDED WITH A HAND-OFF
SHALL STOP.
WITH THE H-O SWITCH IN OFF POSITION THE FAN
EXHAUST FAN SHALL ACTIVATE AND RUN CONTINUOUSLY.
WITH THE H-O SWITCH IN HAND POSITION, THE
5. POWER FAILURE
6. EMERGENCY SHUT DOWN BUTTON
4. MOTORIZED DAMPERS
ACTIVE ONLY.
MOTORIZED DAMPER SHALL OPEN ONLY WHEN FAN IS
M
M
M
FOR EF-5
SW
CO
DAMPER
LOW LEAKAGE
@ 1" wg)
(3 CFM/SQ FT
SHUTDOWN
EMERGENCY
CONTACT FROM
HO
NOT TO SCALE-
3 EXHAUST FAN
EF
EF
EXHAUST FAN (EF-6 & EF-12)
M7
M7
M7
OF NEW FIRE STATION, K16
CONSTRUCT BUILDING FOR BAYS
CHONG, ST
209625
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
FAN ACCESS DOOR
LOUVRE
EXHAUST AIR
CONNECTION
FLEX
ISOLATORS
SPRING
INDICATED ON DRAWINGS)
(MOTORIZED WHERE
BACKDRAFT DAMPER
EXHAUST AIR FAN
REFER TO SPECIFICATIONS
SEISMIC RESTRAINT
INSULATION
25 ACOUSTIC
3000 Min.
A
TOP STOCK
BOLT
INSULATION
PIPE
BOTTOM STOCK
SADDLE
PROTECTION
PIPE
STOCK
INSULATION
SADDLE
PROTECTION
C.I. ROLLER
2 x 3263
(UNIT : mm)
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
4 x 25
2 x 32 2 x 32
2 x 32
PIPE SIZE A STOCK SIZE
10 x 50
(UNIT : mm)
7 x 38
10 x 44
10 x 63
13 x 63
PIPE SIZE BOLT SIZEA TOP STOCK BOTTOM STOCK
"D
1"
PIPE
(TYP)
MAX.45°
4" 4"
MAX.12
NOTE:STEEL ANGLE
40x40x8 THK
(TYP OF 6)
BOLT & NUT
") 8
10 (
STEEL PLATE
") THK16
7 (
(TYP)
MAX. 45°
"D
PIPE
WELDED (TYP)
STEEL ANGLE
") THK4
(2"x2"x
50x50x8 THK
STEEL PLATE
" THK8
(4"x12"x
100x300x10
(2-1/2") AND LARGER.
PIPE SIZE FOR 65mm
"D2" IS NOMINAL
("2") AND SMALLER.
PIPE SIZE FOR 50mm
"D1" IS NOMINAL
2.
1.
UH
P
P
SUPPLY MAIN
HOT WATER
RETURN MAIN
HOT WATER
STRAINER
PIPE CAP
AIR VENT
AUTOMATIC
(TYP)
SHUT-OFF VALVE
UNION (TYP)
GUAGE (TYP)
TEMPERATURE
GUAGE (TYP)
PRESSURE
VALVE
CONTROL
THREE-WAY
HEATER
UNIT
BALANCE VALVE
DOUBLE PORT VENTURI
G.L
MASTIC
WATERPROOF
REDUCING TEE
CIVIL DRAWING
ELEVATION SEE
FOR INVERT
REDUCING TEE
UNION
13 FEMALE ADAPTER
WATER METER
PRESSURE GAUGE
MALE ADAPTER
GATE VALVE
MALE ADAPTER
FFL
20 HOSE BIBB
INSTALLATION
VERTICAL
SUITABLE FOR
STRAINER
FLOOR.
PIPE SLEEVE THRU
PIPE SLEEVE THRU FOOTING.
M-8
1 TYP INLINE EXHAUST FAN DETAIL
PIPE HANGER
WATER SERVICE
PIPE ANCHOR
HOT WATER PIPING TO UNIT HEATER
(THREE WAY CONTROL VALVE HORIZONTAL DISCHARGE)
2 3
4 5
DETAILS-2
M8 M8 M8
M8 M8
OF NEW FIRE STATION, K16
CONSTRUCT BUILDING FOR BAYS
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
DRAI
NCONDENSAT
E
D
RL
RS
ABOVE
C
EIL
IN
G
BE
LO
W
CEIL
IN
G
(O
UTD
OOR
UNI
T)
PIP
ES
T
HRU
TH
E W
AL
L
SP
LIT
T
YP
E
A/C U
NI
T
(IN
DOOR
UNI
T)
SP
LIT
T
YP
E
A/C U
NI
T
TH
ER
MOST
AT
C
ONTR
OLL
ER
PLU
S 10
0DUCT S
IZE
D U
C T
S
IZ
E P L U
S
EXHAUST DUCT
P
P
UH
AIR VENT
AUTOMATIC
HEATER
UNIT
VALVE
CONTROL
THREE WAY
STRAINER
UNION (TYP)
GUAGE (TYP)
TEMPERATURE
GUAGE (TYP)
PRESSURE
(TYP)
SHUT-OFF VALVE
PIPE CAP
SUPPLY MAIN
HOT WATER
RETURN MAIN
HOT WATER
BALANCE VALVE
DOUBLE PORT VENTURI
(TYP OF 3)
GATE VALVE
BACKFLOW PREVENTER
REDUCED PRESSURE
PIPE HANGER
(TYP OF 2)
PRESSURE GAUGE
STRAINER
PET COCK (TYP OF 2)
REDUCING TEE (TYP)
(TYP OF 2)
GAUGE TAPPING
GLOBE VALVE
UNION (TYP)
PRESSURE RELIEF VALVE
REDUCER
TO SYSTEM
CW
PRESSURE REDUCING VALVE
C
PIPE
(I
N C
L U
D
IN
G
IN
S U
L A T
IO
N
MEMBRANE
WATERPROOFING
CLAMPING FLANGE
WATERPROOFING
ANCHOR
MASONRY WALL
CONCRETE OR
INSULATION
PIPE WITHOUT
P
IP
E
D
IA
m m
ALL AROUND
MIN. 7 CLEARANCE
RUBBER OR PLASTIC)
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
EXTERIOR INTERIOR
METAL JACKET
INSULATION
SEALANT #10
PIPE SLEEVE
BACK UP MATERIAL
SEALANT #2
INSULATION
PIPE WITH
M-9
HOT WATER PIPING TO UNIT HEATER1
(THREE WAY CONTROL VALVE VERTICAL DISCHARGE) -
2 REF. PIPING ISOMETRIC DIAGRAM
WALL CAP DETAIL
BACKFLOW PREVENTER & PRESSURE REGULATING VALVE PIPE SLEEVE-THRU FOOTING
DETAILS-3
M9 M9 M9
M9 M9
OF NEW FIRE STATION, K16
CONSTRUCT BUILDING FOR BAYS
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SEALANT #2
(TYP)
METAL BAND
SLEEVE
CEILING
METAL JACKET
SLEEVE
INSULATION
INSULATION
PIPE WITHOUT
SEALANT #2
PIPE
ALL AROUND
7 MIN CLEARANCE
INSULATION
PIPE WITH
MASONRY WALL
CONCRETE OR
RUBBER OR PLASTIC)
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
BACK UP MATERIAL
SPRING CLIP TYPE
ESCUTCHEON
INSULATION
PIPE WITHOUT
SIZE AS REQ'D
STEEL CHANNEL
PIPE
ALL AROUND
MIN 7 CLEARANCE
#2,3 OR 4
SEALANT
PIPE
INSULATION
PIPE WITH
PLASTIC)
RUBBER OR
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
SLEEVE
INSULATION
INSULATION
C
METAL JACKET
SLEEVE
PIPE WITH INSULATIONPIPE WITHOUT INSULATION
P
IP
E
SEALANT #2
MATERIAL
BACK UP
FIN FLOOR
CEMENT
CLIP TYPE
SPRING
ESCUTCHEON
(TYP)
METAL BAND
PLASTIC)
RUBBER OR
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
7 MIN CLEARANCE
INSTRUCTIONS.
IN ACCORDANCE WITH MANUFACTURER'S LISTED INSTALLATION
FIRESTOPPING SHALL BE PROVIDED AND SHALL BE INSTALLED
UTILITY OR EQUIPMENT ROOMS.
PASSES THROUGH FLOORS OR CEILINGS, EXCEPT IN BOILER,
SURFACES WHERE EXPOSED PIPING, BARE OR INSULATED
ESCUTCHEONS SHALL BE PROVIDED AT ALL FINISHED
INSULATION
SLEEVE
NOTE:
SUCTION
RATE OF PUMP)
DISCHARGE
CALIBRATED
MOTOR
SUPPORT
450450
FIRST PIPE
SUPPORT
DISCHARGE
INCREASER
LEG SUPPORT
ADJUSTABLE
PER MFG.
FLEXIBLE CONNECTION
SUCTION
DIFFUSER
THERMOMETER
SUCTION
GATE VALVE
PRESS. GAGE
PRESS. GAGE(TYP)
6 SHUT-OFF COCK(TYP)
ANCHOR BOLT
150 ( MIN.)
NEOPRENE PAD
115 DIAL, 0-60PSI
THERMOMETER
FLOW RATE OF PUMP)
PIPE SIZE SHALL BE AS
CALIBRATED TRIPLE
DUTY VALVE(BALANCE TO
SHOWN ON PROJECT PLANS
FRONT ELEVATION
PUMP
ANCHOR BOLT
BEDPLATE
SIDE ELEVATION
SEE FRONT ELEVATION
APPROVED SHOP DWGS. FOR PUMP
FROM DIMENSION GIVEN ON
REINFORCED CONC. BASE CONSTRUCT
BASE MOUNTED CIRC. PUMP PIPING4
MANUAL
DAMPER
BACK DRAFT
WALL VENTILATOR DETAIL
BY MF
G.
WALL
OUTSIDE
VENTILATOR
WALL
RECOMMENDED BY MFG.
SCREWS SIZE & Q'TY AS
M-10
- M10
1 PIPE SLEEVE-THRU INTERIOR WALL
2 PIPE SLEEVE-THRU METAL WALL
3 PIPE SLEEVE-THRU FLOOR
DETAILS-4
M10 M10
M10 M10
OF NEW FIRE STATION, K16
CONSTRUCT BUILDING FOR BAYS
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
ELECTRIC WATER COOLER
NOTE : WATER COOLER SHELL BE STATIONARY
WATER-PROOF MEMBRANE
FLOOR DRAIN
SEE NOTE-2
AREA/PIT DRAIN
SEE NOTE-1
12550
AS REQ'D
REDUCING TEE
DRAINAGE PATTERN
DRAIN PIPE
AIR GAP FITTING
WALL
WASHER DRAIN STAND PIPE
FRONT VIEW SIDE VIEW
PIPE SLEEVE
DRAINS SHALL BE CONNECTED TO CAST IRON P-TRAP.
A CHROMIUM PLATED BRONZE, NICKEL BRONZE OR NICKEL BRASS STRAINER.
4. DRAINS SHALL HAVE A CAST IRON BODY AND SEEPAGE PAN AND
2. NEOPRENE RUBBER GASKET COMPRESSION TYPE JOINT.
FILL/BED
WATER-PROOF MEMBRANE
FINISH/TILE FLOOR
STRUCTURAL
DRAIN AND BACKWATER VALVE
SEE NOTE-2
A
SLAB
CEMENT
SEE NOTE-1
3.
STRUCTURAL
SLAB
CEMENT
FILL/BED
A
FINISH/TILE FLOOR
WATER-PROOF MEMBRANE
AOUTLET SIZE
FLOOR/SHOWER DRAIN
SEE NOTE-2
SEE NOTE-1
FINISH/TILE FLOOR
STRUCTURAL
SLAB
FILL/BED
CEMENT
A
1. WATER-PROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.
50 DRAIN
20 HW 50
20 CW
MACHINE
WASHING
CW & HW
225 W x 150 D x 150 H
SERVICE BOX
W/HOSE BIBB
WASHER VALVE
20 UNION
BOX
50mm OPEN
SIGHT DRAIN
40 VENT
50 STAND
PIPE
CAST IRON DRAIN PIPE
P-TRAP
ELECTRIC WATER COOLER
DRAIN/WATER CONNECTION
VENT PIPE
WATER HAMMER ARRESTOR
"C"
"D"
"A"
"B"
33-60
61-113
1-11
12-32
STAINLESS STEEL
FLOW CONTROL
TO LAST
FIXTURE
THREADED PLUG
SHELL
ORIFICE
TYPE HEIGHT DIAMETER
FROM BRANCH
FIXTURE UNIT
SUPPLY
CAPACITY
DWGS FOR LOCATION
20 OR 25 SEE
AND SIZE
H E
IG
H T
FLUID
STAINLESS STEEL
ADAPTOR
BELLOWS
DISPLACEMENT
DISPLACEMENT
PRESSURE PNEUMATIC
HYDRAULIC
CUSHION
DIAMETER
M-11
M11
DETAILS-5
M11 M11
M11
OF NEW FIRE STATION, K16
CONSTRUCT BUILDING FOR BAYS
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
INDIRECT FLOOR DRAIN
TYPICAL IN LINE PUMP PIPING DETAIL
DISCHARGE
SUCTION
CALIBRATED BALANCING
NOTES : 1.WATER-PROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.
PLUG Y-BRANCH
WHEN NOT THRU RUN
1/8 BEND
LEAD CAULKING
JUTE PACKING, SEE NOTE-2
FINISH FLOOR
NEOPRENE GASKET
2.CHROMIUM-PLATED BRONZE, NICKEL BRONZE,NICKEL BRASS OR
STAINLESS STEEL FLUSH TYPE ACCESS COVER PLATE
FLOOR CLEANOUT
CAST IRON
PIPE
Y-BRANCH
SCORIATED COVER
SEE NOTE-2
TWO PIECE THREADED
ADJUSTABLE HOUSING
WATER-PROOF MEMBRANE
PRESSURE GAUGE
(TYP)
SHUT-OFF COCK
PROVIDE CHECK VALVE
DOMESTIC HOT WATER
RECIRULATION PUMP
IN DISCHARGES
VALVE
(TYP OF 3)
BACK FLOW PREVENTER & PRESSURE REDUCING STATION
50mm INDIRECT DRAIN
CW
WATER METER
UNION
REDUCER
UNION
M
COCK (TYP OF 2)
TO NEAREST FLOOR DRAIN
( TYP OF 2 )
PRESSURE GAGE
PRESSURE REDUCING VALVE
REDUCING TEE (TYP)
UNION
6 SHUT-OFF
UNION
REDUCER
TO SYSTEM
STRAINER
BALL VALVE
UNION
GLOBE VALVE
UNION (TYP)
TYPE BACK-FLOW PREVENTER
UNION
REDUCED PRESSURE PRINCIPLE GLOBE VALVE
CAST IRON P-TRAP
CAST IRON
CONNECTOR
CAST IRON PIPE
FINISH
FL.
G A
P 150 MIN
(M
IN
(M
IN
100MIN
CAST IRON PIPE
FLOOR DRAIN MODIFIED AS SHOWN
OR ADJUSTABLE BRASS COLLAR
FLOOR LEVEL GRATE ASSEMBLY
MAY BE REPLACED BY FUNNEL AND
ADJUSTABLE STRAINER BODY
BRASS FUNNEL
REMOVABLE STRAINER
BRASS RING BRAZED TO
BRASS HOLDING SCREW, 3REQ'D
CHROME PLATED
REMOVABLE CONE SHAPED
INDIRECT DRAIN
SCREEN. BRONZE OR COPPER
REMOVABLE CHROME PLATED
EMERG. EYE WASH SHOWER DETAIL
A 200 DIA BOLT CIRCLE
90 DIA HOLES ON
225 DIA FLANGE WITH
250 DELUGE SHOWER HEAD
VALVE
SELF-CLOSING BALL
PLUGGED NIPPLE
15 IPS BRASS
32 IPS DRAIN
SELF-CLOSING
BALL VALVE
"A"
25 IPS BRASS
250DIA
"A"
,1
T
O
F L O
O R
,1
T
O
F L O
O R
DRAIN
32 IPSPUSH
250DIA
"A-A" VIEW
32 IPS SUPPLY INLET
250DIA
P U
S H
SUPPLY INLET
OPTIONAL 32 IPS
M12-
M-12
DETAILS-6
M12 M12
M12 M12
OF NEW FIRE STATION, K16
CONSTRUCT BUILDING FOR BAYS
| 209625_CONSTRUCT BUILDING FOR BAYS OF NEW FIRE STATION, K16_M7 |
| 209625_CONSTRUCT BUILDING FOR BAYS OF NEW FIRE STATION, K16_M8 |
| 209625_CONSTRUCT BUILDING FOR BAYS OF NEW FIRE STATION, K16_M9 |
| 209625_CONSTRUCT BUILDING FOR BAYS OF NEW FIRE STATION, K16_M10 |
| 209625_CONSTRUCT BUILDING FOR BAYS OF NEW FIRE STATION, K16_M11 |
| 209625_CONSTRUCT BUILDING FOR BAYS OF NEW FIRE STATION, K16_M12 |
File details come from the government source that posted it.