CODE REQUIRED SIGNAGE rev. 10/15/2014
TYPE OF SIGN WHERE REQUIRED CODE REFERENCES SIGN STATES SIZE/ARRANGEMENT SIGN REFERENCE SAMPLE SIGN ELEVATION
ACCESSIBILITY
ANSI 117.1 703
EXIT SIGN
A tactile sign stating EXIT and complying with ICC A117.1 shall be provided adjacent to each door to an area of refuge, an exterior area for assisted rescue, an exit stairway, an exit ramp, an exit passageway and the exit discharge.
IBC 1011.3
LSC 7.10.1.3
Raised Lettering/Braille. 5'-3" to top of sign. E-1, E-D, E-U
EVACUATION
PLAN
Provide at Elevator Lobbies and back of Hotel rooms IBC 3008.2
Graphic depiction of floor, you are here location, exits, stairs, elevators. May include EL-1 sign
The building is to have an approved fire safety and evacuation plan in compliance with section 404 of the IFC.
Mount w/ top of sign at 5'-3" unless includes EL-1 in which case mount with bottom 2-in above elevator call button.
EP-1
ROOM
IDENTIFICATION
INTERIOR ENTRANCES TO
GUEST ROOMS, TENANT
SPACES, APARTMENTS,
PATIENT ROOMS,
CLASSROOMS, ASSEMBLY
ROOMS.
ANSI 117.1 703.1 Raised Lettering/Braille R-1
MISCELLANEOUS
TYPE OF SIGN WHERE REQUIRED CODE REFERENCES SIGN STATES SIZE/ARRANGEMENT SIGN REFERENCE SAMPLE SIGN ELEVATION
LAWFUL
OCCUPANCY
Maximum occupant load of assembly rooms. IBC 1004.3
Post in Group A assembly occupancy spaces with > 50 persons. Recommended Height is 8-ft to bottom. No code required format. Some municipaility's sign is a framed 8 1/2" x 11" certificate
O-1
FIRE FIGHTING EQUIPMENT
CABINETS
STANDPIPES, FIRE HOSES, FIRE
EXTINGUISHERS AND FIRE
DEPARTMENT VALVES WITHOUT
CLEAR DOORS, PICTOGRAPHS
OR OTHER APPROVED MEANS
OF IDENTIFICATION.
IBC 905.7.1
FIRE EXTINGUISHER
or FIRE HOSE VALVE or
AUTOMATIC
SPRINKLER RISER
Provide signs with letters 2 in.
min.; Char. & background contrast
Provided with Cabinet or cabinet with glazing.
Provide at FP equip rooms
TYPE OF SIGN WHERE REQUIRED CODE REFERENCES SIGN STATES SIZE/ARRANGEMENT SIGN REFERENCE SAMPLE SIGN ELEVATION
NO SMOKING
Signs are to be posted in conspicuous locations in each structure or location in which smoking is prohibited and locations with hazardous materials.
IFC 310.3 "NO SMOKING"
The content, lettering, size, color and location of required "No Smoking" signs is to be approved. Sign bottom 5'-0" aff.
H-1
ELECTRICAL
ROOM
Room designation sign or hazard identification sign, below IFC 605.3.1 ELECTRICAL ROOM
Doors into electrical control panel rooms are to be marked with a plainly visible and legible sign.
R-1
GOOD PRACTICE / WHERE REQUESTED
NO EXIT If likely to be mistaken for an exit door sign with “NO EXIT” LSC 7.10.8.3 "NO EXIT"
Letters in "NO" must be 2" high and 3/8" stroke width; letters in "EXIT" must be 1" high and below "NO" per LSC
D-4
TYPE OF SIGN WHERE REQUIRED CODE REFERENCES SIGN STATES SIZE/ARRANGEMENT SIGN REFERENCE SAMPLE SIGN ELEVATION
STAIRWELL
STORAGE
Signage restricting storage of any kind in the stairwell.
Restricting storage and bike parking in stairwells.
No requirement NOTICE N-2