This solicitation requests proposals for the construction and renovation of family housing at Wright-Patterson Air Force Base in Ohio. The project includes whole-house interior and exterior modernization of 29 government-owned houses of various sizes, from three to six bedrooms. Scope of work encompasses upgrades to exteriors, building systems, and interior spaces. Functional improvements may include kitchen, bathroom and closet reconfiguration as well as garage expansion. Work will be completed through phased renovations under a single firm-fixed-price construction contract awarded using a best value tradeoff evaluation of technical qualifications, past performance, and price by the Department of the Army Corps of Engineers Louisville District. The solicitation is available through the System for Award Management and questions can be directed to the specified contracting officer by email.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T EUS Army Corps of Engineers ®
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
VOLUME:
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
G-001
C O
V E
R S
H E
E T
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G P
L
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
J W
IL
K
E R
S O
N
N B
E R
B E
R
IC
H
S D
E G
A R
O
R C
U R
R A
N
D E
C E
M B
E R
W Q
R -1
-F
-0
CORRECTED FINAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
LOUISVILLE DISTRICT
W912QR-19-F-0263
WRIGHT-PATTERSON AFB, DAYTON, OHIO
IMPROVE FAMILY HOUSING
P2: 476088
TYPE B
F
IL
E N
U M
B E
R
TYPE B
A C
O R
R E
C T
E D
F
IN
A L
D E
C E
M B
E R
C
E R
T
IF
IE
D
F
IN
A L
S U
B M
IT
T
A L
JA
N
U A
R Y
CERTIFIED FINAL SUBMITTAL
JA
N
U A
R Y
JANUARY 2021
1/21/21
18 February 2021
W912QR21R0013
W
2Q R
R
-0
ARIMS: 200A DIsposition: Maintain for 15yrs after construction
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
G-002
D R
A W
IN
G
I N
D E
X
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G P
L
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
J W
IL
K
E R
S O
N
N B
E R
B E
R
IC
H
S D
E G
A R
O
R C
U R
R A
N
D E
C E
M B
E R
W Q
R -1
-F
-0
CORRECTED FINAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
F
IL
E N
U M
B E
R
TYPE B
SHEET INDEX
SHEET
NUMBER SHEET NAME
ED102 FIRST FLOOR PLAN - ELECTRICAL - DEMOLITION
ED103 SECOND FLOOR PLAN - ELECTRICAL - DEMOLITION
ED104 THIRD FLOOR PLAN - ELECTRICAL - DEMOLITION
EL101 BASEMENT FLOOR CEILING PLAN - LIGHTING
EL102 FIRST FLOOR CEILING PLAN - LIGHTING
EL103 SECOND FLOOR CEILING PLAN - LIGHTING
EL104 THIRD FLOOR CEILING PLAN - LIGHTING
EP101 BASEMENT FLOOR PLAN - POWER
EP102 FIRST FLOOR PLAN - POWER
EP103 SECOND FLOOR PLAN - POWER
EP104 THIRD FLOOR PLAN - POWER
E-601 SCHEDULES - ELECTRICAL
E-602 SCHEDULES - ELECTRICAL
T-001 GENERAL INFORMATION - SYSTEMS
TD101 BASEMENT FLOOR PLAN - SYSTEMS - DEMOLITION
TD102 FIRST FLOOR PLAN - SYSTEMS - DEMOLITION
TD103 SECOND FLOOR PLAN - SYSTEMS - DEMOLITION
TD104 THIRD FLOOR PLAN - SYSTEMS - DEMOLITION
T-101 BASEMENT FLOOR PLAN - SYSTEMS
T-102 FIRST FLOOR PLAN - SYSTEMS
T-103 SECOND FLOOR PLAN - SYSTEMS
T-104 THIRD FLOOR PLAN - SYSTEMS
T-501 DETAILS - SYSTEMS
SHEET INDEX
SHEET
NUMBER SHEET NAME
G-001 COVER SHEET
G-002 DRAWING INDEX
GI001 CODE SUMMARY
GI002 FIRE PROTECTION / LIFE SAFETY CODE REVIEW
GI003 LIFE SAFETY PLAN
S-001 STRUCTURAL NOTES
S-002 STRUCTURAL NOTES
S-101 FOUNDATION PLAN
S-102 1ST FLOOR FRAMING PLAN
S-103 2ND FLOOR AND LOW ROOF FRAMING PLAN
S-104 3RD FLOOR FRAMING PLAN
S-105 ROOF FRAMING PLAN
S-106 SHEARWALL PLAN
S-501 FOUNDATION DETAILS
S-505 FRAMING DETAILS
S-506 FRAMING DETAILS
S-507 FRAMING DETAILS
A-001 GENERAL INFORMATION
AD101 BASEMENT DEMOLITION PLAN
AD102 1ST FLOOR DEMOLITION PLAN
AD103 2ND FLOOR DEMOLITION PLAN
AD104 3RD FLOOR DEMOLITION PLAN
AD105 ROOF DEMOLITION PLAN
A-101 BASEMENT PLAN
A-102 1ST FLOOR PLAN
A-103 2ND FLOOR PLAN
A-104 3RD FLOOR PLAN
A-105 ROOF PLAN
A-106 BASEMENT REFLECTED CEILING PLAN
A-107 1ST FLOOR REFLECTED CEILING PLAN
A-108 2ND FLOOR REFLECTED CEILING PLAN
A-109 3RD FLOOR REFLECTED CEILING PLAN
A-201 BUILDING ELEVATIONS
A-202 BUILDING ELEVATIONS
A-301 BUILDING SECTIONS
A-302 ENLARGED WALL SECTIONS
A-303 ENLARGED WALL SECTIONS
A-304 ENLARGED WALL SECTIONS
A-401 ENLARGED PLANS
A-402 ENLARGED PLANS
A-403 INTERIOR ELEVATIONS
A-404 INTERIOR ELEVATIONS
A-501 DETAILS
A-502 DETAILS
A-503 DETAILS
A-504 DETAILS
A-505 CASEWORK DETAILS
A-506 DETAILS
A-507 DETAILS
A-601 DOOR/WINDOW SCHEDULES & DOOR ELEVATIONS
A-602 HEAD AND JAMB DETAILS & WINDOW ELEVATIONS
A-603 HEAD AND JAMB DETAILS
I-110 TYPE B BASEMENT FINISH PLAN
I-111 TYPE B FIRST FLOOR FINISH PLAN
I-112 TYPE B SECOND FLOOR FINISH PLAN
I-113 TYPE B THIRD FLOOR FINISH PLAN
I-211 TYPE B FINISH ELEVATIONS
I-212 TYPE B FINISH ELEVATIONS
I-601 TYPE B FINISH SCHEDULES AND DETAILS
FX101 BASEMENT FIRE SPRINKLER PLAN
FX102 FIRST FLOOR FIRE SPRINKLER PLAN
FX103 SECOND FLOOR FIRE SPRINKLER PLAN
FX104 THIRD FLOOR FIRE SPRINKLER PLAN
P-001 GENERAL INFORMATION - PLUMBING
PD101 BASEMENT FLOOR PLAN - PLUMBING - DEMOLITION
PD102 FIRST FLOOR PLAN - PLUMBING - DEMOLITION
PD103 SECOND FLOOR PLAN - PLUMBING - DEMOLITION
P-101 BASEMENT FLOOR PLAN - SANITARY WASTE AND VENT
P-102 FIRST FLOOR PLAN - SANITARY WASTE AND VENT
P-103 SECOND FLOOR PLAN - SANITARY WASTE AND VENT
P-104 BASEMENT FLOOR PLAN - DOMESTIC WATER
P-105 FIRST FLOOR PLAN - DOMESTIC WATER
P-106 SECOND FLOOR PLAN - DOMESTIC WATER
P-501 DETAILS - PLUMBING
P-601 SCHEDULES - PLUMBING
P-901 DIAGRAMS - PLUMBING
M-001 NOTES, SYMBOLS AND ABBREVIATIONS - MECHANICAL
MD101 BASEMENT FLOOR PLAN - MECHANICAL - DEMOLITION
MD102 FIRST FLOOR PLAN - MECHANICAL - DEMOLITION
MD103 SECOND FLOOR PLAN - MECHANICAL - DEMOLITION
MD104 THIRD FLOOR PLAN - MECHANICAL - DEMOLITION
M-101 BASEMENT FLOOR PLAN - MECHANICAL
M-102 FIRST FLOOR PLAN - MECHANICAL
M-103 SECOND FLOOR PLAN - MECHANICAL
M-104 THIRD FLOOR PLAN - MECHANICAL
M-501 DETAILS - MECHANICAL
M-601 SCHEDULES - MECHANICAL
M-602 SCHEDULES - MECHANICAL
M-401 ENLARGED PLAN AND SECTIONS - MECHANICAL
M-901 3D - MECHANICAL ROOM
E-001 GENERAL INFORMATION - ELECTRICAL
ED101 BASEMENT FLOOR PLAN - ELECTRICAL - DEMOLITION
A C
O R
R E
C T
E D
F
IN
A L
D E
C E
M B
E R
C
E R
T
IF
IE
D
F
IN
A L
S U
B M
IT
T
A L
JA
N
U A
R Y
CERTIFIED FINAL SUBMITTAL
JA
N
U A
R Y
1/21/21 W
2Q R
R
-0
UFC 1-200-01 - GENERAL BUILDING REQUIREMENTS, 20 JUNE 2016,
CHANGE 2, 01 NOV 2018
UFC 3-600-01 - FIRE PROTECTION ENGINEERING FOR FACILITIES, 8 AUG
2016, CHANGE 2, 25 MAR 2018
UFC 4-711-01 - FAMILY HOUSING, 10 AUG 2018
INTERNATIONAL RESIDENTIAL CODE (IRC), 2018 ED.
NFPA 13D - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
IN ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES,
2019 ED.
NFPA AUTOMATIC SPRINKLER SYSTEMS FOR RESIDENTIAL
OCCUPANCIES HANDBOOK, 2016
NFPA 291 - RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND
MARKING OF HYDRANTS, 2019
WRIGHT-PATTERSON AIR FORCE BASE DESIGN GUIDE, MARCH 2016
MODIFICATIONS TO THE
APPLICABLE CODES PER UFC
USE / OCCUPANCY SINGLE-FAMILY DWELLING (DETACHED): RESIDENTIAL
MULTIPLE SINGLE-FAMILY DWELLING (ATTACHED): RESIDENTIAL
GARAGES*:
NEW DETACHED: RESIDENTIAL, ACCESSORY TO DWELLING UNIT
NEW ATTACHED: RESIDENTIAL
SHEDS - REPURPOSED EXISTING GARAGES FOR STORAGE:
RESIDENTIAL, ACCESSORY TO DWELLING UNIT
*SEE SHEET G-002 FOR TABLE OF NEW/EXISTING GARAGES/SHEDS
FIRE RESISTANT
CONSTRUCTION
1-HOUR FIRE-RESISTIVE CONSTRUCTION MUST BE PROVIDED
BETWEEN ATTACHED DWELLING UNITS AND BETWEEN DWELLING
UNITS AND ATTACHED PARKING/GARAGES. THIS SEPARATION
WILL BE BOTH VERITICAL AND HORIZONTAL. IT WILL BE
CONSTRUCTED AS A 1 HOUR FIRE BARRIER. ANY DOORS IN THE
FIRE RATED WALL WILL BE RATED A MINIMUM OF 45 MINUTES.
STRUCTURES DETACHED AND LOCATED A MINIMUM OF 5 FT FROM
THE LOT LINE OR OTHER STRUCTURES DO NOT REQUIRE FIRE
RESISTIVE SEPARATION.
INTERIOR FINISHES FLAME SPREAD: 200 OR LESS ON WALL AND CEILING FINISH
SMOKE DEVELOPED: 450 OR LESS ON WALL AND CEILING
FINISH.
FIRE PROTECTION
SYSTEMS
FIRE SPRINKLER SYSTEMS: BUILDINGS TO BE FULLY SPRINKLERED PER NFPA
13D. NFPA 13D ALLOWS SOME AREAS NOT TO BE PROTECTED BY SPRINKLER.
THESE LOCATIONS ARE NOTED ON THE DRAWINGS. GARAGES ARE NOT
REQUIRED TO BE SPRINKLERED. EXTERIOR STORAGE WITH NO ENTRY TO MAIN
DWELLING NOT REQUIRED TO BE SPRINKLERED.
FIRE ALARM SYSTEMS. A BUILDING FA SYSTEM IS NOT REQUIRED. SMOKE
ALARMS AND CARBON MONOXIDE ALARMS ARE TO BE PROVIDED AS INDICATED
BELOW. SEE ELECTRICAL PLANS FOR LOCATIONS PROVIDED. NFPA 13D DOES
NOT REQUIRE THAT THE SPRINKLER SYSTEM BE MONITORED FOR TAMPER
(NPFA 13D 7.1.2) OR FLOW (NFPA 13D 7.6) AS THE BUILDING IS EQUIPPED WITH
SMOKE ALARMS.
SMOKE ALARMS. MULTIPLE-STATION, INTERCONNECTED, HARD-WIRED, 120 VAC
WITH 9V BATTERY BACKUP SMOKE ALARMS SHALL BE PROVIDED INSIDE EACH
SLEEPING ROOM, OUTSIDE EACH SLEEPING AREA IN THE IMMEDIATE VICINITY
OF THE BEDROOMS AND AT LEAST ONE ON EACH FLOOR, INCLUDING THE
BASEMENT. SMOKE ALARMS ARE NOT REQUIRED IN CRAWL SPACES. SMOKE
ALARMS SHALL NOT BE INSTALLED WITHIN 3FT OF A BATHROOM WITH A TUB OR
SHOWER OR WITHIN 6FT OF PERMANENT INSTALLED COOKING APPLIANCES.
SMOKE ALARMS SHALL BE LISTED IN ACCORDANCE WITH UL 217 AND COMPLY
WITH NFPA 72 AND IRC R314.
CARBON MONOXIDE (CO) ALARMS. MULTIPLE-STATION, INTERCONNECTED,
HARD-WIRED, 120 VAC WITH 9V BATTERY BACKUP CO ALARMS SHALL BE
PROVIDED OUTSIDE EACH SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
BEDROOMS AND IN ROOMS WITH FUEL-FIRED APPLIANCES. CO ALARMS SHALL
BE LISTED IN ACCORDANCE WITH UL 2034 AND COMPLY WITH IRC R315.
COMBINATION SMOKE/CO ALARMS. COMBINATION SMOKE AND CO ALARMS
SHALL BE PERMITTED IN LIEU OF SMOKE ALARMS. COMBINATION SMOKE/CO
ALARMS SHALL BE LISTED IN ACCORDANCE WITH UL 2034 AND UL 217.
MEANS OF EGRESS EGRESS DOOR: AT LEAST ONE EGRESS DOOR SHALL BE PROVIDED
FOR EACH DWELLING UNIT. THE EGRESS DOOR SHALL BE SIDE-
HINGED AND SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32 INCHES
WHEN MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
WITH THE DOOR OPEN 90 DEGREES. THE MINIMUM CLEAR HEIGHT OF
THE DOOR OPENING SHALL NOT BE LESS THAN78 INCHES IN HEIGHT
MEASURED FROM THE TOP OF THE THRESHOLD TO THE BOTTOM OF
THE STOP. OTHER DOORS SHALL NOT BE REQUIRED TO COMPLY WITH
THESE MINIMUM DIMENSIONS. EGRESS DOORS SHALL BE READILY
OPENABLE FROM INSIDE THE DWELLING WITHOUT THE USE OF A KEY
OR SPECIAL KNOWLEDGE OR EFFORT.
STAIRWAYS: STAIRWAYS MUST BE A MINIMUM OF 36 INCHES WIDE
(CLEAR WIDTH). HANDRAILS CANNOT PROJECT MORE THAN 4 ½
INCHES INTO EITHER SIDE OF THE STAIRWAY. HEADROOM IN
STAIRWAYS MUST NOT BE LESS THAN 6’8”. STAIR RISE BETWEEN
FLOOR LEVELS OR LANDINGS MUST NOT EXCEED 147 INCHES.
EMERGENCY ESCAPE WINDOW: BASEMENTS, HABITABLE ATTICS, AND
EVERY SLEEPING ROOM IS REQUIRED TO HAVE AT LEAST ONE
OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING. THE
OPENING MUST HAVE A MINIMUM OPENING AREA OF 5.7 SQUARE
FEET. THE NET HEIGHT MUST NOT BE LESS THAN 24 INCHES AND THE
NET CLEAR WIDTH MUST NOT BE LESS THAN 20 INCHES.
CEILING HEIGHTS MUST BE A MINIMUM OF 7’-0” (EXCEPT BASEMENTS
WHICH MUST BE A MINIMUM OF 6’-8”).
CONTINUOUS MEANS OF EGRESS. THE MEANS OF EGRESS MUST BE
CONTINUOUS AND UNOBSTRUCTED. IT MUST NOT REQUIRE TENANTS
TO PASS THROUGH THE GARAGE (IRC §R311.1).
HALLWAYS: HALLWAYS MUST BE AT LEAST 3 FEET WIDE (IRC §R311.6).
HANDRAILS: HANDRAILS MUST BE PROVIDED ON AT LEAST ONE SIDE
OF STAIRS WITH 4 OR MORE RISERS (IRC §R311.7.8). HANDRAILS
SHALL BE NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES
ABOVE THE SLOPED PLANE ADJOINING THE TREAD NOSINGS.
HANDRAILS MUST NOT PROJECT MORE THAN 4 ½ INCHES ON EITHER
SIDE (IRC §R311.7.8.2). HANDRAILS MUST HAVE AT LEAST 1 ½ INCHES
OF SPACE BETWEEN THE HANDRAIL AND WALL.
CODES AND STANDARDS
REFERENCED HEREIN
UFC DOCUMENTS DESCRIBE HOW THE BUILDING AND LIFE
SAFETY CODES ARE TO BE APPLIED:
UFC 1-200-01, GENERAL BUILDING REQUIREMENTS
UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES
UFC 4-711-01, FAMILY HOUSING
THE REQUIREMENTS ON THIS SHEET ARE BASED ON THESE
DOCUMENTS. WHERE THE UFC DOCUMENTS CONFLICT, THE
STRICTEST REQUIREMENT IS APPLIED.
THIS REVIEW IS APPLICABLE TO ALL HOUSING UNIT TYPES AND
GARAGES. SPECIFIC EXCEPTIONS ARE NOTED AS NEEDED.
BUILDING CODE VERSION INTERNATIONAL RESIDENTIAL CODE, 2018 EDITION*
*NOTE THAT IBC DIRECTS THE USER TO IRC (UFC
3-600-01 PER UFC 1-200-01 SECTION 1-4.2). IRC IS THE
PRIMARY CODE.
EXISTING FACILITY REQUIREMENTS ARE PROVIDED IN UFC
3-600-01 SECTION 34-6. SINCE THE RENOVATIONS IN THIS
FACILITY EXCEED 50% OF THE REPLACEMENT COST THE
FACILITY MUST COMPLY WITH REQUIREMENTS UNDER SECTION
34-6.1 WHICH INCLUDE THE FOLLOWING:
1-HOUR FIRE-RESISTIVE CONSTRUCTION MUST BE PROVIDED
BETWEEN DWELLING UNITS, AND BETWEEN THE DWELLING UNIT
AND ATTACHED PARKING.
SPRINKLER PROTECTION MUST BE PROVIDED THROUGHOUT
THE FACILITY, DESIGNED AND INSTALLED IN ACCORDANCE WITH
NFPA 13D.
MULTIPLE-STATION, INTERCONNECTED, HARD-WIRED, 120 VAC
SMOKE DETECTORS MUST BE PROVIDED INSIDE EACH SLEEPING
ROOM AND AT LEAST ONE ON EACH FLOOR, INCLUDING
BASEMENTS.
AIR FORCE ALLOWS INTERCONNECTED WIRELESS SMOKE
ALARMS FOR USE IN SINGLE-FAMILY HOUSING.
IRC APPENDIX J PROVIDES ADDITIONAL REQUIREMENTS AND
REQUIRES THAT THE CONSTRUCTION BE CLASSIFIED. WORK IS
PRIMARILY “ALTERATION” AND “REPAIR”; HOWEVER, SINCE THE
FACILITY CANNOT BE OCCUPIED DURING THIS WORK IT WILL BE
CLASSIFIED AS “RECONSTRUCTION” UNDER IRC AJ601. THIS WILL
REQUIRE THE FOLLOWING TO BE IMPLEMENTED:
NEWLY CONSTRUCTED ELEMENTS MUST COMPLY WITH THE
REQUIREMENTS OF THE IRC (SEE TWO EXCEPTIONS UNDER
AJ501.1 FOR WINDOWS AND ELECTRICAL EQUIPMENT).
STAIRWAYS MUST BE PROVIDED WITH ILLUMINATION IN
ACCORDANCE WITH R303.7. INTERIOR STAIRWAYS MUST BE
PROVIDED WITH ILLUMINATION OF NOT LESS THAN 1 FOOT
CANDLE. PROVIDE A WALL SWITCH AT EACH FLOOR WHERE THE
STAIRWAY HAS 6 OR MORE RISERS.
HANDRAILS ON EXIT STAIRWAYS WILL BE REPLACED TO
COMPLY WITH R311 ON AT LEAST ONE SIDE.
GUARDS WILL BE PROVIDED ON ANY PORTION OF STAIRS NOT
EQUIPPED WITH GUARDS IN ACCORDANCE WITH R312.
INTERIOR WALL AND CEILING FINISH IN WORK AREAS WILL
COMPLY WITH R302.9 OR SHALL BE REMOVED OR TREATED
WITH AN APPROVED FIRE-RETARDANT COATING. WALL AND
CEILING FINISHES MUST HAVE A FLAME SPREAD RATING OF 200
OR LESS. WALL AND CEILING FINISHES MUST HAVE A SMOKE
DEVELOPED INDEX OF NOT MORE THAN 450.
BUILDING
REHABILITATION
UFC 3-600-01
BUILDING
REHABILITATION
IRC
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
GI001
C O
D E
S U
M M
A R
Y
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
R P
A T
R
IC
K
A P
E R
D U
K
S D
E G
A R
O
R B
J O
R E
N S
E N
J A
N U
A R
Y
W Q
R -1
-F
-0
CERTIFIED FINAL SUBMITTAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
ALL
FireLogix Engineering, Ltd.
215 North Broadway Street
Lebanon, Ohio 45036
(513) 206-9651 www.firelogix.com
THIS DRAWING IS FOR
REFERENCE ONLY. IT IS NOT
PART OF THE CONSTRUCTION
CONTRACT AND ALL
INFORMATION CONTAINED HERE
IS LOCATED ON THE
CONSTRUCTION DOCUMENTS.
W
2Q R
R
-0
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
GI002
F
IR
E P
R O
T E
C T
IO
N
L
IF
E
S A
F E
T Y
C O
D E
R E
V
IE
W
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
R P
A T
R
IC
K
A P
E R
D U
K
S D
E G
A R
O
R B
J O
R E
N S
E N
J A
N U
A R
Y
W Q
R -1
-F
-0
CERTIFIED FINAL SUBMITTAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
ALL
THIS DRAWING IS FOR
REFERENCE ONLY. IT IS NOT
PART OF THE CONSTRUCTION
CONTRACT AND ALL
INFORMATION CONTAINED HERE
IS LOCATED ON THE
CONSTRUCTION DOCUMENTS.
FireLogix Engineering, Ltd.
215 North Broadway Street
Lebanon, Ohio 45036
(513) 206-9651 www.firelogix.com W
2Q R
R
-0
SS
UP
DN
DN
UP
DN
DN
DN
DNUP
DN
DN
SMOKE PARTITION
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
AIDE'S ROOM
BATH 6
ST2
LAUNDRY
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
COAT ROOM
MECH
STORAGE
MEANS OF EGRESS
TO FLOOR ABOVE
EGRESS DOOR
TO GRADE
ST EXT 1
GARAGE
MUD RM
KITCHEN
DINING RM LIVING RM
SUN RM
BATH 4
FOYER
OFFICE
PORCH
BATH 3
COVERED
SCREENED PATIO
OPEN RAMP
SEC DINING
CL
LN
CL
EGRESS DOOR
PROVIDE COMPLETE HORIZONTAL
AND VERTICAL 1-HR FIRE
BARRIER SEPARATION OF
ATTACHED GARAGE
BATH 3
BEDROOM 3CL CL
CL
BEDROOM 2
STAIR
BATH 2
BEDROOM 4
SITTING RM
BEDROOM 1BATH 1
CL
CL
ROOF
ROOF
ROOF
ROOFROOF
ROOF
ROOF ROOF
LIN
CLOSET
CLOSET
CLOSET
PRIMARY MEANS OF EGRESS
TO FLOOR BELOW
EGRESS WINDOW
EMERGENCY ESCAPE AND
RESCUE OPENING
EGRESS WINDOW
EMERGENCY ESCAPE AND
RESCUE OPENING
ROOF ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ATTIC
ROOF
PRIMARY MEANS OF EGRESS
TO FLOOR BELOW
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
GI003
L
IF
E S
A F
E T
Y P
L A
N
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
R P
A T
R
IC
K
A P
E R
D U
K
S D
E G
A R
O
R B
J O
R E
N S
E N
J A
N U
A R
Y
? W Q
R -1
-F
-0
CERTIFIED FINAL SUBMITTAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
TYPE B
FireLogix Engineering, Ltd.
215 North Broadway Street
Lebanon, Ohio 45036
(513) 206-9651 www.firelogix.com
GENERAL NOTES:
KEYED NOTES
1. THIS DRAWING IS FOR REFERENCE ONLY. IT IS NOT PART OF THE
CONSTRUCTION CONTRACT AND ALL INFORMATION CONTAINED HERE IS
LOCATED ON THE CONSTRUCTION DOCUMENTS.
2. EGRESS DOORS AND EMERGENCY ESCAPE / RESCUE OPENINGS ARE NOTED
ON THE LIFE SAFETY PLANS. SEE ARCHITECTURAL PLANS FOR DOOR AND
WINDOW DETAILS. SEE SHEET GI001 CODE SUMMARY AND GI002 FIRE
PROTECTION / LIFE SAFETY CODE REVIEW FOR ADDITIONAL CODE
INFORMATION.
3. SEE ELECTRICAL EP SERIES PLANS FOR SMOKE AND CARBON MONOXIDE
ALARMS.
4. SEE FIRE PROTECTION FX SERIES PLANS FOR FOR FIRE SPRINKLER.
LEGEND
3/32" = 1'-0"E1
BASEMENT LIFE SAFETY PLAN
3/32" = 1'-0"A1
FIRST FLOOR LIFE SAFETY PLAN
3/32" = 1'-0"E5
SECOND FLOOR LIFE SAFETY PLAN
3/32" = 1'-0"A5
THIRD FLOOR LIFE SAFETY PLAN
16'8' 32'0 16'8' 32'0
16'8' 32'016'8' 32'0
W
2Q R
R
-0
CODES AND STANDARDS
THE FOLLOWING CODES AND STANDARDS HAVE BEEN USED AS THE BASIS FOR
DESIGN AND/OR SHALL BE UTILIZED BY THE CONTRACTOR TO ESTABLISH MINIMUM
LEVELS OF QUALITY AND CONSTRUCTION TECHNIQUES.
1. GENERAL
A. UFC 4-711-01, "FAMILY HOUSING," 8-10-2018.
B. INTERNATIONAL RESIDENTIAL CODE (IRC 2018).
C. AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMUM DESIGN LOADS AND
ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER STRUCTURES," (ASCE 7-16).
2. CONCRETE
A. AMERICAN CONCRETE INSTITUTE, "BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE" (ACI 318-16).
B. AMERICAN CONCRETE INSTITUTE, "SPECIFICATIONS FOR STRUCTURAL
CONCRETE," (ACI 301-16).
C. AMERICAN CONCRETE INSTITUTE, "GUIDE TO CONCRETE FLOOR AND SLAB
CONSTRUCTION" (ACI 302.1R-15).
3. WOOD
A. 2018 NATIONAL DESIGN SPECIFICATION (NDS) FOR WOOD CONSTRUCTION.
B. 2018 AMERICAN WOOD COUNCIL, "WOOD FRAME CONSTRUCTION MANUAL"
4. STEEL
A. AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "STEEL CONSTRUCTION
MANUAL," FIFTEENTH EDITION.
B. AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "SPECIFICATION FOR
STRUCTURAL STEEL ," (ANSI/AISC 360-16).
C. AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING CODE-STEEL" (AWS
D1.1-2015).
THE STRUCTURE HAS BEEN DESIGNED FOR THE FOLLOWING LOADS.
1. ROOF DEAD LOADS
CLAY TILE ROOF 12 PSF
ROOF SHEATHING 3 PSF
INSULATION 1 PSF
CEILINGS 3 PSF
MEP 2 PSF
DESIGN CRITERIA
3. ROOF LIVE LOADS
TOP CHORD UNIFORM LOAD (UNREDICIBLE) 20 PSF
BOTTOM CHORD UNIFORM LOAD (UNREDICIBLE) 10 PSF (NON-CONCURRENT
W/ TOP CHORD LIVE LOAD)
5. SNOW LOADS
GROUND SNOW LOAD (Pg) 20 PSF FLAT ROOF SNOW LOAD (Pf) 14 PSF
SLOPED ROOF SNOW LOAD 9 PSF (12:12 ROOF SLOPE)
14 PSF (4:12 ROOF SLOPE)
EXPOSURE FACTOR (Ce) 1.0 IMPORTANCE FACTOR (Is) 1.0 THERMAL FACTOR (Ct) 1.0 SLOPE FACTOR (Cs) 1.0 DRIFT SURCHARGE LOAD (Pd) 27 PSF
WIDTH OF DRIFT 6.5 FT
2. FLOOR DEAD LOADS
FLOOR TILE 5 PSF
FLOOR SHEATHING 3 PSF
INSULATION 1 PSF
CEILINGS 1 PSF
MEP 2 PSF
4. FLOOR LIVE LOADS
TYP. FLOOR 40 PSF
HABITABLE ATTIC 30 PSF
6. WIND LOADS
BUILDING
ULTIMATE DESIGN WIND SPEED (Vult) 107 MPH ALLOWABLE STRESS DESIGN WIND SPEED (Vasd) 83 MPH
RISK CATEGORY II
EXPOSURE CATEGORY C
INTERNAL PRESSURE COEFF. (GCpi) +/- 0.18
7. SEISMIC LOADS
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR (Ie) 1.0
0.2 SEC MAPPED SPECTRAL ACCELERATION (SS) 0.150
1.0 SEC MAPPED SPECTRAL ACCELERATION (S1) 0.070
SITE CLASS C
0.2 SEC DESIGN SPECTRAL ACCELERATION (SDS) 0.160
1.0 SEC DESIGN SPECTRAL ACCELERATION (SD1) 0.112
SEISMIC DESIGN CATEGORY B
1. SHALLOW FOUNDATION DESIGN IS BASED ON THE RECOMMENDATIONS REPORTED
IN THE SITE SPECIFIC GEOTECHNICAL EXPLORATION REPORT PREPARED BY
TERRACON CONSULTANTS, INC. DATED FEBURARY 28, 2020.
2. THE FOUNDATIONS WERE DESIGNED BASED ON THE FOLLOWING NET ALLOWABLE
SOIL BEARING PRESSURES:
A. ISOLATED SPREAD FOUNDATIONS 2,000 PSF
B. CONTINUOUS FOUNDATIONS 2,000 PSF
3. ALLOWABLE BEARING PRESSURES ARE BASED ON SITE PREPARATION AS
DISCUSSED IN THE GEOTECHNICAL REPORT. UNDOCUMENTED FILLS ARE EXPECTED
BELOW ALL NEW STRUCTURAL FOOTINGS AND SLABS AND SHALL BE UNDERCUT AND
REPLACED WITH NEW STRUCTURAL FILL (BASE BID SHALL INCLUDE PRICE FOR 2' OF
UNDERCUT AND FILL). THE DEPTH AND EXTENT OF UNDERCUTTING SHALL BE
DETERMINED BY GEOTECHNICAL PERSONNEL DURING CONSTRUCTION. RE-USE OF
EXCAVATED FILL AS STRUCTURAL FILL SHALL BE DETERMINED DURING REMOVAL BY
GEOTECHNICAL ENGINEER.
4. ALL FOUNDATION BEARING SURFACES SHALL BE INSPECTED BY THE GEOTECHNICAL
ENGINEER PRIOR TO STEEL OR CONCRETE PLACEMENT TO ENSURE THAT THE
BEARING SURFACES ARE CONSISTENT WITH THE ALLOWABLE BEARING PRESSURES
NOTED.
5. CONTRACTOR SHALL KEEP ALL FREE STANDING WATER OUT OF EXCAVATION
CONTRACTOR SHALL PROVIDE DEWATERING MEASURES AS NECESSARY PRIOR TO
PLACING CONCRETE.
6. EXISTING SOIL WHICH IS DEEMED NON-USABLE BY THE GEOTECHNICAL ENGINEER
DUE TO FAILURE OF THE CONTRACTOR TO PROMPTLY DE-WATER THE SITE SHALL BE
REMOVED AND REPLACED WITH SUITABLE FILL AT THE CONTRACTOR’S EXPENSE.
7. DESIGN OF TEMPORARY AND PERMANENT SHORING FOR EXCAVATIONS SHALL BE
THE RESPONSIBILITY OF THE CONTRACTOR.
8. FOR WALLS OR GRADE WALLS HAVING FILL ON EACH SIDE, PROCEED WITH
BACKFILLING OPERATIONS SIMULTANEOUSLY IN UNIFORM LIFTS. DIFFERENTIAL
ELEVATION OF TOP OF LIFTS BETWEEN EACH SIDE SHALL NOT EXCEED 18 INCHES.
FOUNDATIONS
1. MINIMUM 28 DAY CONCRETE COMPRESSIVE STRENGTH SHALL BE AS FOLLOWS:
A. SPREAD & CONTINUOUS FOOTINGS, GRADE BEAMS 3,000 PSI
B. FOUNDATION WALLS 4,000 PSI
2. CONCRETE SHALL BE PROPORTIONED, BATCHED, MIXED, PLACED,
CONSOLIDATED, AND CURED IN ACCORDANCE WITH ACI 301, 304, 308, 309 AND 318.
3. ALL CONCRETE EXPOSED TO WEATHER SHALL BE AIR ENTRAINED (W/ 4-6% AIR
ENTRAINMENT).
4. WHERE STRIP/GRADE FOOTINGS OR WALLS INTERSECT COLUMN FOUNDATIONS,
LONGITUDINAL REINFORCEMENT SHALL BE CONTINUOUS THROUGH THE COLUMN
FOUNDATION.
5. UNLESS OTHERWISE SHOWN, THE CONCRETE CLEAR COVER AT ALL
REINFORCING STEEL SHALL BE:
A. CONCRETE CAST AGAINST EARTH 3"
B. CONCRETE EXPOSED TO EARTH OR WEATHER 2"
C. CONCRETE NOT EXPOSED TO EARTH OR WEATHER 3/4"
6. ALL CONCRETE SHALL BE MECHANICALLY VIBRATED IN ACCORDANCE WITH ACI
304 AND ACI 309.
7. PROVIDE 3/4"x3/4"x 45 DEGREE CHAMFERED CORNERS AT ALL EXPOSED
CONCRETE CORNERS UNO.
8. MAXIMUM WATER TO CEMENT RATIO SHALL BE AS FOLLOWS:
CONCRETE EXPOSED TO FREEZING & THAWING 0.55
CONCRETE SUBJECT TO DE-ICERS OR TO BE WATERTIGHT 0.40
ALL OTHER CONCRETE TYPES 0.55
CONCRETE
WOOD FRAMING
1. MATERIAL CERTIFICATES: FOR DIMENSION LUMBER SPECIFIED TO COMPLY WITH MINIMUM
ALLOWABLE UNIT STRESSES. INDICATE SPECIES AND GRADE SELECTED FOR EACH USE
AND DESIGN VALUES APPROVED BY THE AMERICAN LUMBER STANDARDS COMMITTEE
BOARD OF REVIEW.
2. U.N.O. ON PLANS SAWN LUMBER SHALL BE THE FOLLOWING MIN. GRADES. ANY LUMBER
SPECIES SUBSITUTIONS MUST BE APPROVED BY ENGINEER OF RECORD.
BEAMS/HEADERS (2x10 OR LARGER): SYP #1
STUD WALLS: SPF#2
ALL OTHER FRAMING: SYP #2
3. STACK LUMBER, PLYWOOD, AND OTHER PANELS; PLACE SPACERS BETWEEN EACH BUNDLE
TO PROVIDE AIR CIRCULATION. PROVIDE FOR AIR CIRCULATION AROUND STACKS AND
UNDER COVERINGS.
4. ENGINEERED WOOD PRODUCTS: PROVIDE ENGINEERED WOOD PRODUCTS ACCEPTABLE
TO AUTHORITIES HAVING JURISDICTION AND FOR WHICH CURRENT MODEL CODE
RESEARCH OR EVALUATION REPORTS EXIST THAT SHOW COMPLIANCE WITH BUILDING
CODE IN EFFECT FOR PROJECT.
L.V.L. MIN. PROPERTIES
E = 1,900,000 PSI
Fb = 2,600 PSI
P.S.L. MIN. PROPERTIES
E = 2,000,000 PSI
Fc // = 2,900 PSI
5. ALLOWABLE DESIGN STRESSES: PROVIDE ENGINEERED WOOD PRODUCTS WITH
ALLOWABLE DESIGN STRESSES, AS PUBLISHED BY MANUFACTURER, THAT MEET OR
EXCEED THOSE INDICATED. MANUFACTURER'S PUBLISHED VALUES SHALL BE DETERMINED
FROM EMPIRICAL DATA OR BY RATIONAL ENGINEERING ANALYSIS AND DEMONSTRATED BY
COMPREHENSIVE TESTING PERFORMED BY A QUALIFIED INDEPENDENT TESTING AGENCY.
6. GENERAL: PROVIDE FASTENERS OF SIZE AND TYPE INDICATED THAT COMPLY WITH
REQUIREMENTS SPECIFIED IN THIS ARTICLE FOR MATERIAL AND MANUFACTURE. WHERE
ROUGH CARPENTRY IS EXPOSED TO WEATHER, IN GROUND CONTACT, OR IN AREA OF HIGH
RELATIVE HUMIDITY, PROVIDE FASTENERS WITH HOT-DIP ZINC COATING COMPLYING WITH
ASTM A 153/A 153M.
NAILS, BRADS, AND STAPLES: ASTM F 1667.
POWER-DRIVEN FASTENERS: CABO NER-272.
WOOD SCREWS: ASME B18.6.1.
LAG BOLTS: ASME B18.2.1.
BOLTS: STEEL BOLTS COMPLYING WITH ASTM A 307, GRADE A, ; WITH ASTM A 563 HEX
NUTS AND, WHERE INDICATED, FLAT WASHERS.
7. SET ROUGH CARPENTRY TO REQUIRED LEVELS AND LINES, WITH MEMBERS PLUMB, TRUE
TO LINE, CUT, AND FITTED. FIT ROUGH CARPENTRY TO OTHER CONSTRUCTION; SCRIBE
AND COPE AS NEEDED FOR ACCURATE FIT. LOCATE FURRING, NAILERS, BLOCKING, AND
SIMILAR SUPPORTS TO COMPLY WITH REQUIREMENTS FOR ATTACHING OTHER
CONSTRUCTION.
8. DO NOT USE MATERIALS WITH DEFECTS THAT IMPAIR QUALITY OF ROUGH CARPENTRY OR
PIECES THAT ARE TOO SMALL TO USE WITH MINIMUM NUMBER OF JOINTS OR OPTIMUM
JOINT ARRANGEMENT.
9. SECURELY ATTACH ROUGH CARPENTRY WORK TO SUBSTRATE BY ANCHORING AND
FASTENING AS INDICATED.
10. USE COMMON WIRE NAILS, UNLESS OTHERWISE INDICATED. SELECT FASTENERS OF SIZE
THAT WILL NOT FULLY PENETRATE MEMBERS WHERE OPPOSITE SIDE WILL BE EXPOSED TO
VIEW OR WILL RECEIVE FINISH MATERIALS. MAKE TIGHT CONNECTIONS BETWEEN
MEMBERS. INSTALL FASTENERS WITHOUT SPLITTING WOOD; PREDRILL AS REQUIRED.
11. ATTACH ITEMS TO SUBSTRATES TO SUPPORT APPLIED LOADING. RECESS BOLTS AND
NUTS FLUSH WITH SURFACES, UNLESS OTHERWISE INDICATED. WHERE POSSIBLE, SECURE
ANCHOR BOLTS TO FORMWORK BEFORE CONCRETE PLACEMENT.
12. FRAMING STANDARD: COMPLY WITH AWC'S "WOOD FRAME CONSTRUCTION MANUAL"
UNLESS OTHERWISE INDICATED.
13. FRAMING WITH ENGINEERED WOOD PRODUCTS: INSTALL ENGINEERED WOOD PRODUCTS
TO COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
14. DO NOT SPLICE STRUCTURAL MEMBERS BETWEEN SUPPORTS.
15. ARRANGE STUDS SO WIDE FACE OF STUD IS PERPENDICULAR TO DIRECTION OF WALL OR
PARTITION AND NARROW FACE IS PARALLEL. PROVIDE SINGLE BOTTOM PLATE AND
DOUBLE TOP PLATES USING MEMBERS OF 2-INCH NOMINAL THICKNESS WHOSE WIDTHS
EQUAL THAT OF STUDS, EXCEPT SINGLE TOP PLATE MAY BE USED FOR NON-LOAD-BEARING
PARTITIONS. ANCHOR PLATES TO SUPPORTING CONSTRUCTION, UNLESS OTHERWISE
INDICATED.
16. CONSTRUCT CORNERS AND INTERSECTIONS WITH THREE OR MORE STUDS. PROVIDE
BLOCKING AND FRAMING AS INDICATED AND AS REQUIRED TO SUPPORT FACING
MATERIALS, FIXTURES, SPECIALTY ITEMS, AND TRIM.
17. PROVIDE CONTINUOUS HORIZONTAL BLOCKING AT MIDHEIGHT OF WALLS MORE THAN 96
INCHES HIGH, USING MEMBERS OF 2-INCH NOMINAL THICKNESS AND OF SAME WIDTH AS
WALL OR PARTITIONS.
18. FIRE BLOCK CONCEALED SPACES OF WOOD-FRAMED WALLS AND PARTITIONS AT EACH
FLOOR LEVEL AND AT CEILING LINE OF TOP STORY. WHERE FIRE BLOCKING IS NOT
INHERENT IN FRAMING SYSTEM USED, PROVIDE CLOSELY FITTED WOOD BLOCKS OF 2-INCH
NOMINAL THICK LUMBER OF SAME WIDTH AS FRAMING MEMBERS.
19. FOR NON-LOAD-BEARING PARTITIONS, PROVIDE DOUBLE-JAMB STUDS WITH HEADERS NOT
LESS THAN 4-INCH NOMINAL DEPTH FOR OPENINGS 48 INCHES AND LESS IN WIDTH, 6-INCH
NOMINALDEPTH FOR OPENINGS 48 TO 72 INCHES IN WIDTH, 8-INCH NOMINAL DEPTH FOR
OPENINGS 72 TO 120 INCHES IN WIDTH, AND NOT LESS THAN 10-INCH NOMINAL DEPTH FOR
OPENINGS 10 TO 12 FEET IN WIDTH.
20. PROVIDE STAIR FRAMING MEMBERS OF SIZE, SPACE, AND CONFIGURATION INDICATED OR, IF NOT INDICATED, TO COMPLY WITH THE FOLLOWING REQUIREMENTS:
STRINGER SIZE: 2-BY-12-INCH NOMINAL-SIZE, MINIMUM.
NOTCHING: NOTCH STRINGERS TO RECEIVE TREADS, RISERS, AND SUPPORTS; LEAVE AT
LEAST 5 INCHES OF EFFECTIVE DEPTH.
STRINGER SPACING: AT LEAST 3 STRINGERS FOR EACH 36-INCH CLEAR WIDTH OF STAIR.
21. PROVIDE BLOCKING BETWEEN PLYWOOD JOINTS ON EXTERIOR WALLS (AND INTERIOR
SHEARWALLS) WHERE HORIZONTAL PANEL JOINTS DO NOT ALIGN WITH HORIZONTAL
FRAMING (I.E. HEADERS/RIM JOISTS).
22. AT MINIMUM, PROVIDE NAILING AS DIRECTED BY THE IRC FOR VARIOUS CONDITIONS
UNLESS NOTED OTHERWISE ON PLANS.
23. PROVIDE 1/2" PLYWOOD CUT TO MATCH HEADER DEPTH BETWEEN EA. PLY OF STANDARD
SAWN LUMBER HEADERS.
24. PROVIDE ADJUSTABLE VENEER WIRE TIES (9 GA. MIN. THICKNESS) WITH A HOOK
EMBEDDED INTO THE MORTAR JOINT EXTENDING 2" MIN. INTO MORTAR JOINT W/ 5/8" MIN.
MORTAR COVER. FASTEN TO SUPPORTING FRAMING W/ #10 WOOD SCREWS PER IRC
TABLE R703.8.4(2).
1. STRUCTURAL PERFORMANCE: PROVIDE METAL-PLATE-CONNECTED WOOD TRUSSES
CAPABLE OF WITHSTANDING DESIGN LOADS WITHIN LIMITS AND UNDER CONDITIONS
INDICATED.
2. MAXIMUM DEFLECTION UNDER DESIGN LOADS: ROOF TRUSSES: TOTAL VERTICAL
DEFLECTION OF L/360 OF SPAN OR 1/2" WHICHEVER IS LESS.
3. SHOP DRAWINGS: SHOW LOCATION, PITCH, SPAN, CAMBER, CONFIGURATION, AND
SPACING FOR EACH TYPE OF TRUSS REQUIRED; SPECIES, SIZES, AND STRESS GRADES
OF LUMBER; SPLICE DETAILS; TYPE, SIZE, MATERIAL, FINISH, DESIGN VALUES,
ORIENTATION, AND LOCATION OF METAL CONNECTOR PLATES; AND BEARING DETAILS.
BWSC TO APPROVE PRIOR TO INSTALLATION.
4. FOR INSTALLED PRODUCTS INDICATED TO COMPLY WITH DESIGN LOADS, INCLUDE
STRUCTURAL ANALYSIS DATA SIGNED AND SEALED BY THE QUALIFIED PROFESSIONAL
ENGINEER RESPONSIBLE FOR THEIR PREPARATION. BWSC TO APPROVE PRIOR TO
INSTALLATION.
5. PRODUCT CERTIFICATES: FOR METAL-PLATE-CONNECTED WOOD TRUSSES, SIGNED BY
OFFICER OF TRUSS FABRICATING FIRM.
6. QUALIFICATION DATA: FOR METAL-PLATE MANUFACTURER AND FABRICATOR.
7. METAL CONNECTOR-PLATE MANUFACTURER QUALIFICATIONS: A MANUFACTURER THAT
IS A MEMBER OF TPI AND THAT COMPLIES WITH TPI QUALITY-CONTROL PROCEDURES
FOR MANUFACTURE OF CONNECTOR PLATES PUBLISHED IN TPI 1.
8. MANUFACTURER'S RESPONSIBILITIES INCLUDE PROVIDING PROFESSIONAL
ENGINEERING SERVICES NEEDED TO ASSUME ENGINEERING RESPONSIBILITY.
9. ENGINEERING RESPONSIBILITY: PREPARATION OF SHOP DRAWINGS AND
COMPREHENSIVE ENGINEERING ANALYSIS BY A QUALIFIED PROFESSIONAL ENGINEER.
10. FABRICATOR QUALIFICATIONS: SHOP THAT PARTICIPATES IN A RECOGNIZED QUALITY-
ASSURANCE PROGRAM THAT INVOLVES INSPECTION BY SPIB (SOUTHERN PINE
INSPECTION BUREAU), TIMBER PRODUCTS INSPECTION, TPI, OR OTHER INDEPENDENT
TESTING AND INSPECTING AGENCY ACCEPTABLE TO ARCHITECT AND AUTHORITIES
HAVING JURISDICTION.
11. SOURCE LIMITATIONS FOR CONNECTOR PLATES: OBTAIN METAL CONNECTOR PLATES
THROUGH ONE SOURCE FROM A SINGLE MANUFACTURER.
12. COMPLY WITH TPI RECOMMENDATIONS TO AVOID DAMAGE AND LATERAL BENDING.
PROVIDE FOR AIR CIRCULATION AROUND STACKS AND UNDER COVERINGS.
13. INSPECT TRUSSES SHOWING DISCOLORATION, CORROSION, OR OTHER EVIDENCE OF
DETERIORATION. DISCARD AND REPLACE TRUSSES THAT ARE DAMAGED OR
DEFECTIVE.
14. CUT TRUSS MEMBERS TO ACCURATE LENGTHS, ANGLES, AND SIZES TO PRODUCE
CLOSE-FITTING JOINTS.
15. FABRICATE METAL CONNECTOR PLATES TO SIZES, CONFIGURATIONS, THICKNESSES,
AND ANCHORAGE DETAILS REQUIRED TO WITHSTAND DESIGN LOADS FOR TYPES OF
JOINT DESIGNS INDICATED.
16. ASSEMBLE TRUSS MEMBERS IN DESIGN CONFIGURATION INDICATED; USE JIGS OR
OTHER MEANS TO ENSURE UNIFORMITY AND ACCURACY OF ASSEMBLY WITH JOINTS
CLOSELY FITTED TO COMPLY WITH TOLERANCES IN TPI.
17. POSITION MEMBERS TO PRODUCE DESIGN CAMBER INDICATED. FABRICATE WOOD
TRUSSES WITHIN MANUFACTURING TOLERANCES IN TPI 1.
18. CONNECT TRUSS MEMBERS BY METAL CONNECTOR PLATES LOCATED AND SECURELY
EMBEDDED SIMULTANEOUSLY IN BOTH SIDES OF WOOD MEMBERS BY AIR OR
HYDRAULIC PRESS.
19. INSTALL WOOD TRUSSES ONLY AFTER SUPPORTING CONSTRUCTION IS IN PLACE AND
IS BRACED AND SECURED.
20. BEFORE INSTALLING, SPLICE TRUSSES DELIVERED TO PROJECT SITE IN MORE THAN
ONE PIECE.
21. HOIST TRUSSES IN PLACE BY LIFTING EQUIPMENT SUITED TO SIZES AND TYPES OF
TRUSSES REQUIRED, EXERCISING CARE NOT TO DAMAGE TRUSS MEMBERS OR JOINTS
BY OUT-OF-PLANE BENDING OR OTHER CAUSES.
22. INSTALL AND BRACE TRUSSES ACCORDING TO TPI RECOMMENDATIONS AND AS
INDICATED. INSTALL TRUSSES PLUMB, SQUARE, AND TRUE TO LINE AND SECURELY
FASTEN TO SUPPORTING CONSTRUCTION.
23. SPACE TRUSSES AS INDICATED; ADJUST AND ALIGN TRUSSES IN LOCATION BEFORE
PERMANENTLY FASTENING.
24. ANCHOR TRUSSES SECURELY AT BEARING POINTS; USE METAL FRAMING ANCHORS.
INSTALL FASTENERS THROUGH EACH FASTENER HOLE IN METAL FRAMING ANCHOR
ACCORDING TO MANUFACTURER'S FASTENING SCHEDULES AND WRITTEN
INSTRUCTIONS.
25. SECURELY CONNECT EACH TRUSS PLY REQUIRED FOR FORMING BUILT-UP GIRDER
TRUSSES.
26. INSTALL AND FASTEN PERMANENT BRACING DURING TRUSS ERECTION AND BEFORE
CONSTRUCTION LOADS ARE APPLIED. ANCHOR ENDS OF PERMANENT BRACING WHERE
TERMINATING AT WALLS OR BEAMS.
27. INSTALL WOOD TRUSSES WITHIN INSTALLATION TOLERANCES IN TPI 1.
28. DO NOT CUT OR REMOVE TRUSS MEMBERS.
29. REPLACE WOOD TRUSSES THAT ARE DAMAGED OR DO NOT MEET REQUIREMENTS. DO
NOT ALTER TRUSSES IN FIELD.
30. THE ROOF TRUSSES AND CONNECTIONS SHALL BE A DELEGATED REGISTERED
ENGINEER AND THE DRAWINGS SHALL BEAR THE ENGINEER'S SEAL. SUBMIT DESIGN
DRAWINGS PER SPECIFICATIONS- INCLUDE TRUSS LAYOUT, DESIGN LOADS, MEMBER
STRESSES, CONNECTION SUMMARY, AND REQUIRED BRIDGING/BRACING
WOOD TRUSSES
1. GENERAL NOTES AND TYPICAL DETAILS DESCRIBE GENERAL CRITERIA APPLICABLE TO
ALL SIMILAR CONDITIONS THROUGHOUT THE PROJECT REGARDLESS OF WHETHER OR
NOT THEY ARE SPECIFICALLY REFERENCED IN THE PLANS OR DETAILS.
2. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION, THE CONTRACTOR
SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION FROM THE STRUCTURAL
ENGINEER BEFORE CONTINUING WITH CONSTRUCTION.
3. CONTRACTOR SHALL COORDINATE THE STRUCTURAL DOCUMENTS WITH THE
ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION AND CIVIL
DOCUMENTS. ARCHITECT/STRUCTURAL ENGINEER SHALL BE NOTIFIED OF ANY
DISCREPANCY.
4. THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR COMPLIANCE WITH THE
CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE CONFIRMED AT THE JOBSITE, FOR
FABRICATION PROCESSES, AND FOR THE MEANS, METHODS, TECHNIQUES,
SEQUENCES AND PROCEDURES OF CONSTRUCTION.
5. NO SUBSTITUTIONS OF MATERIAL WILL BE ALLOWED WITHOUT WRITTEN PERMISSION
FROM THE ENGINEER.
6. SHOP DRAWINGS SHALL NOT BE REVIEWED FOR APPROVAL UNLESS CHECKED BY THE
FABRICATOR AND APPROVED BY THE CONTRACTOR.
7. CONTRACTOR SHALL COMPLY WITH LOCAL, STATE, FEDERAL AND OWNERS SAFETY
REGULATIONS WHILE WORKING. STRUCTURAL ENGINEER DOES NOT ASSUME ANY
RESPONSIBILITY FOR CONSTRUCTION SITE SAFETY.
8. CONTRACTOR SHALL REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS
9. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND
ELEVATIONS BEFORE STARTING WORK. NOTIFY STRUCTURAL ENGINEER OF ANY
DISCREPANCY. NOTIFY STRUCTURAL ENGINEER IN WRITING OF CONDITIONS
ENCOUNTERED IN THE FIELD CONTRADICTORY TO THOSE SHOWN ON THE
STRUCTURAL CONTRACT DOCUMENTS.
10. DESIGN OF TEMPORARY SHORING FOR EXISTING WALLS OR JOISTS IS THE
RESPONSIBILITY OF THE CONTRACTOR.
11. TESTING OF EXISTING BRICK SHALL BE PERFORMED ON A REPRESENTATIVE AREA TO
BE DEMOLISHED PER ASTM C67 AND OTHER RELEVANT STANDARDS. PROVIDE
INFORMATION TO STRUCTURAL ENGINEER REGARDING EXISTING MASORY PRISM
STRENGTH, AND MORTAR FLEXURAL BOND/SHEAR STRENGTH PRIOR TO MAJOR
DEMOLITION.
12. INFILLED/REPAIRED BRICK SHALL BE REPLACED WITH SALAVAGED BRICK FROM
DEMOLITION. ALL NEW BRICK WORK SHALL BE TOOTHED IN TO EXISTING, NEW
MASONRY MORTAR SHALL MATCH EXISTING MORTAR MIX.
13. EXISTING DAMAGED FRAMING, CUT JOISTS, CRACKED BRICK, OR OTHERWISE
UNUSUAL CONDITIONS SHALL BE REPORTED TO THE ENGINEER OF RECORD FOR
REVIEW.
MISCELLANEOUS
1. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60 (DEFORMED).
2. WELDED WIRE REINFORCEMENT (WWR) SHALL CONFORM TO ASTM A1064 AND SHALL
BE PROVIDED IN FLAT SHEETS ONLY. FABRIC SHALL LAP TWO FULL MESHES AND BE
SECURELY FASTENED AT EACH SIDE AND EACH END.
3. DETAILING, FABRICATION AND ERECTION OF REINFORCING STEEL, UNLESS
OTHERWISE NOTED, SHALL CONFORM TO ACI 315, "DETAILS AND DETAILING OF
REINFORCED CONCRETE STRUCTURES", SP-66, THE CRSI, "MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES" AND ACI 318.
4. REINFORCING STEEL SHALL BE CONTINUOUS ACROSS ALL CONSTRUCTION JOINTS
UNO.
5. REINFORCING STEEL SHALL NOT BE HEATED OR WELDED AND MUST BE DRY AND FREE
OF CONTAMINANTS SUCH AS RUST, DIRT, GREASE, AND PROTECTIVE COATINGS.
6. ALL BAR SPLICES SHALL BE CLASS B TENSION SPLICES IN ACCORDANCE WITH ACI 318.
REINFORCING STEEL FOR CONCRETE
ABBREVIATIONS
AB ANCHOR BOLT
ADD'L ADDITIONAL
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
APPROX APPROXIMATE, APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
B/ BOTTOM OF
BLDG BUILDING
BM BEAM
BO BOTTOM OF
BOD BASIS OF DESIGN
BOT BOTTOM
BP BASEPLATE
BRG BEARING
CC CENTER TO CENTER
CJ CONTROL JOINT, CONSTRUCTION JOINT
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CP COMPLETE PENETRATION
DIA DIAMETER
DIAG DIAGONAL
DL DEAD LOAD
DO DITTO
DWG DRAWING
EOS EDGE OF SLAB
EA EACH
EF EACH FACE
EL ELEVATION
EOR ENGINEER OF RECORD
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FIN FLR FINISHED FLOOR
FTG FOOTING
GA GAUGE
GALV GALVANIZE, GALVANIZED
HDD HEADED
HORIZ HORIZONTAL
INT INTERIOR
JT JOINT
K KIPS
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
L ANGLE
LG LONG
LL LIVE LOAD
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LVL LAMINATED VENEER LUMBER
LW LIGHT-WEIGHT
MANUF MANUFACTURER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MIN MINIMUM
MTL METAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NW NORMAL-WEIGHT
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
PAF POWDER ACTUATED FASTENER
PC PRECAST CONCRETE
PEJF PRE-MOLDED EXPANSION JOINT FILLER
PEMB PRE-ENGINEERED METAL BUILDING
PL PLATE
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT PRESERVATIVE TREATED
RD ROOF DRAIN
REF REFER, REFERENCE
REINF REINFORCING
REQD REQUIRED
RET RETAINING
SCHED SCHEDULE
SECT SECTION
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB-ON-GRADE
SPEC SPECIFICATIONS
STIFF STIFFENER
SQ SQUARE
STD STANDARD
STL STEEL
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T/ TOP OF
THDD THREADED
TO TOP OF
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VIF VERIFY IN FIELD
VERT VERTICAL
W/ WITH
W/O WITHOUT
WP WORKING POINT
WWR WELDED WIRE REINFORCING
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
S-001
S T
R U
C T
U R
A L
N O
T E
S
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G P
L
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
D H
IN
D
S
A M
C G
U
IR
E
S D
E G
A R
O
B K
R O
U S
K O
P
J A
N U
A R
Y
W Q
R -1
-F
-0
CERTIFIED FINAL SUBMITTAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
F
IL
E N
U M
B E
R
TYPE B
BRETT CARTER
S T
A
TE OF O
H
IO
P R
O F E
S
S IONA L EN
G
IN
E
E R
KROUSKOP
PE.57962
R E
GIST ERE
D
1/21/2021
W
2Q R
R
-0
STRUCTURAL STEEL
1. STRUCTURAL STEEL (W-SHAPES) SHALL CONFORM TO ASTM A992.
2. STRUCTURAL STEEL (NON W-SHAPES) AND PLATES - ASTM A36, UNO.
3. HOLLOW STRUCTURAL SHAPES SHALL CONFORM TO THE FOLLOWING:
SQUARE AND RECTANGULAR - ASTM A500, GRADE C (Fy = 50 KSI)
STEEL PIPE – ASTM A53, GRADE B
4. UNO ALL HIGH STRENGTH BOLTS SHALL BE 3/4 INCH DIAMETER, ASTM A325.
5. STRUCTURAL STEEL DESIGN, DETAILING, FABRICATION AND ERECTION SHALL
CONFORM TO:
A. AISC, "SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION
OF STRUCTURAL STEEL FOR BUILDINGS."
B. AISC, "CODE OF STANDARD PRACTICE", INCLUDING COMMENTARY
C. AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 AND
A490 BOLTS"
6. WELDING SHALL CONFORM TO AWS D1.1 "STRUCTURAL WELDING CODE" AND BE
PERFORMED BY CERTIFIED WELDERS USING E70XX WELDING ELECTRODES.
7. REMOVE RUST, DIRT, PAINT AND GALVANIZING FROM STEEL PRIOR TO WELDING.
8. WELDS SHOWN ON STRUCTURAL DRAWINGS ARE MINIMUM DESIGN REQUIREMENTS.
USE THE MINIMUM WELD SIZE PER AISC WHERE WELD SIZE IS NOT INDICATED. THE
FABRICATOR’S SHOP DRAWINGS SHALL REFLECT WELDS IN ACCORDANCE WITH AWS /
AISC REQUIREMENTS.
9. BOLTED CONNECTIONS SHALL BE BEARING TYPE WITH THREADS INCLUDED IN THE
SHEAR PLANE. BOLTS SHALL BE TIGHTENED USING THE "SNUG TIGHT" METHOD. USE
ONE HARDENED WASHER UNDER THE TURNED ELEMENT.
10. BEAM CONNECTIONS SHALL BE STANDARD, SIMPLE SHEAR CONNECTIONS WITH
DOUBLE FRAMING ANGLES UNO. IN NO CASE SHALL THE
LENGTH OF THE FRAMED CONNECTION BE LESS THAN ONE-HALF OF THE "T"
DIMENSION OF THE BEAM WEB.
11. CONNECTION ANGLES SHALL BE 5/16" MINIMUM THICKNESS.
12. MINIMUM BOLTED CONNECTION SHALL BE AS FOLLOWS:
MEMBER DEPTH:
6" - 10" USE 2 ROWS OF BOLTS
12" - 18" USE 3 ROWS OF BOLTS
13. ALL BOLTED CONNECTION HOLES ARE TO BE STANDARD HOLES. SHORT SLOTTED
HOLES ARE NOT PERMITTED (I.E. HOLE DIA. = BOLT DIA. + 1/16")
14. NO OPENINGS SHALL BE CUT IN STRUCTURAL MEMBERS UNLESS SPECIFICALLY
DETAILED IN THE STRUCTURAL DRAWINGS.
15. THE STRUCTURE IS DESIGNED FOR A COMPLETED CONDITION ONLY AND THEREFORE
MAY REQUIRE ADDITIONAL SUPPORT TO MAINTAIN STABILITY BEFORE COMPLETION.
16. ALL STEEL IN PERMANENT CONTACT WITH MASONRY OR CONCRETE SHALL BE
GALVANIZED. ALL STEEL FASTENERS INTO MASONRY ON CONCRETE SHALL BE
GALVANIZED (INTERIOR) OR STAINLESS STEEL (EXTERIOR).
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
S-002
S T
R U
C T
U R
A L
N O
T E
S
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G P
L
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
D H
IN
D
S
A M
C G
U
IR
E
S D
E G
A R
O
B K
R O
U S
K O
P
J A
N U
A R
Y
W Q
R -1
-F
-0
CERTIFIED FINAL SUBMITTAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
F
IL
E N
U M
B E
R
TYPE B
BRETT CARTER
S T
A
TE OF O
H
IO
P R
O F E
S
S IONA L EN
G
IN
E
E R
KROUSKOP
PE.57962
R E
GIST ERE
D
1/21/2021
W
2Q R
R
-0
F3 F3 F3 F3
F3F3
F3F3
F3 F3
16"x16" CONC. PIER W/ (4) #6 VERT.
BARS AND #4 TIES @ 12" (3 TIES @
3" TOP OF PIER) T/PIER ELEV = -0'-6"
TURNDOWN SLAB
EDGE TO 3'-4"
BELOW GRADE
C 7X14.75
CONTRACTOR VERIFY EXISTING
FOOTING SIZE/CONDITION
UNDER NEW COLUMN PRIOR TO
INSTALLATION
WF2
EXISTING ASSUMED CONCRETE
FOOTING
EXISTING ASSUMED CONCRETE
FOUNDATION WALL
WF2
WF2
ASSUMED EXISTING CONCRETE
TURNDOWN FOOTING
T/SLAB
ELEVATION, MATCH
GARAGE FLOOR
(APPROX. -1'-5")
IN NEW BREEZEWAY, PROVIDE 4"
NORMAL WT. CONCRETE SLAB-
ON-GRADE REINFORCED WITH 6x6 W2.9xW2.9 W.W.F. PROVIDE MIN.
6" COMPACTED STONE BASE
UNDER 15 MIL. POLY. VAPOR
RETARDER. PROVIDE AND
INSTALL SHRINKAGE CONTROL
JOINTS AS SPECIFIED IN DETAILS
MATCH EXISTING
B/FTG ELEVATION
S T
E M
S H
E L F
MATCH EXISTING
B/FTG ELEVATION
T/SHELF
ELEVATION = 4" MIN. BELOW
SURROUNDING GRADE
8' - 0 1/4"
6' - 11 1/2"
/8
/8
6' - 11 3/8"
135.00°
34' - 0"
10' - 4 3/8"
F36 F36
B/FTG ELEVATION
= 3'-4" MIN. BELOW
GRADE, TYP.
PROVIDE 4" NORMAL WT.
CONCRETE SLAB-ON-GRADE
REINFORCED WITH 6x6 W2.9xW2.9 WWF PROVIDE MIN. 6"
COMPACTED STONE BASE
UNDER 15 MIL. POLY. VAPOR
RETARDER. PROVIDE AND
INSTALL SHRINKAGE CONTROL
JOINTS AS SPECIFIED IN
DETAILS.
3' - 0" 9' - 0" 10' - 0" 9' - 0" 3' - 0"
MATCH EXISTING B/FTG
ELEVATION TYP.
T/STEM EL. = -0' - 11"
T/SLAB
ELEVATION = -1'-5"
D1
S-501
F1
S-501
A3
S-501
A1
S-501
11 3/8" T/WALL @ DOOR = -1'-11"
SLAB CONTROL JOINT
7' - 9 1/4" 10' - 4" 9' - 10 3/4"
E5
S-501
SLAB CONTROL
JOINT
PROVIDE #4x2'-6"
BAR @ CENTER OF
SLAB @ CORNERS
OF SLAB ISOLATION
JOINT (TYP.)
UNFINISHED CRAWLSPACE
W/ 15 MIL VAPOR BARRIER
OVER 4" CRUSHED STONE
OVER NATIVE SOIL
PROVIDE #5x36" LONG DOWELS @
12" OC VERT. DRILL AND EPOXY TO
EXISTING FOUNDATION WALL W/ 8"
EMBED INTO EXISTING
FOUNDATION (TYP.)
T/SHELF
ELEVATION = 4" MIN. BELOW
SURROUNDING GRADE
F O
O T
IN
G
W A
L L
S H
E L F
S T
E M
T/STEM EL. = -1' - 3"
A5
S-501
A7
S-501
EXISTING B/FTG
ELEVATION = -4'-8" VIF
EXISTING B/FTG
ELEVATION = -11'-5" VIF
FACE OF
EXISTING BRICK
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LAYOUT, SPAN DIRECTION,
ETC. OF EXISTING ELEMENTS SHOWN IN FIELD. ANY DISCREPANCIES SHALL
BE REPORTED TO THE ARCHITECT/ENGINEER OF RECORD.
2. ELEVATIONS ARE REFERENCED FROM THE FIRST LEVEL TOP OF SUBFLOOR
DATUM ELEVATION OF 0'-0". SEE CIVIL DRAWINGS FOR EQUIVALENT MEAN
SEA LEVEL ELEVATION.
3. CONTRACTOR TO COORDINATE FOUNDATION LAYOUT WITH PLUMBING AND
OTHER UNDERGROUND UTILITIES. STEP/LOWER FOUNDATIONS AS
NECESSARY TO PREVENT CONFLICTS.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
S-101
F O
U N
D A
T
IO
N P
L A
N
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G P
L
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
D H
IN
D
S
A M
C G
U
IR
E
S D
E G
A R
O
B K
R O
U S
K O
P
J A
N U
A R
Y
W Q
R -1
-F
-0
CERTIFIED FINAL SUBMITTAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
F
IL
E N
U M
B E
R
TYPE B
3/16" = 1'-0"A1
FOUNDATION PLAN
8'4' 16'0 8'4' 16'0
GENERAL NOTES:
CONTINUOUS FOOTING SCHEDULE
MARK
DIMENSIONS REINFORCING
WIDTH THICKNESS BOTTOM TOP
WF2 2' - 0" 1' - 0" (3) #5 CONT. W/ #4 TIES @ 36" TRANS. -
SPREAD FOOTING SCHEDULE
MARK
DIMENSIONS
THICKNESS
REINFORCING
WIDTH LENGTH BOTTOM TOP
F3 3' - 0" 3' - 0" 1' - 0" (4) #5 EW -
F36 3' - 0" 6' - 0" 1' - 0" (4) #5 LW, (7) #5 SW -
BRETT CARTER
S T
A
TE OF O
H
IO
P R
O F E
S
S IONA L EN
G
IN
E
E R
KROUSKOP
PE.57962
R E
GIST ERE
D
1/21/2021
W
2Q R
R
-0
UP
2x12 JOISTS @
16" OC MAX.
EXISTING JOISTS SHALL BE CUT AS
REQUIRED TO INSTALL NEW FACE
MOUNT HANGERS TO NEW BEAM
H S S5X5X1/4
H S S5X5X1/4
H S S5X
5X 1/
H S S5X
5X 1/
H S S5X
5X 1/
H S S5X
5X 1/
H S S5X
5X 1/
H S S5X
5X 1/
H S S5X5X1/4
H S S5X5X1/4
H S S5X5X1/4
H S S5X5X1/4
H S S5X5X1/4
C 7X14.75
BEAR ON EXISTING ASSUMED
TIMBER TOP PLATE, OR PROVIDE
NEW POCKET W/ DOUBLE 2X PT
PLATE W/ 6" BEARING
TRIPLE 1 3/4"x9 1/4" LVL
HEADER (FLUSH)
DOUBLE 1 3/4"x9 1/4"
LVL HEADER (FLUSH)
(F L U
S H
C 7X14.75
H S S5X
5X 1/
EXISTING ASSUMED
JOISTS @ 16" OC VIF
W X
PROVIDE 2X4 WOOD-KNEE
WALLS @ 16" OC W/ PT SILL
PLATES AND 3/4" T&G
PLYWOOD SHEATHING @
RAISED FLOOR AREA IN
BREEZEWAY (HATCHED
AREA)
PS
L
PO
ST
NEW PARTIAL DEPTH BEAM POCKET
MAY BE REQUIRED IN EXISTING
CONC. FOUNDATION WALL FOR
BEAM BEARING PLATE, VIF
NEW 2x JOIST SISTERED
TO EXISTING
C 7X14.75
F9
S-501
F9
S-501
F8
S-506
D9
S-501
D1
S-506
F4
S-505 D9
S-505
SIM.
C1
S-505
9' - 0" 9' - 0"
4x
PT P
O
ST
4x
PT P
O
ST
CENTER NEW POSTS
ON EXISTING ASSUMED
SOLID 8" BRICK
PARTIAL-HEIGHT WALL
4x
PT P
O
ST
4x
PT P
O
ST
4x
4x
P.T . P
O
ST
P.T . P
O
ST
EXISTING ASSUMED CONCRETE
PORCH
REMOVE EXISTING CAST IRON PORCH
COLUMNS AND REPLACE WITH NEW
PT POSTS SHOWN. PROVIDE POST
BASE SIMILAR TO W/ 6"
ANCHOR EMBEDMENT TO ASSUMED
SOLID CONCRETE BASE
/D9 S-501
3.
5X
5.
A5
S-501
A7
S-501
2x12 PT LEDGER
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LAYOUT, SPAN DIRECTION,
ETC. OF EXISTING ELEMENTS SHOWN IN FIELD. ANY DISCREPANCIES SHALL
BE REPORTED TO THE ARCHITECT/ENGINEER OF RECORD.
2. ALIGN TOP OF NEW FLOOR SHEATHING WITH EXISTING FLOOR SHEATHING.
3. EXISTING DIAGONALLY SHEATHED PLANK SUBFLOOR TO REMAIN. NEW
SUBFLOOR SHALL BE 3/4" T&G APA STRUCTURAL 1 RATED SHEATHING.
FASTEN TO SUPPORTING FRAMING W/ CODE APPROVED ADHESIVE AND 10d
NAILS @ 12" OC FIELD, 6" OC EDGE.
4. ALL NEW EXTERIOR WALLS SHALL BE 2x6 SPF #2 (OR BETTER) STUDS @ 16"
OC
5. EXTERIOR WALL SHEATHING SHALL BE MINIMUM 15/32" APA STRUCTURAL 1
RATED SHEATHING (FULLY BLOCKED). FASTEN TO SUPPORTING FRAMING
W/ 8d NAILS @ 12" OC FIELD, 6" OC EDGE UNLESS NOTED OTHERWISE.
6. SHADED WALLS INDICATE NEW OR ASSUMED EXISTING INTERIOR BEARING
WALLS. CONCTRACTOR TO VERIFY LAYOUT OF EXISTING BEARING WALLS
PRIOR TO DEMOLITION.
7. ALL BEARING WALL JAMB STUDS AND WOOD POSTS SHALL RUN
CONTINUOUS TO EXISTING OR NEW FOUNDATION WALL. SEE DETAIL
FOR DETAIL @ FLOOR SPLICE.
8. NEW FLUSH WOOD BEAMS IN EXISTING FLOOR SYSTEM SHALL MATCH
NEAREST SOLID LUMBER OR LVL BEAM DEPTH. SIZE SHOWN ON PLAN IS
MINIMUM DEPTH ALLOWED.
9. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL DIMENSIONS.
10. SEE DETAIL FOR REQUIRED FLOOR-TO-WALL ANCHORAGE AT
EXISTING JOISTS TO EXISTING BRICK WALLS.
11. SEE ARCHITECTURAL FOR EXISTING LINTELS THAT REQUIRE
REPLACEMENT. SEE DETAILS AND EXISTING LINTEL REPLACEMENT
SCHEDULE ON STRUCTURAL DETAIL SHEETS.
12. AT CONTRACTORS OPTION, NEW WOOD FRAMING OTHER THAN
BEAMS/HEADERS IN EXISTING FRAMING MAY BE SUBSTITUTED WITH COLD-
FORMED STEEL FRAMING. SYSTEM SHALL BE A DELEGATED DESIGN AND
STAMPED SHOP DRAWINGS AND CALCULATIONS SHALL BE PROVIDED TO
THIS ENGINEER FOR REVIEW.
/A1 S-505
/E1 S-507
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
*** SAFETY PAYS ***
*** SUPPORT VALUE ENGINEERING - IT PAYS ***
F
IL
E N
A M
E
F
IL
E N
U M
B E
R
PLAN NORTH
S-102
S
T F
L O
O R
F R
A M
IN
G
P L
A N
W R
IG
H
T -P
A T
T E
R S
O N
A F
B
D A
Y T
O N
O
H
IO
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G P
L
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
D H
IN
D
S
A M
C G
U
IR
E
S D
E G
A R
O
B K
R O
U S
K O
P
J A
N U
A R
Y
W Q
R -1
-F
-0
CERTIFIED FINAL SUBMITTAL
IM
P
R O
V E
F A
M
IL
Y H
O U
S
IN
G
P
F
IL
E N
U M
B E
R
TYPE B
3/16" = 1'-0"A1
1ST FLOOR FRAMING
8'4' 16'0 8'4' 16'0
GENERAL NOTES:
BRETT CARTER
S T
A
TE OF O
H
IO
P R
O F E
S
S IONA L EN
G
IN
E
E R
KROUSKOP
PE.57962
R E
GIST ERE
D
1/21/2021
W
2Q R
R
-0
DN
UP
DN
DN
PT 2X12 LEDGER
2X8 RAFTERS @ 16" OC MAX
PRE-ENGINEERED WOOD
TRUSSES @ 24" OC
H S S5X5X1/4 H
S S5X
5X 1/
4H S S5X5X1/4 H
S S5X
5X 1/
H S S5X
5X 1/
H S S5X
5X 1/
H S S5X
5X 1/
H S S5X
5X 1/
4H S S5X5X1/4
H S S5X5X1/4
H S S5X5X1/4
H S S5X5X1/4
PRE-ENGINEERED WOOD
GIRDER TRUSS
PROVIDE CUSTOM SADDLE BRACKET
WELDED TO TOP OF COLUMN FOR
BEAM ATTACHMENT, SEE DETAIL
W8X24
DOUBLE L6x3 1/2"x5/16" L.L.V.
C 7X
.7
W X
EXISTING JOISTS SHALL BE
CUT AS REQUIRED TO
INSTALL NEW FACE MOUNT
HANGERS TO NEW BEAM
TPL. 2x6 HEADER (TYP.)
PROVIDE PROFILED 6x6 POST @
ANGLED CORNERS, WITH 1"
NOTCH FOR HEADER BEARING
EXISTING ASSUMED
JOISTS @ 16" OC VIF
H S S5X5X1/4 H
S S5X
5X 1/
CONT. TRIPLE 1 3/4"X9 1/2"
LVL (TYP.)
DBL. 2x8 HEADER
PRE-ENGINEERED WOOD
TRUSSES @ 24" OC
DBL. PT 2x8 HEADER
4x4 PT POST
PT 2X12 LEDGER
2x8 PT RAFTERS @ 16" OC
DOUBLE PT 2X10
HIP BEAM
PROVIDE DOUBLE
2x6 POST BETWEEN
EACH WINDOW TO
BOTTOM OF BEAM
HEADER (TYP.)
TRIPLE 2x8 HEADER
VALLEY SET TRUSS OVERBUILD.
ROOF SHEATHING SHALL BE
CONTINUOUS UNDERNEATH
C 7X14.75
TRIPLE 1 3/4"x 9 1/4" LVL BEAM
F9
S-505
F4
S-506
F4
S-505
D8
S-506
E1
S-505
B8
S-506
B8
S-505 F1
S-506
C1
S-506
F1
S-506
/F9 S-505
P.T . P
O
ST
P.T . P
O
ST
4x
4x
REMOVE EXISTING CAST IRON PORCH
COLUMNS AND REPLACE WITH NEW
PT POSTS SHOWN. PROVIDE POST
CAP TO EXISTING BEAM SIM. TO /E1 S-505
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LAYOUT, SPAN DIRECTION,
ETC. OF EXISTING ELEMENTS SHOWN IN FIELD. ANY DISCREPANCIES SHALL
BE REPORTED TO THE ARCHITECT/ENGINEER OF RECORD.
2. EXISTING DIAGONALLY SHEATHED PLANK SUBFLOOR TO REMAIN. NEW
SUBFLOOR SHALL BE 3/4" T&G APA STRUCTURAL 1 RATED SHEATHING.
FASTEN TO SUPPORTING FRAMING W/ CODE APPROVED ADHESIVE AND 10d
NAILS @ 12" OC FIELD, 6" OC EDGE.
3. ALL NEW EXTERIOR WALLS SHALL BE 2x6 SPF #2 (OR BETTER) STUDS @ 16" O.C.
4. EXTERIOR WALL SHEATHING SHALL BE MINIMUM 15/32" APA STRUCTURAL 1
RATED SHEATHING (FULLY BLOCKED). FASTEN TO SUPPORTING FRAMING
W/ 8d NAILS @ 12" OC FIELD, 6" OC EDGE UNLESS NOTED OTHERWISE.
5. SHADED WALLS INDICATE NEW OR ASSUMED EXISTING INTERIOR BEARING
WALLS. CONTRACTOR TO VERIFY LAYOUT OF EXISTING BEARING WALLS
PRIOR TO DEMOLITION.
6. NEW ROOFS SHALL BE SHEATHED WITH 19/32" APA STRUCTURAL I RATED
SHEATHING W/ RSRS-03 NAILS @ 12" OC FIELD, 6" O.C. EDGE.
7. TYP. TRUSS/RAFTER BEARING ELEVATION…