LoadBank_Connection_Switch_Cabinet_Specification.pdf

PDF 2 MB Posted

Attached to
Construct Security Forces & Communications Training Facility Federal contract opportunity
Solicitation number
W912PQ19R9000
Issued by
Department of the Army New York Army National Guard

About this file

Loadbank Connection Switch Cabinet Specs

View the file

Other files for this federal contract opportunity

Other files attached to Construct Security Forces & Communications Training Facility, newest first.
File Type Posted
Aluminum_Standing_Seam_Roofing_Specification.pdf PDF
W912PQ19R9000_0006.pdf PDF
W912PQ19R9000_0005.pdf PDF
Commissioning_Specifications.pdf PDF
Electric_Traction_Passenger_Elevators_Specifications.pdf PDF
W912PQ19R9000_0004.pdf PDF
W912PQ19R9000_0003.pdf PDF
Sheet_C-504_dated_05_29_2019.pdf PDF
Revised_Specs_Vol_2.pdf PDF
Revised_Specs_Vol_1.pdf PDF
Geotechnical_Engineering_Report.pdf PDF
W912PQ19R9000_0002.pdf PDF
Attendance_Sheet.pdf PDF
Pre-Proposal_Slides_SF_&_Comm_Bldg.pdf PDF
W912PQ19R9000_0001.pdf PDF
EXHIBIT_C.pdf PDF
1170188_Volume_2_Specs.pdf PDF
W912PQ19R9000.pdf PDF
Combined_Drawing_Set_-_Issue_For_Construction.pdf PDF
1170188_Volume_1_Rev_1.pdf PDF
EXHIBIT_A.pdf PDF
EXHIBIT_D.pdf PDF
EXHIBIT_B.pdf PDF
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

gilleyk Highlight gilleyk Highlight

FFCC-S1 - - - - - - - -

FFCC-S1 - U3 - A - 1200 TM 80 - 1200 TM 80 - 1200 TM 80 - ALU - LA - A25

EX.

PART NO.

LOAD BANK

C.B. AMPS

400-1600

LOAD BANK

C.B. TRIP UNIT

TM = THERMAL MAGNETIC

LS = ELECTRONIC LS

LSI = ELECTRONIC LSI

LSG = ELECTRONIC LSG

LSIG = ELECTRONIC LSIG

KS = MOLDED CASE SWITCH

LOAD BANK

C.B. RATING

80 = 80% RATED

100 = 100% RATED

PERMANENT GEN.

C.B. AMPS

400-1600

PERMANENT GEN.

C.B. TRIP UNIT

TM = THERMAL MAGNETIC

LS = ELECTRONIC LS

LSI = ELECTRONIC LSI

LSG = ELECTRONIC LSG

LSIG = ELECTRONIC LSIG

KS = MOLDED CASE SWITCH

PERMANENT GEN.

C.B. RATING

80 = 80% RATED

100 = 100% RATED

PORTABLE GEN.

C.B. AMPS

400-1600

PORTABLE GEN.

C.B. TRIP UNIT

TM = THERMAL MAGNETIC

LS = ELECTRONIC LS

LSI = ELECTRONIC LSI

LSG = ELECTRONIC LSG

LSIG = ELECTRONIC LSIG

KS = MOLDED CASE SWITCH

PORTABLE GEN.

C.B. RATING

80 = 80% RATED

100 = 100% RATED

ENCLOSURE

CONSTRUCTION

CRS = COLD ROLLED STEEL

ALU = 5052 ALUMINUM

304 = 304 STAINLESS STEEL

316 = 316 STAINLESS STEEL

VOLTAGE

A B C N G

U1 = 120/240V (2PH + N + G) BLK RED WHT GRN

U2 = 240V (3PH + G) BLK RED BLU GRN

U3 = 208Y/120V (3PH + N + G) BLK RED BLU WHT GRN

U4 = 480Y/277V (3PH + N + G) BRN ORG YEL WHT GRN

U5 = 480V (3PH + G) BRN ORG YEL GRN

VOLTAGE

A B C N G

C1 = 120/240V (2PH + N + G) RED BLK WHT GRN

C2 = 240V (3PH + G) RED BLK BLU GRN

C3 = 208Y/120V (3PH + N + G) RED BLK BLU WHT GRN

C4 = 600Y/347V (3PH + N + G) RED BLK BLU WHT GRN

C5 = 600V (3PH + G) RED BLK BLU GRN

USA

CAMLOCK COLOUR GUIDE

CANADA

CAMLOCK COLOUR GUIDE

600V 480V 240V

A = 25 50 65

B = 35 65 100

C = 65 100 200

ASSEMBLY SCCR (kA)

ACCESSORIES

AXX = 400A CAMLOCK CABLE SET (XX = FT)

AA = CAMLOCK SNAP COVERS

AB = CUSTOM POWDER COAT COLOR

AC = HEATER C/W STAT

AD = GFCI RECEPTACLE

AE = KEY INTERLOCK

AF = TERMINAL STRIP

AG = PHASE SEQUENCE MONITOR

AH = POWER METER

AI = MICRO-SWITCH

AJ = LEG STAND SET

BLANK = NONE

AMPS OPTION LA OPTION LB OPTION LC

400A (2) #6 AWG - 250MCM, (2) #2 GND (1) #4 AWG - 600MCM, (1) #1/0 GND (1) 300 - 800 MCM, (1) #2/0 GND

800A (3) #4 AWG - 600MCM, (3) #1/0 GND (2) 300 - 800 MCM, (2) #2/0 GND (2) 500 - 1000 MCM, (2) #2/0 GND

1200A (4) #4 AWG - 600MCM, (4) #1/0 GND (3) 300 - 800 MCM, (3) #2/0 GND (3) 500 - 1000 MCM, (3) #2/0 GND

1600A (5) #4 AWG - 600MCM, (5) #1/0 GND (4) 300 - 800 MCM, (4) #2/0 GND (4) 500 - 1000 MCM, (4) #2/0 GND

LUG CONFIGURATIONS (PER POLE)