LoadBank_Connection_Switch_Cabinet_Specification.pdf
PDF 2 MB Posted
- Attached to
- Construct Security Forces & Communications Training Facility Federal contract opportunity
- Solicitation number
- W912PQ19R9000
About this file
Loadbank Connection Switch Cabinet Specs
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Aluminum_Standing_Seam_Roofing_Specification.pdf | ||
| W912PQ19R9000_0006.pdf | ||
| W912PQ19R9000_0005.pdf | ||
| Commissioning_Specifications.pdf | ||
| Electric_Traction_Passenger_Elevators_Specifications.pdf | ||
| W912PQ19R9000_0004.pdf | ||
| W912PQ19R9000_0003.pdf | ||
| Sheet_C-504_dated_05_29_2019.pdf | ||
| Revised_Specs_Vol_2.pdf | ||
| Revised_Specs_Vol_1.pdf | ||
| Geotechnical_Engineering_Report.pdf | ||
| W912PQ19R9000_0002.pdf | ||
| Attendance_Sheet.pdf | ||
| Pre-Proposal_Slides_SF_&_Comm_Bldg.pdf | ||
| W912PQ19R9000_0001.pdf | ||
| EXHIBIT_C.pdf | ||
| 1170188_Volume_2_Specs.pdf | ||
| W912PQ19R9000.pdf | ||
| Combined_Drawing_Set_-_Issue_For_Construction.pdf | ||
| 1170188_Volume_1_Rev_1.pdf | ||
| EXHIBIT_A.pdf | ||
| EXHIBIT_D.pdf | ||
| EXHIBIT_B.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
gilleyk Highlight gilleyk Highlight
FFCC-S1 - - - - - - - -
FFCC-S1 - U3 - A - 1200 TM 80 - 1200 TM 80 - 1200 TM 80 - ALU - LA - A25
EX.
PART NO.
LOAD BANK
C.B. AMPS
400-1600
LOAD BANK
C.B. TRIP UNIT
TM = THERMAL MAGNETIC
LS = ELECTRONIC LS
LSI = ELECTRONIC LSI
LSG = ELECTRONIC LSG
LSIG = ELECTRONIC LSIG
KS = MOLDED CASE SWITCH
LOAD BANK
C.B. RATING
80 = 80% RATED
100 = 100% RATED
PERMANENT GEN.
C.B. AMPS
400-1600
PERMANENT GEN.
C.B. TRIP UNIT
TM = THERMAL MAGNETIC
LS = ELECTRONIC LS
LSI = ELECTRONIC LSI
LSG = ELECTRONIC LSG
LSIG = ELECTRONIC LSIG
KS = MOLDED CASE SWITCH
PERMANENT GEN.
C.B. RATING
80 = 80% RATED
100 = 100% RATED
PORTABLE GEN.
C.B. AMPS
400-1600
PORTABLE GEN.
C.B. TRIP UNIT
TM = THERMAL MAGNETIC
LS = ELECTRONIC LS
LSI = ELECTRONIC LSI
LSG = ELECTRONIC LSG
LSIG = ELECTRONIC LSIG
KS = MOLDED CASE SWITCH
PORTABLE GEN.
C.B. RATING
80 = 80% RATED
100 = 100% RATED
ENCLOSURE
CONSTRUCTION
CRS = COLD ROLLED STEEL
ALU = 5052 ALUMINUM
304 = 304 STAINLESS STEEL
316 = 316 STAINLESS STEEL
VOLTAGE
A B C N G
U1 = 120/240V (2PH + N + G) BLK RED WHT GRN
U2 = 240V (3PH + G) BLK RED BLU GRN
U3 = 208Y/120V (3PH + N + G) BLK RED BLU WHT GRN
U4 = 480Y/277V (3PH + N + G) BRN ORG YEL WHT GRN
U5 = 480V (3PH + G) BRN ORG YEL GRN
VOLTAGE
A B C N G
C1 = 120/240V (2PH + N + G) RED BLK WHT GRN
C2 = 240V (3PH + G) RED BLK BLU GRN
C3 = 208Y/120V (3PH + N + G) RED BLK BLU WHT GRN
C4 = 600Y/347V (3PH + N + G) RED BLK BLU WHT GRN
C5 = 600V (3PH + G) RED BLK BLU GRN
USA
CAMLOCK COLOUR GUIDE
CANADA
CAMLOCK COLOUR GUIDE
600V 480V 240V
A = 25 50 65
B = 35 65 100
C = 65 100 200
ASSEMBLY SCCR (kA)
ACCESSORIES
AXX = 400A CAMLOCK CABLE SET (XX = FT)
AA = CAMLOCK SNAP COVERS
AB = CUSTOM POWDER COAT COLOR
AC = HEATER C/W STAT
AD = GFCI RECEPTACLE
AE = KEY INTERLOCK
AF = TERMINAL STRIP
AG = PHASE SEQUENCE MONITOR
AH = POWER METER
AI = MICRO-SWITCH
AJ = LEG STAND SET
BLANK = NONE
AMPS OPTION LA OPTION LB OPTION LC
400A (2) #6 AWG - 250MCM, (2) #2 GND (1) #4 AWG - 600MCM, (1) #1/0 GND (1) 300 - 800 MCM, (1) #2/0 GND
800A (3) #4 AWG - 600MCM, (3) #1/0 GND (2) 300 - 800 MCM, (2) #2/0 GND (2) 500 - 1000 MCM, (2) #2/0 GND
1200A (4) #4 AWG - 600MCM, (4) #1/0 GND (3) 300 - 800 MCM, (3) #2/0 GND (3) 500 - 1000 MCM, (3) #2/0 GND
1600A (5) #4 AWG - 600MCM, (5) #1/0 GND (4) 300 - 800 MCM, (4) #2/0 GND (4) 500 - 1000 MCM, (4) #2/0 GND
LUG CONFIGURATIONS (PER POLE)
**FOR CUSTOM LUG SIZES, SPECIFY WHEN PLACING ORDER
| Text1: |
| Text2: |
| Text3: |
| Text4: |
| Text5: |
| Text6: |
| Text7: |
| Text8: |
| Text9: |
| Text10: |
| Text11: |
| Text12: |