BLDG 150
BLDG 180
ACCESS CONTROL
TO BE PROVIDED BY
B140 PROJECT
PRECAST CONCRETE
JERSEY BARRIER
PRECAST CONCRETE
JERSEY BARRIERS
PRECAST CONCRETE
JERSEY BARRIERS
EQUIPMENT YARD
BLDG 160
CONCRETE
SIDEWALK
SEE NOTE 2
F
A
L
C
O
N
S
T
NCO DRIVE
AIRCRAFT APRON
PROJECT BY OTHERS
SEE PAVEMENT
JOINTING PLAN CS400
N 719867.71
E 1471744.65
N 719952.05
E 1471832.06
N 719952.44
E 1471898.97
N 719895.82
E 1471963.42
N 719813.40
E 1472069.48
SEE SHEET CS102 FOR SITE
PLAN ENLARGEMENT
LEGEND:
ASPHALT PAVEMENT
PCC PAVEMENT
CONCRETE SIDEWALK
GRASS
CS501
A2
CS501
D1
CS500
C1
92654B150C-CS101.DWG
SITE PLAN
K. ROBERTSS. WAGNER
S. LUEHRS
ECS101
9/22/16
92654
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned project contract rev.drawing file
C O
P Y
R I G
H
B
U R
A
D
M c D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
GENERAL SITE NOTES:
1. CONTRACTOR SHALL SURVEY AND FIELD VERIFY SIDEWALK ELEVATIONS AND
TIE-IN LOCATIONS PRIOR TO BEGINNING SITE DEMOLITION.
2. CONTRACTOR SHALL MAINTAIN POSITIVE DRAINAGE AWAY FROM EQUIPMENT
YARD AND BUILDING.
3. CONTRACTOR SHALL COORDINATE THE TIMING OF THE HANGAR SLABS
PAVEMENT REMOVAL AND REPLACEMENT WITH THE AIRCRAFT APRON
PROJECT (BY OTHERS).
4. SEE STRUCTURAL DRAWINGS FOR MISCELLANEOUS SITE EQUIPMENT AND
PADS.
5. SEE DRAWING CS400 FOR CONCRETE JOINTING AND ELEVATION PLAN FOR
INTERIOR HANGAR AREA.
A1
SITE PLAN
SCALE: 1" = 20'
N
20' 40'0
CS500
A4
CS500
C1
A 11/4/16 B.1 SUBMITTAL SEW
GENERAL LANDSCAPING NOTES:
1. CONTRACTOR SHALL EXAMINE THE FINISHED SURFACE, GRADES, TOPSOIL
QUALITY, AND TOPSOIL DEPTH PRIOR TO LANDSCAPING. NO WORK SHALL BE
CONDUCTED UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
CONTRACTOR SHALL VERIFY LIMITS OF WORK BEFORE STARTING WORK.
2. CONTRACTOR SHALL IMPORT AND/OR PROVIDE SALVAGED TOPSOIL MEETING
THE REQUIREMENTS OF THE SPECIFICATIONS.
3. THE CONTRACTOR SHALL FURNISH AND PLACE A MINIMUM OF 4.00 INCHES OF
TOPSOIL, WITH THE LOWER PORTION BLENDED INTO EXISTING SOILS.
4. CONTRACTOR SHALL PROPERLY WATER ALL NEW LANDSCAPING NECESSARY
TO ESTABLISH GROWTH.
5. CONTRACTOR SHALL PROVIDE LANDSCAPING MAINTENANCE FOR 120 DAYS
AFTER CONSTRUCTION IS COMPLETE.
6. CONTRACTOR SHALL MAINTAIN EXISTING VEGETATION AS MUCH AS
PRACTICABLE.
10.00
10.00
CS500
A4
CS500
A4
B 1/4/17 B.2 SUBMITTAL SEW
C 2/28/17 B.3 SUBMITTAL SEW
D 4/14/17 B.3 FINAL SUBMITTAL SEW
E
E 7/7/17 AMENDMENT 1 SEW
7.89
N 720010.32
E 1471960.65
N 720015.61
E 1471954.64
N 719983.08
E 1471936.54
N 719972.67
E 1471948.42
N 719942.62
E 1471922.03
N 719819.82
E 1472061.81
N 719881.14
E 1471979.77
N 719866.21
E 1471966.66
LEGEND:
ASPHALT PAVEMENT
CS501
A2
CONCRETE SIDEWALK
GRASS
CS500
C1
92654B150C-CS102.DWG
ENLARGED SITE PLAN
K. ROBERTSS. WAGNER
S. LUEHRS
ECS102
9/22/16
92654
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned project contract rev.drawing file
C O
P Y
R I G
B
U R
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
A1
ENLARGED SITE PLAN
SCALE: 1" = 20'
N
20' 40'0
A 11/4/16 B.1 SUBMITTAL SEW
MATCH EXISTING GRADE AT SIDEWALK
STAIR RISE AND RUN
TO MATCH EXISTING
(SEE NOTE 2)
ELEVATION AT
EQUIPMENT YARD WALL
TO MATCH STRUCTURAL
328.50± (SEE NOTE 3)
SIDEWALK SHALL MEET
ADA REQUIREMENTS FOR
ACCESSIBLE ROUTES
GRASS
GENERAL SITE NOTES:
1. SEE NOTES ON CS101.
2. CONTRACTOR SHALL SURVEY AND FIELD VERIFY SIDEWALK ELEVATIONS AND
TIE-IN LOCATIONS PRIOR TO BEGINNING SITE DEMOLITION.
3. CONTRACTOR SHALL MAINTAIN ADEQUATE POSITIVE DRAINAGE AWAY FROM
EQUIPMENT YARD AND BUILDING.
BLDG 150
F
A
L
C
NCO DRIVE
B 1/4/17 B.2 SUBMITTAL SEW
SIDEWALK SHALL
MEET ADA
REQUIREMENTS
FOR ACCESSIBLE
ROUTES
MATCH GRADE
MATCH GRADE
AT ASPHALT
MATCH GRADE
MATCH GRADE
20.00 20.00 20.00 20.00 20.00 20.00 20.0016.00
2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
14.09
2.00
SEE STRUCTURAL FOR
EQUIPMENT YARD
CONCRETE
C 2/28/17 B.3 SUBMITTAL SEW
BUILDING SIGN
CS500
A5
D 4/14/17 B.3 FINAL SUBMITTAL SEW
PERSPECTIVE VIEW
NOT TO SCALE
M
I N
M
I N
FLOW
M
I N
M
I N
NOTES:
1. WOVEN WIRE FENCE TO BE FASTENED SECURELY TO
FENCE POSTS WITH WIRE TIES OR STAPLES.
2. FILTER CLOTH TO BE FASTENED SECURELY TO
WOVEN WIRE FENCE WITH TIES SPACED EVERY 24"
AT TOP AND MID SECTION
3. WHEN TWO SECTIONS OF FILTER CLOTH ADJOIN
EACH OTHER THEY SHALL BE OVER- LAPPED BY SIX
INCHES AND FOLDED.
4. MAINTENANCE SHALL BE PERFORMED AS NEEDED
AND MATERIAL REMOVED WHEN "BULGES" DEVELOP
IN THE SILT FENCE.
STEEL EITHER "T" OR "U"
TYPE OR 2" HARDWOOD.
WOVEN WIRE 14 1/2 GA.
6" MAX. MESH OPENING.
FILTER X, MIRAFI 100X,
STABILINKA T140N OR
APPROVED EQUAL.
GEOFAB, ENVIROFENCE,
OR APPROVED EQUAL.
POSTS:
FENCE:
FILTER CLOTH:
PREFABRICATED
UNIT:
H E
I G
H T
F
F
I L T
E R
F
L
O
W
F
L
O
W
10' MAX CENTER TO CENTER
36" MIN. FENCE
POST ( 10' MAX.
C. TO C. )
WOVEN WIRE FENCE ( 14 1/2
GA. MIN., MAX 6" MESH
SPACING) WITH FILTER
CLOTH OVER
UNDISTURBED GROUND
EMBED FILTER
CLOTH MIN. 6" INTO
GROUND
36" MIN. FENCE
POSTS DRIVEN
16" INTO GROUND
WOVEN WIRE
FENCE (14 1/2
GA., MAX. 6"
MESH SPACING).
5' MAX
M
A X
VARIES
4" TROWEL FINISH (TYP.)
BROOM
1/8"
1/2"
TOOLED
JOINTS
(TYP)
EXPANSION JOINTS
@ 25' CTRS MAX
T
Y P
TOOLED JOINT
PLAN
5" P.C.C.
18"
CRUSHED
ROCK BASE
COMPACTED SUBGRADE
SECTION A
1/2" RADIUS (TYP.)
1. BROOM FINISH SHALL BE APPLIED NORMAL TO DIRECTION OF TRAFFIC.
2. SAW JOINTS TO BE LOCATED TO MAINTAIN AN APPROXIMATE SQUARE
SLAB AS INDICATED ON PLANS.
3. EXPANSION JOINTS TO BE LOCATED WHERE WALK ABUTS CONCRETE
CURBS, DRIVES, STRUCTURES AND WHERE WALK CHANGES DIRECTION.
TOOLED JOINT EXPANSION JOINT
NOTES:
PRE-FORMED EXP.
JOINT MATERIAL
1/8" RAD 1/8" RAD
EXPANSION JOINT
SECTION B
COMPACTED SUBGRADE
18" CRUSHED ROCK BASE
5" P.C.C.
A4
PRECAST CONCRETE JERSEY BARRIER
SCALE: NTS
A1
SILT FENCE
SCALE: NTS
A
B
24"
1. BARRIER SHALL BE SPACED TO PROVIDE NO MORE THAN 3.00'
CLEAR BETWEEN ADJACENT BARRIERS OR EDGE OF
PAVEMENT.
NOTES:
C1
CONCRETE SIDEWALK
SCALE: NTS
A5
BUILDING SIGN
SCALE: NTS
8" CONCRETE SONOTUBE TO
48" MIN BELOW GRADE
3" SQ. SIGN POST
SLOPE AWAY FROM POST
FINISH GRADE
FREESTANDING SIGN TYPICAL ELEVATION
FREESTANDING SIGN
NOTES:
1. SIGN IS FREESTANDING, STEEL FRAME FABRICATED PER DIMENSIONS NOTED. SIGN CONTRACTOR SHALL
PROVIDE SHOP DRAWINGS SHOWING ALL FRAMING, CONNECTIONS, WELDS, FINAL SIGN DIMENSIONS, APPROVED MATERIALS, COLORS AND LOGOS FOR APPROVAL.
2. ALL VINYL GRAPHICS SHALL BE HIGH PERFORMANCE SELF ADHESIVE TYPE AND SHALL BE APPROVED BY THE
CONTRACTING OFFICER PRIOR TO FABRICATION.
3. ALL SIGNS SHALL BE SET LEVEL AND PLUMB
4. ALL EXPOSED JOINTS & CORNERS SHALL BE FINISHED SMOOTH AND PAINTED
5. KNICKS, SCRATCHES OR DAMAGE CAUSED DURING INSTALLATION SHALL BE REPAIRED IMMEDIATELY BY THE
SIGN CONTRACTOR.
REFER TO TYPICAL
FOOTING DETAIL,
THIS DETAIL
92654
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned project contract rev.drawing file
C O
P Y
R I G
B
U R
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
92654B150C-CS500.DWG
SITE DETAILS
S. WAGNER
S. LUEHRS
ECS500
9/22/16
A 11/4/16 B.1 SUBMITTAL SEW
B 1/4/17 B.2 SUBMITTAL SEW
C 2/28/17 B.3 SUBMITTAL SEW
D 4/14/17 B.3 FINAL SUBMITTAL SEW
7 8 9 10 11 12 13 14 15 16 17
P
Q
R
S
T
U
M
A1 S-500
D2 S-501
EXISTING TRUSS
EXISTING TRUSS
EXISTING TRUSS
EXISTING TRUSS
EXISTING TRUSS
TR
U
SS
ED
R U
N W
AY
E
N C
LO
SE
D T
R
AC
K
FALL RESTRAINT TRACK
FALL RESTRAINT TRACK
FALL
R
ESTRAIN
T TRACK
FALL
R
ESTRAIN
T TRACK
FA
LL
R
ES
TR
AI
N T
TR
AC
K
2 TON UNDERHUNG
BRIDGE CRANE
B/STL EL 125' - 3"
B/STL EL 125' - 3"
B/STL E
L 1
3"
B/STL E
L 1
3"
B/
ST
L
EL
EXISTING TRUSS
6 18
1. SEE SPECIFICATION 11 01 50 FOR FALL RESTRAINT REQUIREMENTS.
2. FALL RESTRAINT RAIL SHALL CONNECT TO PRIMARY ROOF TRUSSES ONLY.
3. BLACK TRIANGLES INDICATE LOCATIONS OF FALL RESTRAINT TRUSSED TRACK SUPPORT.
4. FALL RESTRAINT AT BRIDGE CRANE LOCATION SHALL HAVE EMPLOY AN OPERATIONAL PROCEDURE
TO LOCK OUT/TAG OUT FALL RESTRAINT WHEN CRANE IS USED (AND VICE VERSA).
1. RUNWAY BEAM SHALL BE COMPRISED OF TRUSSED STEEL ENCLOSED TRACK SUPPORTED AT BLACK
CIRCLE LOCATIONS.
2. END TRUCKS SHALL BE SIZED TO FIT THE ENCLOSED TRACK AND MEET ANSI B30.11.
3. FESTOON GLIDERS/TROLLEYS ARE REQUIRED TO SUPPORT POWERED HOIST.
4. PROVIDE FESTOON END CLAMPS WHERE REQUIRED, AND APPROPRIATE STACK
SECTION FOR FESTOON STORAGE.
5. PROVIDE STANDARD HANGERS WITH SWAY BRACING AND CONNECTIONS TO EXISTING STRUCTURE
FOR TRUSSED STEEL RUNWAY TRACK.
6. BRIDGE SHALL BE COMPRISED OF A TRUSSED STEEL ENCLOSED TRACK BRIDGE WITH
ELECTRIC HOIST, TROLLEY, AND BRIDGE (2 TON CAPACITY), ANSI MH 27.2 REQUIREMENTS.
7. MAXIMUM HANGER LOAD: 6500 LB.
8. BRIDGE CRANE SHALL BE PER SPEC 41 22 23.19.
9. CAPACITY: 2 TON
10. TYPE: BOTTOM RUNNING ENCLOSED TRACK
11. REQUIRED HOOK HEIGHT FROM OPERATING FLOOR: 32'-0"
12. APPROXIMATE BRIDGE SPAN: 33'-0"
13. CRANE TO OPERATE: INDOORS
14. POWER SOURCE: 480 VOLTS 60 HZ
TY
P45
16' - 6" 16' - 6"
/8
TR
U
SS
ED
R
U N
W
AY
E N
C
LO
SE
D
T R
AC
K
FALL RESTRAINT TRACK
SUPPORT POINT, TYP
CRANE ANCHOR POINT, TYP
BOTTOM CHORD
BRACING, TYP
HATCHED AREA
REPRESENTS
CRANE COVERAGE
TYP
~ 2' - 7"
TYP
~ 6' - 0"
TYP
~ 7' - 0"
FALL RESTRAINT NOTES:
UNDERHUNG BRIDGE CRANE NOTES:
TOC
100' - 0"
Level 1 100' - 0"Level 1 100' - 0" Level 1 100' - 0"Level 1 100' - 0" Level 1 100' - 0"Level 1 100' - 0"
7 8 9 10 11 12 13 14 15 16 17
A1
S-501FALL RESTRAINT TRACK FALL RESTRAINT TRACK
~1 4'
3"
TRUSSED STEEL
TRACK BRIDGE,
HOOK HEIGHT EL =
32'-0" ABOVE FINISH
FLOOR
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
PY
R
IG
B
U R
N S
AN
D
M cD
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
ES-500
FALL RESTRAINT AND CRANE PLAN
10/09/16
P. MANIS W. BAILEY
C. MCGEE
SCALE: 1/8" = 1'-0"B1 FALL RESTRAINT AND CRANE PLAN
SCALE: 1" = 10'-0"A1 FALL RESTRAINT AND CRANE ELEVATION
A 11/4/16 B.1 SUBMITTAL PM
B 1/4/17 B.2 SUBMITTAL PM
C 2/28/17 B.3 SUBMITTAL PM
D 4/14/17 B.3 FINAL SUBMITTAL PM
E 7/7/17 Amendment 1 PME
E
1. THE EXISTING EQUIPMENT MAY BE REUSED IF FOUND TO BE
IN WORKING ORDER AND IT MEETS THE REQUIREMENTS OF
THIS CONTRACT. ALL EXISTING CONDITIONS ALONG WITH ALL
NEW WORK SHALL BE SHOWN IN THE DESIGN AND
CALCULATIONS. FINAL TESTING WILL NOT DIFFERENTIATE
BETWEEN NEW AND EXISTING, ALL SHALL BE TESTED AS
NEW. THE CONTRACTOR SHOULD ASSUME THE EXISTING
CONDITIONS ARE DEFICIENT UNTIL FOUND TO BE
SATISFACTORY.
2. SERVE THE FIRE SUPPRESSION FROM THE EXISTING
DOMESTIC SYSTEM. PERFORM A HYDRANT FLOW TEST,
AND INCORPORATE THIS TEST INTO THE HYDRAULIC
CALCULATIONS. HYDRANT FLOW TESTING SHALL BE IN
ACCORDANCE WITH NFPA 291, AND THE RESULTS OF THE
TESTING SHALL BE SUBMITTED AS INDICATED IN NFPA 291
FIGURE 4.11.2.
FOR INFORMATION ONLY: FLOW TEST 1
DATE JUNE 14, 2016
STATIC 83 PSI
RESIDUAL 42 PSI
FLOW 2,116 GPM
3. THE FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED AND
INSTALLED BY A LICENSED / CERTIFIED COMPANY WHERE
EMPLOYEES ARE LICENSED / CERTIFIED TO INSTALL FIRE
PROTECTION EQUIPMENT IN THE STATE OF VERMONT.
4. ALL COMPONENTS AND ASSEMBLIES USED IN THIS FIRE
PROTECTION SYSTEM MUST BE SPECIFICALLY UL LISTED
OR FM APPROVED FOR THEIR INTENDED USE.
5. USE SCHEDULE 40 BLACK STEEL FIRE WATER PIPING ON
THIS PROJECT EXCEPT WHERE NOTED. PROVIDE PIPING
MATERIAL SUITABLE FOR USE IN POTABLE WATER SYSTEMS
IN COMPLIANCE WITH THE INTERNATIONAL PLUMBING
CODE AND LOCAL JURISDICTION PRIOR TO THE BACKFLOW
PREVENTER.
1. PROVIDE ALL NECESSARY COMPONENTS TO MODIFY THE EXISTING
WET-PIPE SPRINKLERS IN THE SUPPORT AREA AND EXISTING
PRE-ACTION SYSTEM IN THE HANGAR BAY. EXTEND THE EXISTING
WET-PIPE SYSTEM INTO THE NEW OFFICE ADDITION. MODIFY THE
FOAM SYSTEM FOR THE CHANGE IN AIRCRAFT, AND MODIFIED
PERFORMANCE REQUIREMENTS INDICATED FOR NEW PARKING
PLAN.
2. COORDINATE ALL REQUIRED SYSTEMS TO THE SATISFACTION OF
THE ENGINEER AND AUTHORITY HAVING JURISDICTION. ANY
DEFICIENCIES, INCONSISTENCIES, OR POORLY COORDINATED
INSTALLATIONS SHALL BE CORRECTED BY THE CONTRACTOR AT
NO ADDITIONAL COST.
3. FINAL DESIGN REQUIREMENTS (DEVICE QUANTITY, SIZE, AND
LOCATIONS) ARE THE SOLE RESPONSIBILITY OF THE FIRE
SUPPRESSION CONTRACTOR. DRAWINGS INDICATE MINIMUM
REQUIREMENTS; THE FIRE SUPPRESSION CONTRACTOR WILL
BE RESPONSIBLE FOR VERIFYING AND COORDINATING FINAL
DESIGN REQUIREMENTS WITH THESE CONSTRUCTION
DOCUMENTS, SPECIFICATIONS, REFERENCE DOCUMENTS,
APPLICABLE CODES, AND FACILITY USER REQUIREMENTS.
4. ALL DRAIN PENETRATIONS THRU EXTERIOR WALL SHALL BE NO
GREATER THAN 2'-0" ABOVE FINISHED GRADE
5. INSTALL FIRE PROTECTION PIPE HANGERS PER THE FOLLOWING
LIMITATIONS:
A) THE DEAD LOAD APPLIED TO ANY STRUCTURALLY
MEMBER SHALL NOT EXCEED 300 LBS. PROVIDE .
TRAPEZE HANGERS TO DISTRIBUTE THE LOAD
BETWEEN STRUCTURAL MEMBERS WHERE A
HANGER EXCEEDS THE LIMITATIONS.
B) SWAY BRACES FOR PIPING LATERAL LOADS
SHALL NOT BE ATTACHED TO ROOF JOIST
BOTTOM CHORDS. BRACE LOADS (WORKING
STRESS) SHALL BE LIMITED TO THE FOLLOWING:
1. 300 LBS. WHEN ATTACHED TO JOIST
TOP CHORD.
2. 300 LBS. WHEN ATTACHED TO FLOOR
SLAB.
6. ALL VALVES INCLUDING CONTROL AND TRIM VALVES SHALL BE
WITHIN 6'-0" AFF.
7. INSTALL ALL FIRE SUPPRESSION FOAM / WATER PIPING AS PART
OF THIS PROJECT IN ACCORDANCE WITH NFPA 13 PROTECTION
OF PIPING DAMAGE IN AREAS SUBJECT TO EARTHQUAKES. SHORT
PERIOD RESPONSE FACTOR Ss 0.355 PER STRUCTURAL SHEET S-001.
8. REPLACE EXISTING FIRE PUMP TO SUPPORT NEW PRESSURE
DEMANDS. SYSTEM SHALL BE DESIGNED TO KEEP PRESSURE UNDER
ANY CONDITION WITH THE EXISTING UNDERGROUND PIPING TO LESS
THAN 200 PSI.
9. BASE FOAM GENERATOR BRACING CALCULATIONS ON A Ss 0.95. THE
USE OF ALL THREAD ROD OR CABLING FOR SUPPORTING OR BRACING
GENERATORS IS NOT ALLOWED.
10. REFERENCE STRUCTURAL DRAWINGS FOR SUPPORT DETAILS OF THE
FOAM GENERATORS IN HANGAR BAY.
11. MAINTAIN MINIMUM CLEAR HEIGHT OF FIRE SUPPRESSION EQUIPMENT
IN HANGAR BAY INCLUDING FOAM GENERATORS OF 26 FEET.
SECTION, DETAIL OR
ELEVATION IDENTIFICATION
MARK
PLATE NUMBER WHERE SECTION,
DETAIL OR ELEVATION IS TAKEN
SECTION, DETAIL OR ELEVATION TITLE
PLATE NUMBER WHERE DETAIL IS
DRAWN
DETAIL
NUMBER
DETAIL CALLOUT SYMBOL
DETAIL/SECTION TITLE
SECTION CUT SYMBOL
SECTION
LETTER
PLATE NUMBER
WHERE SECTION IS
DRAWN
VIEW
SECTION
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
FP FIRE PROTECTION
FPC FIRE PUMP CONTROLLER
JPC JOCKEY PUMP CONTROLLER
NC NORMALLY CLOSED
NO NORMALLY OPEN
(S) ELECTRICALLY SUPERVISED
SQ FT SQUARE FOOT
EXISTING
TO REMAIN DEMOLITION
NEW WORK
EXISTING
TO REMAIN
CONSTRUCTION INTERFACE
FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA
PRESSURE RELIEF VALVE
OUTSIDE SCREW AND YOKE
VALVE (OS&Y)
VALVE
ANGLE VALVE
DOUBLE CHECK BACKFLOW
PREVENTOR
INDICATING BUTTERFLY VALVE
PRESSURE REGULATING VALVE
ALARM CHECK VALVE
CHECKVALVE
BASKET STRAINER
PIPE CAP
AUTOMATIC DRAIN VALVE
FIRE DEPARTMENT
CONNECTION
FLOW METER
PRESSURE GAUGE
INDUCTOR
SIGHT GLASS
PRESSURE SWITCH
DELUGE VALVE
DRY VALVE
PREACTION VALVE
SOV
SOLENOID VALVE
FLOW SWITCH
FIRE SUPPRESSION LEGEND FIRE SUPPRESSION ABBREVIATIONS FIRE SUPPRESSION DESIGN CRITERIA FIRE SUPPRESSION GENERAL NOTES
DRAIN PIPING
FIRE PROTECTION PIPING
PIPING SYMBOLS
AUTOMATIC AIR RELEASE VALVE
FIRE PUMP
JOCKEY PUMP
F
J
RISER LOCATION
HAZARD CLASSIFICATION
NOTE 1: PROVIDE 200ºF RATED SPRINKLERS IN MECHANICAL AND COMMUNICATION ROOMS.
NOTE 2: WHERE CEILINGS ARE PRESENT USE WHITE QUICK RESPONSE SEMI-RECESSED PENDENT SPRINKLERS.
NOTE 3: WHERE CEILINGS ARE NOT PROVIDED USE BRASS UPRIGHT SPRINKLERS.
NO HATCH
MARK
WET
SYSTEM
TYPE
WET
SINGLE INTERLOCK
PRE-ACTION
REMOTE
AREA
SQ FT
HOSE
DEMAND
GPM
TEMP
RATING TYPE
ORDINARY
ORDINARY
175ºF
QUICK RESPONSE
SEMI-RECESSED PENDENT
QUICK RESPONSE
UPRIGHT
QUICK RESPONSE
UPRIGHT
NOTES
1,2
0.10
DENSITY
GPM/SF
0.20
0.20
MAXIMUM AREA
PER HEAD
SQ FT
LIGHT HAZARD
ORDINARY HAZARD
HANGAR BAY
UFC 4-211-01
SPRINKLER CHARACTERISTICS
FINISH
WHITE
BRASS
BRASS
FIRE SUPPRESSION SYSTEM
DRY SYSTEM
WET SYSTEM
PREACTION SYSTEM
FOAM SYSTEM
ELBOW UP OR DOWN
TEE UP OR DOWN
SYMBOL IDENTIFICATION LEGEND
EXISTING EQUIPMENT
DEMO EXISTING EQUIPMENT
NEW EQUIPMENT
FOAM GENERATOR
MINIMUM
K-FACTOR
5.6
8.0
8.0
6-WAY FLOW TEST HEADER
FOAM TANK
E
FIRE PUMP SCHEDULE
PUMP
TYPE
FP-1*
MARK
ELECTRICAL DATA
HSCP
DRIVE
TYPE
ELECTRIC
SERVICE
TYPE
FLOW
RATE
(GPM)
TOTAL
HEAD
(PSI) HP V/Ph/Hz NOTES
FIRE PUMP
JOCKEY PUMP
2000 190 400 460/3/60
FP-2* HSCP ELECTRIC FIRE PUMP 2000 190 400 460/3/60
JP-1* MSC ELECTRIC 20 195 5 460/3/60
* FIRE PUMPS SERVE B150, B130, B131, AND B132.
HSCP = HORIZONTAL, SPLIT-CASE
MSC = MULTI-STAGE CENTRIFUGAL
PRIMARY PUMP; SOFT START
SECONDARY PUMP; SOFT START
VARIABLE SPEED
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
EFX001
FIRE SUPPRESSION NOTES, LEGEND AND
ABBREVIATIONS
02/27/17
A. DAHL C. CAHILL
A. HANKINS
A 11/4/2016 B.1 SUBMITTAL AH
B 1/4/17 B.2 SUBMITTAL AH
C 2/27/17 B.3 SUBMITTAL AH
D 4/14/17 B.3 FINAL SUBMITTAL AH
E 7/7/17 AMENDMENT 1 AH
HAZARD SCHEDULE
HAZARD CLASSIFICATION
NO HATCH
MARK
LIGHT HAZARD
ORDINARY HAZARD
HANGAR BAY
UFC 4-211-01
1 2 3 4 5 6
7 8
9 10 11
F
E
D
C B
A
TOOL/ PARTS
STORAGE
BATTERY
CHARGING
COLLATERAL
STORAGE
SPECIAL ACCESS
STORAGE (SAPF)
TOOL ROOM
STAIR
ST02
VRC LIFT
EV02
TOOL ISSUE
HANGAR BAY
MOF
MOF SUPER.
COMM
ELEV. VEST.
STAIR
ST01
CORRIDOR
DEBRIEF/ FSE
MX TRAINING
TESTING
HEF
AAS CC
AAS ADMIN
AAS NCOIC
CORRIDOR
QA
QA CLASSROOM
MXG
CONFERENCE
ROOM
DSG OFF
QA CHIEF
MXG CD
ADMIN
MEETING ROOM
CORRIDOR
MXG CC
MXG CHIEF
1ST SHIRTS (2)
ADMIN SUPER
VESTIBULE
MXG XO
AMXS/ CC
AMXS/ CHIEF
BREAK AREA
MEN'S SHOWER/
LOCKER
WOMEN'S
SHOWER/
LOCKER
WOMEN'S TOILET
MEN'S TOILET
JAN
TOILET
VESTIBULE
M E
C H
A N
IC
A
L
MECH YARD
ELECTRICAL
COMMS
E G
R E
S S
O F
F
IC
E
EGRESS
MAINTENANCE
AVIONICS
AVIONICS OFFICE
AVIONICS SUPER.
ALIS WORK ROOM
APG
APG SUPER.
APG OFFICE
CORRIDOR
AMU READY
ROOM
MEN'S TOILET/
SHOWER
CORRIDOR
SHOWER
WOMEN'S TOILET
ELEV
EV01
DSG OFF
TOOL/ PARTS
STORAGE
BATTERY
CHARGING
COLLATERAL
STORAGE
SPECIAL ACCESS
STORAGE (SAPF)
TOOL ROOM
STAIR
ST02
VRC LIFT
EV02
TOOL ISSUE
HANGAR BAY
MOF
MOF SUPER.
COMM
ELEV. VEST.
STAIR
ST01
CORRIDOR
DEBRIEF/ FSE
MX TRAINING
TESTING
HEF
AAS CC
AAS ADMIN
AAS NCOIC
CORRIDOR
QA
QA CLASSROOM
MXG
CONFERENCE
ROOM
DSG OFF
QA CHIEF
MXG CD
ADMIN
MEETING ROOM
CORRIDOR
MXG CC
MXG CHIEF
1ST SHIRTS (2)
ADMIN SUPER
VESTIBULE
MXG XO
AMXS/ CC
AMXS/ CHIEF
BREAK AREA
MEN'S SHOWER/
LOCKER
WOMEN'S
SHOWER/
LOCKER
WOMEN'S TOILET
MEN'S TOILET
JAN
TOILET
VESTIBULE
M E
C H
A N
IC
A
L
MECH YARD
ELECTRICAL
COMMS
E G
R E
S S
O F
F
IC
E
EGRESS
MAINTENANCE
AVIONICS
AVIONICS OFFICE
AVIONICS SUPER.
ALIS WORK ROOM
APG
APG SUPER.
APG OFFICE
CORRIDOR
AMU READY
ROOM
MEN'S TOILET/
SHOWER
CORRIDOR
SHOWER
WOMEN'S TOILET
ELEV
EV01
DSG OFF
MOF CC
STORAGE
PRINTER/
SHREDDER ROOM
C5
FX101
1 1
1 1
E3
FX101
12 13 14 15 16 17
U
T
S
R
Q
P
N
M
L
K
H
18 19 20 21 22 23 24
J
G
C.1
BATTERY
STORAGE
(NO SPRINKLERS REQUIRED)
EGRESS
STORAGE
B5
FX101
OPEN
TO ABOVE
11 11
F F
HEF
R
Q
J
FOAM TANK
TO BUILDING
B130
FROM SUPPLY
AFTER PUMP
1 2 3
ELEV
EV01
ELEV. VEST.
L
K
H
G
SIDE WALL SPRINKLER
FROM FIRE
WATER SUPPLY
(S)
P
(S)FROM SPRINKLER
SUPPLY
TO EXTERIOR
DRAIN
BATTERY
CHARGING
BATTERY
STORAGE
TO BATTERY
STORAGE
SPRINKLERS
TO BATTERY
CHARGING
SPRINKLERS
N
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
A
B C
D
KEYPLAN
EFX101
FIRE SUPPRESSION OVERALL FIRST FLOOR
PLAN
02/27/17
A. DAHL C. CAHILL
A. HANKINS
NOTES:
1. REFER TO FX001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
2. PROVIDE SPRINKLER COVERAGE BELOW STAIRS
PER NFPA 13.
KEYED NOTES:
EXISTING HEF GENERATORS HAVE BEEN LOCATED
AND SHOWN AS REFERENCE. RELOCATE
GENERATORS AS NECESSARY TO CONFORM TO
DESIGN CRITERIA AND MINIMUM ELEVATION
CLEARANCES. CONTRACTOR RESPONSIBLE FOR
FINAL PLACEMENT AND COORDINATION WITH ALL
OTHER DESIGN CRITERIA AND DISCIPLINES.
REMOVE EXISTING SPRINKLER SYSTEMS. AFTER RE-
BUILD, EXTEND SUPPORT AREA WET-PIPE SYSTEM.
ADD OR RELOCATE SPRINKLERS AND PIPING FOR THE
NEW WALLS AND CEILINGS.
ELECTRIC PUMPS TO BE REPLACED.
REMOVE DRY-PIPE SYSTEM AND ASSOCIATED PIPE,
HANGERS, ELECTRICAL AND CONDUIT.
REVISE PIPING AND SYSTEMS TO MEET DESIGN
CRITERIA.
HANGAR BAY PRE-ACTION AND HEF SYSTEM
BOUNDARY
SEE A1 PLAN VIEW ON THIS SHEET FOR DESIGN
CRITERIA.
PROVIDE SIDEWALL PIT SPRINKLER PER NFPA 13.
PROVIDE DEDICATED SHUTOFF VALVE AND FLOW
SWITCH FOR BATTERY ROOM SPRINKLERS.
EXISTING DRAFT CURTAINS.
SCALE: 3/32" = 1'-0"A1
FIRE SUPPRESSION OVERALL FIRST FLOOR PLAN
SCALE: 3/16" = 1'-0"C5
FIRE SUPPRESSION ENLARGED PLAN -
HEF 110
SCALE: 3/16" = 1'-0"E3
FIRE SUPPRESSION ELEVATOR DETAIL
SCALE IN FEET
0 8' 16' 24'
SCALE: 3/16" = 1'-0"B5
FIRE SUPPRESSION ENLARGED PLAN -
BATTERY ROOMS
JPC
F P
C F
P C
A 11/4/2016 B.1 SUBMITTAL AH
B 1/4/17 B.2 SUBMITTAL AH
C 2/27/17 B.3 SUBMITTAL AH
D 4/14/17 B.3 FINAL SUBMITTAL AH
E 7/7/17 AMENDMENT 1 AH
SOV
EMERGENCY
MANUAL
RELEASE
MAIN
DRAIN
DRAIN TO
EXTERIOR
DRAIN TO
EXTERIOR
DRIP CUP
PRESSURE
REGULATING
TRIM
FROM
HEADER
TO FOAM
SYSTEM
RELEASE AND REMOTE
RESETTING TRIP
SPEED
CONTROL TRIM
18" MINIMUM
AUXILIARY DRAIN VALVESPLASH BLOCK
MAIN DRAIN (S)
FIRE PUMP/PRV
TEST HEADER
(6 VALVES)
(S)
P R
E A
C T
IO
N
S Y
S T
E M
T O
H A
N G
A R
B A
Y
(S)
H E
F F
O A
M S
Y S
T E
M T
O H
A N
G A
R
W E
T -P
IP
E
S Y
S T
E M
T O
S U
P P
O R
T A
R E
A S
(S)
(S)
EXTERIOR WALL
FOAM TANK
STRAIGHT PIPE PER
MANUFACTURER
D1
FX601
(S)
(S)
D R
Y -P
IP
E
S Y
S T
E M
T O
A T
T
IC
(S)
(S)
(S)
J
F
F D2
FX601
FLANGED
CONNECTION
FIRE WATER SUPPLY
SERVICING BUILDING B130
FROM FIRE WATER SUPPLY
TO B130 FOAM ROOMS
NEW PUMPS AND ASSOCIATED
PIPING. REMOVE EXISTING
COMPONENTS AS NECESSARY.
NEW DELUGE, FOAM TANK, AND
ASSOCIATED PIPING. REMOVE EXISTING
COMPONENTS AS NECESSARY.
C1
FX601
(S)
25 GALLON SURGE
ARRESTER
(S) (S)
10" MANIFOLD10" MAIN E
FP1
FP2
FPC
(S) (S) (S)
(S)(S)
(NC)
(NC)
TO PUMP TEST
HEADER
FROM FIRE
WATER SUPPLY TO FIRE
SPRINKLER
RISERS
FPC
JP
JPC
FPC-2
FPC-1
JPC-1
(S)
100 GALLON SURGE
ARRESTER (TYP OF 2)
DRAIN VALVE
(TYP OF 2)
(S)
LIQUID FILLED
GAUGE WITH
SHUT-OFF (TYP.)
FROM FLOW
CONTROL VALVE
3/4" COPPER LINE
FROM FIRE
WATER SUPPLY
WITH BALL VALVE
PROVIDE
INSTRUCTIONAL
SIGNAGE
BALL VALVE WITH CAP
AND TEST CONNECTION
PRESSURE / VACUUM
VENT
REVERSE FLOAT LEVEL
GAUGE
SUCTION LINE
CURRENT
CONCENTRATE LEVEL
SECTION OF DOUBLE
WALL POLYETHYLENE
CONCENTRATE TANK
MINIMUM REQUIRED
STRAIGHT PIPE LENGTH
PER MANUFACTURER
TO FOAM SYSTEM
REDUCER (WHEN REQUIRED)
INDUCTOR
CHECK VALVE
T-FITTING MOUNTED
DIRECTLY ABOVE BALL VALVE
SUPERVISED BALL VALVE
EMPTY
50 GALLON INCREMENTS PERMANENTLY MARKED
ON TANK OR GAUGE
INDICATE MINIMUM REQUIRED CONCENTRATE LEVEL
FULL
INACCESSIBLE CONCENTRATE
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
EFX601
FIRE SUPPRESSION ONE LINE DIAGRAM
AND DETAILS
02/27/17
A. DAHL C. CAHILL
A. HANKINS
N.T.S.SCALE:D1
DELUGE VALVE RISER DETAIL
FOAM SYSTEM
N.T.S.SCALE:A1
HIGH EXPANSION FOAM RISER DIAGRAM
N.T.S.SCALE:D2
FIRE PUMP DETAIL
NOTES:
1. REFER TO FX001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
2. REFER TO S-403 FOR FOAM GENERATOR SUPPORT
DETAIL.
N.T.S.SCALE:C1
FOAM INDUCTOR DETAIL
A 11/4/2016 B.1 SUBMITTAL AH
B 1/4/17 B.2 SUBMITTAL AH
C 2/27/17 B.3 SUBMITTAL AH
D 4/14/17 B.3 FINAL SUBMITTAL AH
E 7/7/17 AMENDMENT 1 AH
GENERAL NOTES:
AIR DISTRIBUTION DEVICE IDENTIFICATION
AIR FLOW
SA-A
(2)175-8"
SPEC. TYPE
PIPE LINE ACCESSORIES
WITH EQUIPMENT
COMPONENTS TO BE FURNISHED
NECK SIZE
HVAC LEGEND
DETAIL/SECTION TITLE
NUMBER = DETAIL DESIGNATOR
LETTER = SECTION DESIGNATOR
DETAIL
SECTION CUT SYMBOL
SECTION
DESIGNATOR
INDICATES PERSPECTIVE
AND LIMITS OF SECTION
DETAIL/ENLARGED CALLOUT SYMBOL
INDICATES
LIMITS OF
DETAIL/SECTION
DETAIL/SECTION
DESIGNATOR
DRAWING WHERE
DETAIL/SECTION IS TAKEN
DRAWING WHERE
SECTION IS DRAWN
DRAWING WHERE
DETAIL/SECTION IS
DRAWN
SYSTEM TYPE
QUANTITY
CONSTRUCTION
INTERFACE
EXISTING
NEW
DEMOLITION
MECHANICAL ABBREVIATIONS
GATE VALVE
OS&Y
OUTSIDE SCREW & YOKE
BUTTERFLY VALVE
CHECK VALVE
3-WAY VALVE
BALL VALVE
PDV
PUMP DISCHARGE VALVE
BALANCING VALVE
RELIEF, SAFETY OR THERMAL RELIEF VALVE
CONTROL VALVE
M
MOTORIZED CONTROL VALVE
SUCTION DIFFUSER
AV
AUTOMATIC AIR VENT ASSEMBLY
MV MANUAL AIR VENT - SEE SPECIFICATIONS
FOR APPROPRIATE VALVE TYPE.
FLEX CONNECTION
THERMOMETER
BP BACKFLOW PREVENTION ASSEMBLY
SELF CONTAINED PRESSURE
REDUCING (REGULATING) VALVE
PRESSURE GAUGE
Y-TYPE STRAINER
REMOVABLE CAP
REDUCER (CONCENTRIC)
REDUCER (ECCENTRIC)
UNION
BLIND FLANGE
TEST CONNECTION
M METER
PUMP
A
M-001
A
M-001
A
M-003
HOSE GATE VALVE DRAIN
GLOBE VALVE
ANGLE VALVE
PLUG VALVE
DBB
DOUBLE BLOCK &
BLEED PLUG VALVE
IF
INSULATING FLANGE
REMOVABLE PLUG
PIPE WITH HEAT TRACE
S STRAINER
M
CONTROL DAMPER, MOTOR
OPERATED
MANUAL BALANCE DAMPER
BD
BACKDRAFT DAMPER
AD
AD
ACCESS DOOR (AD)
ACCESS PANEL (AP)
S
AD
S
DAMPERS:
SMOKE (SD) -
FIRE (F) -
AD
SECURITY BARS
FLEXIBLE DUCT CONNECTION
RECTANGLUAR ELBOW WITH
TURNING VANES
RECTANGULAR TEE WITH
TURNING VANES
RECTANGULAR RADIUS ELBOW
R RISE IN RESPECT TO AIR-FLOW
D DROP IN RESPECT TO AIR-FLOW
SQUARE OR RECTANGULAR TO
ROUND TRANSITION
SUPPLY AIR OR OUTSIDE AIR
DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST AIR DUCT SECTION
ROUND FLEXIBLE DUCT
(5'-0" MAX LENGTH)
SQUARE OR RECTANGULAR
SUPPLY DIFFUSER
RETURN AIR DIFFUSER
EXHAUST AIR DIFFUSER
T THERMOSTAT
CO2 CARBON DIOXIDE MONITOR
H HUMIDISTAT
LINEAR SLOT DIFFUSER
VAV- VARIABLE AIR VOLUME
TERMINAL BOX
(3'-0") FINNED TUBE RADIATION.
LENGTH OF ELEMENT SHOWN IN
PARENTHESIS
ESS EMERGENCY SHUT-OFF SWITCH
M MOTOR
CF CEILING FAN CONTROL PANEL
DEMOLITION
EXISTING
NEW
EXISTING
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
EM-001
MECHANICAL GENERAL NOTES, SYMBOLS,
AND ABBREVIATIONS
09/22/16
T. KARRE R. JORDAN
C. McAFEE
1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS APPLICABLE TO PROJECT. SEE PLANS FOR
SPECIFIC SYMBOLS AND ABBREVIATIONS.
2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY
CODE.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON
OTHER CONTRACT DOCUMENT DRAWINGS.
5. MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, ETC., THROUGHOUT ACCESS ROUTES AND IN
MECHANICAL ROOMS.
6. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS, AND VALVING.
7. VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT.
8. ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, PIPE, OR PIPE INSULATION UNLESS NOTED OTHERWISE.
9. DUCT DIMENSIONS INDICATED REFER TO SHEET METAL DIMENSIONS. SHEET METAL SIZE SHALL BE AIR OPENING DIMENSION PLUS THE THICKNESS OF ACOUSTICAL LINER WHERE LINER IS INSTALLED. WHERE LINER IS NOT INSTALLED, AIR OPENING SIZE
AND SHEET METAL SIZE SHALL BE THE SAME.
10. DUCT STATIC PRESSURE CLASSIFICATION: UNLESS OTHERWISE INDICATED, CONSTRUCT DUCTS ON THE DISCHARGE SIDE OF FANS AND VAV BOXES TO HAVE 1.0 IN. W.C. POSITIVE PRESSURE AND DUCTS ON THE INLET SIDE OF EQUIPMENT TO HAVE 1.0 IN.
W.C. NEGATIVE PRESSURE CLASSIFICATIONS. DUCTS ON OUTLET SIDE OF AHU'S SHALL HAVE 3.0 INCH POSITIVE PRESSURE
CLASS DUCT.
11. LOCATE TRANSFER AIR DUCTS AND OPENINGS 24" ABOVE HIGHEST CEILING ELEVATION UNLESS OTHERWISE NOTED.
12. COORDINATE ALL WALL AND ROOF PENETRATIONS WITH STRUCTURAL AND ARCHITECTURAL PLANS.
13. INSTALL TEMPERATURE CONTROLS AT 48" ABOVE FINISHED FLOOR AND COORDINATE WITH OTHER DEVICES LOCATED ON
WALLS. COORDINATE WITH ARCHITECTURAL WALL FINISHES.
14. OCCUPANCY SENSORS SHALL BE PROVIDED BY DIVISION 26. WIRE OCCUPANCY SENSOR BACK TO CORRESPONDING VAV BOX AS SCHEDULED FOR VENTILATION CONTROL. CO2 SENSORS SHALL BE PROVIDED BY DIVISION 23. WIRE CO2 SENSOR BACK TO
CORRESPONDING VAV BOX AS SCHEDULED FOR VENTILATION.
15. PROVIDE STRUCTURAL EQUIPMENT PADS IN ACCORDANCE WITH DETAIL IN STRUCTURAL DRAWINGS.
16. ALL EXISTING DUCTWORK SHOWN ON DRAWINGS IS SCHEMATIC AND ARE BASED ON EXISTING RECORD DRAWINGS PROVIDED BY THE OWNER AND DO NOT REFLECT EXACT EXISTING CONDITIONS. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS ON JOB SITE. CONTRACTOR SHALL REROUTE NEW WORK TO ACCOMMODATE EXACT LOCATIONS OF EXISTING UTILITIES, STUBOUTS, AND/OR CONNECTIONS.
17. CONTRACTOR SHALL AIR BALANCE ALL GRILLES TO CFM'S SHOWN ON PLANS.
18. PROVIDE BRACING FOR OVERHEAD EQUIPMENT WEIGHING OVER 31 LBS PER UFC 4-010-01. SEE SPECIFICATION 2305 48.00.40.
IA INSTRUMENT AIR
INVT EL INVERT ELEVATION
L LOUVER
LR LONG RADIUS
MA MIXED AIR
MJ MECHANICAL JOINT
MW MAKE-UP WATER (AFTER BACKFLOW
PREVENTER)
NC NORMALLY CLOSED (FAIL POSITION)
NG NATURAL GAS
NO NORMALLY OPEN (FAIL POSITION)
OA OUTSIDE AIR
OB OPPOSED BLADE
OD OVERFLOW DRAIN
PB PARALLEL BLADE
PCR PUMP CONDENSATE RETURN
PCW PROCESS COLD WATER
PFX PLATE AND FRAME HEAT EXCHANGER
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
R RELIEF LINE
RA RETURN AIR
RED REDUCER-REDUCING
RG REFRIGERANT HOT GAS DISCHARGE
RL EFRIGERANT LIQUID
RMJ RESTRAINED MECHANICAL JOINT
RS REFRIGERANT SUCTION
RWR RADIATION WATER RETURN
RWS RADIATION WATER SUPPLY
SA SUPPLY AIR
SCH SCHEDULE
SCR SPRING RETURN CLOSED
SF SUPPLY FAN
SHR SHORT RADIUS
SO SLIP ON
SP STATIC PRESSURE SENSOR
SR SUPPLY REGISTER
ST STEAM TRAP
STM STEAM
SW SOCKET WELD
TA TRANSFER AIR
TOA TREATED OUTSIDE AIR
TOC TOP OF CONCRETE
TOD TOP OF DUCT
TOS TOP OF STEEL
UH UNIT HEATER
V VENT
VAV VARIABLE AIR VOLUME
VRF VARIABLE REFRIGERANT FLOW
WE WELD END
WN WELD NECK
12"Ø ROUND DUCT DIMENSION
24x1 RECTANGULAR DUCT DIMENSION (INCHES)
24x12 RECTANGULAR DUCT DIMENSION (INCHES)
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARF ABOVE RAISED FLOOR
ARV AIR RELEASE VALVE
BBO BOILER BLOW-OFF
BLWDN BLOWDOWN
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BP BOOSTER PUMP
BPP BOILER PRIMARY PUMP
BW BUTT WELD
BWW ACKWASH WATER
CF CEILING FAN
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CL CENTER LINE OF PIPE ELEVATION
CONC CONCENTRIC
COND COOLING COIL CONDENSATE DRAIN
CR CONDENSATE RETURN
CT CHEMICAL TREATMENT
CTB COOLING TOWER BLOWDOWN
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
D DRAIN
DE DIESEL EXHAUST
DH DEHUMIDIFIER
DIW DEIONIZED WATER
DN DOWN
DRG DIFFUSER, REGISTER, GRILLE
EA EXHAUST AIR
EF EXHAUST FAN
EG EXHAUST GRILLE
EL ELEVATION
ELL ELBOW
ER EXHAUST REGISTER
ET EXPANSION TANK
EXIST EXISTING
F FAN
FCU FAN COIL UNIT
FD FEEDWATER
FF FLAT FACED
FO FLAT OVAL
FOB FLAT ON BOTTOM
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOT FLAT ON TOP
HWB HOT WATER BOILER
HWP HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
A 11/4/16 B.1 SUBMITTAL
B 1/4/17 B.2 SUBMITTAL
C 2/28/17 B.3 SUBMITTAL
D 4/14/17 B.3 FINAL SUBMITTAL
E 7/7/17 AMENDMENT 1
1312111098
U
T
S
2 3 4 5 6
A1
M-501
B1
M-301
SF-103
SF-102
SF-101
GH-101
(5)1000-16x16
OA-P
24ø OA
32ø OA
22' - 11" BOD EL
67x26 SA DN
36x34 RA DN
RTU-101
30x60 EA DN
96x96 OUTSIDE
AIR LOUVER
18x16 OA
16x12 OA
26' - 7" BOD EL
18x16 OA
16x12 OA
M
24x24 OPENING
WITH MOTORIZED
DAMPER
18x16 OA
26' - 5" BOD EL
N
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
A
B C
D
KEYPLAN
DM-112
SECOND FLOOR / ROOF - HVAC PLAN - AREA
B
12/15/16
T. KARRE R. JORDAN
C. McAFEE
KEYED NOTES:
NOT USED.
4" FLUE UP THRU ROOF.
96"x96" LOUVER, 20'-0" AFF.
SCALE: 1/8" = 1'-0"A1
SECOND FLOOR - HVAC PLAN - AREA B
0 4' 8' 16'
N
GENERAL NOTES:
1.
2.
SEE SHEET M-001 FOR MECHANICAL GENERAL
NOTES, SYMBOLS AND ABBREVIATIONS.
SEE DRAWING M-602 FOR RETURN AND
TRANSFER AIR SCHEDULE, SCHEDULE
INDICATED AIRFLOW, GRILLE TYPE AND DUCT
SIZE.
M A
T C
H L
IN
E S
E E
S H
E E
T M
-1
MATCHLINE SEE SHEET M-111
A 1/4/17 B.2 SUBMITTAL
B 2/28/17 B.3 SUBMITTAL
C 4/14/17 B.3 FINAL SUBMITTAL
D 7/7/17 AMENDMENT 1
MECHANICAL
ELECTRICAL
AS-101
HWP-101
UH-101 UH-102
ET-101
DDC
PANEL
DDC
PANEL
HWP-102
3" HWS
3" HWR
2" HWS
HWB-101
HWB-102
4" HWS
HWP-103
HWP-104
2 1/2" HWR
2 1/2" HWS
CHEMICAL SHOT
FEEDER
EEW-1
HWB-103
4" HWR
2" HWR
AR-102
AR-101RAD-101
AC-102
AC-101
DWH-101
HWP-105
BOILER
CONTROL
PANEL
ABOVE
BELOW
4" HWS
4" HWR
4" HWR
2" HWR
4" HWS
2" HWS
4" HWS
MECHANICAL
ELECTRICAL
DWH-101
AC-101
UH-101
UH-102
DDC
PANEL
DDC
PANEL
HWB-101
HWB-102
72"x16" LOUVER 72"x16" LOUVER
500-12x10
OA-P
500-12x10
OA-P
16x12 OA
36x36 OA
36x36 EA UP
(2)1000-18x14
OA-P
x O
A x O
A x O
A
MM
EEW-1
HWB-103
30x60 EA UP
TO GH-101
18x16 OA
12' - 4" BOD EL
4ø COMBUSTION AIR
12' - 10" BOD EL
4ø COMBUSTION AIR
11' - 10" BOD EL
4ø COMBUSTION AIR
11' - 10" BOD EL
4ø COMBUSTION AIR
11' - 10" BOD EL
E
E
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
EM-402
MECHANICAL ENLARGED PLANS
09/30/16
T. KARRE R. JORDAN
C. McAFEE
SCALE: 1/2" = 1'-0"A1
MECHANICAL PIPING PLAN - ENLARGED MECH/ELEC ROOM
GENERAL NOTES:
1.
2.
SEE SHEET M-001 FOR MECHANICAL GENERAL
NOTES, SYMBOLS AND ABBREVIATIONS.
PROVIDE 4 INCH HOUSEKEEPING PADS LOCATED
UNDER BOILERS, EXPANSION TANK, AND
CHEMICAL TREATMENT TANK.
KEYED NOTES:
ROUTE 4" COMBUSTION AIR INTAKE FROM BOILERS AND WATER
HEATERS THRU SIDE WALL AND TERMINATE WITH TURN DOWN
PIPE THRU WALL.
4" FLUE UP THRU ROOF.
1" MAKE-UP WATER. SEE DRAWING P402 FOR CONTINUATION.
TRANSITION 36x36 DUCT TO AIR COMPRESSOR CONNECTION
SIZE.
ROUTE 36"x36" EA UP AND TRANSITION TO 30"x60" GRAVITY HOOD
CONNECTION. PROVIDE MOTORIZED DAMPER PRIOR TO HOOD
CONNECTION.
BOILER EMERGENCY KILL SWITCH.
INSTALL ONE NEW AND TWO EXISTING BOILERS ONTO NEW
BUDERUS CASCADE FRAME WITH LOW LOSS HEADER AND
MANIFOLD KIT.
INSTALL NEW BUDERUS BOILER CONTROL PACKAGE AND WIRE
ALL THREE BOILERS . CONNECT TO DDC SYSTEM.
CONNECT HWS / R PIPING TO BOILER LOW LOSS HEADER
CONNECTIONS.
SPACE RESERVED FOR FIRE ALARM. DO NOT ROUTE PIPING IN
AREA INDICATED.
0 1' 2' 4'
N
T
T
TO SF-101
TO SF-102
SCALE: 1/2" = 1'-0"A3
MECHANICAL HVAC PLAN - ENLARGED MECH/ELEC ROOM
0 1' 2' 4'
N
E
A 11/4/16 B.1 SUBMITTAL
B 1/4/17 B.2 SUBMITTAL
C 2/28/17 B.3 SUBMITTAL
D 4/14/17 B.3 FINAL SUBMITTAL
AIR FLOW
DUCT
AIR FLOW
DUCT
GRIDS AND DAMPERS MUST NOT DAMAGE LINERS
NOTE:
ADJUSTABLE DAMPER
SUPPLY OUTLET
ADJUSTABLE DAMPER
SUPPLY OUTLET
QUALIZING GRID (WHEN
SPECIFIED ALTERNATIVE
TO EXTRACTOR)
REGISTER AND DIFFUSER CONTAIN
VOLUME CONTROL AT GRILLE.
GRILLE HAS NO VOLUME CONTROL.
GRILLE FLANGES MUST
COVER DUCT FLANGES.
STRAP HANGERS TRAPEZE HANGERS
60" MAX.
REINFORCEMENT MAY BE USED FOR
ATTACHMENT IF IT QUALIFIES FOR BOTH
DUTIES DO NOT EXCEEED ALLOWABLE
LOAD LIMITS
ONE HALF-ROUND MAY BE USED
IF DUCT SHAPE IS MAINTAINED.
24" DIA. MAX.50" DIA. MAX.
10" DIA. MAX.
LOAD RATED
FASTENERS
HANGER
STRAPS
HANGER RODS,
WIRES OR STRAPS
BAND OF SAME SIZE
AS HANGAR STRAP
NUTS
HANGERS
MUST NOT
DEFORM DUCT
SHAPE
UNLESS FOOT OF STRAP
IS PLACED UNDER A
BOTTOM REINFORCEMENT
SCREWS
SCREWS MAY
BE OMITTED
IF HANGER LOOPS
SECURE
WIRE
STRAP
ALTERNATE LOCATION
(VERIFY UPPER
TRAPEZE LOAD CAPACITY)
ANGLES
BAND
STRAP OR
ANGLE
ROD
SIZE BOLT (S)
FOR LOAD
1" MIN.
ROD
EXHAUST FAN
VIBRATION ISOLATORFLEX
CONNECTION
HANGER ROD
MOUNTING BRACKET
OR CHANNEL
SEISMIC BRACING
E
E DUCT
1-1/2" POCKET SLIP
1-1/2" MIN. TO 3"
MAX. INSTALLED.
6" NOMINAL WITH
MATERIAL TAUT.
WASHER
1" FLANGE AND HEM
FLEXIBLE MATERIAL
AS SPECIFIED
1" x 1/8"
BAND IRON
BOLT ON 4" CENTERS
ALTERNATE
POSITION OF BOLT
FLANGED
CONNECTION
OF FAN SIDE
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
SHEET METAL AS
SPECIFIED FOR DUCTWORK
12" x 12" 2 1 26 26 24
2226242216" x 16"
2226222324" x 24"
DOOR
19MM
SASH LOCK
DUCT
50MM
SPACER
HINGE
GASKET
FRAME WITH CLINCH LOCK
MAX DOOR
SIZE
SHEET METAL GAGE
THICKNESS
DOOR BACK FRAME
NO. OF
HINGES
NO. OF
HINGES
OPENING WITH BIRD SCREEN
SLOPE
EXTERIOR WALL
INSULATED
PLENUM BOX
(SEE PLANS FOR SIZE)
MOTORIZED DAMPER
M
LOUVER
NOTES:
1. CONSTRUCT PLENUM BOX WITH
1% SLOPE TOWARDS LOUVER
8"
12"
M
MANUAL AIR VENT
BALL VALVE (TYP.)
UNION (TYP.)
MANUAL VENT
BALANCING VALVE
DRAIN VALVE (TYP)
ISOLATION VALVE
2-WAY CONTROL VALVE
(MAX. P = 5 PSI)
VAV
HWR HWS
LOUVER
EXTERIOR
WALL
SLOPE DUCTWORK CONNECTED
TO LOUVER TOWARDS THE
BUILDING EXTERIOR
MOTORIZED DAMPER
EXHAUST OR OUTSIDE AIR
DUCT. SEE PLANS FOR SIZE.M
EA
BIRDSCREEN
UPBLAST EXHAUST FAN
ROOF CURB, COORDINATE
W/EQUIPMENT FURNISHED
SEE ARCHITECTURAL DWGS
FOR FLASHING DETAILS
EA
MOTORIZED DAMPER
EXHAUST AIR DUCT. SEE PLANS
FOR SIZE. COORDINATE
W/EQUIPMENT FURNISHED.
M
EA
ROOF EXHAUST FAN
BIRDSCREEN
M
92654
S c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
EM-502
MECHANICAL DETAILS
09/30/16
T. KARRE R. JORDAN
C. McAFEE
NTSSCALE:D1
DIFFUSER, GRILLE, & REGISTER CONNECTIONS
NTSSCALE:D3
LOWER DUCT HANGAR ATTACHMENTS
NTSSCALE:C1
CABINET OR INLINE EXHAUST FAN
NTSSCALE:C3
RECTANGULAR FLEXIBLE CONNECTION
NTSSCALE:A4
ACCESS DOOR IN DUCTWORK
NTSSCALE:C5
LOUVER DETAIL - HANGAR, ROOMS 164, 166 & 171
SCALE: 12" = 1'-0"A5
VARIABLE AIR VOLUME BOX PIPING
NTSSCALE:E5
DUCTWORK CONNECTED TO EXTERIOR LOUVER
NTSSCALE:A1
ROOF EXHAUST FANS
A 11/4/16 B.1 SUBMITTAL
B 1/4/17 B.2 SUBMITTAL
C 2/28/17 B.3 SUBMITTAL
D 4/14/17 B.3 FINAL SUBMITTAL
92654 c a le
F o r M ic ro fi lm in g
In c h e s
M il li m e te rs date detailed checkeddesigned project contract rev.drawing fileC O
P Y
R
IG
B
U R
N S
A N
D M c D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C
DATEREV.
REVISIONS
DESCRIPTION INIT
VERMONT AIR NATIONAL GUARD
BURLINGTON INTERNATIONAL AIRPORT
SO BURLINGTON, VERMONT
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - CURZ152802
F-35 MX HANGAR POWER
AND INST. EQUIP ALL SPOTS
BUILDING 150
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
EM-601
MECHANICAL SCHEDULES
10/12/16
T. KARRE R. JORDAN
C. McAFEE
PRE-CONDITIONED AIR UNIT SCHEDULE (CAS)
EQUIPMENT
TAG LOCATION
ALTITUDE
(FT)
AIRFLOW
(LB/MIN)
WATER VAPOR
MIN-MAX
(GRAINS/LB)
EXTERNAL
STATIC
PRESSURE
(PSIG)
DELIVERED
STATIC
PRESSURE
(PSIG)
TOTAL
STATIC
PRESSURE
(PSIG)
AMBIENT CONDITIONS SUPPLY AIR CONDITIONS SUPPLY FAN MOTOR
SUMMER DB
(DEG F)
SUMMER WB
(DEG F)
WINTER DB
(DEG F)
MIN SUPPLY
TEMP
(DEG F)
MAX SUPPLY
TEMP
(DEG F) VOLTS PHASE
CAS-101 MECH YARD 350 46.5 0-55 0.5 5.25 NOTE 1 85 70 -10 35 55 460 3
CAS-102 MECH YARD 350 46.5 0-55 0.5 5.25 NOTE 1 85 70 -10 35 55 460 3
CAS-103 MECH YARD 350 46.5 0-55 0.5 5.25 NOTE 1 85 70 -10 35 55 460 3
CAS-104 MECH YARD 350 46.5 0-55 0.5 5.25 NOTE 1 85 70 -10 35 55 460 3
CAS-105 MECH YARD 350 46.5 0-55 0.5 5.25 NOTE 1 85 70 -10 35 55 460 3
NOTES:
1. PRESSURE DROPS ASSOCIATED WITH FILTERS, COILS, ETC. SHALL BE INCLUDED IN THE TOTAL INTERNAL STATIC PRESSURE BY THE EQUIPMENT MANUFACTURER. DIRTY FILTER PRESSURE
SHALL BE USED FOR FILTERS.
2. WATER VAPOR SHALL CONTAIN NO WATER DROPLETS.
3. AIRFLOW, WATER VAPOR, AND DELIVERED STATIC PRESSURE INDICATED IN SCHEDULE REFER TO ATTRIBUTES AT THE AIRCRAFT CONNECTION.
4. ABI#1: PRECONDITIONED AIR UNITS (CAS) EQUIPMENT, CAS CONTROLS, INSTALLATION, SYSTEM TESTING, AND WARRANTY SHALL BE PART OF ABI#1. ALL ASSOCIATED FACILITY POWER, PIPING, REELS, HOSE AND OTHER ACCESSORIES SHALL BE PART OF THE BASE BID.
ROOFTOP UNIT SCHEDULE (RTU) 1/3
EQUIPMENT
TAG SERVICE LOCATION
ALTITUDE
(FT)
MAX.
AIRFLOW
(CFM)
MIN.
AIRFLOW
(CFM)
OUTSIDE
AIRFLOW
(CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W.C.)
TOTAL
STATIC
PRESSURE
(IN. W.C.)
MINIMUM
CIRCUIT
AMPS
SUPPLY FAN SUPPLY FAN MOTOR RETURN FAN RETURN FAN MOTOR
MAX
BHP FAN RPM TYPE
VOLUME
CONTROL
MIN. MOTOR
HP
MOTOR
RPM
MOTOR
TYPE VOLTS PHASE MAX BHP
EXTERNAL
STATIC
PRESSURE
(IN W.C.)
AIRFLOW
(CFM) FAN RPM TYPE
VOLUME
CONTROL
MIN.
MOTOR HP
MOTOR
RPM
MOTOR
TYPE VOLTS PHASE
RTU-101 NORTH ROOF 350 9500 4070 1970 1.9 NOTE 1 94.88 17.62 1281 FC VFD 20 1300 BELT 460 3 5.17 0.9 8095 1441 FC VFD 7.5 1400 BELT 460 3
RTU-102 SOUTH ROOF 350 6450 2675 1030 1.6 NOTE 1 75.05 11 1349 FC VFD 15 1300 BELT 460 3 2.57 0.75 5460 1117 FC VFD 5 1100 BELT 460 3
ROOFTOP UNIT SCHEDULE (RTU) 2/3
EQUIPMENT
TAG
COOLING COIL
REFRIGERANT
TYPE
COMPRESSOR CONDENSER FANS
SUMMER
AMBIENT
TEMPERATURE
(DEG F)
COIL AIR
QUANTITY
(CFM)
EAT DB
(DEG. F.)
EAT WB
(DEG. F.)
LAT DB
(DEG. F)
LAT WB
(DEG. F.)
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
MAX. FACE
VELOCITY
(FPM)
MAX. AIR
PRESSURE
DROP
(IN. W.C.) TYPE
CAPACITY
MODULATION NUMBER
EFFICIENCY
(EER) NUMBER HP
RTU-101 9500 79.5 66.1 55 54 350.9 255 500 0.5 R-410A VARIABLE SPEED SCROLL 25% THRU 100% 2 10.9 3 1 90
RTU-102 6450 79.1 65.8 55 53.3 244.3 170.6 500 0.5 R-410A VARIABLE SPEED SCROLL 25% THRU 100% 2 10.3 3 1 90
ROOFTOP UNIT SCHEDULE (RTU) 3/3
EQUIPMENT
TAG
HEAT EXCHANGER PRE-FILTER FINAL FILTER
DIRTY FILTER
PRESSURE DROP
(IN. W.C.)
APPROX. UNIT
WEIGHT
(LBS) NOTESHEATING COIL TYPE FUEL
HEATING COIL
AIRFLOW
(CFM)
EAT
(DEG. F.)
LAT (DEG.
F.)
INPUT
(MBH)
MIN.
EFFICIENCY
COIL FACE
VELOCITY
(FPM)
AIR
PRESSURE
DROP
(IN. W.G.) TYPE
EFFICIENCY
(MERV)
PRESSURE
DROP
(IN. W.C.) TYPE
EFFICIENCY
(MERV)
PRESSURE
DROP
(IN. W.C.)
RTU-101 INDIRECT GAS FIRED NATURAL GAS 9025 51 65 164.7 83 500 0.2 CARTRIDGE 8 0.3 CARTRIDGE 13 0.35 1.5 6500 1, 2
RTU-102 INDIRECT GAS FIRED NATURAL GAS 4415 49.8 65 87.4 83 500 0.2 CARTRIDGE 8 0.3 CARTRIDGE 13 0.35 1.5 6500 1, 2
NOTES
1. PRESSURE DROPS ASSOCIATED WITH FILTERS, COILS, ETC. SHALL BE INCLUDED IN THE TOTAL INTERNAL STATIC PRESSURE BY THE EQUIPMENT MANUFACTURER. DIRTY FILTER PRESSURE SHALL BE USED FOR FILTERS.
2. MANUFACTURER SHALL PROVIDE WITH SINGLE POINT ELECTRICAL CONNECTION.
DIFFUSER, REGISTER, & GRILLE SCHEDULE (DRG)
TAG DESCRIPTION SYSTEM TYPE MOUNTING
THROW
PATTERN DAMPER
BLADE
SPACING NOTES
A 12" X 12" SQUARE CEILING LOUVERED SUPPLY AIR DIFFUSER SUPPLY SURFACE 4-WAY YES N/A
B 24" X 24" SQUARE CEILING LOUVERED SUPPLY AIR DIFFUSER SUPPLY SURFACE 4-WAY YES N/A
C 24" X 24" SQUARE CEILING LOUVERED SUPPLY AIR DIFFUSER SUPPLY LAY-IN 4-WAY NO N/A
D 24" X 24" RETURN AIR EGGCRATE 1/2" CORE GRILLE RETURN LAY-IN N/A NO 1/2"
E 24" X 12" RETURN AIR EGGCRATE 1/2" CORE GRILLE RETURN SURFACE N/A YES 1/2" 1
F 24" X 12" RETURN AIR EGGCRATE 1/2" CORE GRILLE RETURN LAY-IN N/A YES 1/2" 1
G 24" X 12" TRANSFER AIR EGGCRATE 1/2" CORE GRILLE TRANSFER LAY-IN N/A NO 1/2"
H 24" X 12" TRANSFER AIR EGGCRATE 1/2" CORE GRILLE TRANSFER SURFACE N/A NO 1/2"
J 24" X 24" TRANSFER AIR PERFORATED CORE GRILLE TRANSFER LAY-IN N/A NO N/A
K 12" X 12" EXHAUST AIR EGGCRATE 1/2" CORE GRILLE EXHAUST SURFACE N/A YES 1/2"
L 12" X 12" TRANSFER AIR EGGCRATE 1/2" CORE GRILLE TRANSFER SURFACE N/A NO 1/2"
M LOUVERED DUCT MOUNTED SIDEWALL GRILLE RETURN DUCT N/A YES 3/4"
N LOUVERED DUCT MOUNTED SIDEWALL GRILLE EXHAUST DUCT N/A NO 3/4"
P LOUVERED DUCT MOUNTED SIDEWALL GRILLE OUTSIDE AIR DUCT SINGLE - 0 DEG. NO 3/4"
Q LOUVERED DUCT MOUNTED SIDEWALL GRILLE OUTSIDE AIR DUCT SINGLE - 45 DEG. YES 3/4"
R LOUVERED DUCT MOUNTED SIDEWALL GRILLE TRANSFER DUCT SINGLE NO 3/4"
S CIRCULAR FACE LOUVERED SUPPLY DIFFUSER SUPPLY OPEN CEILING 360 DEG NO N/A
NOTES:
1. OMIT DAMPERS WHERE DAMPERS ARE LOCATED IN BRANCH DUCT.
MAKE-UP AIR UNIT SCHEDULE (MAU) 1/2
EQUIPMENT
TAG SERVICE LOCATION
ALTITUDE
(FT)
MAX.
AIRFLOW
(CFM)
OUTSIDE
AIRFLOW
(CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W.C.)
TOTAL
STATIC
PRESSURE
(IN. W.C.)
SUPPLY FAN SUPPLY FAN MOTOR
MAX BHP FAN RPM TYPE
VOLUME
CONTROL
MIN.
MOTOR HP
/ MIN. VFD
MOTOR
RPM
MOTOR
TYPE VOLTS PHASE
MAU-101 HANGAR NORTH ROOF 350 11000 11000 0.5 NOTE 1 7.63 800 FC VFD 10 1725 BELT 460 3
MAU-102 TOOL STORAGE SOUTH ROOF 350 800 800 0.25 NOTE 1 0.36 1540 PLENUM VFD 1 1765 BELT 460 3
MAKE-UP AIR UNIT SCHEDULE (MAU) 2/2
EQUIPMENT
TAG
HEAT EXCHANGER FILTER DIRTY FILTER
PRESSURE
DROP
(IN. W.C.)
APPROX.
UNIT WEIGHT
(LBS) NOTESTYPE FUEL
HEATING COIL
AIRFLOW
(CFM)
EAT
(DEG. F.)
LAT
(DEG. F.)
INPUT
CAPACITY
(MBH)
OUTPUT
CAPACITY
(MBH) TYPE
EFFICIENCY
(MERV)
PRESSURE
DROP
(IN. W.C.)
MAU-101 DIRECT GAS FIRED NATURAL GAS 11000 -10 65 90 89.1 CARTRIDGE 8 0.3 0.75 1900 1,2
MAU-102 DIRECT GAS FIRED NATURAL GAS 800 -10 80 80 78 CARTRIDGE 8 0.3 0.75 750 1,2
NOTES:
1. PRESSURE DROPS ASSOCIATED WITH FILTERS, COILS, ETC. SHALL BE INCLUDED IN THE TOTAL INTERNAL STATIC PRESSURE BY THE EQUIPMENT MANUFACTURER. DIRTY FILTER
PRESSURE SHALL BE USED FOR FILTERS.
2. VFD PROVIDED BY CONTROLS CONTRACTOR.
HOT WATER BOILER SCHEDULE (HWB)
TAG NO. LOCATION TYPE
ALTITUDE
(FT.) FLUID
PRESSURE
RATING
(PSIG)
LVG.
WATER
TEMP
(DEG. F.)
ENT.
WATER
TEMP
(DEG. F.)
MINIMUM
GROSS
OUTPUT
(MBH) FUEL SOURCE
BURNER
INPUT (CFH @
1000 BTU/CF)
MIN.
EFFICIENCY
(%) VOLTS PHASE REMARKS
HWB-101 MECH ROOM CONDENSING 350 WATER 50 140 120 302 NATURAL GAS 330 92 120 1 1, 2, 3
HWB-102 MECH ROOM CONDENSING 350 WATER 50 140 120 302 NATURAL GAS 330 92 120 1 1, 2, 3
HWB-103 MECH ROOM CONDENSING 350 WATER 50 140 120 302 NATURAL GAS 330 92 120 1 2, 3, 4, 5
FAN SCHEDULE
TAG LOCATION FAN TYPE SERVICE AIRFLOW
FAN
SPEED
(RPM)
FAN SPEED
CONTROL
STATIC
PRESSURE
(IN WG)
SOUND
LEVEL
(DBA)
ELECTRICAL
INTERLOCK
WITH
DRIVE
TYPE
WEIGHT
(LBS) NOTES
MIN
MOTOR
HP
OPERATING
BHP
MOTOR
TYPE
STARTER/
DISCONNECT
PROVIDED BY VOLTAGE PHASE
EF-101 141 - MEN'S SHOWER LOCKER INLINE CENTRIFUGAL RESTROOM EXHAUST 1270 1725 CONSTANT 0.5 57 0.25 0.24 ODP PROVIDED BY 26 115 1 RTU-101 DIRECT 46 1
EF-102 150 - EXPLOSIVE STORAGE INLINE CENTRIFUGAL EXHAUST 350 1048 CONSTANT 0.3 53 0.25 0.06 TEFC PROVIDED BY 26 115 1 RTU-102 BELT 83 2
EF-103 ROOF CENTRIFUGAL ROOF RESTROOM EXHAUST 350 941 CONSTANT 0.5 50 0.25 0.06 ODP PROVIDED BY 26 115 1 RTU-102 DIRECT 47 1
EF-104 ROOF CENTRIFUGAL UPBLAST EMERGENCY EXHAUST 2000 1576 CONSTANT 0.3 68 0.75 0.41 ODP PROVIDED BY 26 115 1 DIRECT 66 1
EF-105 HANGAR BAY INLINE MIXED FLOW EXHAUST 11000 657 CONSTANT 0.625 51 2 1.75 OPD PROVIDED BY 26 460 3 MAU-101 BELT 488
EF-106 171 - BATTERY CHARGING CEILING CABINET FAN EXHAUST 75 950 CONSTANT 0.3 40 0.15 0.15 ODP PROVIDED BY 26 115 1 MAU-102 DIRECT 15 1
EF-107 ROOF CENTRIFUGAL UPBLAST EMERGENCY EXHAUST 2000 1576 CONSTANT 0.3 68 0.75 0.41 ODP PROVIDED BY 26 115 1 DIRECT 66 1
EF-201 207 - MOC SHOWER CEILING EXHAUST FAN RESTROOM EXHAUST 75 700 CONSTANT 0.25 0 0 0 ODP PROVIDED BY 26 115 1 DIRECT 0 3
EF-202 206 - MOC TOILET CEILING EXHAUST FAN RESTROOM EXHAUST 150 700 CONSTANT 0.25 0 0 0 ODP PROVIDED BY 26 115 1 DIRECT 0 3
EF-203 201 - TOOL / PARTS STORAGE INLINE CENTRIFUGAL EXHAUST 1500 1489 CONSTANT 0.3 56 0.5 0.28 ODP PROVIDED BY 26 115 1 DIRECT 55 1
SF-101 HANGAR BAY INLINE CENTRIFUGAL MECH ROOM VENTILATION 2000 1500 CONSTANT 0.6 63 0.75 0.45 ODP PROVIDED BY 26 115 1 DIRECT 91 1
SF-102 HANGAR BAY INLINE CENTRIFUGAL ELEC ROOM VENTILATION 1000 1548 CONSTANT 0.55 54 0.25 0.18 ODP PROVIDED BY 26 115 1 DIRECT 57 1
SF-103 HANGAR BAY INLINE CENTRIFUGAL COMPRESSOR SUPPLY 12000 559 CONSTANT 0.6 51 2 1.78 ODP PROVIDED BY 26 460 3 AC-102 BELT 990 4
GRAVITY HOOD SCHEDULE
TAG NO. SERVICE
THROAT SIZE
(IN.)
CURB CAP SIZE
(IN.) CFM
MAX PRESSURE
DROP
(IN. W.C.) DAMPER
UNIT WEIGHT
(LBS) NOTES
GH-101 EXH - MECH ROOM 30 X 60 36 X 66 12000 0.15 MOTORIZED 197 1, 2
NOTES:
1. PROVIDE WITH INSECT SCREEN.
2. UNIT SHALL BE ALUMINUM LOW SILHOUETTE RELIEF HOOD.
NOTES:
1. DIRECT DRIVE ECM MOTOR WITH UNIT MOUNTED SPEED CONTROLLER.
2. EXPLOSION PROOF, SPARK RESISTANT CONSTRUCTION.
3. EXISTING FAN. FOR REFERENCE ONLY.
4. CONTRACTOR SHALL VERIFY SIZING BASED ON AIRFLOW REQUIREMENTS OF AIR COMPRESSOR.
NOTES:
1. CONTRACTOR TO RELOCATE EXISTING BOILER, PUMP PACKAGE, AND ACCESSORIES. MOUNT EXISTING BOILERS TO NEW SUPPORT FRAME. PROVIDE NEW BUDERUS CONTROLS FM458, LOGOMATIC 4323 AND LONWORKS GATEWAY.
2. UNITS SHALL BE MOUNTED ON 4 INCH THICK HOUSEKEEPING PAD.
3. RELOCATE EXISTING CONDENSATE NUETRALIZATION KIT AND CONNECT ALL BOILERS.
4. PROVIDE NEW BUDERUS MODEL GB162-100 CONDENSING BOILER COMPLETE WITH PUMP MODULE. CONNECT NEW BOILER TO RELOCATED BOILER CONTROLS PACKAGE. PROVIDE ALL
SENSORS, INCLUDING BOTH SUPPLY AND RETURN SENSORS REQUIRED FOR CONNECTION.
5. CONTRACTOR SHALL PROVIDE NEW BUDERUS CASCADE FRAME TL3 FOR SUPPORTING THREE BOILERS, SUPPLY AND RETURN HEADER AND LOW LOSS HEADER.
A 11/4/16 B.1 SUBMITTAL
B 1/4/17 B.2 SUBMITTAL
C 2/28/17 B.3 SUBMITTAL
D 4/14/17 B.3 FINAL SUBMITTAL
TO
SPACEH
VAV-DA-T
VAV BOX
CONTROLLER
ZN-T ZN-CO2
VAV-D-C
HWS
VAV BOX
VAV-SA-F
V-##
VAV-HTG-V
HWR
SEQUENCE OF OPERATION SINGLE DUCT VAV BOX
GENERAL:
SINGLE DUCT VAV CONTROLLERS PROVIDE ROOM LEVEL TEMPERATURE CONTROL WITH
CONDITIONED AIR FROM AIR HANDLING UNITS. ROOMS USE A TYPICAL WALL THERMOSTAT TO
CONTROL THE ROOM/SPACE TEMPERATURE SETPOINT.
UNOCCUPIED:
THE VAV BOX DAMPER SHALL MODULATE TO ITS MINIMUM POSITION. THE ROOM TEMPERATURE
SHALL BE ALLOWED TO VARY TO ITS UNOCCUPIED TEMPERATURE SETBACK SETPOINT BEFORE THE
VAV BOX RESPONDS TO RETURN THE SPACE TEMPERATURE TO OCCUPIED SETPOINT. ONCE THE
SETPOINT IS RE-ESTABLISHED, THE VAV BOX SHALL RETURN TO THE UNOCCUPIED MODE.
OCCUPIED:
COOLING: THE VAV BOX DAMPER ACTUATOR SHALL BE FULLY OPENED.
WHEN THE ROOM TEMPERATURE SENSOR SENSES A DROP IN ROOM TEMPERATURE BELOW ROOM
COOLING TEMPERATURE SETPOINT, THE DAMPER SHALL MODULATE TO MAINTAIN THIS SETPOINT UNTIL DAMPER REACHES MINIMUM POSITION. ON A RISE IN ROOM TEMPERATURE ABOVE COOLING
TEMPERATURE SETPOINT, THE VAV DAMPER ACTUATOR SHALL MODULATE TOWARDS OPEN TO
MAINTAIN THE ROOM COOLING TEMPERATURE SETPOINT.
HEATING: WHEN THE ZONE TEMPERATURE IS BELOW THE ZONE HEATING TEMPERATURE SETPOINT, THE HEATING VALVE SHALL MODULATE TO MAINTAIN AIR…