W912HN-21-B-3002_VOL1E_AMD4 Rev 1.pdf
PDF 177 KB Posted
- Solicitation number
- W912HN21B3002
About this file
This document package includes specifications and drawings for a solicitation to provide fire suppression systems at the University Registrar, Force Modernization & Proponency Facility at Fort Gordon, Georgia. The solicitation was posted on 2 December 2020 under number W912HN21B3002 by the Department of the Army Corps of Engineers Engineering District Savannah. Bids are due at 1:00 PM ET on 12 January 2021 with bid opening scheduled for 2:00 PM ET the same day. The package contains four specification files, eleven drawing files, and provides details on requirements for installation of sprinkler piping, hangers, drains, valves, and related fire suppression systems. Offerors are instructed to attend a pre-bid WebEx meeting for additional information.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROD SIZE (A)
ALL-THREAD ROD
B
PIPE
SIZE
A B C
1/2 3/8 3-1/8 2-5/8
3/4 3/8 3-1/8 2-1/2
1 3/8 3-3/8 2-5/8
1-1/4 3/8 3-3/4 2-7/8
1-1/2 3/8 3-7/8 2-7/8
2 3/8 4-1/2 3
2-1/2 3/8 5-5/8 4-1/8
3 3/8 5-7/8 4
4 3/8 7-3/8 5
5 1/2 9-1/8 6-1/4
6 1/2 10-1/8 6-3/4
8 1/2 13-1/8 8-3/4
ALL SIZES ARE IN INCHES
C
SWIVEL NUT
ADJUSTABLE BAND
HANGER
AT LEAST ONE FULL
THREAD OF ROD MUST
BE EXPOSED
SPRINKLER PIPING
45° ELBOW
SMOOTH BORE CORROSION
RESISTANT OUTLET
LOCATED 18-INCHES ABOVE
GRADE
EXTERIOR WALL
SEAL PENETRATION AROUND PIPE
TO FULL THICKNESS OF WALL
PIPE RESTRAINING CLAMP (TYPICAL)
ADJUSTABLE BAND HANGER (TYPICAL)
DRAIN FROM SPRINKLER ZONE
CONTROL ASSEMBLY
INTERIOR EXTERIOR
UNSECURE AREA SECURE AREA
FLAT WASHER -
TYPICAL
ALL-THREAD ROD (SIZED PER NFPA 13)
DOWN TO PIPE HANGER
UNISTRUT CHANNEL
ALL-THREAD ROD (SIZED PER
NFPA 13) UP TO STRUCTURAL
ATTACHMENT
NUT - TYPICAL
NOTES:
1. BASED ON 1000 PSF SOIL BEARING.
2. RBA: REQUIRED BEARING AREA IN SQUARE FEET
3. TA: THRUST ANGLE IN DEGREES
4. ALL THRUST BLOCKS TO BE CONSTRUCTED OF HIGH EARLY
STRENGTH CONCRETE THAT HAS A SPECIFIED COMPRESSIVE
STRENGHT OF 2500 PSI AND A REQUIRED AVERAGE
COMPRESSIVE STRENGTH OF 3500 PSI WITHIN SEVEN DAYS
AFTER PLACEMENT.
5. SEE TABLE FOR MINIMUM THRUST BLOCK SIZE.
6. ALL BLOCKS TO BEAR AGAINST UNDISTURBED EARTH
90° VERTICAL BEND
THRUST BLOCK SCHEDULE
PIPE
SIZE
90° BEND
RBA TA
8" 9.55 45°
PIPE CLAMP 20 GA STRAP (MATCH CLAMP WIDTH)
3/4" WELD ELL
PITCH TOWARDS DRAIN
EQUIPMENT
3/4" DRAIN
NOTE:
1. SLOPE SHEET METAL
TOWARDS DRAIN.
MIN.
3"
DIA.
PIPE
MIN.
3"
48" CENTERS
TO VISIBLE
LOCATION
MAX.
8"
1.5" DRAIN LINE FROM
ELEVATOR MACHINE
ROOM ZONE CONTROL
ASSEMBLY WITH AIR GAP
FINISHED FLOOR
12"X12"X8" DEEP
FLOOR SINK FITTING
AND 6" OUTLET
(BY OTHERS)
US Army Corps of Engineers ®
G
2 3 4 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C A
T E
G O
R Y
C O
D E
C:\Users\dlittle\Documents\10053876-F-MCA2-Central_dlittle@stantonengineering.com.rvt
1/18/2021 12:08:45 PM READY TO ADVERTISE (RTA)
FX502
MCA2
F
IR
E S
U P
P R
E S
S
IO
N D
E T
A
IL
S
F O
R T
G O
R D
O N
G
E O
R G
IA
S A
V A
N N
A H
D
IS
T R
IC
T
W
E S
T O
G L E
T H
O R
P E
A V
E N
U E
S A
V A
N N
A H
G
A
H D
R A
R L
IN
G T
O N
V
IR
G
IN
IA
T
IR
W
IN
D L
IT
T L E
D H
O F
M A
N N
D C
A N
D
IA
N O
V E
M B
E R
W H
N B
-- 1 -3
-0
S C
I M
IS
S
IO
N
C O
M M
A N
D U
N
IV
E R
S
IT
Y R
E G
IS
T
R A
R F
O R
C E
M O
D E
R N
IZ
A
T
IO
N A
N D
P R
O P
O N
E N
C Y
F Y
P
N
NTS
A1
INSTALLATION OF ADJUSTABLE BAND HANGER
NTS
A3
DRAIN/TEST CONNECTION TO BUILDING EXTERIOR
NTS
A7
SECURE AREA SPRINKLER PIPING PENETRATION DETAIL
1 PROVIDE A UL LISTED DIELECTRIC UNION INSIDE THE SECURE
PERIMETER ADJACENT TO THE PENETRATION. FOR GROOVED
SPRINKLER PIPING, GROUND THE CONDUIT WITHIN 6 INCH OF
THE PERIMETER PENETRATION USING A NO. 4 WIRE
(0.2043-DIAMETER COPPER WIRE) TO THE BUILDING GROUND
KEYED NOTES:
NTS
E1
INSTALLATION OF TRAPEZE HANGER
NTS
E7
THRUST BLOCK
R
E V
IS
E
D I N
A C
C O
R D
A N
C E
W
IT
H A
M E
N D
M E
N T
/1
/2
NTS
E3
AUTOMATIC AIR VENT ON WET PIPE SYSTEM
NTS
C7
SPRINKLER TROUGH DETAIL
NTS
C1
SPRINKLER FLOOR DRAIN DETAIL
FX502 FIRE SUPPRESSION DETAILS