This document is a comprehensive set of design and construction drawings for Facility F (Guard House) within the Kuwait Apache Alert Facilities project located at Ali Al Salem Air Base, Kuwait. The project is designated as Solicitation No. W912ER26RA016, with drawings issued in July 2026 by the U.S. Army Corps of Engineers Middle East District for the Kuwait Ministry of Defence and Kuwait Air Force (KMOD/KAF).
The Guard House is a single-story, approximately 24 square meter facility comprising a guard room (13 m²) and toilet (3 m²), designed to meet Kuwait Fire Forces (KFF) and International Building Code requirements. The structural design utilizes intermediate reinforced concrete moment frames with reinforced concrete slab-on-grade, concrete grade beams, and concrete columns, all detailed in accordance with ACI 318-19 standards. The facility features 200mm concrete masonry unit (CMU) walls with 100mm brick cladding exterior veneer, a sloped EPDM roofing system, bullet-resistant steel windows and doors, and precast concrete coping. Mechanical systems include a ductless mini-split heat pump cooling unit (7.9 kW), exhaust fan (170 LPS), and domestic hot water system (3.5 kW tankless heater) with rooftop water storage tank (450L). Plumbing provisions include toilet fixtures, floor drain, and water supply/sanitary systems. Electrical systems consist of a main distribution panel (MDPF) served by the facility's Maintenance Supply Warehouse power panel, lighting fixtures with emergency battery backup capability, and comprehensive grounding and lightning protection. Telecommunications infrastructure includes IDS/CCTV systems, balanced magnetic switches, data drops, and security cabinets. The facility requires compliance with KFF Volume requirements, UFC standards, NFPA codes, and USACE engineering manuals regarding fire safety, life safety, structural design, and operational safety. All construction documents, material specifications, schedules, and performance requirements are detailed across 14 drawing volumes covering general notes, structural, architectural, mechanical, plumbing, electrical, and telecommunications systems.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Army Corps of Engineers ®
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
VOLUME - FACILITY
VOLUME OF 14
FACILITY A - ALERT SHELTER
FACILITY C - LOGISTICS READINESS CENTER
FACILITY D - MAINTENANCE SUPPLY WAREHOUSE
FACILITY F - GUARD HOUSE
FACILITY H - PILOT READINESS FACILITY
FACILITY J - POL SHED
FACILITY K - SUBSTATION
FACILITY M - STORAGE SHADE
FACILITY N - WASH RACK SUNSHADE
FACILITY O - FIRE WATER PUMP HOUSE
GENERAL NOTES AND SITE DESIGN
INDEX OF VOLUMES
VOLUME
NUMBER
VOLUME TITLE
FACILITY G1 - SUNSHADES - SINGLE
FACILITY E - ALERT MAGAZINE
FACILITY STD - STANDARD DETAILS14
MIDDLE EAST DISTRICT
X:\REVIT PROJECTS\KUWAIT\2023\KU-509974-2 - APACHE ALERT MISSION FACILITIES\F - GUARD HOUSE\KU-509974-2F-DM-G-GUHA_RVT25.rvt
7/14/2026 12:42:18 PM
/1
/2
:4
:1
P
M
ALI AL SALEM AB, KUWAIT
KMOD – KUWAIT AIR FORCE
W912ER26RA016
JULY 2026
KU-509974-2
KUWAIT APACHE ALERT FACILITES
GI001
F A
C
IL
IT
Y
C O
V E
R S
H E
E T
A L I A
L S
A L E
M A
B K
U W
A
IT
C O
'B A
N N
O N
C O
'B A
N N
O N
E S
T
IL
L M
A N
J U
L Y
W E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
D R
A C
K M
A L E
S
K U
-5 -2
F -G
I0
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
E
S
F
C D
C
F - GUARD HOUSE6
of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
X:\REVIT PROJECTS\KUWAIT\2023\KU-509974-2 - APACHE ALERT MISSION FACILITIES\F - GUARD HOUSE\KU-509974-2F-DM-G-GUHA_RVT25.rvt
7/14/2026 12:42:18 PM
/1
/2
:4
:1
P
M
GI011
IN
D
E X
O F
D R
A W
IN
G
S
A L I A
L S
A L E
M A
B K
U W
A
IT
C O
'B A
N N
O N
C O
'B A
N N
O N
E S
T
IL
L M
A N
J U
L Y
W E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
D R
A C
K M
A L E
S
K U
-5 -2
F -G
I0
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
E
S
F
C D
C
INDEX OF DRAWINGS
KU-509974-2 - FACILITY F - GUARD HOUSE
SHEET
ID
FILE NAME REV. NO.
AM/COP
NO.
SHEET TITLE
GENERAL
GI001 KU-509974-2F-GI001 FACILITY COVER SHEET
GI011 KU-509974-2F-GI011 INDEX OF DRAWINGS
GI041 KU-509974-2F-GI041 BUILDING CODE AND LIFE SAFETY ANALYSIS
GI101 KU-509974-2F-GI101 LIFE SAFETY AND FIRE SUPPRESSION PLAN - GROUND FLOOR
STRUCTURAL
S-001 KU-509974-2F-S-001 GENERAL NOTES
SB101 KU-509974-2F-SB101 FOUNDATION AND SLAB-ON-GRADE PLAN
SF101 KU-509974-2F-SF101 FRAMING PLAN - ROOF
SF201 KU-509974-2F-SF201 STRUCTURAL ELEVATIONS
SF301 KU-509974-2F-SF301 FRAMING SECTIONS
SF501 KU-509974-2F-SF501 STRUCTURAL DETAILS
SF502 KU-509974-2F-SF502 IMF BEAM & COLUMN DETAILS
SF503 KU-509974-2F-SF503 GRADE BEAM DETAILS
SF504 KU-509974-2F-SF504 MASONRY DETAILS 1
SF505 KU-509974-2F-SF505 MASONRY DETAILS 2
SF506 KU-509974-2F-SF506 MASONRY DETAILS 3
SF601 KU-509974-2F-SF601 STRUCTURAL SCHEDULES
ARCHITECTURAL
A-001 KU-509974-2F-A-001 GENERAL ARCHITECTURAL NOTES
AB101 KU-509974-2F-AB101 AIR BARRIER PLAN AND SECTION
AE101 KU-509974-2F-AE101 BUILDING PLANS
AE201 KU-509974-2F-AE201 BUILDING ELEVATIONS
AE301 KU-509974-2F-AE301 BUILDING SECTIONS
AE401 KU-509974-2F-AE401 ENLARGED PLANS AND ELEVATIONS
AE402 KU-509974-2F-AE402 WALL SECTIONS
AE603 KU-509974-2F-AE603 DOOR AND WINDOWS SCHEDULE AND DETAILS
AE901 KU-509974-2F-AE901 PERSPECTIVE VIEWS
INTERIORS
IN101 KU-509974-2F-IN101
FINISH PLAN, SIGNAGE PLAN, FURNITURE PLAN SCHEDULE &
LEGEND - GROUND FLOOR
PLUMBING
PL101 KU-509974-2F-PL101 SANITARY PLAN - GROUND FLOOR - COMPOSITE
PL102 KU-509974-2F-PL102 DOMESTIC WATER PLAN - GROUND FLOOR - COMPOSITE
PL601 KU-509974-2F-PL601 PLUMBING SCHEDULES
PL901 KU-509974-2F-PL901 DOMESTIC WATER ISOMETRIC VIEW
PL902 KU-509974-2F-PL902 SANITARY ISOMETRIC VIEW
MECHANICAL
MH101 KU-509974-2F-MH101 MECHANICAL PLAN - GROUND FLOOR - COMPOSITE
MH601 KU-509974-2F-MH601 MECHANICAL SCHEDULES
ELECTRICAL
EL101 KU-509974-2F-EL101 ELECTRICAL PLANS - GROUND FLOOR AND ROOF
EP601 KU-509974-2F-EP601 ONE-LINE DIAGRAM
TELECOMMUNICATIONS
T001 KU-509974-2F-T001 TELECOMMUNICATIONS LEGEND
TM101 KU-509974-2F-TM101 IDS/CCTV PLAN - GROUND FLOOR
TN101 KU-509974-2F-TN101 TELECOMMUNICATIONS DROP PLAN - GROUND FLOOR
TN501 KU-509974-2F-TN501 CABINET DEATILS / RISER - GUARD HOUSE
1. PROJECT'S APPLIED CODES & STANDARDS:
2. BUILDING CODE REQUIREMENTS:
A. COMPLIANCE:
1) CONTRACTOR AWARDED THIS PROJECT IS REQUIRED TO COMPLY WITH KUWAIT REQUIREMENTS AND ALL OTHER APPLICABLE CODES, STANDARDS, AND
REQUIREMENTS.
2) ALL FIRE AND LIFE SAFETY DRAWINGS ARE CONCEPTUAL IN NATURE. CONTRACTOR DESIGN “SHOP” DRAWINGS MUST COMPLY WITH KUWAIT
REQUIREMENTS AND ALL OTHER APPLICABLE CODES, STANDARDS, AND REQUIREMENTS.
B. INTERNATIONAL CODE COUNCIL: "ICC" AS APPLICABLE REFERENCE OR GUIDANCE
1) IBC-2021 INTERNATIONAL BUILDING CODE. "IBC"
C. NATIONAL FIRE PROTECTION ASSOCIATION: "NFPA" AND/OR AS REFERENCED BY KFF.
1) NFPA 1-24: FIRE CODE
2) NFPA 10-2022 STANDARD FOR PORTABLE FIRE EXTINGUISHERS.
3) NFPA 70-2023 NATIONAL ELECTRICAL CODE.
4) NFPA 170-2024 STANDARD FOR FIRE SAFETY AND EMERGENCY SYMBOLS.
D. STATE OF KUWAIT:
1) KFF KUWAIT FIRE FORCES "KFF" REQUIREMENTS FOR SAFETY AND FIRE PREVENTION.
2) KMOD KUWAIT MINISTRY OF DEFENCE.
3) MEP KUWAIT MILITARY ENGINEERING PROJECTS.
4) MPW KUWAIT MINISTRY OF PUBLIC WORKS.
5) MEW KUWAIT MINISTRY OF ELECTRICITY AND WATER.
E. UNIFIED FACILITIES CRITERIA (UFC) AS APPLICABLE REFERENCE OR GUIDANCE:
"ALL UFC'S ARE FOR GUIDANCE AND WHEN LOCAL CODES DO NOT ADDRESS THE REQUIREMENT"
1) UFC 1-200-01-2022, CHANGE 3: (FEB24): DOD BUILDING CODE.
2) UFC 3-600-01-2016, CHANGE 6: (MAY21): FIRE PROTECTION ENGINEERING FOR FACILITIES.
F. UNIFIED FACILITIES GUIDE SPECIFICATIONS: “UFGS”
1) UFGS 01 33 00: SUBMITTAL PROCEDURES
2) UFGS 10 44 16: FIRE EXTINGUISHERS
G. UNITED STATES ARMY CORPS OF ENGINEERS: “USACE”
1) DIM-2022: DESIGN INSTRUCTIONS MANUAL: "USACE" MIDDLE EAST DISTRICT “MED”
2) EM: ENGINEERING MANUAL “EM” 385-1-1: SAFETY AND HEALTH REQUIREMENTS:
REFERENCES ARE NOT ALL INCLUSIVE.
**BUILDING AND LIFE SAFETY CODE REQUIREMENTS MEETS OR EXCEEDS KFF REQUIREMENTS AND ARE PROVIDED WITHIN EACH SPECIFIC SECTION AS:
REQUIRED/ALLOWABLE AND PROVIDED/ACTUAL.
A. OCCUPANCY CLASSIFICATION:
1) KFF VOLUME 1, CHAPTER 4, FIRST: ADMINISTRATIVE: (BUSINESS)
B. CONSTRUCTION TYPE:
1) KFF VOLUME 1, CHAPTER 5, TABLE NO. 5-1: TYPE: THE THIRD, FIRE RESISTANT- NONE:
C. MIXED USE & OCCUPANCY:
1) KFF VOLUME 1, CHAPTER 5, SECTION FIFTEENTH: NOT APPLICABLE (N/A):
D. BUILDING HEIGHTS AND AREA:
IBC CHAP. 5, TABLES 504.3, 504.4 & 506.2:
1). HEIGHT:
HEIGHT IN METERS: (M) ALLOWABLE: 16.8 ACTUAL: 5.1
HEIGHT IN STORIES: ALLOWABLE: 2 ACTUAL: 1
2) AREA: SQUARE METERS: (SM) ALLOWABLE: 2137 ACTUAL: 15
AREA FACTOR INCREASE FOR FRONTAGE DISTANCE: ALLOWABLE: YES ACTUAL: N/A
E. FIRE RESISTIVE REQUIREMENTS:
1) IBC-2021 SECTION 602, TABLES 601, 602, & 705.5: TYPE II-B (THIRD TYPE) CONSTRUCTION: RATING IN HOURS:
PRIMARY STRUCTURAL FRAME: REQUIRED: 0 PROVIDED: 0
EXTERIOR BEARING WALLS: REQUIRED: 0 PROVIDED: 0
INTERIOR BEARING WALLS: REQUIRED: 0 PROVIDED: 0
EXTERIOR NONBEARING WALLS: KFF VOLUME 1, CHAPTER 5,TABLE NO. 5-2
INTERIOR NONBEARING WALLS / PARTITIONS: REQUIRED: 0 PROVIDED: 0
FLOOR CONSTRUCTION & SECONDARY STRUCTURAL MEMBERS: REQUIRED: 0 PROVIDED: 0
ROOF CONSTRUCTION & SECONDARY STRUCTURAL MEMBERS: REQUIRED: 0 PROVIDED: 0
2) EXTERIOR NONBEARING WALLS AND PARTITIONS:
KFF, VOLUME 1, CHAPTER 5, TABLE 5-2: BUILDING RISK AND OCCUPANCY: REQUIRED: >9 PROVIDED: >9
FIRE-RATING IN HOURS: REQUIRED: 0 PROVIDED: 0
3) KFF INTERIOR FIRE RESISTIVE REQUIREMENTS:
KFF VOLUME 1, CHAPTER 5, THIRD: FIRE AND SMOKE ZONE SEPARATION: REQUIRED: N/A PROVIDED: N/A
4) HAZARDOUS MATERIALS STORAGE
I. KFF VOLUME 4: REMAIN BELOW MAXIMUM PERMISSIBLE CAPACITY REQUIRED: YES PROVIDED: YES
F. FIRE PROTECTION AND LIFE SAFETY SYSTEMS:
1) FIRE ALARM SYSTEMS: AREA <500 SM: "FIRE ALARM REPORTING WILL BE ONLY LOCAL PER KAF" I. KFF VOLUME 6, CHAPTER 5: MANUAL AND AUTOMATIC FIRE WARNING SYSTEMS: REQUIRED: NO PROVIDED: NO
2) FIRE SUPPRESSION SYSTEMS:
I. AUTOMATIC SPRINKLER SYSTEM:
KFF VOLUME 6, CHAPTER 5: AREA <500 SM: REQUIRED: NO PROVIDED: NO
II. SUPPLEMENTAL SUPPRESSION SYSTEM(S):
A) A) FOAM-WATER SYSTEMS:
KFF VOLUME 6, CHAPTER 8 AND KFF VOLUME 6, CHAPTER 8: REQUIRED: NO PROVIDED: NO
B) INTERNAL FIRE HOSE NETWORK: AREA <2000 SM
KFF VOLUME 6, CHAPTER 5: AREA <500 SM:
25 MM RUBBER HOSE AND HOSE CABINET: REQUIRED: NO PROVIDED: NO
STANDPIPE SYSTEM WITH 38 MM HOSE STATIONS: REQUIRED: NO PROVIDED: NO
III. EXTINGUISHING SYSTEMS:
I. PORTABLE FIRE EXTINGUISHERS:
KFF VOLUME 6, CHAPTER 5, ADMINISTRATIVE OFFICES: REQUIRED: YES PROVIDED: YES
II. CLEAN AGENT EXTINGUISHING SYSTEMS:
KFF VOLUME 2, CHAPTER 7, SECTION 3/8/4, 1/3/8/4: REQUIRED: NO PROVIDED: NO
3. LIFE SAFETY REQUIREMENTS:
A. CLASSIFICATION OF OCCUPANCY:
1) KFF VOLUME 1, CHAPTER 4, FIRST: ADMINISTRATIVE: (BUSINESS)
B. OCCUPANT LOAD:
1) KFF VOLUME 1, CHAPTER 6, TABLE 6-2 ADMINISTRATIVE: OFFICE: (GROSS) 15 SM / 14 SQM / PERSON ALLOWABLE: 2 ACTUAL: 2
C. CAPACITY OF MEANS OF EGRESS: KFF MINIMUM DOOR SIZE IS 850 MM:
1) KFF VOLUME 1, CHAPTER 6, TABLE 6-1: STAIRWAYS: OCCUPANT LOAD (OL) X 7.6 MM ALLOWABLE: N/A ACTUAL: N/A
LEVEL COMPONENTS AND RAMPS: 5.1 MM / PERSON ALLOWABLE: 10.2 ACTUAL: 850
D. NUMBER OF EXITS:
1) KFF VOLUME 1, CHAPTER 6, THIRTEENTH: NUMBER OF EXITS: REQUIRED: 1 PROVIDED: 1
I. BUSINESS OCCUPANCIES ARE PERMITTED TO HAVE A SINGLE EXIT SINCE ALL OF THE FOLLOWING REQUIREMENTS ARE MET:
-THE SINGLE EXIT DISCHARGES DIRECTLY OUTSIDE AT THE LEVEL OF EXIT DISCHARGE.
-TOTAL TRAVEL DISTANCE INCLUDING WITHIN THE EXIT DOES NOT EXCEED 30 M.
-THE TOTAL TRAVEL DISTANCE IS ON THE SAME STORY.
II. KFF VOLUME 1, CHAPTER 6, THIRD SECTION: REQUIRED: 1 PROVIDED: 1
A SINGLE EXIT IS PERMITTED SINCE THE FOLLOWING LIMITATIONS ARE NOT EXCEEDED:
-COMMON PATH OF TRAVEL EXCEEDS 23 M.
-TWO-WAY TRAVEL DISTANCE EXCEEDS 35 M.
-OCCUPANT LOAD EXCEEDS 50.
-AREA OF SPACE / ROOM EXCEEDS 250 SQM.
E. ARRANGEMENT OF MEANS OF EGRESS: NONSPRINKLERED:
1) KFF VOLUME 1, CHAPTER 6, FOURTH: EXITS LOCATED AT A DISTANCE FROM ONE ANOTHER: REQUIRED: N/A PROVIDED: N/A
F. TRAVEL DISTANCE TO EXIT: NONSPRINKLERED:
1) KFF VOLUME 1, CHAPTER 17: COMMON PATH OF TRAVEL: (CPT) ALLOWABLE: 23 ACTUAL: N/A
TRAVEL DISTANCE: (TD) ALLOWABLE: 35 ACTUAL: 6.3
2) KFF VOLUME 1, CHAPTER 6, SECTION 17: DEAD END: (DE) (CLOSED END) ALLOWABLE: 7.5 ACTUAL: N/A
3) EMERGENCY AND EXIT LIGHTS: KFF VOLUME 6, CHAPTER 5 & VOLUME 2, PART 3: REQUIRED: YES PROVIDED: YES
G. INTERIOR FINISH: KFF DOES NOT ADDRESS:
1) IBC-2021 TABLE 803.13 INTERIOR WALL AND CEILING FINISH: BUSINESS: NONSPRINKLERED: (CLASS A, B OR C)
INTERIOR EXIT STAIRS, RAMPS AND EXIT PASSAGES: REQUIRED: A PROVIDED: A
CORRIDORS, ENCLOSURE ACCESS STAIRWAY AND RAMPS. REQUIRED: B PROVIDED: B
ROOMS AND ENCLOSED SPACES: REQUIRED: C PROVIDED: C
2) IBC-2021, SECTION 804.4.2 FLOOR FINISH CLASS I OR II: FLOOR FINISH: STORAGE: ALLOWABLE: II ACTUAL: II
3) IBC-2021: TABLE 1505.1, ROOF COVERING CLASS A, B OR C: ROOF COVERING CLASSIFICATION: ALLOWABLE: C ACTUAL: C
H. ACCESSIBILITY: KUWAIT UNIVERSAL DESIGN CODE:
4. CODE COMPLIANCE SITE DESIGN:
THE KUWAIT MINISTRY OF DEFENSE (KMOD), KUWAIT AIR FORCE (KAF) APACHE ALERT MISSION COMPLEX CODE COMPLIANCE SITE PLAN ARE PRESENTED IN THE SITE DESIGN DRAWING SHEETS UNDER GI101, GI117, GI122, GI126, GI127, GI128, GI131, GI132, GI133 AND GI134.
**BUILDING AND LIFE SAFETY CODE REQUIREMENTS MEETS OR EXCEEDS KFF REQUIREMENTS.
F. FIRE PROTECTION AND LIFE SAFETY SYSTEMS: (CONTINUED)
IV. SMOKE VENTILATION AND EXHAUST SYSTEMS:
1. KFF VOLUME 6, CHAPTER 5 AND KFF VOLUME 5, CHAPTER 3: REQUIRED: NO PROVIDED: NO
G. SEE STANDARD DRAWINGS SF001, SF002, SF501, SF502 AND OTHER FACILITY DRAWINGS:
**BUILDING AND LIFE SAFETY CODE REQUIREMENTS MEETS OR EXCEEDS KFF REQUIREMENTS.
2. BUILDING CODE REQUIREMENTS: (CONTINUED)
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
X:\REVIT PROJECTS\KUWAIT\2023\KU-509974-2 - APACHE ALERT MISSION FACILITIES\F - GUARD HOUSE\KU-509974-2F-DM-FP-GUHA_RVT25.rvt
7/9/2026 2:30:19 PM
/9
/2
:3 :1
P
M
GI041
B U
IL
D
IN
G
C O
D E
A N
D L
IF
E
S A
F E
T Y
A N
A L Y
S
IS
A L I A
L S
A L E
M A
B K
U W
A
IT
D F
A B
E R
M M
O O
R E
R D
IP
E
R T
J U
L Y
W E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -G
I0
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
E
S
F
C D
C
FEC
F E
C
D EXT
0 0
80 100
COMPONENT:
DOOR (D)
STAIRWAY (S)
ACTUAL CLEAR WIDTH
ACTUAL EGRESS
EXIT TYPE:
INTERIOR (INT)
EXTERIOR (EXT)
REQUIRED CLEAR WIDTH
EGRESS CAPACITY
EGRESS CAPACITY TAG
GUARD ROOM
TD-A
D EXT
850 850
2 165
TOILET
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE & NORTH ARROW
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
GENERAL NOTES
X:\REVIT PROJECTS\KUWAIT\2023\KU-509974-2 - APACHE ALERT MISSION FACILITIES\F - GUARD HOUSE\KU-509974-2F-DM-FP-GUHA_RVT25.rvt
7/9/2026 2:30:20 PM
/9
/2
:3 :2
P
M
GI101
L
IF
E S
A F
E T
Y A
N D
F
IR
E S
U P
P R
E S
S
IO
N P
L A
N
G R
O U
N D
F L O
O R
A L I A
L S
A L E
M A
B K
U W
A
IT
D F
A B
E R
M M
O O
R E
R D
IP
E
R T
J U
L Y
W E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -G
I1
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
E
S
F
C D
C
LEGEND
PATH OF EGRESS
TRAVEL DISTANCE
TravelDistance_Type
(CPT, TD, DE)
TravelDistance_Route
(A, B, C, etc.) ALLOWABLE (MM) ACTUAL (MM)
GUARD ROOM 101 TD A 23000 6302
1 : 251
LIFE SAFETY AND FIRE SUPPRESSION PLAN - GROUND FLOOR
PORTABLE FIRE EXTINGUISHER IN A
CABINET IN FINISHED AREAS OR BRACKETS
(BR) ACCEPTABLE IN UNFINISHED AREAS.
PATH OF EGRESS TRAVEL
1. CONTRACTOR AWARDED THIS PROJECT IS REQUIRED TO
COMPLY WITH KUWAIT REQUIREMENTS AND ALL OTHER
APPLICABLE CODES, STANDARDS, AND REQUIREMENTS.
2. ALL FIRE AND LIFE SAFETY DRAWINGS ARE CONCEPTUAL
IN NATURE. CONTRACTOR DESIGN “SHOP” DRAWINGS
MUST COMPLY WITH KUWAIT REQUIREMENTS AND ALL
OTHER APPLICABLE CODES, STANDARDS, AND
REQUIREMENTS.
3. FOR APACHE ALERT MISSION COMPLEX EXTINGUISHING
SYSTEMS, FIRE PROTECTION, FIRE ALARM, LIFE SAFETY
AND SUPPRESSION SYSTEM STANDARD DETAILS AND
SYMBOLS SEE STANDARD DETAILS SHEETS SF001, SF002,
SF003, SF501, SF502, AND SPECIFIC FACILITY DRAWINGS.
4. FOR EXIT AND EMERGENCY LIGHTS REFER THE
ELECTRICAL DRAWINGS.
5. HAZARDOUS MATERIALS STORAGE SHALL REMAIN BELOW
MAXIMUM PERMISSIBLE CAPACITY.
OCCUPANT LOAD
ROOM
NO. ROOM NAME USE GROUP AREA
OCCUPANT
LOAD
101 GUARD ROOM BUSINESS 13 m² 1
102 TOILET BUSINESS 3 m² 1
TOTAL OCCUPANT LOAD 2
0 2.51.00.5 1.5
1:25
SHEET KEY NOTES
1. PLACE FIRE EXTINGUISHERS IN ACCORDANCE WITH KFF
VOL 2. PART 3, CH. 1 HAND FIRE EXTINGUISHERS FOR
SIZE, TYPE, AND LOCATION.
PLAN NORTH
C&C WALL WIND PRESSURE (kPa)
ZONE EFFECTIVE
WIDTH, M²
POSITIVE
PRESSURE
NEGATIVE
PRESSURE
4 0.96 -1.04
0.82 -0.90
0.72 -0.80
-1.28
-1.08
-0.99
0.86 -0.94
0.93
4.65
9.30
46.45
C&C ROOF WIND PRESSURE (kPa)
ZONE POSITIVE
PRESSURE
NEGATIVE
PRESSURE
1 0.43 -1.67
2'
2'
2'
2'
0.36
0.34
0.34
-1.41
-1.30
-2.20
-1.87
-1.73
-1.40
-2.99
-2.34
-2.06
EFFECTIVE
WIDTH, M²
0.93
4.65
9.30
46.45
0.93
4.65
9.30
46.45
0.93
4.65
9.30
46.45
0.93
4.65
9.30
46.45
0.93
4.65
9.30
46.45
0.43
0.36
0.34
0.34
0.43
0.36
0.34
0.34
0.43
0.36
0.34
0.34
C&C PARAPET WIND PRESSURE (kPa)
ZONE EFFECTIVE
WIDTH, M²
PRESSURE
CASE A, ZONE 2 3.15
2.54
2.12
3.95
3.20
2.87
2.12
2.73
0.93
4.65
9.30
46.45
0.93
4.65
9.30
46.45
CASE A, ZONE 3
CASE B, CORNER ZONE
CASE B, INTERIOR ZONE
CASE A, ZONE 2
CASE A, ZONE 2
CASE A, ZONE 2
-1.99
-1.80
-1.71
-1.52
0.93
4.65
9.30
46.45
-2.23
-1.94
-1.81
0.93
4.65
9.30
46.45
CASE A, ZONE 3
CASE A, ZONE 3
CASE A, ZONE 3
CASE B, CORNER ZONE
CASE B, CORNER ZONE
CASE B, CORNER ZONE
CASE B, INTERIOR ZONE
CASE B, INTERIOR ZONE
CASE B, INTERIOR ZONE -1.52
-0.80
-1.05
-2.20
-1.87
-1.73
-1.40
-1.40
0.96
0.82
0.72
0.86
3'
3'
3'
3'
-2.99
-2.34
-2.06
0.93
4.65
9.30
46.45
0.43
0.36
0.34
0.34 -1.40 a a
2' a
+Z
+Y
+X
2'
2'
3'
3'
2a
4a
4a
2a
2a
2a θ
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
S-001
G E
N E
R A
L N
O T
E S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
J G
O N
G L
IK
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
-0
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
GENERAL NOTES
1. REFERENCE STANDARDS:
UFC 1-200-01 DOD BUILDING CODE WITH CHANGE 3, 26 FEBRUARY 2024
UFC 3-301-01 STRUCTURAL ENGINEERING, CHANGE 1, 2 OCTOBER 2023
UFC 3-320-06A CONCRETE FLOOR SLABS ON GRADE SUBJECTED TO HEAVY LOADS, 1 MARCH 2005
IBC 2021 INTERNATIONAL BUILDING CODE, 2021
ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
AISC 341-16 SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS
ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, 2019
TMS 402/602-16 BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES
2. DESIGN LOAD CRITERIA
RISK CATEGORY : II
ROOF DEAD LOAD: SELF WEIGHT + 3.0kPa ROOF LIVE LOAD: 1.0 kPa MINIMUM STAIRS AND LANDINGS LIVE LOAD: 4.8 kPa SLAB ON GRADE (TYPICAL, UNO) : 4.8 kPa
SNOW LOAD: N/A
SEISMIC LOAD:
SITE CLASS: C
IMPORTANT FACTOR, Ie: 1.0
SPECTRAL RESPONSE ACCELERATIONS:
SHORT PERIOD, Ss: 0.410g ONE SECOND PERIOD, S1: 0.110g
DESIGN SPECTRAL RESPONSE ACCELERATIONS:
SHORT PERIOD, SDS: 0.355g ONE SECOND PERIOD, SD1: 0.110g
SEISMIC DESIGN CATEGORY: C
SEISMIC ANALYTICAL PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE
LATERAL FORCE RESISTING SYSTEM : INTERMEDIATE REINFORCED CONCRETE MOMENT FRAME
RESPONSE MODIFICATION FACTOR, R: 5.0
SYSTEM OVERSTRENGTH FACTOR, Ω0: 3.0
DEFLECTION AMPLIFICATION FACTOR, Cd: 4.5 SEISMIC RESPONSE COEFFICIENT, Cs: 0.071 DESIGN BASESHEAR, V: 44.0kN (0.071W, W= SEISMIC WEIGHT)
WIND LOAD:
BASIC WIND SPEED, V: 161 KPH
EXPOSURE CATEGORY: C
IMPORTANT FACTOR, Iw: 1.00 INTERNAL PRESSURE COEFFICIENT, GCpi: +/-0.18 TOPOGRAPHIC FACTOR, Kzt: 1.0 DIRECTIONALITY FACTOR, Kd: 0.85
3. SOIL PROPERTIES:
A. NET ALLOWABLE SOIL BEARING PRESSURE: 168 kPa (3500 psf) B. MODULUS OF SUBGRADE REACTION: 19.8 kPa/mm (73 pci)
4. MATERIAL DESIGN PROPERTIES:
A. CONCRETE, f'c 28 MPa (4000 psi) B. REINFORCING STEEL, fy 420 MPa (60 ksi) C. CMU MASONRY , f'm 14 MPa (2 ksi) D. GROUT COMPRESSIVE STRENGTH 17.3 MPa (2.5 ksi)
NOTES:
1. ALL EXTERIOR WALLS, WINDOWS, DOORS, MECH. LOUVERS, ROOFING COMPONENTS, AND
ALL OTHER ASSEMBLIES OR OPENINGS WITHIN THE BUILDING ENVELOPE SHALL BE
DESIGNED FOR THE C&C DESIGN WIND PRESSURES AS SHOWN BY ZONE.
2. LOCATION OF ZONES IS PROVIDED PER ASCE 7-16, FIG. 30.3-1 & 30.3-5A.
3. DISTANCE (a) = 340mm.
4. ROOF ANGLE (θ) = 2.3 DEG.
5. THE CONTRACTOR SHALL USE COMPONENT AND CLADDING WIND PRESSURE TO DESIGN
ALL ELEMENTS ATTACHED TO THE BUILDING.
NTS1
C&C WIND PRESSURE MONOSLOPE
1. SEE S0.01 FOR GENERAL NOTES.
2. SEE S-501 - S503 FOR CONCRETE DETAILS.
3. SEE S-504 - S506 FOR MASONRY DETAILS.
4. SEE S-601 FOR FOUNDATION, BEAM, AND COLUMN
SCHEDULES.
1. TOP OF FLOOR SLAB = 0.00 mm UNO
2. TOP OF FOUNDATION = 0.00 mm UNO
3. BOTTOM OF FOUNDATION = SEE S-302 AND S-601
4. SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND
PROPERTIES OF INTERIOR WALLS. SEE S-506 FOR INTERIOR
WALL REINFORCEMENT.
5. SEE ARCHITECTURAL AND PLUMBING DRAWINGS FOR
FINISH FLOOR ELEVATIONS, FLOOR SLOPES, AND
LOCATIONS, SIZES, AND ELEVATIONS OF FLOOR DRAINS.
SF201
SF201
SF201
SF201
1 2
A
B
C
SF301
TOP OF SLAB
F1
GB-1
GB-1
CJ
SF301
EL. 0
(TYP)
200 CMU
GB-1
GB-2
(TYP)
(T Y
P
O P
E N
IN
G
SF301
SF501
SF501
F1 C1C1
F1 F1
C1 C1
1 150 mm THICK CONCRETE SLAB-ON-GRADE, WITH ONE (1) LAYER OF 100 x 100-W4.5 x W4.5 (OR D13 AT 450 O.C. EACH
WAY) OVER VAPOR RETARDER AND 150MM THICK DENSE
GRADED AGGREGATE OVER COMPACTED SOIL.
LOCATE CONTROL JOINT BETWEEN GRID LINE B COLUMNS.2
3 EXPANSION JOINT MATERIAL ALONG PERIMETER BETWEEN
SLAB-ON-GRADE AND GRADE BEAM. SEE DETAIL . /4 SF501
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE & NORTH ARROW
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
SHEET KEY NOTES
GENERAL NOTES
/1
/2
:4 :4
A
M
SB101
F O
U N
D A
T
IO
N A
N D
S L
A B
-O N
-G R
A D
E P
L A
N
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
B
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1 : 251
FOUNDATION AND SLAB-ON-GRADE PLAN
PLAN NORTH
0 2.51.0.5 1.5
1:25
1. TOP OF CONCRETE ROOF SLAB VARIES, SEE
ELEVATIONS.
2. SEE SS001 FOR GENERAL NOTES AND LOADING
CRITERIA.
3. SEE SF501 FOR ELEVATED SLAB DETAILS.
4. COORDINATE INSTALLATION OF SCUPPER
OPENINGS IN PARAPET WALLS WITH
ARCHITECTURAL DRAWINGS.
5. ALL ROOF BEAMS BM-1, BM-2, OR BM-3, UNO.
6. ALL COLUMNS C-1, UNO.
7. PROVIDE 200 mm THICK CONCRETE ROOF SLAB REINFORCED WITH D16 AT 300 mm O.C. E.W. T&B.
8. ROOF ACCESS LADDER TO BE DESIGNED BY
CONTRACTOR.
1 2
A
B
C
SF301
SF301
SF301
PARAPET
200 MM
B M
-1
BM-2
BM-2
P A
R A
P E
T M
M
B M
-1
BM-3
PARAPET
200 MM
P A
R A
P E
T M
M
.2
RS-1
3713EL. VARIES
TOP OF SLAB
1 1 WATER STORAGE TANK ON ROOF. SEE MECHANICAL
DRAWINGS FOR TANK SIZE AND EXACT LOCATION. SEE
3/SS510 FOR EQUIPMENT SUPPORT PAD DETAIL.
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE & NORTH ARROW
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
SHEET KEY NOTES
GENERAL NOTES
/1
/2
:4 :4
A
M
SF101
F R
A M
IN
G
P L
A N
R
O O
F
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1 : 25
ROOF FRAMING PLAN
PLAN NORTH
0 2.51.0.5 1.5
1:25
TOS
T.O. ROOF
T.O. PARAPET
TOF
-1200
ABC
B.O. ROOF
V E
R
IF
Y W
A
R C
H
VERIFY W/ ARCH
C1 C1
BM-1
F1
GB-1
BM-1
GB-1
F1
BM-3
RS-1
GB-1
TOS
T.O. ROOF
T.O. PARAPET
TOF
-1200
B.O. ROOF
C1C1
BM-2
GB-1
F1 F1
GB-1
225 225
RS-1
3626EL. VARIES
GB-1
TOS
T.O. ROOF
T.O. PARAPET
TOF
-1200
A B C
B.O. ROOF
C1C1
GB-1GB-1
BM-1
F1 F1
225224
RS-1
GB-1
41001700
BM-3
TOS
T.O. ROOF
T.O. PARAPET
TOF
-1200
1 2
B.O. ROOF
C1 C1
BM-3
RS-1
3842EL. VARIES
BM-2
BM-3
GB-1
GB-2
GB-1
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF201
S T
R U
C T
U R
A L
E L
E V
A T
IO
N
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1 : 50
WEST ELEVATION
1 : 50
NORTH ELEVATION
1 : 50
EAST ELEVATION
1 : 50
SOUTH ELEVATION
OPEN
0 52.50.5 1.0 1.5 2.0
1:50
TOS
T.O. ROOF
T.O. PARAPET
TOF
-1200
ABC
EL. 3618
GB-1
BM-3
CMU
SLAB ON GRADE
(REFER TO PLAN
FOR SPECIFICS)
2.29°
BM-2
PARAPET
200 MM
PARAPET
200 MM
GB-2
B.O. ROOF
BM-2
RS-1
4100 1700
SF501
TOS
T.O. ROOF
T.O. PARAPET
TOF
-1200
1 2
B.O. ROOF
RS-1
EL. VARIES
BM-2
C1
F1
C1
F1
FINISH GRADE
TOS
T.O. ROOF
T.O. PARAPET
TOF
-1200
1 2
B.O. ROOF
BM-1
GB-1
SLAB ON
GRADE
CMU (TYP)
RS-1
(SEE PLAN)
PARAPET
200 MM
SF501
SF501
3676EL. VARIES
BM-1
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF301
F R
A M
IN
G
S E
C T
IO
N
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1 : 503
SECTION 3
1 : 501
SECTION 1
1 : 502
SECTION 2
GL
13MM EXPANSION FELT BETWEEN
GRADE BEAM AND SLAB EDGE
CONCRETE SLAB ON GRADE,
(REFER TO PLAN FOR SPECIFICS
CONCRETE GRADE BEAM,
(REFER TO SCHEDULE FOR
SIZE AND REINFORCEMENT)
TOS
SEE PLAN
50MM RIGID INSULATION
VAPOR BARRIER
S P
L
IC
E
C L A
S S
B T
E N
S
IO
N
200MM CMU WALL ,
(REFER TO SCHEDULE
FOR SPECIFICS)
D16 DOWEL BARS
@ 300MM O/C
BOND BEAM, (REFER TO
SCHEDULES)
GRAVEL LAYER OVER
COMPACTED SOIL
100MM VENEER WALL,
(REFER TO ARCH)
VERIFY W/ ARCH
ROOF SLAB REINFORCEMENT,
SEE PLAN AND SCHEDULE
BEAM REINFORCEMENT,
SEE PLAN AND SCHEDULE
D13 @ 250 O.C. EACH FACE
20MM CHAMFER (TYP)
T.0. PARAPET
SEE PLAN
T.0. ROOF
SEE PLAN
ROUGHEN SURFACE TO
6MM AMPLITUDE (MIN)
TYP
CLR
T Y
P C
L R
B.0. ROOF
SEE PLAN
ROOF SLAB
ELEV. VARIES
R E
FE
R
T O
P
LA
N
"T
\3
T
SLAB REINFORCEMENT
(SEE PLAN)
BACKER ROD OR SEALANT AS
REQUIRED (SEE ARCH)
GL
CONCRETE COLUMN, (REFER TO PLAN
AND SCHEDULES FOR SPECIFICS)
13MM EXPANSION MATERIAL AT COLUMN
CONCRETE SLAB-ON-GRADE
(REFER TO PLAN FOR SPECIFICS)
CONCRETE FOOTING (REFER
TO SCHEDULE FOR SIZE AND
REINFORCEMENT)
T.O. SLAB
SEE PLAN
GL
TOF
SEE PLAN
TOS
CONCRETE GRADE BEAM
(REFER TO SCHEDULE FOR SIZE
AND REINFORCEMENT)
A
A-A
VAPOR BARRIER
"T
GRADE BEAM REINFORCEMENT (REFER
TO SCHEDULE FOR SPECIFICS)
A
VAPOR BARRIER (TYP)
150MM (MIN) GRAVEL LAYER
OVER COMPACTED SOIL (TYP)
CONCRETE SURFACE
ROUGHENED TO 6MM AMPLITUDE
GRADE BEAM STIRRUPS AT COLUMN
JOINT W/ STD 135° HOOKS AT ENDS,
SPACING TO MATCH GRADE BEAM
STIRRUP SPACING
50 (TYP)
50MM BLINDING CONCRETE, TYP
50MM RIGID INSULATION
150MM (MIN) GRAVEL LAYER
OVER COMPACTED SOIL
SEE PLAN
50MM BLINDING CONCRETE, TYP
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF501
S T
R U
C T
U R
A L
D E
T A
IL
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
NTS4
SECTION AT GRADE BEAM
NTS2
TYPICAL PARAPET DETAIL
NTS1
TYPICAL SOG CONTROL JOINT
NTS3
TYPICAL CONCRETE COLUMN DETAIL
COLUMNS DETAIL NOTES:
1. THIS DETAIL IS APPLICABLE ALL CONCRETE COLUMNS.
2. ALL DIMENSIONS ARE IN MM, UNO.
3. ALL SPLICES SHALL BE CLASS B TENSION SPLICE. NO SPLICE
PERMITTED AT JOINTS. SPLICE SHALL BE PROVIDED AT CENTER
HALF OF COLUMNS.
4. PROVIDE 90° STD HOOK AT COLUMN ENDS, TYP.
5. BEAMS AND SLAB REINFORCEMENT NOT SHOWN FOR CLARITY.
6. CHAMFERS ARE 20MM (MIN), TYP.
A A
GL
COLUMN C1
T.O. ROOF
SEE PLAN
TOS
SEE PLAN
TOF
SEE PLAN
D
O
/C
GRADE BEAM
(SEE SCHEDULE)
ROOF BEAM
(SEE SCHEDULE)
D
/C
A T
C L A
S S
B T
E N
S
IO
N S
P L
IC
E
D
O
/C
A-A
COLUMN VERTICAL
REINFORCEMENT
(SEE SCHEDULE)
COLUMN TIE
(SEE SCHEDULE)
"A"
NOTES:
1. THIS DETAIL APPLIES TO CONCRETE BEAMS BM-1.
2. ALL STIRRUPS START 50MM FROM FACE OF SUPPORTS (SS = 50MM), UNO.
3. ALL SPLICES SHALL BE CLASS B. SPLICE LOCATION SHOWN IS OPTIONAL. NO SPLICE PERMITTED AT JOINTS. CONTRACTOR
MAY SUGGEST DIFFERENT SPLICE LOCATIONS. NO SPLICE PERMITTED WITHIN 2H FROM FACE OF SUPPORT.
4. PROVIDE 90° STD HOOK AT BEAM ENDS, TYP.
5. COLUMN RENIFORCEMENT NOT SHOWN FOR CLARITY.
6. CHAMFERS ARE 20MM (MIN), TYP.
A CB
"B" "SP" "B"
(TYP)
50 MAX B
B
DESIGNATION SIZE NO. OF LEGS SPACING
A D10 2 200
B D10 2 55
D10 2 55
STIRRUP DISTRIBUTION @ LONGITUDINAL BEAMS (BM-1)
SP
NOTES:
1. THIS DETAIL APPLIES TO CONCRETE BEAMS BM-2.
2. ALL STIRRUPS START 50MM FROM FACE OF SUPPORTS (SS = 50MM), UNO.
3. ALL SPLICES SHALL BE CLASS B. SPLICE LOCATION SHOWN IS OPTIONAL. NO SPLICE
PERMITTED AT JOINTS. CONTRACTOR MAY SUGGEST DIFFERENT SPLICE LOCATIONS. NO
SPLICE PERMITTED WITHIN 2H FROM FACE OF SUPPORT.
4. PROVIDE 90° STD HOOK AT BEAM ENDS, TYP.
5. COLUMN REINFORCEMENT NOT SHOWN FOR CLARITY.
6. CHAMFERS ARE 20MM (MIN), TYP.
B
B
"C" "SP" "C"
(TYP)
50 MAX
DESIGNATION SIZE NO. OF LEGS SPACING
C D13 2 55
SP D13 2 55
STIRRUP DISTRIBUTION @ TRANSVERSE BEAMS (BM-2)
B-B
BEAM BOTTOM
REINFORCEMENT
(SEE SCHEDULE)
STIRRUP
(SEE SCHEDULE)
BEAM TOP
REINFORCEMENT
(SEE SCHEDULE)
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF502
IM
F
B E
A M
C
O L
U M
N D
E T
A
IL
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1 : 203
TYPICAL CONCRETE IMF COLUMN
1 : 202
LONGITUDINAL IMF BEAMS DETAILS
1 : 201
TRANSVERSE IMF BEAMS DETAILS
0 0.2 10.4 0.6 0.8 2
1:20
(TYP)
50 MAX
NOTES:
1. ALL DIMENSIONS ARE IN MM, UNO.
2. ALL STIRRUPS START 50MM FROM FACE OF SUPPORTS (SS = 50MM), UNO.
3. ALL SPLICES SHALL BE CLASS B SPLICE. SHOWN SPLICE LOCATIONS ARE OPTIONAL. NO SPLICE PERMITTED AT JOINTS. CONTRACTOR CAN
SUGGEST DIFFERENT SPLICE LOCATIONS. NO SPLICE PERMITTED WITHIN 2H FROM FACE OF SUPPORT.
4. PROVIDE 90° STD HOOK AT BEAM ENDS, TYP.
5. PROVIDE "K" STIRRUPS IF RG LENGTH IS ≤ 0MM.
6. COLUMN REINFORCEMENT NOT SHOWN FOR CLARITY.
7. CHAMFERS ARE 20MM (MIN), TYP.
A
A
"RG" "SP" "RG""RG"
GL
AT 2H
"K"
AT 2H
"K"
AT 2H
"K"
(TYP)
50 MAX
AT 2H
"K"
GL GL
A-A
TOP, BOTTOM, & MIDDLE
REINFORCEMENT
(SEE SCHEDULE)
STIRRUP
REINFORCEMENT
(TYP)
"CC"
H
DESIGNATION SIZE NO. OF LEGS SPACING
K D13 2 SEE GRADE BEAM SCHEDULE
RG D13 2 SEE GRADE BEAM SCHEDULE
GRADE BEAMS STIRRUPS DISTRIBUTION
SP D13 2 150
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF503
G R
A D
E B
E A
M D
E T
A
IL
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
TYPICAL GRADE BEAM DETAIL
NOTES:
1. LADDER JOINT REINFORCEMENT AND ADJUSTABLE ANCHOR PART SHALL BE HOT DIP GALVANIZED.
2. PROVIDE AT LEAST ONE ANCHOR FOR EACH 0.17M2 OF WALL AREA.
3. PROVIDE ADDITIONAL ANCHORS AROUND OPENINGS LARGE THAN 400MM IN EITHER DIMENSION.
SPACE ANCHORS AROUND PERIMETER OF OPENING AT A MAXIMUM OF 600MM ON CENTER AND
PLACE ANCHORS WITHIN 300MM OF OPENING PERIMETERS, WALL ENDS, AND CONTROL JOINT.
4. HORIZONTAL REINFORCEMENT IN CMU BOND BEAM NOT SHOWN IN PLAN VIEW FOR CLARIFY.
CONC BEAM OR COLUMN
(REINF NOT SHOWN)
100 VENEER WALL
(SEE ARCH.)
NOTES:
1. ALL PARTS OF CMU VENEER ANCHORS (ADJUSTABLE ANCHOR/PINTLE, CLIP, AND ANCHORAGE FASTENERS) SHALL BE HOT DIP GALVANIZED AND DESIGNED TO WITHSTAND A FORCE OF 815N (MIN) IN TENSION AND COMPRESSION, AT MAXIMUM ALLOWED OFFSET OF 31.8MM (DISENGAGEMENT OF THE PINTLE FROM THE VENEER ANCHOR).
2. ANCHORAGE FASTENERS TO CONCRETE SHALL BE PER MANUFACTURER'S RECOMMENDATION AND IN ACCORDANCE
WITH THE REQUIREMENTS IN ACI 318.
3. PROVIDE AT LEAST ONE ANCHOR FOR EACH 0.17M2 OF WALL AREA.
4. PROVIDE ADDITIONAL ANCHORS AROUND OPENINGS LARGE THAN 400MM IN EITHER DIMENSION. SPACE ANCHORS AROUND PERIMETER OF OPENING AT A MAXIMUM OF 610MM ON CENTER AND PLACE ANCHORS WITHIN 300MM OF
OPENING PERIMETERS, WALL ENDS, AND CONTROL JOINT.
5. REINFORCEMENT IN CONCRETE NOT SHOWN FOR CLARITY.
B
B
PLAN
CMU VENEER ANCHORS SPACED
@ 400 O.C. VERTICAL AND @ 450
O.C. HORIZONTAL.
M
M M
O T
A R
C O
V E
R
M
IN
RIGID INSULATION
(SEE ARCH.)
100 VENEER WALL
RIGID INSULATION
(SEE ARCH.)
CMU VENEER
ANCHOR
SECTION B-B
CONC BEAM OR COLUMN
(REINF NOT SHOWN)
ANCHORAGE
FASTENERS
(SEE NOTE 2)
W
A R
C H
C O
O R
D
ANCHORAGE OF 100 VENEER WALL TO CMU BACKING
ANCHORAGE OF 100 VENEER WALL TO CONCRETE BACKING
CMU WALL (SEE
REINF.)
LADDER JOINT
REINFORCEMENT,
MW11, SPACED
VERTICALLY AT
400 O.C.
ADJUSTABLE ANCHOR
PART, MW18, SPACING
HORIZONTALLY AT 450
O.C. MAX.
100 VENEER WALL
450 (MAX)
M
M M
O R
T A
R C
O V
E R
M
IN
A
A
PLAN
CMU BOND BEAM
AND HORZ. REINF.
(SEE )
VERT REINF
(SEE )
CMU WALL
100 VENEER WALL
(SEE ARCH.)
RIGID INSULATION
(SEE ARCH.)
ADJUSTABLE
ANCHOR PART
LADDER JOINT
REINFORCEMENT
SECTION A-A
/1 SF506
/1 SF506
/1 SF506
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF504
M A
S O
N R
Y D
E T
A
IL
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1 : 10
VENEER ANCHORAGE
0 10.50.1 0.2 0.3 0.4
1:10
J O
IN
T
M A
T E
R
IA
L M
M C
O M
P R
E S
S
IB
L E
NOTE:
SLAB, BEAM, AND WALL
REINFORCEMENT NOT SHOWN FOR
CLARITY
CONCRETE ROOF SLAB, REFER
TO PLAN FOR SPECIFICS
CONCRETE BEAM, REFER
TO SCHEDULE
CONCRETE PARAPET,
SEE DETAIL .
L203X203X12.7 W/ LONG-SLOTTED HOLE
IN VERTICAL LEG
CMU WALL 13MMØX110MM HWS AT 400MM O/C
16MMØX150MM WEDGE ANCHOR,
INSTALL AT BOTTOM OF SLOTTED HOLE
/2 SF501
NOTE:
SLAB, BEAMS, AND WALL
REINFORCEMENT NOT SHOWN FOR
CLARITY
CONCRETE SLAB, REFER
TO PLAN FOR SPECIFICS
CONCRETE BEAM, REFER
TO SCHEDULE
CMU WALL
25MM COMPRESSIBLE
JOINT MATERIAL
L203X203X12.7 W/ LONG-SLOTTED HOLE
IN VERTICAL LEG, TYP
13MMØX110MM HWS AT 400MM O/C, TYP
16MMØ THRU BOLT,
INSTALL AT BOTTOM OF SLOTTED HOLE
NOTE:
SLAB AND WALL REINFORCEMENT
NOT SHOWN FOR CLARITY
CONCRETE SLAB, REFER
TO PLAN FOR SPECIFICS
CMU WALL
25MM COMPRESSIBLE JOINT MATERIAL
L203X203X12.7 W/ LONG-SLOTTED HOLE
IN VERTICAL LEG (TYP)
13MMØX110MM HWS AT 400MM O/C (TYP)
16MMØ THRU BOLT,
INSTALL AT BOTTOM OF SLOTTED HOLE
T.O. PARAPET
PRECAST COPING FASTENERS,
BY SUPPLIER
PRECAST CONCRETE COPING,
SEE ARCH.
CONCRETE PARAPET,
SEE DETAIL .
CONCRETE BEAM, SEE PLANS
ROOF SLAB,
SEE PLANS
VENEER WALL, SEE ARCH
NOTE:
SLAB AND BEAM REINFORCEMENT
NOT SHOWN FOR CLARITY
/2 SF501
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
GRAPHIC SCALE
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF505
M A
S O
N R
Y D
E T
A
IL
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1 : 204
EXTERIOR CMU WALL BRACING
1 : 202
INTERIOR CMU WALL BRACING TO
CONCRETE BEAM
1 : 203
INTERIOR CMU WALL BRACING TO
CONCRETE SLAB
1 : 201
PRECAST CAP SUPPORT
0 0.2 10.4 0.6 0.8 2
1:20
CONCRETE FOUNATION OR
GRADE BEAM, (REFER TO PLAN)
200MM BOND BEAM TO
MATCH WALL THICKNESS
W/ (1) - D16 TYP.
200MM BOND BEAM TO
MATCH WALL THICKNESS
W/ (1) - D16 TYP
T/CMU WALL
DOWEL LAP SPLICE AT
EACH VERTICAL BAR
(TYP)
90° STD HOOK INTO TOP BOND BEAM
(TYP). ALTERNATIVELY, SPLICE
ADDITIONAL BAR WITH STD. HOOK.
D16 AT 600MM
VERTICAL BARS,
TYP.
R E
F E
R T
O L
A P
S P
L
IC
E S
C H
E D
U L E
NOTES:
1. REFER TO ARCH FOR OPENING SIZES AND LOCATIONS.
2. REFER TO ARCH FOR CONTORL JOINT INFORMATION.
3. REFER TO SCHEDULES FOR BOND BEAMS REINFORCEMENT
4. REFER TO SCHEDULES FOR BOND BEAMS BEARING ABOVE OPENINGS, UNO.
5. REFER TO ARCH DRAWINGS FOR TOP OF WALL ELEVATIONS OF INTERIOR WALLS.
6. PROVIDE MASONRY CONTROL JOINTS AT ALL INTERSECTIONS BETWEEN EXTERIOR AND INTERIOR PARTITION WALLS. PROVIDE MASONRY CONTROL JOINTS
AT ALL CORNERS OR JOGS IN EXTERIOR MASONRY WALLS. PROVIDE MASONRY CONTROL JOINTS SO THAT NO LENGTH OF UNJOINTED WALL EXCEEDS 6000mm OR 1.5 TIMES THE WALL HEIGHT, WHICHEVER IS LESS. PROVIDE CONTROL JOINTS WITHIN 1200mm OF ALL CORNERS FOR WALLS LONGER THAN 9000mm, U.N.O. REFER TO ARCH DWGS FOR ADDITIONAL INFO.
(T Y
P m m M
A X m m M
A X
AT FULL HEIGHT WALL
200MM MAX
SCHEDULE (TYP)
REFER TO LINTEL
S C
H E
D U
L E
T
Y P
R
E F
E R
T O
L
IN
T E
L
SCHEDULE (TYP)
REFER TO LINTEL
CONTROL JOINT, (TYP)
REFER TO ARCH
D16 AT 1200MM
HORIZONTAL BARS.
(2) -D16 ADDITIONAL
VERTICAL REBARS
ALTERNATE
COURSES
(2)-D16 ADDITIONAL
VERTICAL REBARS
D13 DOWEL EVERY
OTHER COURSE
20075
LL127X76X7.9 (LLV) w/ 13MMØ
EXP BOLT AT 400MM
LOOSE LINTEL,
SEE SCHEDULE
CMU WALL,
SEE ARCH.
CMU BOND BEAM,
SEE SCHEDULE
SEE SCHEDULE
THICKNESS
NOTES:
1. EXTEND HORIZ REINF 40 BAR DIA BEYOND JAMB FACE EA SIDE (600MM MIN).
2. PROVIDE STEEL LINTEL WHERE A WALL CONTROL JOINT TRANSECTS THE
LINTEL.
VENEER WALL,
SEE ARCH.
MISCELLANEOUS LOOSE LINTEL SCHEDULE
THICKNESS SPAN LOOSE LINTEL
200MM UP TO 1200MM LL102X89X7.9
NOTES:
1. SEE ARCHITECTURAL DRAWINGS FOR OPENING SIZES AND LOCATIONS.
2. CONNECT ALL ANGLES TO ALL 2 AND 3 ANGLE LINTELS BACK TO BACK AT 400MM
OC MAX.
3. ALL ANGLES LONG LEG VERTICAL, UNLESS OTHERWISE NOTED.
4. BEARING END OF STEEL LINTEL AT CONTROL JOINT SHALL BE WRAPPED WITH
BUILDING PAPER.
5. PROVIDE MINIMUM 200MM BEARING ON BRICK OR SOLID CONCRETE BLOCK.
6. PROVIDE MINIMUM 200MM x WALL THICKNESS x 200MM HIGH GROUTED CMU OR
BRICK BEARING PAD UNDER ALL LINTELS, UNO. GROUT JAMBS OF MASONRY
OPENINGS 1800MM AND LARGER FULL HEIGHT FOR 200MM MINIMUM WIDTH.
7. CONNECT LINTEL TO COLUMN IF MASONRY OPENING IS ADJACENT TO COLUMN
AND LINTEL HAS LESS THAN 200MM BEARING ON CMU BEYOND COLUMN FLANGES.
8. STEEL LINTELS IN EXTERIOR WALLS ARE TO BE GALVANIZED.
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF506
M A
S O
N R
Y D
E T
A
IL
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
NTS1
TYPICAL MASONRY WALL DETAIL
NTS2
TYPICAL MASONRY DETAIL
CMU LINTEL SCHEDULE
OPENING CLEAR SPAN BEAM WIDTH BEAM DEPTH BEARING WIDTH
BOTTOM
REINFORCEMENT
TOP
REINFORCEMENT STIRRUPS
UP TO 1500mm WALL THICKNESS 410mm 200mm (2) -16 - D10 @ 200mm OC
NTS3
CMU LINTEL DETAIL
/1 SF503
/1 SF503
/2 SF502
/1 SF502
US Army Corps of Engineers®
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
/1
/2
:4 :4
A
M
SF601
S T
R U
C T
U R
A L
S C
H E
D U
L E
S
A L I A
L S
A L E
M A
B K
U W
A
IT
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
P H
IL
A
D E
L P
H
IA
D
IS
T R
IC
T
A
R C
H S
T R
E E
T
P H
IL
A
D E
L P
H
IA
P
A
A K
O L L
IA
S
A K
O L L
IA
S
M A
L J U
B O
O R
I
J U
L Y
W
E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -S
F
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
CONCRETE BEAM SCHEDULE
MARK WIIDTH DEPTH
TOP
REINFORCEMENT
BOTTOM
REINFORCEMENT
STIRRUP SPACING
(SIZE) REMARKS
BM-1 400 350 (3) D19 (3) D19 55 (D10) IMF BEAMS @ GRIDLINES 1 & 2. SEE DETAIL .
BM-2 400 350 (3) D19 (3) D19 55 (D10) IMF BEAMS @ GRIDLINES B & C. SEE DETAIL .
BM-3 400 350 (3) D19 (3) D19 300 (D10) GRAVITY BEAM @ GRIDLINE A
CONCRETE COLUMN SCHEDULE
MARK
DIMENSIONS REINFORCEMENT
REMARKSWIDTH DEPTH LONGITUDINAL TIES
C1 400 400 8 - D19 D10 @ 145 O.C.
COLUMN FOOTING SCHEDULE
MARK
DIMENSIONS REINFORCEMENT
REMARKSLENGTH (L) WIDTH (W) THICKNESS TOP BOTTOM
F1 1600 1600 300 (6) D16 EA. WAY (6) D16 EA. WAY
CONCRETE GRADE BEAM SCHEDULE
MARK WIDTH DEPTH
TOP REINFORCEMENT BOTTOM REINFORCEMENT MIDDLE REINFORCEMENT STIRRUPS
REMARKSREBAR SIZE QUANTITY REBAR SIZE QUANTITY REBAR SIZE QUANTITY END OF BEAM (K) MIDDLE OF BEAM (RG)
GB-1 625 1200 D16 4 D16 4 D16 3 (EA. SIDE) 150 300 SEE DETAIL .
GB-2 420 1200 D16 4 D16 4 D16 3 (EA. SIDE) 150 300 SEE DETAIL .
ROOF SLAB SCHEDULE
MARK TOP REINFORCEMENT BOTTOM REINFORCEMENT REMARKS
RS-1 D16 @ 200 EA. WAY D16 @ 200 EA. WAY THICKNESS VARIES FROM 200MM @ GRIDLINE 'C' TO 432MM @ GRIDLINE 'A'
SHEET ID
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
IS
O
A
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P L O
T D
A T
E
F
IL
E N
A M
E
M
ID
D L E
E A
S T
D
IS
T R
IC
T
G
H
I
J
K
L
M
N
O
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
R
IN
C E
F R
E D
E R
IC
K
D R
IV
E
W
IN
C H
E S
T E
R V
A
GENERAL SHEET NOTES
X:\REVIT PROJECTS\KUWAIT\2023\KU-509974-2 - APACHE ALERT MISSION FACILITIES\F - GUARD HOUSE\KU-509974-2F-DM-A-GUHA_RVT25.rvt
7/10/2026 9:40:13 AM
/1
/2
:4 :1
A
M
A-001
G E
N E
R A
L A
R C
H
IT
E C
T U
R A
L N
O T
E S
A L I A
L S
A L E
M A
B K
U W
A
IT
D G
U R
A K
D G
U R
A K
Z K
O T
H E
J U
L Y
W E
R R
A
K M
O D
K
U W
A
IT
A
IR
F O
R C
E
K U
-5 -2
A F
R E
E M
A N K
U -5
-2
F -A
-0
G U
A R
D H
O U
S E
K U
W A
IT
A
P A
C H
E A
L E
R T
F A
C
IL
IT
IE
S
F
C D
C
1. REFER TO A-001 SHEET FOR SYMBOLS AND ABBREVIATIONS.
2. DRAWINGS MUST NOT BE SCALED FOR CONSTRUCTION PURPOSES.
3. ALL LEVELS ON DRAWINGS ARE SHOWN IN MILLIMETERS UNLESS OTHERWISE
INDICATED.
4. REFER TO SA SHEETS LOCATED IN "VOLUME 14 - STANDARD DETAILS", FOR
ADDITIONAL STANDARD DETAILS.
5. WALL TYPES WITH UL DESIGN NUMBERS SHALL BE CONSTRUCTED TO UL
STANDARDS. PRODUCTS USED SHALL BEAR UL CLASSIFICATION WHERE
REQUIRED BY THE UL DESIGN.
6. DETAILS FOR EXTERNAL WALLS AND EXTERNAL GLAZING SYSTEMS ARE
SHOWN SCHEMATICALLY ONLY, AND ARE INTENDED, TOGETHER WITH THE
SPECIFICATIONS AND PROFILES SHOWN, TO ESTABLISH PERFORMANCE,
MATERIALS QUALITIES AND ARCHITECTURAL INTENT.
7. AT STC RATED WALLS, THE PARTITIONS SHALL BE SEALED TO UNDERSIDE OF
STRUCTURE (INCLUDING FLUTED METAL DECKS) AT BOTH SIDES WITH
ACOUSTIC SEALANT, TOP, BOTTOM, INTERSECTIONS, DOOR FRAMES, GLAZED
OPENING FRAMES AND ALL OTHER PENETRATIONS.
8. VERIFY ALL ROUGH-IN DIMENSIONS FOR EQUIPMENT PROVIDED IN THIS
CONTRACT, OR BY OTHERS.
9. REFER TO FINISH SCHEDULES FOR FINISH DESIGNATIONS.
10. FOR SEISMIC BRACING REQUIREMENTS, SEE GENERAL STRUCTURAL NOTES
AND SPECIFICATIONS.
11. REFER TO PARTITION TYPES SHEETS FOR PARTITION CONSTRUCTION.
12. FOR CMU CONTROL JOINTS REFER TO STRUCTURAL DRAWINGS.
13. COORDINATE FINAL LOCATION OF ALL MECHANICAL EQUIPMENT WITH
MECHANICAL DRAWINGS.
14. COORDINATE FINAL LOCATION OF ALL FIRE PROTECTION EQUIPMENT WITH
FIRE PROTECTION DRAWINGS.
A ------------------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES
ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B -------------------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BO BOTTOM OF
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C -------------------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR
FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORD COORDINATE
COR CONTRACTOR OF RECORD
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D -------------------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DOR DESIGNER OF RECORD
DR DOOR
DS DOWNSPOUT
E ------------------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE BOARD
(INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F -------------------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAS BD FASCIA BOARD
FC BRK FACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLASH FLASHING
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC
FRTW FIRE RETARDANT TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G -------------------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT INSTALLED
GOVERNMENT INSTALLED
GFRG GLASS-FIBER-REINFORCED
GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GUT GUTTER
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H -------------------------------
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE
AIR (FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HT HEIGHT
HYDR HYDRAULIC
I -------------------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J -------------------------------
JAN JANITOR
K -------------------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L -------------------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M -------------------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N -------------------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTION
O -------------------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P -------------------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INC
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND
RECEPTACLE
PTN PARTITION
PWR POWER
Q -------------------------------
QT QUARRY TILE
QTY QUANTITY
R -------------------------------
RAF RAISED ACCESS FLOORING
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REC RM RECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV…