Section 25 08 10 Page 1
SECTION 25 08 10
UTILITY MONITORING AND CONTROL SYSTEM TESTING
04/06
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
CONSUMER TECHNOLOGY ASSOCIATION (CTA)
CTA CTA-709.1-D (2014) Control Network Protocol Specification
CTA CTA-709.3 (1999; R 2015) Free-Topology Twisted-Pair
Channel Specification
1.2 DEFINITIONS
1.2.1 Algorithm
A set of well-defined rules or procedures for solving a problem or providing an output from a specific set of inputs.
1.2.2 Analog
A continuously varying signal value (temperature current, velocity, etc.).
1.2.3 Analog to Digital (A/D) Converter
An A/D converter is a circuit or device whose input is information in analog form and whose output is the same information in digital form.
1.2.4 CTA CTA-709.1-D
"Control Network Protocol Specification", Standard communication protocol for networked control systems that provides peer-to-peer communications.
1.2.5 Application Specific Controller
A device that is furnished with a pre-established built in application that is configurable but not re-programmable.
1.2.6 Architecture
Architecture is the general organization and structure of hardware and software.
1.2.7 Binary
A two-state system where an "ON" condition is represented by a high signal level and an "OFF" condition is represented by a low signal level.
Section 25 08 10 Page 2
1.2.8 Building Point of Connection (BPOC)
The point of connection between the UMCS network backbone and the building network backbone. The hardware at this location, which performs/provides the connection is referred to as the BPOC Hardware.
1.2.9 Control Wiring
This includes conduit, wire, and wiring devices to install complete HVAC control systems, including motor control circuits, interlocks, sensors, PE and EP switches, and like devices. This also includes all wiring from node to node, and nodes to all sensors and points defined in the I/O summary shown on drawings or specified herein, and required to execute the sequence of operation. Does not include line voltage power wiring.
1.2.10 Demand
The maximum rate of use of electrical energy averaged over a specific interval of time, usually expressed in kW.
1.2.11 Diagnostic Program
Machine-executable instructions used to detect and isolate system and component malfunctions.
1.2.12 Distributed Control
A system whereby all control processing is decentralized and independent of a central computer. In regards to a LonWorks based system, it also means where the control logic for a single piece of building level control resides in more than one controller (node).
1.2.13 Graphical User Interface (GUI)
Human-machine interfacing allows the operator to manage, command, monitor, and program the system.
1.2.14 Integration
Establishing communication between two or more systems to create a single system.
1.2.15 Interoperable
Two devices are interoperable if installed into the same system and they communicate with each other without the use of another device (such as a gateway).
1.2.16 LonTalk(r)
Open communication protocol developed by the Echelon(r) Corporation.
1.2.17 LONWORKS(r)
The communication technology developed by Echelon(r) Corporation for control systems developed. The technology is based on the CTA CTA-709.1-D protocol
Section 25 08 10 Page 3 and employs interoperable devices along with the capability to openly manage these devices using a network configuration tool.
1.2.18 LONMARK(r) International (LONMARK(r) Interoperability Assoc.)
Standards committee consisting of numerous independent product developers and systems integrators dedicated to determining and maintaining the interoperability guidelines for the LONWORKS(r) industry.
1.2.19 LonMarked(r)
A device that has been certified for compliance with LonMark(r) standards by the LonMark(r) International.
1.2.20 LONWORKS(r) Application Specific Controller (ASC)
A networked device or node that contains a complete, configurable application that is specific to a particular task.
1.2.21 LONWORKS(r) General Purpose Programmable Controller
A programmable control product, that unlike an ASC, is not installed with a fixed factory-installed application program. The application in the controller is custom software produced by the integrator specifically for the project.
1.2.22 LONWORKS(r) Network Services (LNS)
The database format for addressing nodes and variable bindings node-to-node.
1.2.23 Network
A system of distributed control units that are linked together on a communication bus. A network allows sharing of point information between all control units. Additionally, a network provides central monitoring and control of the entire system from any distributed control unit location.
1.2.24 Network Configuration Tool
Software used to create and modify the control network database and configure controllers.
1.2.25 Node ID
A unique 48-bit node identification (ID) tag given to each node by Echelon
Corporation.
1.2.26 Node
An intelligent LONWORKS(r) device with a node ID and communicates via CTA
CTA-709.1-D and is connected to an CTA CTA-709.1-D network.
1.2.27 Operating System (OS)
Software which controls the execution of computer programs and which provides scheduling, debugging, input/output controls, accounting, compilation, storage assignment, data management, and related services.
Section 25 08 10 Page 4
1.2.28 Operator Workstation (OWS)
The OWS consists of a high-level processing desktop or laptop computer that provides a graphic user interface to network.
1.2.29 Peripheral
Input/Output (I/O) equipment used to communicate to and from the computer and make hard copies of system outputs and magnetic files.
1.2.30 Router
A device which routes messages destined for a node on another segment subnet or domain of the control network. The device controls message traffic based on node address and priority. Routers may also serve as communication links between powerline, twisted pair, fiber, coax, and RF media.
1.2.31 Standard Network Variable Type (SNVT)
A network variable of a standard format type used to define data information transmitted and receive by the individual nodes.
1.2.32 UMCS Network Media
Transmission equipment including cables and interface modules (excluding
MODEMs) permitting transmission of digital information.
1.2.33 XIF
"External Interface File" contains the contents of the manufacturer's product documentation.
1.2.34 Gateway
A device that translates from one protocol to another. Gateways are also called Communications Bridges or Protocol Translators.
1.3 SYSTEM DESCRIPTION
a. The purpose of this Specification is to define generic Factory, Performance Verification, and Endurance Test procedures for Utility
Monitoring and Control Systems (UMCS) and building level DDC. These tests are to be used to assure that the physical and performance requirements of UMCS and building level DDC are tested, and that the test results are adequately documented. The Government will base certain contractual decisions on the results of these tests.
b. This document covers the factory, performance verification, and endurance test procedures for the Utility Monitoring and Control System (UMCS) and
Direct Digital Control for HVAC. The system shall be comprised of the server hardware and software, IP network hardware and software, and building point of connection (BPOC) hardware and software.
c. The contractor who provided building level DDC under Section 23 09 00
INSTRUMENTATION AND CONTROL FOR HVAC is responsible for testing the building level DDC. All control testing and controller tuning required file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx
Section 25 08 10 Page 5 under Section 23 09 00 shall be completed and approved before performing
Performance Verification and Endurance Tests under this section.
d. The following UFGS: Section 23 09 00 INSTRUMENTATION AND CONTROL FOR
HVAC shall be part of the contract documents.
1.3.1 Factory Test
Conduct a factory test at a company site. Perform some of the basic functions of the UMCS and building level DDC, to assure that the performance requirements of the specifications are met.
1.3.2 Performance Verification and Endurance Test
a. Shall be conducted on hardware and software installed at the jobsite to assure that the physical and performance requirements of specifications are met. Tests on network media shall include all contractor furnished media and shall include at least one type of each device installed.
b. Shall be conducted under normal mode operation, unless otherwise indicated in the initial conditions description for each test. System normal mode describes a condition in which the system is performing its assigned tasks in accordance with the contract requirements.
c. Shall utilize the operator workstation (OWS) to issue commands or verify status data.
1.3.3 Test Equipment and Setup
All test equipment calibrations shall be traceable to NIST. The accuracy of the test equipment and overall test method shall be at least twice the maximum accuracy required for the test. For example, if a temperature sensor has an accuracy of +1 degree F over the executed range, the test instrument used shall have an accuracy of at least +0.5 degree F or better. Provide all test equipment unless otherwise noted in the contract documents.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29
SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01
33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Factory Test; G, RO
SD-06 Test Reports
UMCS and Building Level DDC Testing Sequence; G, RO
Performance Verification Test; G, RO
Endurance Testing; G, RO file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/01%2033%2029.docx file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/01%2033%2000.docx file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/01%2033%2000.docx
Section 25 08 10 Page 6
PART 2 PRODUCTS
Not Used
PART 3 EXECUTION
3.1 UMCS AND BUILDING LEVEL DDC TESTING SEQUENCE
Perform a successful factory test prior to start of installation work, as described in this section. During the installation phase, perform all required field testing requirements on the 23 09 00 INSTRUMENTATION AND
CONTROL FOR HVAC, to verify that systems are functioning and installed in accordance with specifications. Submit field test report prior to start of
PVT and endurance testing. After completing all required field testing, perform a successful PVT and endurance test. All tests shall be successfully completed, and test reports received, prior to final acceptance of the UMCS and building level DDC. Perform and document Contractor field test on UMCS and building level DDC.
3.2 COORDINATION
Coordinate the testing schedule with the Government. Coordination shall include controls specified in other sections or divisions which include controls and control devices that are to be part of or interfaced to the UMCS specified in this section.
3.3 PROTECTION
Protect all work and material from damage by the work or workers. The
Contractor is liable for any damage caused and responsible for the work and equipment until finally inspected, tested, and accepted. Protect the work against theft, and carefully store material and equipment received onsite that is not immediately installed.
3.4 FACTORY TEST
3.4.1 Factory Test Plan
Prior to the scheduling of the factory tests, provide the Government with a
Factory Test Plan for approval, and wait to receive notification of approval of the Test Plan and Procedures before performing the tests. The plan shall include the following, as a minimum:
a. System one-line block diagram of equipment used in the factory test model, indicating servers, workstations, peripherals, network equipment, controllers, and instrumentation.
b. System hardware description used in the factory test.
c. System software description used in the factory test.
d. Listing of control and status points in the factory test model; plus a table with the following information:
(1) Input and output variables.
(2) SNVTs for each variable.
(3) Expected engineering units for each variable.
file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx
Section 25 08 10 Page 7
(4) Node ID.
(5) Domain & subnet addressing.
e. Required passwords for each operator access level.
f. List of other test equipment.
3.4.2 Test Procedures
Develop the factory test procedures from the generic test procedures in
ATTACHMENT A. The test procedures shall consist of detailed instructions for test setup, execution, and evaluation of test results. Edit the generic test procedure for the provided UMCS and building level DDC. Perform a factory test on a model of the UMCS and building level DDC for the Government to verify the system will function to the requirements of the contract documents. The test architecture shall mimic a two building arrangement.
There shall be a TCP/IP layer with two Internet Protocol (IP) to Lon routers.
Below each of the routers shall be both programmable (GPPC) and application-specific controllers (ASC). One server and one workstation with printers shall be connected to the IP layer. There shall be simulated input devices connected to controllers to enable the creation of changing variables. If, during testing, the system fails a portion of a test, the Government will inform the Contractor if the entire test or only the portion that failed shall be re-performed. Give the Government a written report of those items which failed, what the problem was, and what was done to correct it. Provide onsite technical support to perform the PVT. ATTACHMENT A presents the generic Test Procedures with the following information:
a. Test identification number.
b. Test title.
c. Objective.
d. Initial conditions (if applicable).
e. Test equipment (if required).
f. Sequence of events.
g. Expected results.
3.4.3 Test Report
Submit a factory final, complete test report after completing the test, consisting of the following, as a minimum:
a. Section one of the submittal shall be a short summary of the factory test.
b. Section two of the submittal shall be a copy of the test plans.
c. Section three shall be the executed test procedure and shall be divided using tabs. Each tab section shall include all pertinent information pertaining to the executed and approved test, showing date and Government representative who witnessed/approved the test.
Section 25 08 10 Page 8
3.5 FIELD TEST REQUIREMENTS
The UMCS contractor shall perform and document contractor start-up and field tests as required by Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC.
The field test validates that the UMCS and building level DDC are in operation without any problems or system errors prior to starting a PVT.
Validate that all software along with all hardware is installed to meet or exceed the contract document requirements. This includes all LONWORKS(r) networking and monitoring hardware and all peripherals associated with the network and hardware. Start-up and field testing shall include:
3.5.1 Start-up Testing
All testing listed in Section 23 09 00 shall be completed.
3.5.2 Point-to-Point Testing
All point-to-point testing of end field devices through proper input/output to graphic and operator interface shall be completed and approved.
3.5.3 Field Calibration
All field calibration shall be completed and approved.
3.5.4 Detailed Functional Testing
Detailed functional tests, verified by the Government that the system operation adheres to the Sequences of Operation.
3.5.5 Alarms and InterlocksAll alarm limits and testing shall be completed.
3.5.6 System Schedules and Setpoints
All schedule start/stops and system setpoints shall be entered, operating, and approved.
3.6 PERFORMANCE VERIFICATION TEST
3.6.1 Test Plan
Prior to the scheduling of the performance verification tests, provide the
Government with a Performance Verification and Endurance Test Plan and
Procedures for approval, and receive notification of approval of the Test
Plan and Procedures. The plan shall include the following, as a minimum:
a. Installed system one-line block diagram, indicating servers, workstations, peripherals, network equipment, controllers, and instrumentation.
b. Installed system hardware description.
c. Installed system software description, including any software revisions made since the factory test.
d. Listing of control and status points installed in the system; plus a table with the following information:
(1) Input and output variables.
file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx
Section 25 08 10 Page 9
(2) SNVTs for each variable.
(3) Expected engineering units for each variable.
(4) Node ID.
(5) Domain & subnet addressing.
e. Required passwords for each operator access level.
f. List of other test equipment.
3.6.2 Test Procedures
Develop the performance verification test procedures from the generic test procedures in ATTACHMENT A. The test procedures shall consist of detailed instructions for test setup, execution, and evaluation of test results. Edit the generic test procedure for the provided UMCS and building level DDC.
Perform a performance verification test (PVT) on the completed UMCS and building level DDC for the Government to verify the system is completely functional. If, during testing, the system fails a portion of a test, the
Government will inform the Contractor if the entire test or only the portion that failed shall be re-performed. Give the Government a written report of those items which failed, what the problem was, and what was done to correct
it. Provide on-site technical support to perform the PVT. ATTACHMENT A presents the generic UMCS Performance Verification Test Procedures with the following information:
a. Test identification number.
b. Test title.
c. Objective.
d. Initial conditions (if applicable).
e. Test equipment (if required).
f. Sequence of events.
g. Expected results.
3.6.3 Test Report
Submit a final, complete PVT test report, after completing the test, consisting of the following, as a minimum:
a. Section one of the submittal shall be a short summary of the performance verification test.
b. Section two of the submittal shall be a copy of the test plans.
c. Section three shall be the executed test procedure and shall be divided using tabs. Each tab section shall include all pertinent information pertaining to the executed and approved test, showing date and Government representative who witnessed/approved the test.
3.7 ENDURANCE TESTING
Section 25 08 10 Page 10
3.7.1 General
Endurance Test shall be designed to demonstrate the specified overall system reliability requirement of the completed system. Conduct the Endurance Test in four phases as described below. The Endurance Test shall not be started until the Government notifies the Contractor, in writing, that the
Performance Verification Tests have been satisfactorily completed, training as specified has been completed, correction of all outstanding deficiencies has been satisfactorily completed, and that the Contractor has permission to start the Endurance Test. Provide an operator to man the system eight hours per day during first shift operations, including weekends and holidays, during Phase I and Phase III Endurance testing, in addition to any Government personnel that may be made available. The Government may terminate testing at any time if the system fails to perform as specified. Upon termination of testing by the Government or by the Contractor, commence an assessment period as described for Phase II and Phase IV. Upon successful completion of the
Endurance Test, submit test reports to the Government explaining in detail the nature of any failures, corrective action taken, and results of tests performed, prior to acceptance of the system. Keep a record of the time and cause of each outage that takes place during the test period.
3.7.2 Phase I
During the Phase I testing, operate the system as specified for 24 hours per day, 7 days per week, for 15 consecutive calendar days, including holidays.
Do not make repairs during this phase of testing unless authorized by the
Government, in writing. If the system experiences no failures during the
Phase I test, proceed directly to Phase III testing, after receiving written permission from the Government.
3.7.3 Phase II
In Phase II, which occurs after the conclusion of Phase I, identify all failures, determine the causes of all failures, repair all failures, and submit a test failure report to the Government. After submitting the written report, convene a test review meeting at the job site to present the results and recommendations to the Government. The meeting shall be scheduled no earlier than five business days after receipt of the report by the
Government. As a part of this test review meeting, demonstrate that all failures have been corrected by performing appropriate Performance
Verification Tests. Based on the Contractor's report, the test review meeting, and the Contractor's recommendation, the Government will independently determine the restart point and may require that the Phase I test be totally or partially rerun. Do not commence any required retesting until after receipt of written notification by the Government.
3.7.4 Phase III
After the conclusion of any retesting which the Government may require, repeat the Phase II assessment as if Phase I had just been completed. If the retest is completed without any failures, proceed directly to Phase III testing, after receiving written permission from the Government. During
Phase III testing, operate the system as specified for 24 hours per day, 7 days per week, for 15 consecutive calendar days, including holidays. Do not make repairs during this phase of testing unless authorized by the
Government, in writing.
Section 25 08 10 Page 11
3.7.5 Phase IV
In Phase IV, which occurs after the conclusion of Phase III, identify all failures, determine the causes of all failures, repair all failures, and submit a test failure report to the Government. After submitting the written report, convene a test review meeting at the job site to present the results and recommendations to the Government. The meeting shall not be scheduled earlier than five business days after receipt of the report by the
Government. As a part of this test review meeting, demonstrate that all failures have been corrected by performing appropriate Performance
Verification Tests. Based on the Contractor's report, the test review meeting, and the Contractor's recommendation, the Government will independently determine the restart point and may require that the Phase III test be totally or partially rerun. Do not commence any required retesting until after receipt of written notification by the Government. After the conclusion of any retesting which the Government may require, the Phase IV assessment shall be repeated as if Phase III had just been completed. The
Contractor will not be held responsible for failures resulting from the following:
a. An outage of the main power supply in excess of the capability of any backup power source, provided that the automatic initiation of all backup sources was accomplished and that automatic shutdown and restart of the
UMCS performed as specified.
b. Failure of a Government-furnished communications link, provided that the
LON nodes and LON routers automatically and correctly operate in the stand-alone mode as specified, and that the failure was not due to contractor furnished equipment, installation, or software.
c. Failure of existing Government-owned equipment, provided that the failure was not due to contractor-furnished equipment, installation, or software.
3.7.6 Failure Reports
Provide UMCS Endurance Test Failure Reports. UMCS Test Failure Reports shall explain in detail the nature of each failure, corrective action taken, results of tests performed. If any failures occur during Phase I or Phase
III testing, recommend the point at which the Phase I or Phase III testing, as applicable, should be resumed.
3.8 ATTACHMENT A
Section 25 08 10 Page 12
TEST PROCEDURES
TITLE: Test Index
OBJECTIVE: The following is an index of tests.
NOTES: Tests one through twenty contain specific "item(s)" that apply to
Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC. The following index of tests provides a summary of which "items numbers" apply to which specification.
Test No. Test Title Section 23 09 00 DDC for HVAC
One Initial System Equipment
Verification
Items 1 through 8 Items 9 through 24
Two System Start-up Items 1 through 4 Items 5 and 6
Three Monitor and Control Software Items 1 through 5 Not Applicable
Four Graphic Display of Data Items 1 through 18 Not Applicable
Five Graphic Navigation Scheme Items 1 and 2 Not Applicable
Six Command Functions Items 1 through 6 Not Applicable
Seven Command Input Errors Items 1 through 6 Items 1 through 6
Eight Special Functions Item 1 Not Applicable
Nine Software Editing Tools Items 1 through 42 Items 1 through 42
Ten Scheduling Items 1 through 7 Items 8 through 10
Eleven Alarm function Items 1 through 15 item 16
Twelve Trending Items 1 through 8 Not Applicable
Thirteen Report Generation Items 1 through 6 Not Applicable
Fourteen CTA CTA-709.1-D to IP Router
Test
Items 1 through 3 Not Applicable
Fifteen CTA CTA-709.1-D Router and
Repeater
Not Applicable Items 1 through 4
Sixteen CTA CTA-709.1-D Gateway
Test
Items 1 through 5 Items 1 through 5
Seventeen Local Display Panel Not Applicable Items 1 through 5 file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx
Section 25 08 10 Page 13
Test No. Test Title Section 23 09 00 DDC for HVAC
Section 25 08 10 Page 14
PVT Checklist
OBJECTIVE:
1. Inspect/test/verify that building-level DDC system is compliant with
Section 23 09 00 and capable of integration with UMCS
INITIAL REQUIREMENTS/CONDITIONS
1. The following tests shall be completed and documentation shall be submitted to the Government.
2. Date of Checklist: __________
3. Time of Checklist: __________
4. Contractor's Representative: ____________________
5. Government's Representative: ____________________
CHECKLIST PROCEDURES
Expected
Item Action Item Results Approved
UMCS AND DDC FOR HVAC
1 Draft or Final Drawings submitted and
As-Built Drawings approved __________
Point schedule(s) showing all required UMCS SNVTs submitted __________
Point schedules(s) showing device network addresses
Local display panel (LDP) locations indicated on drawings submitted __________
Notes: _____________________________________________________________
2 Network Bandwidth Test Test completed, accepted, Report and a report documenting results submitted __________
3 Programming software Most recent version of the programming software for each type of GPPC has been file://coe-nannv001nyc.nan.ds.usace.army.mil/USERS/E3/e3enmazy/SPECSINTACT/Jobs/20180320BRADLEY6/prntdata/Word/23%2009%2000.docx
Section 25 08 10 Page 15
4 XIF Files External interface files (XIF) files for each model of
LONWORKS®-based DDC hardware has been submitted __________
5 Start-up testing report Start-up has been successfully completed and testing report
Controller tuning has been completed and document on point schedule __________
Calibration accuracy check completed and documented in test report __________
Actuator range check
Functional test to demonstrate control sequence
6 Software License Software licenses received for all software on the project __________
End of Test
Specific Abbreviations:
Y = Yes
N = No
NA = Not Applicable
Section 25 08 10 Page 16
TEST NUMBER: One
TITLE: Initial System Equipment Verification
1. To verify that the hardware and software components of the system provided by the Contractor are in accordance with the contract plans and specifications and all approved submittals.
1. Submittals
a. Submit a detailed list of all approved hardware with Manufacturer, model number and location. This list is based on the contract plans, specifications, change orders (if any) and approved submittals which shall be available for reference purposes during the test.
b. Submit a detailed list of all approved software with revision number and purpose of software. This list is based on the contract plans, specifications, change orders (if any) and approved submittals which shall be available for reference purposes during the test.
2. Equipment
a. Verify all equipment is functional.
3. Reference Documentation
a. List user manual documentation and sections pertaining to the testing.
4. Date of Test: __________
5. Time of Test: __________
6. Contractor's Representative: ____________________
7. Government's Representative: ____________________
UMCS
1 The workstation hardware is installed and complies with specification paragraph titled "Workstation Hardware". ________________ __________
2 The Server hardware is installed and complies with specification paragraph titled "Server
Hardware". ________________ __________
Section 25 08 10 Page 17
3 The fiber optic patch panel is installed and complies with specification paragraph titled
"Fiber Optic Patch Panel". ________________ __________
4 The fiber optic media converter is installed and complies with
"Fiber Optic Media Converter". ________________ __________
5 The Ethernet switch is installed paragraph titled "Ethernet
Switch". ________________ __________
6 The IP router is installed and complies with specification paragraph titled "IP Router". ________________ __________
7 The CTA CTA-709.1-D to IP router is specification paragraph titled
"CTA CTA-709.1-D to IP Router". ________________
8 The CTA CTA-709.1-D gateway is specification paragraph titled
"CTA CTA-709.1-D Gateway". ________________
Section 25 08 10 Page 18
DDC FOR HVAC
9 The CTA CTA-709.1-D Router is installed and complies with specification paragraph titled "CTA CTA-709.1-D
Router". ________________ __________
10 The CTA CTA-709.3 Repeater is installed paragraph titled "CTA CTA-709.3
Repeater". ________________ __________
11 The TP/FT-10 network is installed in accordance with CTA CTA-709.3, with double-terminated bus topology. ________________ __________
12 Network wiring extends to the location of UMCS BPOC. ________________ __________
13 The Gateway is installed and complies with specification paragraph titled "Gateway". ________________ __________
14 All control valves are installed and comply with their associated specification paragraph under the section titled "Control Valves". ________________ __________
15 All dampers are installed and
Section 25 08 10 Page 19 comply with their associated section titled "Dampers". ________________ __________
16 All sensors are installed and comply with their associated section titled "Sensors". ________________ __________
17 All indicating devices are installed and comply with their associated specification paragraph under the section titled "Indicating Devices". ________________ __________
18 All user input devices are associated specification paragraph under the section titled "User
Input Devices". ________________ __________
19 All output devices are installed and comply with their associated section titled "Output Devices". ________________ __________
20 All multifunction devices are associated specification paragraph under the section titled
"Multifunction Devices". ________________ __________
21 All compressed air equipment is
Section 25 08 10 Page 20 installed and complies with their associated specification paragraph under the section titled
"Compressed Air". ________________ __________
22 All ASCs are installed and comply with the specification paragraph titled "Application Specific
Controller". ________________ __________
23 All LDPs and laptop computers are provided and comply with the
"Local Display Panel". ________________ __________
24 All GPPCs are installed and comply with the specification paragraph titled "General Purpose
Programmable Controller". ________________ __________
Section 25 08 10 Page 21
TEST NUMBER: Two
TITLE: System Start-up
1. To validate that the system properly initializes and that the GUI properly reconnects to all communicating devices.
2. To validate that both application specific and programmable devices retain all vital information upon a power cycle.
a. Provide a list of all software that will be used to verify point connection at field level controllers and user interface.
b. Provide a list of all software need to verify application specific and programmable controller start-up.
a. All peripherals and cables shall be connected in accordance with manufacturer's requirements.
b. The workstation shall be in the off mode.
c. All controls shall be fully functional and tested.
d. A programmable and application specific controller shall be randomly selected for the test.
3. Date of Test: __________
4. Time of Test: __________
5. Contractor's Representative: ____________________
6. Government's Representative: ____________________
1 Energize the workstation. The workstation will power-up and perform its start-up procedure without generating any errors or problems. __________
a) Operating system Operating system shall be latest version of windows. __________
b) Start Network The Network Configuration
Configuration Tool. Tool drawing will open. __________
c) Start the System The System plug-in will
Plug-in. open. __________
d) Start the Server. The Server will start. __________
e) Start the Workstation. The Workstation will start.
Section 25 08 10 Page 22
The operator shall now have the ability to view data from any device on the network. __________
2 Check the communication Within the workstation from the server to the software, when a device is controllers. selected, dynamic points lists become visible.
Dynamic data represents success. A completion event failure message represents failure. __________
3 Verify on-line status. All devices shall have on-line status indicated by the workstation software
(green indicator). __________
4 View data from the When a graphics page is graphical environment. opened, the points on the page should update.
Question marks in lieu of data reflect failure. __________
DDC FOR HVAC
5 Verify that configuration All configuration data in application parameters should be specific controllers is accessible. __________ written to EEPROM.
a) Open the LONWORKS® Software should open plug-in. without errors. __________
b) Note several Operator is able to view parameters such as a sample of parameters temperature setpoints (data values and setpoints).
and flow settings. __________
c) Remove power from the Device should go off-line controller for a in Network Configuration minimum of 3 minutes. Tool and workstation/server. __________
d) Replace power to the Device should return to controller. on-line status. __________
Section 25 08 10 Page 23
e) Using the plug-in, Parameters shall not have verify that the changed.
parameters have not __________ changes.
6 Verify that configuration data in programmable controllers is retained after a power cycle. ________________ __________
a) From the Workstation Values of the parameters view several can be viewed from the configuration tree structure.
parameters and note the values. __________
b) Remove power for a Controller will go offline minimum of 3 minutes. in workstation software. __________
c) Replace power to the Controller will return to controller. online status. __________
d) From the Workstation Parameters values shall view the same not have changed.
configuration parameters and note the values. __________
Section 25 08 10 Page 24
TEST NUMBER: Three
TITLE: Monitor and Control (M&C) Software Passwords
1. To validate that the system utilizes four basic password levels
2. To validate that each password level has the specified authority
a. Provide documentation of M&C user password capacity in comparison with specification.
b. Provide a complete list of all users along with their passwords and user level prior to testing.
a. Server and Workstation
a. Provide user manual documentation for setting up passwords
1 Create password for new New users shall exist in users. the server Database. __________
a) Set-up 4 users. ________________ __________
b) Assign different levels to each. ________________ __________
2 Demonstrate level 1 authority. ________________ __________
a) Sign in as the level 1 Sign in shall be user. successful. __________
b) Attempt to view a Action shall be possible.
system graphic. __________
c) Attempt to acknowledge Action shall be denied.
an alarm. __________
d) Attempt to configure a Action shall be denied.
Section 25 08 10 Page 25 trend. __________
e) Attempt to configure a Action shall be denied.
report. __________
f) Attempt to override a Action shall be denied.
point. __________
g) Attempt to configure an Action shall be denied.
alarm. __________
h) Attempt to configure a Action shall be denied.
schedule. __________
i) Attempt to configure a Action shall be denied.
demand limiting parameter. __________
j) Attempt to modify a Action shall be denied.
graphic page. __________
k) Attempt to create a Action shall be denied.
custom program. __________
3 Demonstrate level 2 ________________ __________ authority.
a) Sign in as the level 2 Sign in shall be successful.
user. __________
b) Attempt to view a Action shall be possible.
system graphic. __________
c) Attempt to acknowledge Action shall be possible.
an alarm. __________
d) Attempt to configure a Action shall be possible.
trend. __________
e) Attempt to configure a Action shall be possible.
report. __________
f) Attempt to override a Action shall be denied.
point. __________
g) Attempt to configure an Action shall be denied.
alarm. __________
h) Attempt to configure a Action shall be denied.
schedule. __________
i) Attempt to configure a Action shall be denied.
demand limiting parameter. __________
j) Attempt to modify a Action shall be denied.
graphic page. __________
4 Demonstrate level 3
a) Sign in as the level 3 Sign in shall be user. successful. __________
b) Attempt to view a Action shall be possible.
system graphic. __________
Section 25 08 10 Page 26
c) Attempt to acknowledge Action shall be possible.
an alarm. __________
d) Attempt to configure a Action shall be possible.
trend. __________
e) Attempt to configure a Action shall be possible.
report. __________
f) Attempt to override a Action shall be possible.
point. __________
g) Attempt to configure an Action shall be possible.
alarm. __________
h) Attempt to configure a Action shall be possible.
schedule. __________
i) Attempt to configure a Action shall be possible.
demand limiting parameter. __________
j) Attempt to modify a Action shall be denied.
graphic page. __________
5 Demonstrate level 4
a) Sign in as the level 3 Sign in shall be user. successful. __________
b) Attempt to view a Action shall be possible.
system graphic. __________
c) Attempt to acknowledge Action shall be possible.
an alarm. __________
d) Attempt to configure a Action shall be possible.
trend. __________
e) Attempt to configure a Action shall be possible.
report. __________
f) Attempt to override a Action shall be possible.
point. __________
g) Attempt to configure an Action shall be possible.
alarm. __________
h) Attempt to configure a Action shall be possible.
schedule. __________
i) Attempt to configure a Action shall be possible.
demand limiting parameter. __________
j) Attempt to modify a Action shall be possible.
graphic page program. __________
k) Attempt to create a Action shall be possible.
Section 25 08 10 Page 27
Section 25 08 10 Page 28
TEST NUMBER: Four
TITLE: Graphic Display of Data
1. To validate that floor plans and equipment can be graphically displayed through GUI.
2. To validate the proper display of alarms on GUI.
3. To validate the proper display of trend data on GUI.
a. Provide hard copies of "snap shots" of sample graphics pages prior to testing.
a. Complete all graphics.
4. Notes
a. Different types of data and states should be clearly distinguishable from each other.
5. Date of Test: __________
6. Time of Test: __________
7. Contractor's Representative: ____________________
8. Government's Representative: ____________________
Item Action Item Results Approved
1 Demonstrate the use of a Equipment shall be three dimensional represented in a three representation of a dimensional manner.
mechanical system. __________
2 Demonstrate the Dynamic real time data presentation of real time shall be presented on a data. graphics page. __________
Section 25 08 10 Page 29
3 Demonstrate the A user defined parameter presentation of user such as a setpoint shall be entered data. presented on a graphics page.
Different types of data and states should be clearly distinguishable from each other. __________
4 Demonstrate the An indication of override presentation of a point condition shall be viewable in override. on the graphic page.
Different types of data and states should be clearly distinguishable from each other. __________
5 Demonstrate the An indication of the alarm presentation of a device state shall be viewable on in the alarm state. the graphic page. Different types of data and states should be clearly
6 Demonstrate the An indication of out of range presentation of data that condition shall be viewable is out of range. on the graphic page.
Different types of data and states should be clearly
7 Demonstrate the An indication of missing data presentation of missing shall be viewable on the data (controller is graphic page. Different offline). types of data and states should be clearly distinguishable from each
Section 25 08 10 Page 30
8 Demonstrate an error An error message shall be message when the operator displayed.
attempts to execute in improper command. __________
9 Demonstrate point and click Operator shall be able to access to context sensitive easily access context help. sensitive help using the mouse. __________
10 Demonstrate point and click Operator shall be able to access to an engineering access an engineering diagram. diagram using the mouse. __________
11 Demonstrate the creation of Operator shall be able to an engineering diagram. create an engineering diagram. __________
12 Demonstrate the printing of Operator shall be able to a prepared report. print a report using the mouse. __________
13 Demonstrate the display of Operator shall be able to one or more points. request the display of one or more points. __________
14 Demonstrate the operator Operator shall be able to override of a point. override a point. __________
Section 25 08 10 Page 31
15 Demonstrate the Operator shall be able to modification of a modify a time schedule.
time schedule. __________
16 Demonstrate the execution Operator shall be able to of a report. initiate a report. __________
17 Demonstrate the Operator shall be able to presentation of an view an alarm with all of alarm to include: the required data. __________
a) Identification ________________ __________
b) Date and time ________________ __________
c) Alarm Type ________________ __________
d) Set Points ________________ __________
e) Units ________________ __________
f) Current Value ________________ __________
g) Priority ________________ __________
h) Associated message &
Secondary message ________________ __________
18 Demonstrate the Operator shall be able to presentation of view real time trend data real time trend data. as a function of time. __________
Section 25 08 10 Page 32
TEST NUMBER: Five
TITLE: Graphic Navigation Scheme
1. To validate hierarchical graphic displays from main screen to end devices.
a. Provide a hierarchical block diagram of the system network prior to
a. Have all programming completed to demonstrate graphic display.
1 Demonstrate the creation Operator shall be able to of a hierarchical tree organize point data graphic structure for the display in a hierarchical presentation of point tree structure based on any data with at least five organization desired.
levels.
A typical organization could be:
- Installation
- Building
- Building sub area
- Main System-Unit
- Terminal Unit __________
2 Demonstrate the creation Operator shall be able or of a hierarchical organize the graphical navigation structure for navigation from page to
Section 25 08 10 Page 33 the graphic pages. page using any hierarchical structure desired.
Examples:
Home page to building 1
Building 1 to AHU 1
Building 1 back to Home Page
Building 1 to 1st Floor Plan
AHU 1 back to Building 1
AHU 1 back to Home Page
AHU 1 to Terminal Unit
Summary
1st Floor Plan back to
Building 1
1st Floor Plan back to
Home Page
1st Floor Plan to Any
Terminal Device
Terminal Unit Summary back to AHU 1
Terminal Unit Summary back to Building 1
Terminal Unit Summary back to Home Page
Terminal Unit Summary to
Individual Device __________
Section 25 08 10 Page 34
TEST NUMBER: Six
TITLE: Command Functions
1. To demonstrate the functionality and ability to execute command to the end devices.
a. Provide documentation of all command functions prior to testing.
a. Have all command functions programmed and functional.
1 From the tree structure, The modified value shall be modify a parameter such as downloaded to the controller a set point. without delay and the controller performance shall be viewable by the monitoring of other dynamic points. __________
2 From a graphic page, modify The modified value shall be a parameter such as a set downloaded to the controller point. without delay and the controller performance shall be viewable by the monitoring of dynamic points. __________
Section 25 08 10 Page 35
3 From the tree structure, The analog output point place an analog output shall accept the assigned point under operator value and ignore changes override and assign a from application logic until fixed value. the point is taken out of override. __________
4 From a graphic page, place The analog output point shall an analog output point accept the assigned value and under operator override ignore changes from and assign a fixed value. application logic until the point is taken out of override. __________
5 From the tree structure, The digital output point shall place a digital output accept the assigned value and point under operator ignore changes from application override and assign a logic until the point is taken fixed value. out of override. __________
6 From a graphic page, place The digital output point shall a digital output point accept the assigned value and under operator override ignore changes from application and assign a fixed value. logic until the point is taken out of override. __________
Section 25 08 10 Page 36
TEST NUMBER: Seven
TITLE: Command Input Errors
1. To validate that the system ensures the necessary authority for command inputs
2. To validate that the system can control the range of command input values
a. Provide all command input error messages prior to testing.
a. UMCS and DDC hardware and software
1 Login using a password Login occurs. __________ with point command.
2 Request a display of a The system displays the
SNVT. controllers SNVT value. __________
3 Override the SNVT point The SNVT value override to a selected value. changes the value in the controller. __________
Section 25 08 10 Page 37
4 Release the override of The SNVT value returns to a SNVT. normal. __________
5 For an nvi to a The value will go the controller with a limit of maximum of 80.
50 to 80, command the nvi to a value of 90. __________
6 For an nvi to a The operator will be denied controller for which the the ability to command the operator only has read nvi to any value.
privileges, command the nvi to a value of 90. __________
Section 25 08 10 Page 38
TEST NUMBER: Eight
TITLE: Special Functions
1. Verify system has special integration as defined.
a. Provide documentation of all integrations prior to testing.
a. Have all UMCS and DDC hardware and software programmed, integrated, and completed.
1 Verify that a building Data from the other vendors that uses controls from a controllers shall be integrated vendor other than the one into the GUI and the same being installed can be functionality that would exist integrated into the GUI if the controllers were from without any loss of the same manufacture shall functionality. exist.
(A simulated building will be set up using an IP-L router and controllers from
Honeywell, TAC, Trane, etc.) __________
Section 25 08 10 Page 39
Section 25 08 10 Page 40
TEST NUMBER: Nine
TITLE: Software editing tools
1. To validate the performance of the M & C application programming tool for the GPPC.
2. To validate the performance of the display editing tool.
3. To validate the performance of the report generation display tool.
a. Provide documentation and a backup softcopy of the editing tool prior to testing.
b. Provide documentation of any future software upgrade versions that pertain to the software-editing tool.
a. Have working knowledge of the full capability of the software-editing tool.
UMCS and DDC for HVAC
1 Demonstrate the Operator shall be able to programming of an override use the programmed function function in a GPPC. to override an output point in a GPPC. __________
2 Demonstrate software that Operator shall be able to enables the monitoring of monitor points from a GPPC.
data from a GPPC. __________
Section 25 08 10 Page 41
3 Demonstrate timer Control logic shall honor functions within the built in timers.
applications of GPPC. __________
a) delay on ________________ __________
b) delay off ________________…