Renovation and Modernization of Bradley Barracks, West Point, New York
Solicitation number
W912DS19B0008
Issued by

About this file

Amendment 0005

View the file

Other files

File Type Posted
Bid_Abstract.pdf PDF
W912DS19B0008-0009.pdf PDF
Amendment_0008.pdf PDF
Amendment_0008_28_50_00_Emergency_Radio_Communicaiton_Enhanced_System.pdf PDF
Amendment_0007_Q22_RFI_8134159.pdf PDF
Amendment_0007.pdf PDF
Amendment_0007_Q8_Geotechnical_Report_Bradley_Barracks.pdf PDF
Amendment_0007_Q21_Tube_Bundle_Sizing_Form.pdf PDF
Amendment_0007_Q16_corian_lav_810p_RFI_8137732.pdf PDF
Amendment_0006.pdf PDF
W912DS19B0008-Amendment_00004.pdf PDF
Site_Visit_Sign_In_Sheet.pdf PDF
Specs_Book_1_of_4_v1.pdf PDF
Specs_Book_4_of_4_v1.pdf PDF
Specs_Book_2_of_4_v1.pdf PDF
Specs_Book_3_of_4_v1.pdf PDF
Amendment_0003.pdf PDF
Amendment_0001.pdf PDF
Amendment_0002.pdf PDF
W912DS-19-B-0008_Solicitation.pdf PDF
W912DS-19-B-0008_Specs_Book_4_of_4.pdf PDF
W912DS-19-B-0008_Specs_Book_3_of_4.pdf PDF
W912DS-19-B-0008_Drawings_-_Volume_4_of_5.pdf PDF
W912DS-19-B-0008_Drawings_-_Volume_5_of_5.pdf PDF
W912DS-19-B-0008_Specs_Book_1_of_4.pdf PDF
W912DS-19-B-0008_Drawings_-_Volume_3_of_5.pdf PDF
W912DS-19-B-0008_Specs_Book_2_of_4.pdf PDF
W912DS-19-B-0008_Drawings_-_Volume_1_of_5_v1.pdf PDF
W912DS-19-B-0008_Drawings_-_Volume_2_of_5.pdf PDF
Bradley_Barracks_West_Point_Security_Manifest.xlsx XLSX spreadsheet
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

The purpose of Amendment 0005 is:

1) Bid opening date remains 27 August 2019 at 2:00 P.M. EST (Room 16-300)

2) Answ er questions for Informational puposes only.

3) Please see continuation page.

NOTE: Bidders must acknow ledge receipt of this amendment by date specified in the bid (or as amended) by one of the follow ing methods: In the space provided on the SF 1442, by separate letter, or by signing block 15 below . FAILURE TO ACKNOWLEDGE AMENDMENT BY DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR BID IN ACCORDANCE WITH THE LATE BID, LATE MODIFICATION OF BID, OR LATE WITHDRAWAL OF BID (FAR 14.304)

1. CONTRACT ID CODE PAGE OF PAGES

J 1 3

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 16-Aug-2019

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912DS19B0008

X 9B. DATED (SEE ITEM 11)

12-Jul-2019

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

16-Aug-2019

CODE

US ARMY CORPS OF ENGINEERS, NEW YORK

26 FEDERAL PLAZA, RM 16-300

NEW YORK NY 10278-0090

W912DS 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912DS19B0008

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)

The following have been added by full text:

AMENDMENT 0005

TO BIDDERS:

The following changes shall be made to the drawings and specifications.

DRAWINGS:

1. The following DRAWINGS have been REVISED and REISSUED:

a. None

2. The following DRAWINGS have been REVISED but NOT REISSUED:

a. S-113

i. Key note indicator located between Column lines (15,16) & (Ca,Ea) shall be changed from a Key Note 01 “FILL EXISTING SLAB CRACKS WITH EPOXY” indicator to Key Note 10 “CORE DRILL AND SAWCUT CONCRETE SLAB OPENINGS” indicator.

3. The following DRAWINGS have been ADDED:

4. The following DRAWINGS have been DELETED:

SPECIFICATIONS:

1. The following SPECIFICATION SECTIONS have been ADDED and are provided in their entirety herein:

2. The following SPECIFICATIONS SECTIONS have been DELETED in their entirety:

3. The following SPECIFICATIONS SECTIONS have been REVISED and REISSUED:

4. The following SPECIFICATIONS have been REVISED but NOT REISSUED:

W912DS19B0008

(End of Summary of Changes)

(Questions that may be of general interest to all Offerors and/or the Government and that are not readily answered by the proceeding changes will appear below. These questions may have been paraphrased or altered to represent several questions regarding the same subject and/or simply revised to clarify and simplify the question(s). Questions and answers are issued to the Offerors "for information only" and do not revise the solicitation, plans or specifications.)

Question 1: 1.) Please provide size for shelving unit type 4. None provided

2.) Please reference attached drawing A-100 bubble. The schedule lists quantities and various shelving.

Please provide weight capacities for shelf per each unit type.

3.) Please confirm width sizes of all shelving unit types. The drawings indicate custom sizes however, the specification only lists one standard size. Typically shelving widths come in standard 3',4',5' etc widths.

4.) Please advise for each shelving type how many shelf levels are required and do they require a top cover

Answer 1: 1. Shelving racks SS3 "Open Shelves - Type 4" in the small bathroom closets on all floors that are scheduled as standard sized units. See BOD attached:

a. (ULINE Epoxy Coated Wire Bathroom Storage Shelving: Metal Wire 36"W X 18"D X 72"H w/ 4 Adjustable Shelves)"

2. The Cadet trunk room trunk shelves SS1 "Open Shelves – Type 2" are detailed on A-704 and are sized to hold a specific number of government-issued trunks with extra reinforcement (example:

welded braces and front and back rails), the width is 76". Previous barracks utilized "LYON" manufactured shelving that matched the configuration called for on A-704 and in the shelving spec.

See attached picture of unit in MacArthur Long Barracks trunk room.

SS-2: This is the 'Janitor Supply Suite" shelf and is 5' wide standard unit See BOD attached:

(ULINE Epoxy Coated Wire Bathroom Storage Shelving: Metal Wire 60"W X 24"D X 72"H w/ 4 Adjustable Shelves)"

TA-50: This is the cadet storage locker and is detailed on A7/A-704 and described in detail in the associated spec section for metal lockers. It has one fixed shelf and a hanging rod, see detail and spec for additional information.

Question 2: Detail 1, 2 & 3 on Dwg. S-302 show that only 6 each, #4 dowels will be installed in to the slab underside for each shear capital. Please clarify the spacing on the dowels or confirm that only 6 dowels are required per shear capital location.

Answer 2: Only 6 dowels are required per shear capital location. The spacing will vary slightly as the shear capital is proportional to the column size, but controlling dimensions are provided.

Question 3: Please confirm that the government will provide all the CADD files to the contractor

Answer 3: Yes, the Government will provide all CADD files after contract award.

Question 4: What is the Blast design pressure and standoff distance requirement for the exterior windows?

Answer 4: In accordance with the latest version of UFC 4-010-01, blast pressure and standoff distance is not applicable. The UFC requires no less than ¼" nominal polycarbonate or laminated glass consisting of two- 1/8" glass panes bonded together with a minimum of 0.030 pvb. For insulated glass units, use the polycarbonate or laminated glass for the innermost pane as a minimum. For laminated glass, provide a glazing bite in accordance with ASTM F2248. For polycarbonate, provide a glazing bite of no less than 1.5 time the polycarbonate thickness. Please refer to specification 08 81 00 for specific glazing make-up & additional requirements.

Question 5: 1. Basement electrical room appears to show a panel labeled GB, nothing is shown on the one line nor the panel schedule, can you confirm what this is?

2. Confirm that all PVC underground is to be SCH80 and not SCH40?

3. Where is panel EP1 located, nothing is indicated on the floor plans?

4. Feeder size and routing not shown on site plan for exterior lighting, please provide size of conduit and conductors allowed in each conduit?

5. Power to holding tank fan and alarm ABB-1, where is this being fed from, nothing is shown on riser nor ES-100 plans?

6. ALTERNATE #3 ES-101 where is this being fed from, what panel?

7. SKI Lodge scope of work on ES-101, we need to know the manufacturer of that panel in order to get a quote for the 150A breaker that will fit in that panel? Please provide specs for breaker required?

8. Confirm that the service disconnect #2 will be provided by the water booster station vendor, we do not have specs to price it our ourselves, we assume it will be provide with booster unit?

9. Panel DABA missing panel schedule, please provide so we can correctly quote?

Answer 5: This is for the USMA GCH project which has been previously answered and does not apply to Bradley Barracks.

Question 6: Light Fixture Restoration:

1.) What are the Approx. sizes of the two fixtures types to be refurbished.

2)Re-lamping – We noticed the sconces have an LED retro-fit bulb, was the ballast bi-passed?

3)Please advise as to whether re-lamping should be done with an integral LED source. Is that what's required or will a socket for an LED retro-fit bulb suffice?

Answer 6: 1. Attached are photographs of the fixtures to be refurbished, Contactor is responsible for visiting in the site and confirming all existing conditions.

2. Either lamping method is acceptable so that the fixture maintains the same look and quality of light output. Illumination must be consistent across all surface without shadowing.

Question 7: Per Key Note Legend, items are identified on the elevation drawing for repair locations.

Items #10 and #14 are indicated to cover the entire elevation for 100% of all elevations from drawings A- 201 through A-208. However these same Key Notes are also identified on specific locations on other drawings. Given the nature of these Key work codes (#10 & #14 --Sound, Remove and Reinstall deficient stone units) please advise if it is the intent to have the contractor cover 100% of these elevations or only the specific locations within the elevation notes.

Answer 7: Where 10 and 14 are called out specifically are the areas observed with visible stone unit damage requiring repair.

10 and 14 are generally called out on all masonry façade surfaces to cover stones requiring repair which are not visually evident from a distance, or without sounding.

Question 8: Specification section 004500 is referenced as part of the contract documents and a deliverable that needs to be submitted with the bid. No Specification section 004500 was issued. Please issue.

Answer 8: Section 00 45 00 - Presentations and Certifications, is located in the solicitation.

Question 9: Re. spec section 270528.36 40

1.) Is ladder rack or basket tray required in the telecom closets?

2.) Do you require aluminum or steel?

3.) What is the rung spacing required? (6" 9" 12" 18")

4.) What is the radius of fitting? (12" 18" 24" 36" 48")

5.) Is the ladder tray used for power or data?

6.) What is the NEMA rating?

7.) Does 2" refer to rail height or load depth?

Answer 9:

1. Per symbol legend on sheet T-001 cable runway shall be installed in the telecom rooms by the telecom contractor. See T-400 sheets for locations.

2. Per specification section 27 05 28.36.40, paragraph 2.4 cable runway can be constructed of aluminum or steel.

3. See revised spec section 27 05 28.36 40, paragraph 2.1 for rung spacing.

4. See revised spec section 27 05 28.36 40, paragraph 2.1 for radius of fittings.

5. The cable runway is noted in the "Cable Trays for Communications Systems" specifications and the cable runway is noted and shown on the telecom drawings so it is data.

6. NEMA VE 1 per the specifications, typically cable runways do not carry a NEMA requirement.

7. The basket type cable trays shown on the floor plans are 8" wide by 2" high..

Question 10: At the cadet Room Sinks (D1/A-411 & C8/A-702) a heavy-duty towel rack is called out for both sides of the unit.

Is there a call out for the manufacture and model number or will this be a custom metal piece? What is the intended finish?

Answer 10: The heavy duty towel bar is called out as toilet accessory TA-19. The basis of design manufacturer and model number is Bradley, washroom accessory 9065. Per specification 10 28 13 - 2.2.9, the finish shall be satin stainless steel. See cut sheet attached.

Question 11: Drawing S-113 First Floor Plan Part C. Column lines (15,16) & (Ca,Ea) indicate new slab opening (detail 2/S-301). STRUCTURAL SCOPE ITEMS note 01 (fill existing slab cracks with epoxy) is indicated at this same location. Please advise as to what the work scope should be at this location..

Answer 11: Key note as this location is incorrect and should be 10 "CORE DRILL AND SAWCUT

CONCRETE SLAB OPENINGS"

Question 12: Re. C505 C505/1, Please clarify if the temp chain link fence is required to be vinyl coated (per drawing detail notes) or powder coated (per note 1)?

Answer 12: The temporary chain link construction fence and associated components are to be black vinyl coated.

Question 13: Re. C002, Drainage & Utility Notes; Note 25: Please clarify if these frame & grate/cover allowances listed are to include labor to install or if they are only attic stock allowances for material only.

Answer 13: New frames/grates/covers shall be provided on all utilities being reset to grade, as indicated on sheet CU101 of the contract drawings. The quantities listed in Note #25 are additional as required and as directed by the contracting officer. All labor and material as required to properly install each new frame and cover must be included.

Question 14: Re. C002, Drainage & Utility Notes; Note 25: If these material allowances are to include installation, please confirm that no other work is required to be performed outside of demo of existing frame & grate/covers, furnish new frame & grate/covers, and install new frame & grate/covers only..

Answer 14: Correct. No other work it anticipated.

Question 15: As no drainage/sanitary structure schedule is provided, please confirm that all drainage and sanitary structures (catch basins & manholes) are ETR with exception to one drainage manhole noted as "Construct New Manhole" which is located West of the Sally Port.

Answer 15: All drainage/sanitary structurers are ETR (Existing to Remain) with the exception to the following structures:

• (1) New storm inlet type yard 2

• (3) New storm inlet type yard 1

• New storm inlet CB1486J29A

• New storm inlet CB1486J29B

• New storm inlet CB1434J29A

• New storm manhole DMH143I29A.

Question 16: Please designate what type of pipe is required for the:

a) 6" & 8" sanitary service lateral just East of the Sally Port & Bradley Short and,

b) 10" and 12" Storm Leader just East of the Sally Port & Bradley..

Answer 16: The 6" and 8" sanitary service laterals shall be replaced with SDR 35 PVC pipe. B:

The 10" and 12" storm leaders shall be replaced with ductile iron pipe.

Question 17: Sheet Key Note 9: Note 9 designation requires four (4) charge stations to be provided and references the electrical drawings for more information. The electrical drawings contain no information nor show any power supplied to these charge station locations. Please advise as to what scope is required under this contract pertaining to the vehicle charge stations (manufacturers, models, details, power requirements, etc.).

Answer 17: Charging stations are incorporated into fixture type M1 and are indicated on drawing EL-113. There are two locations each with two charging receptacles.

Question 18: Re. CU101, LEGEND Note RH: Please identify/describe the scope of work and provide quantities for the (RH) designation that appears to be a rehabilitation of the existing buried manholes and catch basins.

Answer 18: Perform work in accordance with specifications (33 30 00 – 2.3.1 & 3.2.5.1). Quantities of manholes / catch basins are designated on the plans.

Question 19: Re. CU101, LEGEND Note RH: Please advise what spec section pertains to the spray on polymer liner work required for the (RH) designation

Answer 19: The pertinent Spec sections pertaining to spray on polymer liner work are 33 30 00 – Sanitary Sewerage 2.3.1 & 3.2.5.1.

Question 20: Re. CU101, LEGEND Note RH: Please provide quantities or provide the ID dimensions of the existing catch basin/manhole structures scheduled to receive a spray on polymer liner weredegination (RH) is required.

Answer 20: Quantities of manholes / catch basins are designated on the plans. Structure sizes can be found in the Sewer Inspection Report. Please note, some information in the Sewer Inspection Report may not apply as it includes sanitary and drainage systems for multiple barracks.

Question 21: Can you please provide a quantity breakdown for cracks that need to be gravity fed vs injected? There is a significant price difference between the gravity fed and injected crack repairs which can affect the overall bid pricing significantly given the bid quantity of 30,000 lf plus 2 options of 5,000 lf each. In addition, determination of approximate quantities during the pre-bid walk through is not possible as the existing finishes are not removed yet.

Answer 21: For bidding purposes, 1/2 (50%) of the cracks should be assumed to gravity-fed while 1/2 (50%) should be injected crack repairs. This applies to both the main bid quantity and the 2 options. As indicated, in the question, as injection epoxy is more expensive than gravity fed, the contractor should be willing to transfer percentage from injection epoxy toward gravity-fed epoxy repairs at no cost to the Owner.

Question 22: Dwg S-002, Concrete Repair Notes – C.1 states that minimum crack repair width should be 0.03" or larger for gravity fed or injected epoxy crack repairs. However, on Dwg. S-303 under the Pressure Injection Repair Notes it states that all cracks greater than 0.03" shall be repaired by epoxy injection procedure. Please clarify or provide quantities for the gravity fed and epoxy injected crack repair types.

Answer 22: Only cracks greater than .03" should be repaired regardless of the procedure. The delineation of between gravity and injection crack repair will be determined by the product manufacture literature and recommendations and its appropriateness to the cracks found during construction as well as the engineer's opinion to the appropriateness of the repair procedure. See Question #21 for a breakdown of bid quantities of gravity vs injection epoxy.

Question 23: Please clarify if the slab crack repair (gravity fed or injected) is required only below the width/length of the FRP system (over a crack), or for the full length of cracks (also outside the FRP system).

Answer 23: Slab crack repair is independent although not necessarily unique from the FRP repair.

Crack repairs will be field directed to address structural cracking as appropriate. FRP may be used in conjunction with, or without crack repair based upon field conditions. It is likely that crack repair will occur in areas outside the FRP strengthening.

Question 24: Dwg. S-002, Concrete Repair Notes - Note E, item (5) calls for "UNI-DIRECTIONAL SHEETS WITH STRENGTH EQUIVALENCY OF A #4 AT 12" OC." However, on Dwg. S-401 FRP Quantities Notes - Note 2.C item (a) calls for "THE DELEGATED DESIGNER SHOULD DESIGN

UNI-DIRECTION OR BI-DIRECTIONAL FRP AS PROPER FOR THE TYPE OF REPAIR. AS AN

ESTIMATION, #5's AT 12" OC MAY BE USED FOR BIDDING PURPOSES". "MAY" indicates that either option can be used. Please clarify if #4@12" or #5@12" O.C. should be considered for design and cost estimate of FRP strengthening.

Answer 24: Strength should be based on the notes found on S-401 and that strength varies based upon the application. To clarify, the #5's at 12" OC should be used for estimation for general flexural reinforcement although the actual reinforcement required may vary. Reinforcement at any strength equivalent to or less than #5 at 12" OC would be included in the price.

Question 25: S-401, There are areas around new slab openings where the bidirectional FRP cannot be overlapped due to existing columns located close to the edge of openings (such as gridline "R" and "27a" on Sheet S-401). Please confirm that FRP can be stopped at the face of columns. Otherwise, provide the termination requirements for FRP.

Answer 25: Yes, the FRP can be terminated at the face of the column. Small elevation changes (less than 3") should continue wrapped up and over, and be completed using manufacturer requirements for smoothing the transition in elevation.

Question 26: FRP Quantities Note - Note 1 on Sheet S-401, says that "AREAS SHOWN ON FRP

PLANS (S-401 THROUGH S-408) ARE MANDATORY LOCATIONS OF INSTALLATION AND

ARE NOT INCLUDED IN THE QUANTITIES SHOWN BELOW. IT IS THE GC's RESPONSIBILITY TO TAKE OFF AND ESTIMATE FRP REINFORCEMENT SHOWN IN PLANS." However, detail 2/S301 and notes for FRP around openings, calls for #5@12" O.C. Please clarify if full coverage with FRP is required at these areas, or if design based on #5@12 is acceptable (partial or full coverage).

Answer 26: FRP around openings is designed to be full coverage for a distance of 1'-6" around the opening. This is shown in the S-40X series of plans graphically. That 1'-6" wide FRP should be designed to an equivalent strength of #5 @ 12" OC. Please note that per the S-40X series, this FRP is bi-directional meaning the equivalent strength needs to be met in both directions..

Question 27: Drawing S-401, FRP Quantities Notes - Note 2.C Item (b), states that "CONTRACTOR

SHOULD PRICE 20,000 SF OF FLEXURAL FRP REINFORCEMENT PLUS (2) OWNER OPTIONS

OF 5,000 SF FOR A TOTAL OF 30,000 SF." Please clarify as to how this item shall be paid – will it be square feet of FRP installed or square feet of concrete area strengthened. If this item is paid in square feet of FRP installed, then please provide the approximate unit weight (oz. per sq. yards or grams per sq.

meters) of FRP to be used for pricing.

Answer 27: The base quantities will be paid for in their entirety up the quantity indicated. The measurement will be based on square feet of concrete strengthened. The unit weight/layers will vary significantly based on the manufacturer but can be estimated using the equivalent strength criteria provided.

Question 28: Drawing S-401, FRP Quantities Notes - Note 2.C Item (b) & (c), states that

"CONTRACTOR SHOULD PRICE 20,000 SF OF FLEXURAL FRP REINFORCEMENT PLUS (2)

OWNER OPTIONS OF 5,000 SF FOR A TOTAL OF 30,000 SF. REINFORCEMENT MAY TAKE

PLACE ON TOP OF THE SLAB (NEGATIVE REINFORCEMENT) AND BELOW THE SLAB

(POSITIVE REINFORCEMENT). REINFORCEMENT MAY ALSO TAKE PLACE ON BEAMS."

Please provide breakdown on the quantities for the 3 types of flexural reinforcement likely to take place – SF of negative uni-directional reinforcement shown as Example A, SF of negative bi-directional reinforcement around interior columns shown as Example B and SF of positive reinforcement on the underside of slab and beams. There is a significant price difference between all the 3 repair types and between uni-directional and bi-directional FRP which can affect the overall bid pricing significantly given the bid quantity of 20,000 sf plus 2 options of 5,000 sf each. In addition, determination of approximate quantities during the pre-bid walk through is not possible as the existing finishes are not removed yet.

Answer 28: The intent is to provide repairs as appropriately determined after finishes are removed and therefore a breakdown of these items is not possible. These quantities should be bid as determined by the contractor to include all three possible repairs types in any quantity. The actual repairs will likely be a combination of all three types but the ratios are unknown.

Question 29: Dwg. S-401, FRP Quantities Notes – Note 2.A Item (b) states that the contractor should price 1000 lineal feet of uni-directional FRP beam stirrup reinforcement. Please clarify as to how this item shall be paid – will it be lineal feet of beam or lineal feet of FRP installed? If this item is paid in lineal feet of FRP installed, then please provide the approximate unit weight (oz. per sq. yards or grams per sq. meters) of FRP and the width of the FRP required to be used for pricing.

Answer 29: The base quantities will be paid for in their entirety up the quantity indicated. The measurement will be based on the linear feet of concrete beam strengthened. The unit weight/layers will vary significantly based on the manufacturer but can be estimated using the equivalent strength criteria provided.

Question 30: Dwg. S-401, FRP Quantities Notes – Note 2.A Item (a) calls for #3 rebar @ 8" O.C. for FRP shear strengthening design for beams. Please clarify if FRP is to be designed to provide the strength equivalent to one or two legs of #3 (stirrups) placed at 8" O.C..

Answer 30: The strength shall be equivalent to two legs of a #3 stirrup placed 8" o.c. and the FRP should be wrapped in the same configuration as a typical rebar stirrup under the bottom of the beam where feasible.

Question 31: Dwg. S-401, FRP Quantities Notes – Note 2.B Item (b) states that the contractor should price 500 lineal feet of uni-directional FRP column stirrup reinforcement. Please clarify as to how this item shall be paid – will it be lineal feet of column or lineal feet of FRP installed? If this item is paid in lineal feet of FRP installed, then please provide the approximate unit weight (oz. per sq. yards or grams per sq. meters) of FRP and the width of the FRP required to be used for pricing.

Answer 31: The base quantities will be paid for in their entirety up the quantity indicated. The measurement will be based on the linear feet of concrete column strengthened. The unit weight/layers will vary significantly based on the manufacturer but can be estimated using the equivalent strength criteria provided.

Question 32: Dwg. S-401, FRP Quantities Notes – Note 2.B Item (a) - Please provide the dimensions of the columns that require shear FRP strengthening.

Answer 32: The bid quantities should apply to any column in the building. The bidders can use an average or maximum size of a column as they see fit for their bid. The actual locations of FRP will be determined during construction.

Question 33: Dwg. S-401, FRP Quantities Notes – Note 2.B Item (a) calls for #3 rebar @ 12" O.C. for FRP shear strengthening design for columns. Please clarify if FRP is to be designed to provide the strength equivalent to one or two legs of #3 (stirrups) placed at 12" O.C.

Answer 33: The strength shall be equivalent to a continuous hoop of a #3 stirrup placed 12" o.c.

and the FRP should be wrapped around the entire perimeter of the column.

Question 34: Dwg. S-401, FRP Quantities Notes – Note 2.A - Please provide beam dimensions, slab thickness and effective depth of reinforcement (d) for beams that require FRP shear strengthening.

Answer 34: The bid quantities should apply to any beam or slab in the building. The bidders can use an average or maximum size of beams and slabs as they see fit for their bid. The actual locations of FRP will be determined during construction.

Question 35: Will intumescent topcoat or UL rated fireproofing be required for the FRP? If UL rated fireproofing, please specify the hourly rating and note that this will affect the overall finish elevation of the slab, beams and columns as the UL fireproofing is much thicker than intumescent coating..

Answer 35: No UL fireproofing or intumescent topcoat will be required for the FRP.

Question 36: Detail 1, 2 & 3 on Dwg. S-302 show that only 3 each, #6 bars are required to be drilled through the column. Will any dowels be embedded in to the column especially on the shorter length of the column?

Answer 36: No, only the through dowels shown will be required. There are no dowels required on the shorter face of the column. The concrete interface should be prepped to a CSP profile of 7 as shown on the drawings to promote bond at the interface.

Question 37: Detail 1, 2 & 3 on Dwg. S-302 – Please confirm that the new #5 reinforcement will be as shown on the details as no spacing requirements are provided.

Answer 37: The #5 bars should be ACI minimum clearance from the face of the column or form.

As each shear capital will vary based on the column dimensions, this spacing will vary slightly at each location.

Question 38: Detail 1, 2 & 3 on Dwg. S-302 show to core drill 1" diameter hole in slab for air venting.

Can we use pressurized pumping technique (ACI RAP Bulletin 5) in lieu of the specified air venting technique?.

Answer 38: Yes this technique is allowed although it still requires designed methods (multiple ports) that allow air to escape to ensure air cavities are not being created. The means and methods to ensure proper bond and avoidance of cavities is up to the contractor.

Question 39: S002 Note D, Please confirm that prebagged specialty self-consolidating concrete repair mortar would be acceptable to use in lieu of the ready mix self-consolidated concrete.

Answer 39: A bagged specialty self-consolidating repair cementitious product, as long as it meets the design requirements of the construction documents and specifications, would be approved upon proper submittal of all data sheets. Product will likely need to be extended with aggregate to prevent shrinkage, but should always be installed per manufacturer's instructions.

Question 40: S002 Note B, Can you please provide an approximate quantity breakdown for the spalled concrete surfaces in terms of how much repairs are on topside of the slab vs underside of the slab vs column concrete repairs vs wall concrete repairs vs beam concrete repairs? There is a significant price difference between repairs at all the above listed locations which can affect the overall bid pricing significantly given the bid quantity of 4,000 sq. feet plus 2 options of 750 sq. feet each. In addition, determination of approximate quantities during the pre-bid walk through is not possible as the existing finishes are not removed yet.

Answer 40: The intent is to provide repairs as appropriately determined after finishes are removed and therefore a breakdown of these items is not possible. These quantities should be bid as determined by the contractor to include all possible repairs types in any quantity. The actual repairs will likely be a combination of all types but the ratios are unknown and the Owner wants to maintain flexibility.

Question 41: Dwg S-002, Concrete Repair Notes – B.3 states that the depth of the repair is based on 6" for every sq. foot of concrete repaired. However, on the same drawing, Concrete Repair Notes – B.4.e & f and Dwg. S-303, Concrete Repair Notes – No. 4 mention to assume maximum depth of concrete repairs to not exceed 4 inches. Please clarify. Typically, all partial depth repairs are up to 4 inches deep.

Answer 41: 4" maximum depth should be used for cost estimating purposes. Partial depth repairs in practice should be completed for detail 1/S-303.

Question 42: Dwg S-002, Concrete Repair Notes – B.4.d, mentions full depth slab repairs, see Dwg. S- 303 and other plans for slab thickness. Can you please confirm that full depth slab repairs shall be required in this project? Also, if they are then can you please provide a quantity for these repairs. In addition, please provide a drawing detail and slab thickness as they are not shown on Dwg. S-303.

Answer 42: Please review the as-built drawings for additional information concerning the slab thicknesses. Full-depth repairs will likely be required and should be weighted into the 4,000 SF of concrete repair. Slab thicknesses are called out on partial plans indicated as "EXIST X" C.S." the X being the thickness. The intent is to provide repairs as appropriately determined after finishes are removed and therefore a breakdown of these items is not possible. These quantities should be bid as determined by the contractor to include all possible repairs types in any quantity. The actual repairs will likely be a combination of all types but the ratios are unknown and the Owner wants to maintain flexibility.

Question 43: Dwg S-002, Concrete Repair Notes – G.3 mentions to roughen existing surface to promote bond and ensure floor is free from dirt, grease, solvents, or other materials that would prohibit bonding.

Can you please elaborate on the surface profile requirement in terms of what CSP finish is required for this scope of work?

Answer 43: As required in I.3, the existing surface should have a roughness profile of CSP-7

Question 44: How should the contractors proceed if they have any additional questions after the question deadline?

Answer 44: RFIs will not be answered after the RFI deadline.

Question 45: C505 6/C505, Details dont show waterproofing for concrete work in sally port however past projects have required waterproofing in sally ports. Is waterproofing Required?

Answer 45: Yes, the detail is keyed in the various building sections of the sallyport and detailed on A8/A-432. This waterproofing is to be applied to the existing lower slab/ basement roof that is to remain after upper wear slab at sallyport is removed.

Question 46: A620-A625, Drawings show a steel plate around he window frames with no size or thickness provided. Please provide dimensions and thickness of these steel plates if required

Answer 46: Steel plate and attachment should be designed by window manufacturer/supplier. As each window will have unique fastening patterns, this plate cannot be designed or estimated at this time.

Question 47: I-210, Plans call out for visual display boards CB1, CB2 and CB3 however these are not shown in the Furniture schedule. Please provide quantities or schedule location for these display boards.

Answer 47: Visual display boards CB-1, CB-2 and CB-3, as well as Mural boards MB-1 are all built items and considered casework. They are not part of the Furniture package for this project.

The quantities for each level are as follows:

Level 1

CB-1 – 7

CB-2 – 1

CB-3 – 1

MB-1 – 6

Level 2

CB-1 – 7

CB-2 – 0

CB-3 – 1

MB-1 – 6

Level 3

CB-1 – 7

CB-2 – 0

CB-3 – 1

MB-1 – 6

Level 4

CB-1 – 8

CB-2 – 0

CB-3 – 2

MB-1 – 6

Level 5

CB-1 – 7

CB-2 – 0

CB-3 – 1

MB-1 – 6

Level 6

CB-1 – 7

CB-2 – 0

CB-3 – 1

MB-1 – 6

See Enlarged Floor Plans and Stair Plans for locations.

W912DS19B0008
Amendment 0005 - Bidder Questions and Responses