OPERATION, MAINTENANCE AND MONITORING
PLAN
BUILDING 151 SUB-SLAB DEPRESSURIZATION
SYSTEM
DEFENSE SUPPLY CENTER RICHMOND
Prepared For
Defense Logistics Agency and
Defense Supply Center Richmond
May 2018
OPERATION, MAINTENANCE AND MONITORING
PLAN
BUILDING 151 SUB-SLAB DEPRESSURIZATION
SYSTEM
DEFENSE SUPPLY CENTER RICHMOND
Prepared For:
Defense Supply Center Richmond
USACE – Baltimore District
Prepared By:
Arcadis U.S., Inc.
Contract No. W912DR-13-D-0019
Task Order No. 0005
OPERATION, MAINTENANCE AND
MONITORING PLAN
Defense Supply Center Richmond
Building 151 Sub-Slab Depressurization System
CONTENTS
Acronyms and Abbreviations
1 Introduction
2 System Objectives
3 System Overview
4 SSDS Components
4.1 SSDS Extraction Points
4.2 Differential Pressure Gauges
4.3 System Exhaust Fan
4.4 Controls and Alarms
5 Maintenance and Monitoring
5.1 System Performance Monitoring
5.1.1 Sub-Slab Differential Pressure Monitoring
5.1.2 System Vapor Sampling
5.2 Routine Maintenance
5.2.1 System Exhaust Fan
5.3.1.1 Routine Maintenance
5.3.1.2 Non-Routine Maintenance
5.2.2 System Piping
5.3.2.1 Routine Maintenance
5.3.2.1 Non-Routine Maintenance
5.2.3 System Monitoring Devices
5.2.4 Alarm Notification Procedure
6 System Operation
6.1 Starting the System
6.2 Shutting the System Down
6.3 Responding to Alarms
7 Reporting
8 References
TABLES
Table 1. Equipment List
Table 2. OM&M Schedule
Table 3. Alarm Details
FIGURES
Figure 1. SSDS As-Built Layout
Figure 2. Piping and Instrumentation Diagram
Figure 3. Construction Details – Wall Penetration
Figure 4. Construction Details – Break Room SSDS Point
Figure 5. Construction Detail
Figure 6. Construction Detail – SSDS Fan and Tool Room Window Penetration
APPENDICES
A System Equipment Manuals
ACRONYMS AND ABBREVIATIONS
DLA Defense Logistics Agency
DSCR Defense Supply Center Richmond
HASP Health and Safety Plan in w.c. inches of water column
NFPA National Fire Protection Act
OM&M operation, maintenance and monitoring
OM&M Plan Operation, Maintenance and Monitoring Plan
OU 6 Operable Unit 6
PVC polyvinyl chloride
ROD record of decision
SSDS sub-slab depressurization system
TCE trichloroethylene µg/m3 microgram per cubic meter
U.S. United States
USACE United States Army Corps of Engineers
USEPA United States Environmental Protection Agency
VAARNG Virginia Army National Guard
VADEQ Virginia Department of Environmental Quality
VMP vapor monitoring point
VOC volatile organic compound
1 INTRODUCTION
This Operation, Maintenance and Monitoring Plan (OM&M Plan) was prepared by Arcadis U.S., Inc. for Defense Logistics Agency (DLA) for the Building 151 Sub-Slab Depressurization System (SSDS) at the Defense Supply Center Richmond (DSCR), located in Richmond, Virginia (the “Site”). Building 151 is located within the portion of the installation occupied by the Virginia Army National Guard (VAARNG) and serves as their consolidated vehicle maintenance operations facility. The building consists of vehicle maintenance bays, sub-grade service pits, offices, a breakroom, tool room, and other facilities. It is occupied by mechanics and supervisors during business hours. Building 151 is located within the operable unit (OU) 6 area of concern, and samples of indoor air, sub slab vapor, and outdoor air are collected every 3rd and 5th year in accordance with the record of decision (ROD) for OU 6.
Currently, there is no complete vapor intrusion pathway. However, concentrations of volatile organic compounds (VOCs) are present in sub-slab soil vapor under a portion of Building 151 near sub-slab vapor monitoring points (VMP) VMP173 and VMP168 (monitoring point locations shown on Figure 1) which represent a potential for vapor intrusion to occur in the future should building conditions change. At these locations, sub-slab concentrations of trichloroethene (TCE) exceed United States (U.S.) Environmental Protection Agency (USEPA) Regional Screening Levels for sub-slab soil vapor calculated using the USEPA vapor intrusion screening level calculator for commercial space. TCE concentrations were detected by the U.S. Army Corps of Engineers (USACE) in 2015 in these VMPs at concentrations of 9,136 micrograms per meter cubed (µg/m3) and 101 µg/m3, respectively, which exceed the USEPA screening level of 100 µg/m3.
To address the presence or potential presence of VOCs beneath the building floor slab, vapor mitigation measures have been implemented via installation of an SSDS, with two vapor extraction points. One of the vapor extraction points is located in the tool room and the other is located inside the break room.
Figure 1 shows the configuration of the SSDS in Building 151, including the extraction points, VMPs, and the observed extent of the SSDS-induced sub-slab vacuum after completion of installation.
2 SYSTEM OBJECTIVES
The overall objective of the SSDS is to mitigate the potential for workers within Building 151 to be exposed to vapors originating from the OU 6 groundwater plume via vapor intrusion. The specific performance objectives of the SSDS include:
Induce a negative pressure field beneath the slab of the building near VMP168 and VMP173. The area requiring mitigation is defined by the area encompassing these monitoring points, as shown on Figure 1.
Provide adequate vacuum to effectively mitigate the potential for vapor intrusion. Guidance documents from the New Jersey Department of Environmental Program (NJDEP 2018) indicate that a pressure differential of -0.004 to -0.005 inches of water column (in w.c.) is sufficient to mitigate the vapor intrusion pathway. The Virginia Department of Environmental Quality (VADEQ) does not provide specific guidance on acceptable differential pressure for building mitigation. A conservative vacuum of 0.010 in w.c. was used as the design objective in the area requiring mitigation, though vacuum influence of 0.004 in w.c. is considered to have adequate protection from subsurface vapor intrusion based on the USEPA Guidance.
3 SYSTEM OVERVIEW
The Building 151 SSDS consists of two sub-slab depressurization extraction points (Extraction points 1 and 2), located in the tool room and the break room, respectively, as shown on Figure 1. Pipe from these extraction points runs to a radon mitigation-style fan on the exterior wall of the building, outside the tool room. The extracted sub-slab vapor is then discharged to the atmosphere outside of the building, 18 inches above the roof line of the tool room and away from other vents or windows on the building. A drain pipe is installed at the low point of the system piping, where the system pipe exits the building in the tool room, to prevent condensate from building up in the system and obstructing the air flow. Each vacuum point has a gauge to measure the applied vacuum, a low vacuum indicator light, a gate valve, and a sample port to collect samples of extracted sub-slab vapor. Vacuum monitoring points, located across the area requiring mitigation, enable monitoring of the sub-slab differential pressure extension to ensure performance objectives are achieved.
4 SSDS COMPONENTS
This section describes SSDS components and specifications, including equipment designations for each system component. An equipment list is provided in Table 1. The layout of the SSDS including the locations of extraction points, major system components, and the area of vacuum influence is provided on Figure 1. As-Built drawings of the SSDS components are shown on Figures 2 through 6. Manufacturer’s manuals for system equipment are included in Appendix A.
4.1 SSDS Extraction Points
To facilitate the installation of extraction sumps directly beneath the existing slab, a 1-foot diameter opening was created in the existing concrete floor slab at each extraction point. Sub-slab material was removed to create an extraction sump with a volume of approximately 1 cubic foot. The extraction sump was then filled with clean pea gravel. An open-ended 4-inch diameter schedule 40 carbon steel pipe was installed vertically into the upper 2 inches of the extraction sump pea gravel. A 6-mil polyethylene vapor barrier was placed on top of the washed stone, and new concrete was poured to repair the opening.
The vertical riser pipes for the extraction points were constructed of 4-inch diameter schedule 40 carbon steel pipe and include a vacuum gauge and a vapor sample port. The 4-inch schedule 40 carbon steel riser pipe then transitions to 4-inch schedule 40 polyvinyl chloride (PVC) pipe approximately 6-feet above grade. Extracted soil vapors are conveyed via the 4-inch diameter solvent-welded schedule 40 PVC pipe from the extraction point to the SSDS exhaust fan and discharge stack. Conveyance piping is sloped back toward the extraction points, where possible, to drain condensate from the system piping to below the concrete slab at the extraction points. Where the system pipe exits the main building and in the tool room, the piping is sloped towards the low spot at the tool room window penetration, where a ½ inch condensate drain line is connected to the system pipe, to allow condensate to drain from the system pipes back to below the concrete slab. There is also a cleanout cap at this low spot to allow any accumulating water to be manually cleared, if necessary.
4.2 Differential Pressure Gauges
The vacuum indicators are Dwyer Instruments Magnehelic model 2310 differential pressure gauges with a range of 0-5 in w.c. These gauges, located on the risers at extraction points 1 and 2, indicate the vacuum applied to the sub-slab soil vapor extraction points. One differential pressure gauge is also installed at the system exhaust fan to measure the applied vacuum at the inlet to the SSDS exhaust fan.
4.3 System Exhaust Fan
A RadonAway HS5000 radon exhaust fan capable of operating at a flow rate of 29 standard cubic feet per minute at an inlet vacuum of 20 in w.c. with a maximum pressure rating of 35 in w.c., is used to apply vacuum at the extraction points. The fan is located on the exterior wall of Building 151, just outside of the tool room. The fan discharges approximately 18 inches above the building’s roofline and includes a friction loss free rain hat to prevent intrusion of precipitation into the system.
4.4 Controls and Alarms
One RadonAway Checkpoint IIa P/N 28001-2 system alarm is installed at each vacuum extraction point.
The Checkpoint IIa alarms are plugged into electrical outlets on separate circuits from the fan and are set to alarm when the system vacuum falls below 0.25 in w.c. An illuminated green light on the alarm unit casing indicates the system pressure is above 0.25 in w.c. If the vacuum pressure falls below 0.25 in w.c., the green light will turn off, a red light will illuminate, and an audible alarm will sound. If the warning alarm sounds, the building workers may be directed to disconnect power from the alarm to silence it and alert an appropriate representative from DLA. Note that the alarm is present to alert the building occupants that service is required, it does not indicate a hazardous condition since there is not currently a complete vapor intrusion pathway.
5 MAINTENANCE AND MONITORING
This section describes basic system OM&M requirements. The recommended schedule for OM&M tasks is shown in Table 2. The most current approved version of Table 2 should always be consulted in advance of quarterly OM&M events so that new requirements may be incorporated into the plan promptly.
The OM&M Performance Monitoring Log included in Appendix B should be completed on a quarterly basis and records maintained.
5.1 System Performance Monitoring
On-site system monitoring will be conducted to verify that the system is operating properly. The Performance Monitoring Log included in Appendix B is to be completed at the frequency indicated in Table 2. The System Monitoring Log will be used to summarize the visual observations and data collection necessary to monitor system performance. System monitoring will include, but is not limited to, the following:
General site inspection to ensure the system is running properly;
Inspection of piping and fittings to ensure no damage;
Record applied vacuum at extraction points; and
Record sub-slab differential pressure at sub-slab monitoring points.
5.1.1 Sub-Slab Differential Pressure Monitoring
Sub-slab differential pressures will be measured at VMPs at the frequency indicated in Table 2 and recorded in the Performance Monitoring Log (Appendix B). A micromanometer capable of measuring to the nearest 0.001 in w.c. will be used to measure instantaneous differential pressure at the VMPs with the system operating.
The micromanometer will be zeroed before each VMP measurement with both ports vented to the atmosphere. Micromanometers owned by system operators will be factory-calibrated annually or anytime the unit is dropped or otherwise suspected to be reading inaccurately. To measure sub-slab differential pressures, the threaded cap on the VMPs will be removed and a threaded compression fitting and tubing installed. With the other end of the tubing connected to the positive port on the micromanometer, negative readings measured by the micromanometer indicate a vacuum at the VMP. As discussed above, vacuum readings of 0.004 in w.c. or greater (i.e., pressure of less than -0.004 in w.c.), indicates that adequate vacuum extends to that VMP.
5.1.2 System Vapor Sampling
Since Building 151 is located within the OU 6 area of concern, samples of indoor air, sub slab vapor and outdoor air are to be collected every 3rd and 5th year, in accordance with the ROD for OU 6.
5.2 Routine Maintenance
General routine maintenance items are discussed below. Building 151 personnel will be notified at least 24 hours in advance of any maintenance requiring a system shutdown. Any work requiring lockout/tagout of equipment, or work on energized equipment, will be done in accordance with DLA and USACE requirements and in accordance with proper lockout/tagout requirements as specified in the health and safety plan (HASP).
5.2.1 System Exhaust Fan
5.3.1.1 Routine Maintenance
The system exhaust fan should be inspected for abnormal sound, odor, or vibration on a quarterly basis.
5.3.1.2 Non-Routine Maintenance
If the fan is not operating at normal fan inlet vacuum conditions and fan damage is suspected, complete fan voltage, current check, and dielectric testing to confirm that it is functioning per manufacturer’s performance specification (included in Appendix A). The blower motor voltage and current draw and dielectric testing should be checked by a competent person in accordance with DLA and USACE contractor safety program regarding work on energized equipment. The competent person must also have National Fire Protection Act (NFPA) 70E Arc Flash prevention training.
5.2.2 System Piping
5.3.2.1 Routine Maintenance
Inspect all system piping for signs of damage, leaks, blockages, and lack of structural integrity due to missing or damaged pipe supports. Check the condensate drain line, located in the tool room where the system pipe goes through the exterior wall, to ensure no blockage is present and that condensate is free to drain from the system piping.
5.3.2.1 Non-Routine Maintenance
Upon discovery, isolate damaged or leaking piping within the building from the sub-slab to eliminate leakage into the building. Repair any piping damage that is identified immediately or as soon as possible.
If the condensate drain line or valve is clogged, remove clog to allow condensate to drain from the system piping.
5.2.3 System Monitoring Devices
Alarm details for the monitoring devices are summarized in Table 3. Manufacturer quick start guides and manuals (Appendix A) may be utilized to perform testing of system monitoring devices. Each monitoring device will be tested at the frequency indicated in Table 2 to confirm the device is functioning, accuracy of readings, and alarm response.
5.2.4 Alarm Notification Procedure
The system’s alarm notification procedure should be tested at the frequency indicated in Table 2. The system shutdown will be coordinated in advance with DLA, USACE, VAARNG/Building 151 personnel, and any other appropriate parties, so that an unnecessary alarm response is not initiated.
6 SYSTEM OPERATION
This section covers the general procedures to be followed when starting the system, performing a system shutdown, and responding to alarm conditions.
6.1 Starting the System
The following steps should be taken to properly start the system under normal conditions:
1. Communicate with DLA/USACE to confirm that a system startup should be initiated. Follow the site protocol in the event that the fans are locked or tagged out.
2. Conduct a visual inspection of the system to ensure there are no obvious problems with any of the system process piping or electrical components.
3. To start the system, turn the breaker switch located by the window in the tool room to ‘On’. The exhaust fan should turn on.
4. Once sufficient vacuum has built up in the system piping, plug in and turn on the low vacuum alarm sensors at the extraction points. The green indicator lights on the pressure alarms should illuminate.
5. If the red alarm indicator lights remain illuminated and/or the exhaust fan does not turn on, the appropriate DLA/USACE representative should be notified.
6. Complete the Performance Monitoring Log.
6.2 Shutting the System Down
The following steps should be taken to initiate a system shutdown:
1. Turn off the low vacuum alarm sensors on each SSDS vacuum point by unplugging them.
2. Turn the SSDS offline by switching the exhaust fan switch in the breaker box to the “Off” position.
3. Conduct lockout/tagout in accordance with the USACE health and safety requirements and the HASP.
6.3 Responding to Alarms
The following steps should be taken to respond to an alarm condition. Any work on live electrical circuits should only be performed by personnel deemed to be qualified by the facility manager and in accordance with NFPA 70E health and safety requirements.
1. Record the status of the exhaust fan and note which alarm indicator light is illuminated using an Alarm Response Log (Appendix B) to document any alarm response activities.
2. Conduct a visual inspection of the system for problems with any of the system equipment, process piping or electrical components.
3. Check to see if condensation is present in the process piping low spots and drain if necessary.
4. Confirm all alarm conditions have been corrected.
5. Check the breaker switch in the breaker box located in the tool room to see if it is tripped and reset as necessary.
6. If the exhaust fan does not start, investigate the potential causes listed in the manufacturer’s manual included in Appendix A. Utilize a licensed electrician or qualified person for further diagnosis of the exhaust fan malfunction as necessary. A replacement fan should be procured and installed in accordance with manufacturer’s recommendations.
7. If the alarm condition cannot be corrected, consult the appropriate DLA/USACE representative.
7 REPORTING
A summary of the OM&M field monitoring will be provided for USACE and DLA following each visit on the routine progress calls.
Annual Reports will be provided to USACE and DLA which will include results of monitoring data, interpolation of the extent of vacuum influence, a summary of system performance, system down time, any maintenance performed, and any recommendations related to continued system monitoring. Building 151 vapor monitoring will be conducted in accordance with the ROD as discussed above.
8 REFERENCES
NJDEP, 2018. Vapor Intrusion Technical Guidance. Site Remediation and Waste Management Program.
January.
Quantity Description Designation Specification
1 Exhaust Fan EF RadonAway HS5000
2 System Alarm SA-1, SA-2 RadonAway Checkpoint IIa P/N 28001-2
3 Differential Pressure Gage PG-1, PG-2, PG-EF Dwyer Instruments Magnehelic Differential Pressure Gage Model
Notes:
1) See Appendix B for additional equipment information.
Definitions EF - exhaust fan SA - system alarm PG - pressure gage
Table 1 Significant Equipment List
Operation, Maintenance and Monitoring Plan Defense Supply Center Richmond
Richmond, Virginia - Building 151 Sub-Slab Depressurization System
Table 1 Page 1 of 1
Quarterly Quarterly Quarterly Quarterly Annual
Definitions:
EP - extraction point OM&M - operation, maintenance and monitoring
Inspect for abnormal sounds, odors and vibrations.
Complete performance monitoring log
Low vacuum alarm test Turn off exhaust fan and ensure system alarms at EP-1 and EP-2 are functional
Inspect for leaks, potential blockage, structural integrity and abnormal appearance.
Inspect for cracked piping or fittings, leaks and structural integrity.
Exhaust fan inspection
Extraction point risers and interior piping inspection Exterior piping inspection
Table 2 OM&M Schedule
Defense Supply Center Richmond Richmond, Virginia - Building 151 Sub-Slab Depressurization System
Task NotesFrequency
Operation, Maintenance and Monitoring Plan
Table 2 Page 1 of 1
Instrument Alarm Description Indications Normal Operating Range Alarm Range Potential Cause(s)
SA-1 Low vacuum Red light, audible alarm > 2.0 in w.c. vacuum < 0.25 in w.c. vacuum Fan shutdown, leak in extraction piping, clogged discharge line
SA-2 Low vacuum Red light, audible alarm > 2.0 in w.c. vacuum < 0.25 in w.c. vacuum Fan shutdown, leak in extraction piping, clogged discharge line
Definitions:
in w.c. - inches of water column SA - system alarm
Table 3 Alarm Details
Operation, Maintenance and Monitoring Plan Defense Supply Center Richmond
Richmond, Virginia - Building 151 Sub-Slab Depressurization System
Table 3 Page 1 of 1
PAINT SHOP AND
PAINT BOOTH
LAUNDRY
OFFICE
H A
L L
VEHICLE
MAINTENANCE
BAYS
TRENCH
SUPPLIES/
REFERENCE
LIBRARY
SUPERVISOR
OFFICE
VMP172
VMP170
VMP171
SSDS EXTRACTION
POINT 2
OFFICE
(ASBESTOS
TILES)
SSDS FAN MOUNTED ON OUTSIDE WALL OF
TOOL ROOM. ATMOSPHERIC DISCHARGE
LOCATED ABOVE ROOFLINE OF TOOL ROOM
SSDS VACUUM
HEADER PIPING
HUNG FROM
CEILINGSSDS
EXTRACTION
POINT 1
NEW TOOL ROOM VAPOR
MONITORING POINT
B A
T H
R O
O M
U T
I L I T
Y
TOOL
ROOM
BREAK
ROOM
CP-1
0.003
CP-2
0.000-0.002
CP-3
0.008
CP-4
0.006
CP-5
0.000
CP-6
0.004
CP-7
0.008
CP-8
0.003
VMP173
0.015
VMP169
0.006
0.004
IN WC
0.007
VMP168
0.010
FIGURE
BUILDING 151 LAYOUT OF
SUB-SLAB DEPRESSURIZATION SYSTEM
I M
A G
E S
G
E P r o
A e r i a l j p g
P r o
A e r i a l j
P r o
A e r i a l j p g
X R
E F
S
P R
O J E
C T
N A
M
C I T
Y
M i l w a u k e e
W
I
D
V
G
R O
U P
E
N V
B
C
M c K e o u h
P
C
O p t
M R e q d
T
M
B r a v e r m a n
L
Y R
O p t O
N
O
F F
R
E F
C U s e r s c m c k e o u g h
O n e
D r i v e
A
R C
A D
I S
B o c s U
S A
C
A L
T I M
O R
E D
S C
R
P r o g r a m
O p t i m i z a t i o n
D
W G
F i g s
R d w
Y
O U
T
V
E D
A
D V
E R
S
L
C
H
G
E S
E T
U P
P
D F
O
T S
T Y
L E
T A
B L
E
B
L A
C K
G R
A Y
C
O
T T
E D
M
C K
E O
U G
H
C
A R
O L
NOTES:
1. AERIAL PHOTO SOURCED FROM GOOGLE EARTH PRO,
IMAGERY DATE APRIL 5, 2016.
2. INTERIOR BUILDING CONFIGURATION IS APPROXIMATE
AND IS BASED ON A FIGURE PROVIDED BY
USACE-BALTIMORE TITLED, "VI INVESTIGATION FOR
BUILDING 151 INDOOR AND OUTDOOR AIR, AND
SUB-SLAB VAPOR SAMPLES."
N
LEGEND
VAPOR MONITORING POINT
NEW TOOL ROOM VAPOR MONITORING
POINT
COMMUNICATION POINT (TEMPORARY)
VACUUM READINGS, INCH WC
BAY DOOR
AREA OF VACUUM INFLUENCE
GREATER THAN OR EQUAL TO 0.004
INCH WC, DASHED WHERE INFERRED
AREA REQUIRING MITIGATION
SUB-SLAB DEPRESSURIZATION
SYSTEM
DEFENSE SUPPLY CENTER
RICHMOND, VIRGINIA
BUILDING 151 SSDS DESIGN
0.003
PI
PDI
SP-101
GV-101
GV-102
SP-102
PI
PDI
SSDS POINT
BREAK ROOM
SSDS POINT
TOOL ROOM
4" STEEL
4" STEEL
FAN
DISCHARGE TO
ATMOSPHERE
RADONAWAY HS5000 , 120V, 349 WATTS,
2.9 AMPS. FAN SPECIFICATION MAY
CHANGE BASED ON COMMUNICATION
TESTING.
MITIGATION SYSTEM LOW PRESSURE
LOW VOLTAGE ALARM (RADONWAY
28001-3 OR SIMILAR WITH AUDIBLE
ALARM AND INDICATOR LIGHT)
MITIGATION SYSTEM LOW PRESSURE
LOW VOLTAGE ALARM (RADONWAY
28001-3 OR SIMILAR WITH AUDIBLE
ALARM AND INDICATOR LIGHT)
DWYER INSTRUMENTS MODEL 2310 - 0-5"
W.C. VACUUM OR SIMILAR
DWYER INSTRUMENTS MODEL 2310 - 0-5"
W.C. VACUUM OR SIMILAR
PI
DWYER INSTRUMENTS MODEL 2310 - 0-5"
W.C. VACUUM OR SIMILAR
4" PVC
4" PVC
PIPING AND INSTRUMENTATION
DIAGRAM
FIGURE
I M
A G
E S
X
R E
F S
P
R O
J E
C T
N A
M
C I T
Y
M i l w a u k e e
V
G
R O
U P
E
C
M c K e o u
C
O p
R e q
E
M o v s e s i
R O p t O
N
O
F F
R
E F
C U s e r s c m c k e o u g h O n e D r i v e
A
R C
A D
I S
B
D o c s U
S A
A L T
I M
O R
E D
S C
R
P r o g r m
O t i m i z a t i o n D
W G
C o n s t r u c t i o n D e t a i l s d
Y O
U T
V
E D
A
D V
E R
M
S
T
E C
G
E S
E T
U P
P
D F
O
T S
T Y
L E
T A
B L E
B
L A
C K
G R
A Y
C
T B
P L O
T T
E D
M
C K
E O
U G
H
C
A R
O L
DEFENSE SUPPLY CENTER
RICHMOND, VIRGINIA
MAIN ROOF
ROOF BEAM
FLOOR
UNISTRUT HANGING
PIPE AND CONDUIT
SUPPORTS (BEAM
CLAMP AND THREADED
ROD OR SIMILAR)
ROOF OF
TOOL ROOM
TO TOOL ROOM
SSDS POINT
UNISTRUT HANGING PIPE
AND CONDUIT SUPPORTS
(BEAM CLAMP AND
THREADED ROD OR
SIMILAR)
42" MIN
ELECTRICAL DISCONNECT PANEL,
SHUTOFF SWITCH AND ELECTRIC METER
FOR SSDS FAN (LOCATED ON INTERIOR
OF WALL SEPARATING THE MAIN
BUILDING AND THE TOOL ROOM)
BRICK AND BLOCK WALL
FROM BREAK
ROOM SSDS POINT
CONSTRUCTION DETAILS -
WALL PENETRATION
FIGURE
I M
A G
E S
X
R E
F S
P
R O
J E
C T
N A
M
C I T
Y
M i l w a u k e e
V
G
R O
U P
E
C
M c K e o u
C
O p
R e q
E
M o v s e s i
R O p t O
N
O
F F
R
E F
C U s e r s c m c k e o u g h O n e D r i v e
A
R C
A D
I S
B
D o c s U
S A
A L T
I M
O R
E D
S C
R
P r o g r t i m i z a t i o n D
W G
C o n s t r u c t i o n D e t a i l s d
Y O
U T
V
E D
A
D V
E R
M
S
T
E C
G
E S
E T
U P
P
D F
O
T S
T Y
L E
T A
B L E
B
L A
C K
G R
A Y
C
T B
P L O
T T
E D
M
C K
E O
U G
H
C
A R
O L
NOTES
1. SLOPE HORIZONTAL PIPING, TO PERMIT CONDENSATE
DRAINAGE. 1% SLOPE MUST BE MAINTAINED TOWARDS
VACUUM WELL.
2. HORIZONTAL PIPING SHALL BE SUPPORTED A MINIMUM
OF EVERY 6 FEET.
NOT TO SCALE
DEFENSE SUPPLY CENTER
BREAK ROOM ROOF
ELECTRICAL CONDUIT FOR DISCONNECT
SWITCH, LOW VACUUM SWITCH AND ALARM
UNISTRUT OR SIMILAR PIPE SUPPORTS
BREAK ROOM CEILING
4" SCH 40 PVC
SEALANT AROUND PIPE SIKA FLEX 1A
HOLE (12" TO 18" RADIUS)
BACKFILLED WITH PEA GRAVEL
4" GATE VALVE SCH 40 PVC
1/4" SAMPLE PORT WITH 1/4" BALL VALVE
FOOTING (TYP.)
SSDS POINT WILL BE OFFSET
FROM BUILDING FOOTING IF
ONE IS PRESENT
MITIGATION SYSTEM LOW PRESSURE / LOW
VOLTAGE ALARM (RADONAWAY 28001-3 OR
SIMILAR WITH AUDIBLE ALARM AND INDICATOR
LIGHT
4" GALVANIZED STEEL PIPE
4" SCH 40 PVC LONG RADIUS SWEEP ELBOW
SSDS POINT (TYP.)
MAIN ROOF
ROOF BEAM
TO TOOL ROOM
AND SSDS FAN
UNISTRUT HANGING PIPE SUPPORT (BEAM
CLAMP AND THREADED ROD OR SIMILAR)
ELECTICAL CONDUIT TO
DISCONNECT SWITCH
12" CORE
4" FLANGE STEEL TO PVC TRANSITION -
5 FEET ABOVE FLOOR
CONSTRUCTION DETAILS -
BREAK ROOM SSDS POINT
(TYPICAL - TOOL ROOM POINT SIMILAR)
FIGURE
I M
A G
E S
X
R E
F S
P
R O
J E
C T
N A
M
C I T
Y
M i l w a u k e e
V
G
R O
U P
E
C
M c K e o u
C
O p
R e q
E
M o v s e s i
R O p t O
N
O
F F
R
E F
C U s e r s c m c k e o u g h O n e D r i v e
A
R C
A D
I S
B
D o c s U
S A
A L T
I M
O R
E D
S C
R
P r o g r t i m i z a t i o n D
W G
C o n s t r u c t i o n D e t a i l s d
Y O
U T
V
E D
A
D V
E R
M
S
T
E C
G
E S
E T
U P
P
D F
O
T S
T Y
L E
T A
B L E
B
L A
C K
G R
A Y
C
T B
P L O
T T
E D
M
C K
E O
U G
H
C
A R
O L
NOTES
1. SLOPE HORIZONTAL PIPES DOWN TOWARD VACUUM
WELL 1%, TO PERMIT CONDENSATE DRAINAGE.
2. HORIZONTAL PIPING SHALL BE SUPPORTED A MINIMUM
OF EVERY 6 FEET.
3. 4" SCH 40 STEEL PIPE TO BE USED UP TO 5 FEET ABOVE
FLOOR FOR PROTECTION AGAINST DAMAGE.
NOT TO SCALE
DEFENSE SUPPLY CENTER
EXISTING CONCRETE
FLOOR SLAB
1.5" Ø FLUSH MOUNT
COVER
VAPOR PIN® CAP OR
SIMILAR
VAPOR PIN® SLEEVE
OR SIMILAR
STAINLESS STEEL
VAPOR PIN® OR SIMILAR
SOIL
MOISTURE BARRIER
INSTALLED BETWEEN
PEA GRAVEL AND
CONCRETE.
MINIMUM
6-INCHES
CONCRETE
1' DIA. CORE
8" MIN.
4-INCH
GALVANIZED
STEEL
3" MIN.
SEAL CRACKS WITH
SIKA FLEX 1A SEALANT
THICKNESS
VARIES
PEA GRAVEL
12" TO 18" RADIUS
CONSTRUCTION DETAIL
DEFENSE SUPPLY CENTER
RICHMOND, VIRGINIA
BUILDING 151 SSDS DESIGN
FIGURE
I M
A G
E S
X
R E
F S
P
R O
J E
C T
N A
M
C I T
Y
M i l w a u k e e
V
G
R O
U P
E
C
M c K e o u
C
O p
R e q
E
M o v s e s i
R O p t O
N
O
F F
R
E F
C U s e r s c m c k e o u g h O n e D r i v e
A
R C
A D
I S
B
D o c s U
S A
A L T
I M
O R
E D
S C
R
P r o g r t i m i z a t i o n D
W G
C o n s t r u c t i o n D e t a i l s d
Y O
U T
V
E D
A
D V
E R
M
S
T
E C
G
E S
E T
U P
P
D F
O
T S
T Y
L E
T A
B L E
B
L A
C K
G R
A Y
C
T B
P L O
T T
E D
M
C K
E O
U G
H
C
A R
O L
NOT TO SCALE
TYPICAL VAPOR PIN MONITORING POINT DETAIL
TYPICAL EXTRACTION PIT DETAIL
MAIN ROOF
ROOF BEAM
RADONAWAY HS5000 SSDS FAN
FLOOR
4" SCH 40 PVC LONG RADIUS
SWEEP ELBOW
UNISTRUT C-CHANNEL
WITH PIPE CLAMP
DISCHARGE TO
ATMOSPHERE
FROM VACUUM
WELLS
UNISTRUT HANGING
PIPE AND CONDUIT
SUPPORTS (BEAM
CLAMP AND THREADED
ROD OR SIMILAR)
ELECTRIC METER
SHOWING KWh POWER
USAGE (LOCATED ON
OUTSIDE OF BUILDING)
ELECTRICAL DISCONNECT PANEL,
SHUTOFF SWITCH FOR SSDS FAN
(LOCATED ON INTERIOR OF WALL
120 V CONDUIT INSIDE OF TOOL ROOM)
RAIN HAT TO PREVENT WATER INTRUSION
18" ABOVE ROOF
4" SCH 40 PVC
PIPING TO ROUTE THROUGH
EXISTING VENT IN LOWER PANE
OF WINDOW IN TOOL ROOM
4" TEE WITH GRIPPER
PLUG FOR CLEAN-UP
1/2" PVC BALL VALVE
1/2" TYGON CONDENSATION
DRAIN TUBING
1/2" CONDENSATION DRAIN -
INSTALLED THROUGH
FOOTER AND SEALED
CONSTRUCTION DETAILS -
SSDS FAN AND
TOOL ROOM WINDOW PENETRATION
FIGURE
I M
A G
E S
X
R E
F S
P
R O
J E
C T
N A
M
C I T
Y
M i l w a u k e e
V
G
R O
U P
E
C
M c K e o u
C
O p
R e q
E
M o v s e s i
R O p t O
N
O
F F
R
E F
C U s e r s c m c k e o u g h O n e D r i v e
A
R C
A D
I S
B
D o c s U
S A
A L T
I M
O R
E D
S C
R
P r o g r t i m i z a t i o n D
W G
C o n s t r u c t i o n D e t a i l s d
Y O
U T
V
E D
A
D V
E R
M
S
T
E C
G
E S
E T
U P
P
D F
O
T S
T Y
L E
T A
B L E
B
L A
C K
G R
A Y
C
T B
P L O
T T
E D
M
C K
E O
U G
H
C
A R
O L
NOTES
1. SLOPE HORIZONTAL SECTIONS TOWARDS THE VACUUM
WELLS 1%, TO PERMIT CONDENSATE DRAINAGE.
2. HORIZONTAL PIPING SHALL BE SUPPORTED A MINIMUM
OF EVERY 6 FEET.
3. RUBBER GROMMET SEAL TO BE USED WHERE PIPE
PENETRATES THE EXISTING VENT IN LOWER WINDOW
PANE.
NOT TO SCALE
DEFENSE SUPPLY CENTER
7RadonAway.com P. 800-767-3703 F. 978-521-3964
NEW PRODUCTS
Flex Coupling Magnehelic Gauge Minihelic GaugeMuffler
• Internal condensate bypass
• Brackets for vertical mounting indoors and outdoors
• Inlet: 3.0" PVC / Outlet: 2.0" PVC
• Weight: 18 lbs.
• Size: 15.5"W x 13.3"H x 8.2"D
• Warranty: 1 year (3-year option available)
MODEL WATTS
SOUND RATING (dBA) RECOM. MAX. OP.
PRESSURE “WC
TYPICAL CFM* vs. STATIC PRESSURE WC
OPEN 1/2 CLOSED 0" 10" 15" 20" 25" 35"
HS2000 with cord 174-307 56.5 56.2 51.9 14 63 37 12 - - -
HS3000 with cord 120-250 47.9 48.0 46.2 21 39 30 25 19 - -
HS5000 with cord 223-385 56.0 55.3 53.1 35 44 37 33 29 25 16
HS2000E with switch box 174-307 56.5 56.2 51.9 14 63 37 12 - - -
HS3000E with switch box 120-250 47.9 48.0 46.2 21 39 30 25 19 - -
HS5000E with switch box 223-385 56.0 55.3 53.1 35 44 37 33 29 25 16
MODEL P/N
HS2000 with cord 23004-1
HS3000 with cord 23004-2
HS5000 with cord 23004-3
HS2000E with switch box 23004-4
HS3000E with switch box 23004-5
HS5000E with switch box 23004-6
ITEM P/N
Optional 3-year warranty HS3YR
2" Schedule 40 Vent Muffler 24002
Magnehelic Manometer 0-50" WC 50001-2
Minihelic Manometer 0-40" WC 50027
2 x 2 Flex Coupling (black) 79020
2 x 3 Flex Coupling (black) 79027
3 x 3 Flex Coupling (white) 79037
3 x 3 Flex Coupling (black) 79010
3 x 3 Flex Coupling (gray) 79198
HS fans offer a proven solution for tough radon mitigation jobs, providing up to 25 times the suction of inline tube fans to deal with sand, tight soil or clay sub-slab material.
High Suction Fan with switched electrical box
High Suction Fan with cord
NOTE: Coupling sizes are for selection only, actual sizes may vary fractionally. See Flexible Coupling Sizing Chart on p. 20 or at radonaway.com/couplings
HIGH SUCTION SERIES
BY RADONAWAY®
FEATURES
WHY CHOOSE THIS FAN?
FAN SPECIFICATIONS
ACCESS0RIES FOR HS SERIES FAN PRICING
RADON
FANS
Made in the USA with U.S. and imported parts.
* CFM measured through suction.
DanFisher Rectangle
The World’s Leading Radon Fan Manufacturer
HS Series Installation & Operating
Instructions
RadonAway 3 Saber Way Ward Hill, MA 01835 www.radonaway.com
P/N IN007-REV K 10/15
Page 2 of 8 IN007 Rev K
RadonAway Ward Hill, MA.
HS Series Fan Installation & Operating Instructions Please Read and Save These Instructions.
DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY
INSTALLED. MAKE SURE ELECTRICAL SERVICE TO FAN IS
LOCKED IN "OFF" POSITION. DISCONNECT POWER BEFORE
SERVICING FAN.
1. WARNING! Do not use fan in hazardous environments where fan electrical system could provide ignition to combustible or flammable materials.
2. WARNING! Do not use fan to pump explosive or corrosive gases.
See Vapor Intrusion Application Note #AN001 for important information on VI applications. RadonAway.com/vapor-intrusion
3. WARNING! Check voltage at the fan to insure it corresponds with nameplate.
4. WARNING! Normal operation of this device may affect the combustion airflow needed for safe operation of fuel burning equipment. Check for possible backdraft conditions on all combustion devices after installation.
5. NOTICE! There are no user serviceable parts located inside the fan unit.
Do NOT attempt to open. Return unit to the factory for service.
6. All wiring must be performed in accordance with the National Fire Protection Association’s (NFPA)”National Electrical Code, Standard #70”-current edition for all commercial and industrial work, and state and local building codes. All wiring must be performed by a qualified and licensed electrician.
7. WARNING! In the event that the fan is immersed in water, return unit to factory for service before operating.
8. WARNING! Do not twist or torque fan inlet or outlet piping as Leakage may result.
9. WARNING! Do not leave fan unit installed on system piping without electrical power for more than 48 hours. Fan failure could result from this non-operational storage.
10. WARNING! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
b) Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Page 3 of 8 IN007 Rev K
INSTALLATION & OPERATING INSTRUCTIONS (Rev K) for High Suction Series HS2000 p/n 23004-1 HS3000 p/n 23004-2 HS5000 p/n 23004-3
1.0 SYSTEM DESIGN CONSIDERATIONS
1.1 INTRODUCTION
The HS Series Fan is intended for use by trained, certified/licensed, professional Radon mitigators.
The purpose of this instruction is to provide additional guidance for the most effective use of the HS Series Fan. This instruction should be considered as a supplement to EPA/Radon Industry standard practices, state and local building codes and state regulations. In the event of a conflict, those codes, practices and regulations take precedence over this instruction.
1.2 ENVIRONMENTALS
The HS Series Fan is designed to perform year-round in all but the harshest climates without additional concern for temperature or weather. For installations in an area of severe cold weather, please contact RadonAway for assistance. When not in operation, the HS Series Fan should be stored in an area where the temperature is never less than 32 degrees F. or more than 100 degrees F. The HS Series Fan is thermally protected such that it will shut off when the internal temperature is above 104 degrees F.
Thus if the HS Series Fan is idle in an area where the ambient temperature exceeds this shut off, it will not restart until the internal temperature falls below 104 degrees F.
1.3 ACOUSTICS
The HS Series Fan, when installed properly, operates with little or no noticeable noise to the building occupants. There are, however, some considerations to be taken into account in the system design and installation. When installing the HS Series Fan above sleeping areas, select a location for mounting which is as far away as possible from those areas. Avoid mounting near doors, fold-down stairs or other uninsulated structures which may transmit sound. Insure a solid mounting for the HS Series Fan to avoid structure-borne vibration or noise.
The velocity of the outgoing air must also be considered in the overall system design. With small diameter piping, the "rushing" sound of the outlet air can be disturbing. The system design should incorporate a means to slow and quiet the outlet air. The use of the RadonAway Exhaust Muffler, p/n 24002, is strongly recommended.
Page 4 of 8 IN007 Rev K
1.4 GROUND WATER
Under no circumstances should water be allowed to be drawn into the inlet of the HS Series Fan as this may result in damage to the unit. The HS Series Fan should be mounted at least 5 feet above the slab penetration to minimize the risk of filling the HS Series Fan with water in installations with occasional high water tables.
In the event that a temporary high water table results in water at or above slab level, water will be drawn into the riser pipes thus blocking air flow to the HS Series Fan. The lack of cooling air will result in the HS Series Fan cycling on and off as the internal temperature rises above the thermal cutoff and falls upon shutoff. Should this condition arise, it is recommended that the HS Series Fan be disconnected until the water recedes allowing for return to normal operation.
1.5 CONDENSATION & DRAINAGE
(WARNING!: Failure to provide adequate drainage for condensation can result in system failure and damage the HS Series Fan).
Condensation is formed in the piping of a mitigation system when the air in the piping is chilled below its dew point. This can occur at points where the system piping goes through unheated space such as an attic, garage or outside. The system design must provide a means for water to drain back to a slab hole to remove the condensation.
The use of small diameter piping in a system increases the speed at which the air moves. The speed of the air can pull water uphill and at sufficient velocity it can actually move water vertically up the side walls of the pipe. This has the potential of creating a problem in the negative pressure (inlet) side piping. For HS Series Fan inlet piping, the following table provides the minimum recommended pipe diameters as well as minimum pitch under several system conditions. Use this chart to size piping for a system.
Pipe Diam.
Minimum Rise per Foot of Run*
@ 25 CFM @ 50 CFM @ 100 CFM
4" 1/32 " 3/32 " 3/8 "
3" 1/8 " 3/8 " 1 1/2 "
*Typical operational flow rates:
HS3000, or HS5000 20 - 40 CFM
HS2000 50 - 90 CFM
All exhaust piping should be 2" PVC.
Run
Rise
1.6 SYSTEM MONITOR AND LABEL
A properly designed system should incorporate a "System On" Indicator for affirmation of system operation. A Magnehelic pressure gauge is recommended for this purpose. The indicator should be mounted at least 5 feet above the slab penetration to minimize the risk of filling the gauge with water in installations with occasional high water tables. A System Label (P/N 15022) with instructions for contacting the installing contractor for service and also identifying the necessity for regular radon tests to be conducted by the building occupants, must be conspicuously placed where the occupants frequent and can see the label.
1.7 SLAB COVERAGE
The HS Series Fan can provide coverage of well over 1000 sq. ft. per slab penetration. This will, of course, depend on the sub-slab aggregate in any particular installation and the diagnostic results. In general, sand and gravel are much looser aggregates than dirt and clay. Additional suction points can be added as required. It is recommended that a small pit (2 to 10 gallons in size) be created below the slab at each suction hole.
1.8 ELECTRICAL WIRING
The HS Series Fan plugs into a standard 120V outlet. All wiring must be performed in accordance with the National Fire Protection Association’s (NFPA)”National Electrical Code, Standard #70”-current edition for all commercial and industrial work, and state and local building codes. All wiring must be performed by a qualified and licensed electrician. Outdoor installations require the use of a U.L. listed watertight conduit. Ensure that all exterior electrical boxes are outdoor rated and properly caulked to prevent water penetration into the box. A means, such as a weep hole, is recommended to drain the box.
1.8a ELECTRICAL BOX (optional)
The optional Electrical Box (p/n 20003) provides a weather tight box with switch for outdoor hardwire connection. All wiring must be performed in accordance with the National Fire Protection Association’s (NFPA)”National Electrical Code, Standard #70”-current edition for all commercial and industrial work, and state and local building codes. All wiring must be performed by a qualified and licensed electrician.
Outdoor installations require the use of a U.L. listed watertight conduit. Ensure that all exterior electrical boxes are outdoor rated and properly caulked to prevent water penetration into the box. A means, such as a weep hole, is recommended to drain the box.
1.9 SPEED CONTROLS
Electronic speed controls can NOT be used on HS Series units.
IN007 Rev K
2.0 INSTALLATION
2.1 MOUNTING
Mount the HS Series Fan to the wall studs, or similar structure, in the selected location with
(4) 1/4" x 1 1/2" lag screws (not provided). Insure the HS Series Fan is both plumb and level.
2.2 DUCTING CONNECTIONS
Make final ducting connection to HS Series Fan with flexible couplings. Insure all connections are tight.
Do not twist or torque inlet and outlet piping on HS Series Fan or leaks may result.
2.3 VENT MUFFLER INSTALLATION
Install the muffler assembly in the selected location in the outlet ducting. Solvent weld all connections.
The muffler is normally installed above the roofline at the end of the vent pipe.
2.5 OPERATION CHECKS & ANNUAL SYSTEM MAINTENANCE
____ Make final operation checks by verifying all connections are tight and leak-free.
____ Insure the HS Series Fan and all ducting is secure and vibration-free.
____ Verify system vacuum pressure with Magnehelic. Insure vacuum pressure is within normal operating range and less than the maximum recommended as shown below:
HS2000 14" WC
HS3000 21" WC
HS5000 40" WC
(Above are based on sea-level operation, at higher altitudes reduce above by about 4% per 1000 Feet.)
If these are exceeded, increase number of suction points.
____ Verify Radon levels by testing to EPA protocol.
Addendum
PRODUCT SPECIFICATIONS
*Power consumption varies with actual load conditions
Inlet: 3.0" PVC
Outlet: 2.0" PVC
Mounting: Brackets for vertical mount
Weight: Approximately 18 lbs.
Size: Approximately 15"W x 13"H x 8"D
Minimum recommended inlet ducting (greater diameter may always be used ):
HS3000, HS5000 --- 2.0" PVC Pipe
HS2000 --- Main feeder line of 3.0" or greater PVC Pipe
Branch lines (if 3 or more) may be 2.0" PVC Pipe
Outlet ducting: 2.0" PVC
Storage temperature range: 32 - 100 degrees F.
Thermally protected
Locked rotor protection
Internal Condensate Bypass
Page 8 of 8 IN007 Rev K
IMPORTANT INSTRUCTIONS TO INSTALLER
Inspect the HS Series Fan for shipping damage within 15 days of receipt. Notify RadonAway® of any damages immediately. RadonAway® is not responsible for damages incurred during shipping. However, for your benefit, RadonAway® does insure shipments.
There are no user serviceable parts inside the fan. Do not attempt to open. Return unit to factory for service.
Install the HS Series Fan in accordance with all EPA standard practices, and state and local building codes and state regulations.
Provide a copy of this instruction or comparable radon system and testing information to the building occupants after completing system installation.
WARRANTY
RadonAway® warrants that the HS Series Fan (the “Fan”) will be free from defects in materials and workmanship for a period of 90 days from the date of purchase (the “Warranty Term”).
RadonAway® will replace any Fan which fails due to defects in materials or workmanship during the Warranty Term. The Fan must be returned (at Owner’s cost) to the RadonAway® factory. Any Fan returned to the factory will be discarded unless the Owner provides specific instructions along with the Fan when it is returned regardless of whether or not the Fan is actually replaced under this warranty. Proof of purchase must be supplied upon request for service under this Warranty.
This Warranty is contingent on installation of the Fan in accordance with the instructions provided. This Warranty does not apply where any repairs or alterations have been made or attempted by others, or if the unit has been abused or misused. Warranty does not cover damage in shipment unless the damage is due to the negligence of RadonAway®.
1 YEAR EXTENDED WARRANTY WITH PROFESSIONAL INSTALLATION.
RadonAway® will extend the Warranty Term of the fan to one (1) year from date of purchase or fifteen (15) months from the date of manufacture, whichever is sooner, if the Fan is installed in a professionally designed and professionally installed active soil depressurization system or installed as a replacement fan in a professionally designed and professionally installed active soil depressurization system by a qualified installer. Proof of purchase and/or proof of professional installation may be required for service under this warranty. Outside the Continental United States and Canada the extended Warranty Term is limited to one (1) year from the date of manufacture.
RadonAway® is not responsible for installation, removal or delivery costs associated with this Warranty.
LIMITATION OF WARRANTY
EXCEPT AS STATED ABOVE, THE HS SERIES FANS ARE PROVIDED WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE.
IN NO EVENT SHALL RADONAWAY BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF, OR RELATING TO, THE FAN OR THE PERFORMANCE THEREOF.
RADONAWAY’S AGGREGATE LIABILITY HEREUNDER SHALL NOT IN ANY EVENT EXCEED THE AMOUNT OF THE PURCHASE PRICE OF SAID PRODUCT. THE SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY SHALL BE THE REPAIR OR REPLACEMENT OF THE PRODUCT, TO THE EXTENT THE SAME DOES NOT MEET WITH RADONAWAY’S
WARRANTY AS PROVIDED ABOVE.
For service under this Warranty, contact RadonAway for a Return Material Authorization (RMA) number and shipping information. No returns can be accepted without an RMA. If factory return is required, the customer assumes all shipping costs, including insurance, to and from factory.
RadonAway® 3 Saber Way Ward Hill, MA 01835 USA TEL (978) 521-3703
FAX (978) 521-3964
Email to: Returns@RadonAway.com
Record the following information for your records:
Serial No. Purchase Date mailto:Returns@RadonAway.com
INSTALLATION & OPERATING INSTRUCTIONS
Instruction P/N IN015 Rev E
FOR CHECKPOINT IIa TM P/N 28001-2 & 28001-3
RADON SYSTEM ALARM
INSTALLATION INSTRUCTIONS
(WALL MOUNTING)
Select a suitable wall location near a vertical section of the suction pipe. The unit should be mounted about four or five feet above the floor and as close to the suction pipe as possible. Keep in mind that with the plug-in transformer provided, the unit must also be within six feet of a 120V receptacle. NOTE: The Checkpoint IIa is calibrated for vertical mounting, horizontal mounting will affect switchpoint calibration.
Drill two ¼” holes 4” apart horizontally where the unit is to be mounted.
Install the two ¼” wall anchors provided.
Hang the CHECKPOINT IIa from the two mouting holes located on the mounting bracket. Tighten the mounting screws so the unit fits snugly and securely against the wall.
Drill a 5/16” hole into the side of the vent pipe about 6” higher than the top of the unit.
Insert the vinyl tubing provided about 1” inside the suction pipe.
Cut a suitable length of vinyl tubing and attach it to the pressure switch connector on the CHECKPOINT IIa.
CALIBRATION AND OPERATION.
The CHECKPOINT IIa units are calibrated and sealed at the factory to alarm when the vacuum pressure falls below the factory setting and should not normally require field calibration. Factory Settings are:
28001-2 -.25” WC Vacuum 28001-3 -.10” WC Vacuum
To Verify Operation:
With the exhaust fan off or the pressure tubing disconnected and the CHECKPOINT IIa plugged in, both the red indicator light and the audible alarm should be on.
Turn the fan system on or connect the pressure tubing to the fan piping. The red light and the audible alarm should go off.
The green light should come on.
Now turn the fan off. The red light and audible alarm should come on in about two or three seconds and the green light should go out.
Manufactured by:
RadonAway
Ward Hill, MA (978)-521-3703
WARRANTY INFORMATION
Subject to applicable consumer protection legislation, RadonAway warrants that the CHECKPOINT IIa will be free from defective material and workmanship for a period of (1) year from the date of purchase. Warranty is contingent on installation in accordance with the instructions provided. This warranty does not apply where repairs or alterations have been made or attempted by others; or the unit has been abused or misused. Warranty does not include damage in shipment unless the damage is due to the negligence of RadonAway. All other warranties, expressed or written, are not valid. To make a claim under these limited warranties, you must return the defective item to RadonAway with a copy of the purchase receipt.
RadonAway is not responsible for installation or removal cost associated with this warranty. In no case is RadonAway liable beyond the repair or replacement of the defective product FOB RadonAway.
THERE ARE NO WARRANTIES WHICH EXTEND
BEYOND THE DESCRIPTION ON THE FACE
HEREOF. THERE IS NO WARRANTY OF
MERCHANTIBILITY. ALL OTHER WARRANTIES,
EXPRESSED OR WRITTEN, ARE NOT VALID.
For service under these warranties, contact RadonAway for a Return Material Authorization (RMA) number and shipping information. No returns can be accepted without an RMA. If factory return is required, the customer assumes all shipping costs to and from factory.
������ �������������� � !���"�##$"� %&���%� &� �'(�) *))+),- ��. *�.+/0- ���������� �����&1 �"�##$"�� %&���%� &�����2 *�/ +)2-
�/�(. *�(+)3-4)'(�)�*�.0+2 ,-�������%$�&$� 4, *�./- 4)')/�2) *�.0+./- (��2 *)+/2-.'�/�(. *2)+.3-�,�(. *��+3 �-4)'��. *��)+(-�'��) *(�+/,- 4,'��. *�(3+/0-� �&$�� �!�" �!
567785�958::658�58;
<8=�
9;6>�?<;;�6@:8AB�<B:8
?C8@�>A>8�<: DE85958::65<F8G
HIJ�KLIM�N�IOPK�HQRSKJ�G8
89�CD;8:
8T6A;;U�:9AV8G�D@�A�W
QLPOX
HPYQRSXJ�7D;B�V<5V;8�=D
9A@8;�ZD6@B<@> POX�=8ZA;8�@
9B C<>C�958::658� VD@@8VB<D@ PLIOQ HQQRQ[J POM HPMRSYJ POX�=8ZA;8�@9B ;D?�958::658 VD@@8VB<D@PPOPK HPSRQKJ
P[OIM HPPR\PJ PLPPOPK HQMRXKJWQLPOM HPPQRIJPLPOQ HIPRS[JPSOIM HPIRQ\J
RYM[�HRKQJ�:9AV8�V58AB8
G�7U�I :9AV85�9AG:�?C8@�:6
5=AV8�
ZD6@B8GR�GD�@DB�D7:B
56VBR�
95DE<G8:�9ABC�=D5�58;
<8=�D=� DE85958::658R�
POX�=8ZA;8 @9B�CC� 958::658…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.