W912DR18R0055_-_Attachment_AR_-_Bldg_65_SSDS_O_and_M.pdf.5ms0eat.partial

PDF 3 MB Posted

Attached to
Enviromental AE Services/W912DRDR18R0055
Solicitation number
W912DR-18-S-0009
Issued by

About this file

Attachment AR - Bldg 65 SSDS O&M

View the file

Other files

File Type Posted
W912DR18R0055_-_Amendment_0004_9-5-18.pdf PDF
W912DR18R0055_-_Attachment_BR_-App_G2_Final_OU_&_VMP_Tech_Memo_-_Sept_2014-11-01-15.pdf PDF
W912DR18R0055_-_Attachment_BS_-App_G1OU6_Summary_of_Subsurface_Soil_Gas_2010.pdf PDF
W912DR18R0055_-_Attachment_BQ_-2017_OU6_and_OU7_Report_Draft_7-2018.pdf PDF
W912DR18R0055_P00003_Solicitation_8-31-18.pdf PDF
W912DR18R0055_P00002_Solicitation_8-31-18.pdf PDF
W912DR18R0055_-_Attachment_BC_-DRAFT_2017_OU8_GWMR_8.4.18.pdf PDF
W912DR18R0055_-_Attachment_BA_-Draft_OU8_SSDS_Report_Tables_1-3.pdf PDF
W912DR18R0055_-_Attachment_BN_-2016-04_Draft_Comm_Inv_Plan_041216.pdf PDF
W912DR18R0055_-_Attachment_BL_-2016_Proposed_OU7_Sampling_Program.pdf PDF
W912DR18R0055_-_Attachment_AT_-_DLA-Richmond_OU-8_S_Lobe_Long_Term_Pump_Test_Tech_Memo_2015-12-01_Draft.pdf PDF
W912DR18R0055_-_Attachment_BJ_-VAG830484_tletter_2015.pdf PDF
W912DR18R0055_-_Attachment_BB_-Draft_OU8_SSDS_Report_2017_REV1_clean.docx DOCX document
W912DR18R0055_-_Attachment_BI_-VAG830484_GeneralPermit2013.pdf PDF
W912DR18R0055_-_Attachment_AS_-_Boring_Logs_PWS.pdf PDF
W912DR18R0055_-_Attachment_BM_-2016_Proposed_OU8_Sampling_Program.pdf PDF
W912DR18R0055_-_Attachment_AZ_-Draft_OU_8_Jul2016_Qtr_Monitoring_TM_092816.pdf PDF
W912DR18R0055_-_Attachment_BP_-Complete_RFI_and_Gov't_responses_8-30-18.pdf PDF
W912DR18R0055_-_Attachment_BE_-_Foma;_DSCR_Bldg_151_Vapor_Mitigation_1-22-18.pdf PDF
W912DR18R0055_-_Attachment_AW_-DRAFT_-_BDGR_OM_Manual_3.pdf PDF
W912DR18R0055_-_Attachment_BK_-2016_Proposed_OU6_Sampling_Program.pdf PDF
W912DR18R0055_-_Attachment_AY_-_OMM_Plan_Bldg_151_SSDS_May_2018.docx DOCX document
W912DR18R0055_-_Attachment_AX_-DRAFT_Bldg_151_SSDS_OMM_Manual_5.11.18_combined.pdf PDF
W912DR18R0055_-_Attachment_BF_-FINAL_OU6_Bldg_151_SSDS_DesignREV1_6.12.18_combined.pdf.nhd3u0q.partial PDF
W912DR18R0055_-_Attachment_AU_-_DRAFT_-_BDGR_OM_Manual_1.pdf PDF
W912DR18R0055_-_Attachment_BO_-Bldg_65_SSDS_O_and_M.pdf PDF
W912DR18R0055_-_Attachment_BG_-Tech_Memo_PFOS_PFOA_2_.pdf PDF
W912DR18R0055_-_Attachment_BH_-VAG830484_Discharge_Monitoring_Report_(DMR).pdf PDF
A_DR-R-0055_RFIs_8-13-18_GOVT_Response_Part_2__8-20-18.docx DOCX document
A_DR-R-0055_RFI_and_responses_Part_1_8-14-18.pdf PDF
W912DR18R0055_-_Attachment_L_-_J151255-2_UDS_Level_2_Report_Final_Report.pdf PDF
W912DR18R0055_-_Attachment_AH_-_Site_visit_Northern_lobe_pump_test_1.jpg JPG image
W912DR18R0055_-_Attachment_H_-_Draft_2018_Annual_Vapor_Rpt_OU7_Bldg_72_7.24.18REV1_combined.pdf PDF
W912DR18R0055_-_Attachment_Z_-_DSCR_2017_OU_8_GWMR_Tables.pdf PDF
W912DR18R0055_-_Attachment_R_-_Site_visit_OU7_3.jpg JPG image
W912DR18R0055_-_Attachment_AG_-_Site_visit_BDGR_6.JPG JPG image
W912DR18R0055_-_Attachment_AD_-_Site_visit_BDGR_3.jpg JPG image
W912DR18R0055_-_Attachment_J_-J151095-1_UDS_Level_2_Report_Final_Report.pdf PDF
W912DR18R0055_-_Attachment_AM_-_June_2018_Planning_Meeting-Compressed.pptx PPTX presentation
W912DR18R0055_-_Attachment_AP_(2)_8_9_18_site_visit_Sign_In_sheet_Pg.2.jpg JPG image
W912DR18R0055_-_Attachment_AE_-_Site_Visit_BDGR_4.jpg JPG image
W912DR18R0055_-_Attachment_N_-_OU7_biowalls.pptx PPTX presentation
W912DR18R0055_-_Attachment_AC_-_Site_visit_BDGR_2.jpg JPG image
W912DR18R0055_-_Attachment__F_-_20171117_DSCR_FINAL_WorkPlanOU7_Remedial_Optimization.pdf PDF
W912DR18R0055_-_Attachment_AJ_-_2018_Draft_Management_Action_Plan_7.18.18REV1_clean.docx DOCX document
W912DR18R0055_-_Attachment_T_-_Figure_4-1_-_Proposed_Wells.pdf PDF
W912DR18R0055_-_Attachment_AN_-_Visit_Request_Form.pdf_-_Adobe_Acrobat_Pro.pdf PDF
W912DR18R0055_-_Attachment_X_-_DRAFT_2017_OU8_GWMR_8.4.18.docx DOCX document
W912DR18R0055_-_Attachment_P_-_Site_visit_OU7_1.jpg JPG image
W912DR18R0055_-_Attachment_G_-_DRAFT_OU-7_Optimization_Memo_-_FINAL.docx DOCX document
Show 40 more

Latest 50 of 75 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

460 West Gay Street West Chester, PA 19380

AECOM Technical Services 8005 Outer Circle Road

Brooks City-Base, TX 78235

P.O. # 10PG13792SA05

Operation & Maintenance Manual

Equipment Description: EN656M72XL, GX-30, Inline Filter, Relief Valve, Gauges in custom shed

JG10E-2423

July 29, 2010

Description Date Revision

Item Qty. Supplier Description Part Number Misc ID Weight 1 1 Ametek Rotron Regenerative Blower EN656M72XL 110 2 1 Gasho Base Weldment B-71 105 3 1 Solberg Mfg. 2 1/2" Inline Filter CSL-851-250HC 15 4 1 Universal 2" Dilution Valve CCS-2 GA-0471 8

4.1 1 Apollo 2" Bronze Ball Valve 64-108-01 2 5 1 Fisher 1" Relief Valve 289H-41 set @ 75" H2O 4 6 2 Gasho Vacuum Gauges 25.0.160.IWC.012.HG 1 7 1 Gasho Pressure Gauge 25.0.160.IWC.006.PSI 1 8 3 SMC Specialties Isolation Valves 025-4F4M-BT 1 9 1 Gasho Moisture Separator GX-30 140

9.1 1 Gasho Basket 12

9.2 1 Gasho Cover Plate 1500-C-0507-4 4" Female 14

9.3 1 Jaeger Tri-packs® 1

9.4 1 Cooney 4" Clean out cap 2

9.5 1 Oil Rite Sight Gauge B1559-1-7 7" C - C 1

9.6 2 Oil Rite Adapters B1656-4 1/2"NPT - 1/2-20 1 10 1 Grainger Manual Sludge Pump 400H 2 11 1 Dwyer Instruments Liquid Level Switch L6-EPB-B-3-S-0 3 12 1 Apollo 1" Drain Valve 64-104-01 1

50 1 Horizon Structures Metal Shed 6' x 4' 51 1 McMaster Carr Hazardous Heater 1752K71 120VAC/1ph/60hz, 15A

51.1 1 McMaster Carr Thermostat 1877K23 5 52 1 McMaster Carr 12" Ventilation Fan 2208K19 115/230VAC/1ph/60hz, 4A 10 53 1 McMaster Carr Thermostat 1877K23 4

53.1 1 McMaster Carr Louvers Air intake 2047K313 Recessed mount 6

53.2 1 McMaster Carr Louvers- outlet 2047K313 Surface mount 6 54 1 McMaster Carr Lights 1586K85 Ceiling mount 12

54.1 1 Grainger XP On/Off switch 2AV98 2

Electrical 60 1 ICP Nema 4 Control Panel with red beacon light 50 61 1 General Electric Power Disconnect Switch THN 3362R 60a, 3R 12 62 1 Breaker Panel 62 1 General Electric Distribution panel with Main Lug TM2010RCU 100A Nema 3R 8

62.1 1 General Electric Breaker, Main THQL2160 2P 60 A 60 Amp, 2 pole 1

62.2 1 General Electric Breaker, Fan THQL1115 1P 15A 15 Amp. 1 pole 1

62.3 1 General Electric Breaker, Heater THQL1115 1P 20A 20 Amp, 1 pole 1

62.4 1 General Electric Breaker, Lights THQL1115 1P 15A 15 Amp. 1 pole 1

62.5 1 General Electric Breaker, GFI THQL1115 1P 15A 15 Amp. 1 pole 1

Gasho, Inc.

JG10E-2423

(2) Identical Units

Environmental / Chemical Processing Blowers

EN 656 & CP 656

3.0 HP Sealed Regenerative w/Explosion-Proof Motor

4.14

7.

15.42

6.

5.

105.2

391.7

6.

9.

STRAIGHT THDS

2.23

BOTH PORTS

6.

(4X) MTG

HOLES

19.37 492.0

.1

2.

5.51

0.59

15.12

182.6 7.19

2.

.7

0.

.3 4.92

382.5 12.81 325.4

11.420 290.1

STD. DIRECTION

OF ROTATION

NOTES

1 TERMINAL BOX CONNECTOR HOLE 3/4” NPT.

2 DRAWING NOT TO SCALE, CONTACT FACTORY FOR SCALE CAD DRAWING.

3 CONTACT FACTORY FOR BLOWER MODEL LENGTHS NOT SHOWN.

IN

MM

Part/Model Number

EN656M5XL EN656M72XL EN656M86XL CP656FU72XLR

Specification Units 080060 080059 080058 080142 Motor Enclosure - Shaft Mtl. - Explosion-proof-CS Explosion-proof-CS Explosion-proof-CS Chem XP-SS Horsepower - 3 3 3 3 Phase - Frequency - Single-60 hz Three-60 hz Three-60 hz Three-60 hz Voltage AC 208-230 208-230/460 575 208-230/460 Motor Nameplate Amps Amps (A) 15.5-14.5 7.4/3.7 3.0 7.4/3.7 Max. Blower Amps Amps (A) 17 10/5 4.1 10/5 Inrush Amps Amps (A) 95-86 54/27 21.6 54/27 Service Factor - 1.0 1.0 1.0 1.0 Starter Size - 1 0/0 0 0/0 Thermal Protection - Class B - Pilot Duty Class B - Pilot Duty Class B - Pilot Duty Class B - Pilot Duty XP Motor Class - Group - I-D, II-F&G I-D, II-F&G I-D, II-F&G I-D, II-F&G

Shipping Weight Lbs Kg

64.4

53.1

53.1

53.1

Voltage - ROTRON motors are designed to handle a broad range of world voltages and power supply variations. Our dual voltage 3 phase motors are factory tested and certified to operate on both: 208-230/415-460 VAC-3 ph-60 Hz and 190-208/380-415 VAC-3 ph-50 Hz. Our dual voltage 1 phase motors are factory tested and certified to operate on both: 104-115/208-230 VAC-1 ph-60 Hz and 100-110/200-220 VAC-1 ph-50 Hz. All voltages above can handle a ±10% voltage fluctuation.

Special wound motors can be ordered for voltages outside our certified range.

Operating Temperatures - Maximum operating temperature: Motor winding temperature (winding rise plus ambient) should not exceed 140°C for Class F rated motors or 120°C for Class B rated motors. Blower outlet air temperature should not exceed 140°C (air temperature rise plus inlet temperature). Performance curve maximum pressure and suction points are based on a 40°C inlet and ambient temperature. Consult factory for inlet or ambient temperatures above 40°C.

Maximum Blower Amps - Corresponds to the performance point at which the motor or blower temperature rise with a 40°C inlet and/or ambient temperature reaches the maximum operating temperature.

XP Motor Class - Group - See Explosive Atmosphere Classification Chart in Section I

D 19

This document is for informational purposes only and should not be considered as a binding description of the products or their performance in all applications. The performance data on this page depicts typical performance under controlled laboratory conditions. AMETEK is not responsible for blowers driven beyond factory specified speed, temperature, pressure, flow or without proper alignment. Actual performance will vary depending on the operating environment and application.

AMETEK products are not designed for and should not be used in medical life support applications. AMETEK reserves the right to revise its products without notification. The above characteristics represent standard products. For product designed to meet specific applications, contact AMETEK Technical & Industrial Products Sales department.

AMETEK TECHNICAL & INDUSTRIAL PRODUCTS

75 North Street, Saugerties, NY 12477 USA: +1 215-256-6601 - Europe: +44 (0) 845 366 9664 - Asia: +86 21 5763 1258 Customer Service Fax: +1 215.256.1338 www.ametektip.com cus-serv Highlight cus-serv Highlight cus-serv Highlight

Environmental / Chemical Processing Blowers

EN 656 & CP 656

3.0 HP Sealed Regenerative w/Explosion-Proof Motor

FEATURES

Manufactured in the USA - ISO 9001 and NAFTA compliant

Maximum pressure: 75 IWG Maximum vacuum: 73 IWG Standard motor: 3.0 HP, explosion-proof Cast aluminum blower housing, impeller , cover & manifold; cast iron

UL & CSA approved motor with permanently sealed ball bearings for explosive gas atmospheres Class I Group D minimum

Sealed blower assembly Quiet operation within OSHA standards

MOTOR OPTIONS

International voltage & frequency (Hz)

BLOWER OPTIONS

Corrosion resistant surface treatments & sealing options Remote drive (motorless) models

ACCESSORIES

Flowmeters reading in SCFM Filters & moisture separators Pressure gauges, vacuum gauges, & relief valves

Variable frequency drive package

Blower Performance at Standard Conditions 60 Hz 50 Hz

In ch es o f W at er m ba r m ba r

M ot or W in di ng Te m p

Ri se

°C

Air Flow Rate - SCFMAir Flow Rate - SCFM

Temperature curves are based on standard model

Air Flow Rate - m3/hourAir Flow Rate - m3/hour

In ch es o f W at er M ot or

W in di ng

Te m p Ri se °C

Bl ow er A ir Te m p

Ri se

°C

Bl ow er A ir Te m p

Ri se

°C

Temperature curves are based on standard model

Legend Pressure:

Suction:

EN656M72XL

EN656M5XL

Legend Pressure:

Suction:

EN656M72XL

EN656M5XL

0 20 40 60 80 100 120 140 160 180 200 220

0 34 68 102 136 170 204 238 272 306 340 374

0 20 40 60 80 100 120 140 160 180 200 220

0 34 68 102 136 170 204 238 272 306 340 374

D 20

This document is for informational purposes only and should not be considered as a binding description of the products or their performance in all applications. The performance data on this page depicts typical performance under controlled laboratory conditions. AMETEK is not responsible for blowers driven beyond factory specified speed, temperature, pressure, flow or without proper alignment. Actual performance will vary depending on the operating environment and application.

AMETEK products are not designed for and should not be used in medical life support applications. AMETEK reserves the right to revise its products without notification. The above characteristics represent standard products. For product designed to meet specific applications, contact AMETEK Technical & Industrial Products Sales department.

AMETEK TECHNICAL & INDUSTRIAL PRODUCTS

75 North Street, Saugerties, NY 12477 USA: +1 215-256-6601 - Europe: +44 (0) 845 366 9664 - Asia: +86 21 5763 1258 Customer Service Fax: +1 215.256.1338 www.ametektip.com

Line

Solberg – Where the Best is in Store for You!

APPLICATIONS & EQUIPMENT

FEATURES & SPECIFICATIONS

OPTIONS (Inquiries Encouraged)

CONFIGURATION DRAWING

1151 Ardmore Ave. Itasca, IL 60143 USA Tel: 630/773-1363 Fax: 630/773-0727

E-mail: sales@solbergmfg.com Web Site: www.solbergmfg.com with with FPT Rated Flow SCFM Polyester Paper Inlet & DIMENSIONS - inches Nominal Element Approx.

Element Element Outlet A B C D E F G Rating Rating Wt. lbs

I CSL-825-038HC CSL-824-038HC 3/8" 3 5/8 9/16 3 3/4 1 7/8 9/16 3 1/2 3 18 25 0.88 I CSL-825-050HC CSL-824-050HC 1/2" 3 5/8 9/16 3 3/4 1 7/8 9/16 3 1/2 3 18 25 0.88

I CSL-843-050HC CSL-842-050HC 1/2" 4 3/8 9/16 5 7/8 2 1/2 9/16 5 3 1/4 20 55 3

I CSL-825-075HC CSL-824-075HC 3/4" 3 3/4 9/16 3 3/4 1 7/8 9/16 3 1/2 3 24 25 0.88

S CSL-843-075HC CSL-842-075HC 3/4" 4 3/8 9/16 5 7/8 2 1/2 9/16 5 3 1/4 25 55 3

I CSL-843-100HC CSL-842-100HC 1" 4 3/8 3/4 5 7/8 2 5/8 3/4 5 3 1/4 35 55 3

S CSL-849-100HC CSL-848-100HC 1" 6 1/2 3/4 7 5/16 4 1/4 3/4 6 13/16 5 1/4 40 115 5

I CSL-843-125HC CSL-842-125HC 1 1/4" 4 3/8 3/4 5 7/8 2 5/8 3/4 5 3 1/4 55 55 3

S CSL-849-125HC CSL-848-125HC 1 1/4" 6 1/2 3/4 7 5/16 4 1/2 3/4 6 13/16 5 1/4 60 115 5 I CSL-849-150HC CSL-848-150HC 1 1/2" 6 1/2 3/4 7 5/16 4 1/2 3/4 6 13/16 5 1/4 80 115 5

I CSL-851-200HC CSL-850-200HC 2" 10 1/4 3/4 8 3/4 5 3/4 7 5/8 9 1/4 175 290 15

I CSL-851-250HC CSL-850-250HC 2 1/2" 10 1/2 1 1/4 8 3/4 5 1/2 1 1/4 7 5/8 9 1/4 210 290 15 I CSL-239-300C* CSL-238-300C* 3" 15 3/4 2 7/8 13 1/4 8 7/8 2 7/8 12 11 300 570 33

CSL14-304

pg. 2

IN

LE

T

VA

C U

U M

F

IL

TE

R

S C

SL

, C

T, V

L, V

S, L

R S

Se rie s

SMALL COMPACT

INLET VACUUM FILTERS

"CSL" Series 3/8” - 3” FPT

Vacuum Pumps & Systems – P.D., Side Channel, Rotary Vane, Screw, Piston Vacuum Packaging Equipment Vacuum Lifters Blowers - Side Channel & P.D.

Intake Suction Filters Pneumatic Conveying Systems Soil Venting/Remediation Remote Installations for Piston

& Screw Compressors

Printing Industry Factory Automation Equip Leak Detection Systems Woodworking Medical Industry

Vacuum gauge available Dome hood for high holding capacity Available in Stainless Steel

Vacuum level: Typically 1x10-3 mmHg (1.3x10-3 mbar) Polyester: 99%+ removal efficiency standard to 5 micron Paper: 99%+ removal efficiency standard to 2 micron Brazed fittings for High vacuum duty Stainless steel torsion clips for durability Low pressure drop Positive engagement O-ring seal system Fully-drawn one piece canister

Large dirt holding capacity and Easy field cleaning, especially when mounted horizontally or inverted Rugged all steel construction w/baked enamel finish Various media Temp (continuous): min -15°F (-26°C ) max 220°F (104°C ) Filter change out differential: 10” - 15” H2O over initial delta P Pressure drop graphs available upon request

Epoxy coated housings Activated carbon prefilter for odor Support brackets

Alternate top-to-canister fastening system for low pressure or pulsating systems

Dimension tolerance + 1/4”

*1/4" taps standard on inlet and outlet

CSL 824-851

Series

CSL 239/238

Series

I = Industrial Duty S = Severe Duty

Ro ta ry P os iti ve

Bl ow er S ile nc er s

8.9

Fi lte rs a nd

Fi lte r- Si le nc er s

8.9

Se e pa ge s 1.

1– 1.

fo r o rd er in g in fo rm at io n w w w .u ni ve rs al si le nc er

.c om

CCS/CS Series Filter-Silencers

CCF/CF Series Filters

Universal Silencer’s cartridge filters and filter-silencers offer high-performance filtration and silencing in a convenient, economical cartridge configuration. Choose from four standard models for pipe sizes ranging from ¹⁄₂" to 16" and for flow capacities ranging from 15 to 7,700 CFM. Three types of filter element media—pleated paper, pleated felt, or wire mesh—are available to suit your application.

The CCF and CF series filters are high-quality air filters without a silencing section.

The CCF has a removable weatherhood, and the CF has a removable top plate. Our CCS and CS intake filter-silencers have a built-in silencing section. The CCS features a removable weatherhood, and the CS has a removable top plate for easy access to the filter element.

Performance Benefits Durability Weatherhoods for CCF and CCS sizes 2¹⁄₂" through 5" are rugged blue ABS composite material that may be painted.

All other components are carbon steel construction with a high-quality semi-gloss enamel finish.

High Performance Unique design options, combined with the latest manufacturing techniques, ensure optimum performance and long life even under demanding conditions.

Functional Choice of filter only or filter-silencer.

Easy to Maintain Removable lightweight weatherhood (CCS and CCF) or removable top plate (CS and CF) for easy access to the filter element.

Versatile Interchangeable element options for desired filtration characteristics in the same housing.

CCS Series (with weatherhood) CS Series (with top plate)

CCF Series (with weatherhood) CF Series (with top plate)

¹⁄₂

Pipe Size

³⁄₄

1¹⁄₄

1¹⁄₂

2¹⁄₂

3¹⁄₂

34-K50-TT*

34-K70-TT*

34-K01-TT*

34-K21-TT*

34-K15-TT*

34-K02-TT*

34-K25-TT*

34-K03-TT*

34-K35-TT*

34-K04-TT*

34-K04-AA*

34-K05-TT*

34-K05-AA*

34-K06-AA*

34-K08-AA*

34-K10-AA*

34-K12-AA*

34-K14-AA*

34-K16-AA*

34-M50-TT*

34-M70-TT*

34-M01-TT*

34-M21-TT*

34-M15-TT*

34-M02-TT*

34-M25-TT*

34-M03-TT*

34-M35-TT*

34-M04-TT*

34-M04-AA*

34-M05-TT*

34-M05-AA*

34-M06-AA*

34-M08-AA*

34-M10-AA*

34-M12-AA*

34-M14-AA*

34-M16-AA*

34-L21-TT*

34-L15-TT*

34-L02-TT*

34-L25-TT*

34-L03-TT*

34-L35-TT*

34-L04-TT*

34-L04-AA*

34-L05-TT*

34-L05-AA*

34-L06-AA*

34-L08-AA*

34-L10-AA*

34-L12-AA*

34-L14-AA*

34-L16-AA*

34-N21-TT*

34-N15-TT*

34-N02-TT*

34-N25-TT*

34-N03-TT*

34-N35-TT*

34-N04-TT*

34-N04-AA*

34-N05-TT*

34-N05-AA*

34-N06-AA*

34-N08-AA*

34-N10-AA*

34-N12-AA*

34-N14-AA*

34-N16-AA*

CCS CS CCF CF

Part Numbers

*Specify “P” at end of part number for unit with pleated paper elements, “F” for pleated felt or “W” for wire mesh.

Sizes ¹⁄₂"–1" Use CCS or CS Series cus-serv Line cus-serv Rectangle

Ro ta ry P os iti ve

Bl ow er S ile nc er s

8.10 Fi

lte rs a nd

Fi lte r-

Si le nc er s

8.10 Se

e pa ge s

1.

1–

1.

fo r o rd er in g in fo rm at io n w w w

.u ni ve rs al si le nc er .c om

CCS/CS Series Filter-Silencers

CCF/CF Series Filters

¹⁄₂

³⁄₄

1¹⁄₄

1¹⁄₂

2¹⁄₂

3¹⁄₂

4 (NPT)

4 (flanged)

5 (NPT)

5 (flanged)

P (size)

1,100 2,200 3,000 4,300 5,900 7,700

Rated Flow Cap.

(CFM)

8.00 8.00 8.00 9.00 9.00 9.00

13.44 13.44 13.44 13.44 13.44 13.44 13.44 18.00 20.00 24.00 24.00 30.00 30.00

D

3.13 3.13 3.13 3.50 3.50 3.50 6.75 6.75 6.75 6.75 6.75 6.75 6.75 9.50

18.00 11.50 11.50 15.44 15.44

H

6.00 6.00 6.00 6.50 6.50 6.50

10.00 10.00 10.00 10.00 10.00 10.00 10..00 14.00 14.00 18.00 18.00 24.00 24.00

B

1.00 1.00 1.13 1.13 4.00 1.81 4.00 4.00 4.00 4.00 4.00 4.00 4.00

N L Approx. Weight with Paper Elements

CCF CCS CF CS CCF CCS CF CS CCF CCS CF CS

1.00 1.00 1.13 1.13 3.00 1.81 3.00 3.00 3.00 3.00 3.00 3.00 3.00

1.00 1.00 1.13 1.13 4.00 1.81 4.00 4.00 4.00 4.00 4.00 4.00 4.00

1.00 1.00 1.13 1.13 3.00 1.81 3.00 3.00 3.00 3.00 3.00 3.00 3.00

3.50 3.50 3.50 7.50 7.50 7.63 7.63

10.50 8.38

10.50 13.31 21.88 15.38 15.38 19.38 19.38

6.50 6.50 6.50 7.88 7.88 7.88

17.69 17.69 17.69 17.69 19.63 18.25 19.56 25.25 33.88 29.25 29.25 36.25 36.25

3.50 3.50 3.50 7.13 7.13 7.25 7.25

10.13 8.00

10.13 12.75 21.38 14.19 14.19 18.25 18.25

6.50 6.50 6.50 7.88 7.88 7.88

17.31 17.31 17.31 17.31 19.25 17.88 19.13 24.75 33.38 28.13 28.13 35.06 35.06

Use

CCS

Series

Use

CS

Series

Use

CCS

Series

Use

CS

Series

Use

CCS

Series

Use

CS

Series

Noise Attenuation, CCS/CS

1,000 2,000 4,000 8,000

Attenuation, dB Octave Band Center Frequency, Hz

Pressure Drop, All Models

0.7 1.6 2.8 4.4 6.3

50% 75%

100% 125% 150%

Pressure Drop

(in. of H20)

Percentage of Rated Flow

All models have a ¹⁄₈" FNPT tap for installation of a gauge or manometer to monitor pressure drop. Sizes ¹⁄₂" through 3¹⁄₂" are standard with female pipe thread connection (FNPT). Sizes 4" and 5" are available with female threads or flanges. Please specify “threaded” or “flanged” when you order 4" and 5" sizes. Sizes 6" through 16" are standard with 150# ANSI drilled plate flanges. Rated capacity is based upon exit velocity of approximately 5,500 ft/min. If pressure drop allowance permits, capacity may be increased by as much as 50%.

cus-serv Line cus-serv Line cus-serv Rectangle

Rectangle

Filter Element 020806.doc 2/9/06

460 West Gay Street

West Chester, PA 19380 610-692-5650 Fax 610-692-5837 cs@gasho.org

Gasho Replacement Inlet Filter Elements

High quality replacement elements are available for the filters of various manufactures used on packages built by Gasho.

Paper elements are normally used in inlet filters and replaced when they are dirty.

Polyester elements are cleanable.

Filter Size, In. Gasho

Filter # Box

Quantity

O.D. I.D. Ht. List Price

1 GA-0470 6 5-13/16 4 2 $17.00

2 GA-0471 6 5-13/16 4 2-1/2 $17.00

2.5-3 GA-0472 2 9-3/4 7-1/4 4 $23.00

4 GA-1063 2 9-3/4 7-1/4 6 $27.00

5 GA-0474 1 11-1/2 9-7/8 7 $35.00

6 GA-0475 1 13-5/8 11-5/8 8-5/8 $53.00

8-12 GA-1163 1 17 13 10 $185.00

GA-0471 Elements are frequently used to replace GA -0470

Manufacturer Cross Reference

Gasho Filter #

Universal Filter #

EM Prod.

Filter #

Full-On Filters #

Solberg #

GA-0470 81-0470 FOF810470 32-00

GA-0471 81-0471 P-642 FOF810471 32-02

GA-0472 81-0472 P-974 FOF810472 32-04

GA-1063 81-1063 P-976 FOF811063 32-06

GA-0474 81-0474 P-1197 FOF810474 32-08

GA-0475 81-0475 P-13118 FOF810475 32-10

GA-1163 81-1163 P-171310 FOF811163 32-12

IPG’s 64 series brass ball valves comply with the latest editions of these published standards:

• AGA Z21.15.CGA9.1 • ASME/ANSI B16.38

• AGA No. 3-88 • MSS SP-110

• ANSI B1.20.1 •UL Guide YSDT

• ANSI B16.18 •UL Guide YRPV

• CAN/CGA-3.16-M88 •UL Guide VQGU

• ASME/ANSI B16.33 •

A

B

C

D

A

B

C

D

Your local Conbraco distributor is:

Apollo®, RP&C and Conbraco are a registered trademarks of Conbraco Industries Inc. which reserves the right to change specifications without notice.©2002 Conbraco Industries Inc.

P.O. Box 247 Matthews, NC 28106

(704) 841-6000 Fax: (704) 841-6020 http://www.conbraco.com

Standards Compliance

Description Materials

1. Body Brass UNI 5705-65

2. Retainer Brass UNI 5705-65

3. Ball Brass UNI 5705-65

4. Seats PTFE

5. Stem Seals PTFE

6. O-Ring NBR 75 Shore A

7. Packing Gland Brass UNI 5705-65

8. Nut Plated Steel

9. Stem Brass UNI 5705-65 Cr Plated

10. Lever Handle Plated Steel 1/4" - 2" Models Aluminum 2 1/2" - 4" Models

Size Part No. A B C D (Cv)

1/4" NPT 64-101-01 0.39 2.02 1.75 3.85 6

3/8" NPT 64-102-01 0.39 2.02 1.75 3.85 7

1/2" NPT 64-103-01 0.59 2.44 1.88 3.85 19

3/4" NPT 64-104-01 0.78 2.71 2.28 4.80 34

1" NPT 64-105-01 0.98 3.07 2.44 4.80 50

1-1/4" NPT 64-106-01 1.25 3.42 3.07 6.02 104

1-1/2" NPT 64-107-01 1.57 3.89 3.34 6.02 268

2" NPT 64-108-01 1.96 4.33 3.79 6.37 309

2-1/2" NPT 64-109-01 2.56 5.59 5.02 8.07 629

3" NPT 64-100-01 3.15 6.45 5.45 8.07 1018

4" NPT 64-10A-01 3.94 7.60 6.34 10.23 1622

-20 0 50 100 150 200 250 300 350 400 Temperature (F˚)

P r e s s u r e

Materials of Construction

64-100 Dimensional Data Size Part No. A B C D (Cv) 1/2" 64-203-01 0.59 2.53 1.88 3.85 19 3/4" 64-204-01 0.78 2.99 2.28 4.80 34 1" 64-205-01 0.98 3.58 2.44 4.80 50 1-1/4" 64-206-01 1.25 4.09 3.07 6.02 104 1-1/2" 64-207-01 1.57 4.56 3.34 6.02 268 2" 64-208-01 1.96 5.43 3.79 6.37 309 2-1/2" 64-209-01 2.56 6.93 5.02 8.07 629 3" 64-200-01 3.15 8.09 5.45 8.07 1018

64-200 Dimensional Data

Optional Kits Valve Size Locking Handle Stem Extensions Balancing Stops 1/4", 3/8" & 1/2" 78-1659-01 78-1501-0 78-1506-01 3/4" & 1" 78-1660-01 78-1502-0 78-1507-01 1-1/4" & 1-1/2" 78-1661-01 78-1503-0 78-1508-01 2" 78-1662-01 78-1504-0 78-1509-01 2-1/2" & 3" - 78-1505-0 78-1510-01

PHFL64S 4/02

CG 7.5M Printed in U.S.A.

NOTE: Specify (-07) suffix for T-Handle i.e. 64-105-07.

64-100 Series

I n t e r n a t i o n a l A Division of Conbraco Industires, Inc.

Bulletin 71.4:289

D

X

08/90

Regulators www.FISHERregulators.com

289 Series Spring-Loaded Relief Valves

The 289 Series relief valve is a throttling relief valve used downstream of pressure regulators to protect the downstream system from overpressure. A smooth throttling action minimizes pressure surges in the system during emergency operation. These relief valves are available in 1/4, 3/4, 1, or 2-inch sizes with spring ranges (relief pressure settings) from 5 inches w.c. to 75 psig (0.01 to 5.2 bar).

All sizes above 1/4-inch feature a pitot tube booster (figure 1) for achieving the highest possible relief capacity with a minimum buildup of system pressure.

When the valve is opening, high gas velocity through the orifice creates an area of relatively low pressure near the end of the pitot tube. This pitot tube effect forms a partial vacuum above the diaphragm which helps to open the valve.

The relief valve diaphragm functions as a valve disk to control flow in all types except the 289H and 289HH, which use O-ring seats. The nitrile or neoprene seating surfaces provide tight shutoff. The 289 Series relief valves are ideal for low pressure settings due to the increased sensitivity provided by the large diaphragm area.

Features

• Throttling Type Relief—Smooth, sensitive throttling action minimizes pressure surges.

• High Flow Rates—As shown by the figure 4 capacity curves, high flow rates can be achieved with minimum pressure buildup due to the boosting system which increases the relief valve opening.

• Small Size—The 289 Series relief valves are small and compact, making them suitable for areas limited in space.

• Reliability Due to Simplicity—A single internal as-sembly decreases the possibility of mechanical failure.

Figure 1. Type 289H and 289HH Relief Valves

1-INCH TYPE 289H AND 289HH 2-INCH TYPE 289H

W1870-2

W1870-2

W0210-1 W0209-2

Available Configurations Type 289A (figure 2): 1/4-inch spring-loaded relief valve for relief pressure settings of 3 to 22 psig, (0.21 to 1.5 bar) two spring ranges Type 289H (figure 1): 1 or 2-inch spring-loaded relief valve for relief pressure settings of 1 to 50 psig (0.07 to 3.5 bar) four spring ranges, in the 1-inch size and of 7-inches w.c. to 10 psig, (0.02 to

0.69 bar), four spring ranges, in the 2-inch size Type 289HH (figure 1): 1-inch spring-loaded relief valve for relief pressure settings of 45 to 75 psig (3.1 to 5.2 bar) Type 289L (figure 3): 3/4 or 1-inch spring-loaded relief valve for relief pressure settings of 10 to 40-inches w.c., (0.03 to 0.1 bar), two spring ranges Type 289U (figure 2): 1/4-inch spring-loaded relief valve for relief pressure settings of 5-inches w.c. to 3 psig, (0.01 to 0.21 bar), two spring ranges

Inlet Connections Type 289L: 3/4 or 1-inch NPT female Types 289A and 289U: 1/4-inch NPT female Type 289H: 1 or 2-inch NPT female Type 289HH: 1-inch NPT female

Outlet (Vent) Connections Same size as inlet connection

Maximum Allowable Relief (Inlet) Pressure(1) and Maximum Relief Set Pressure

See table 1

Capacity Data See figure 4

Standard Construction Materials Valve Body and Spring Case Types 289A and 289U: Zinc Type 289H (1-inch), 289HH, and 289L: Aluminum Type 289H (2-inch): Cast iron body with aluminum spring case Diaphragm Type 289A: Neoprene Types 289H and 289HH: Nitrile or fluoroelastomer All Others: Nitrile

1. The pressure/temperature limits in this bulletin and any applicable standard limitation should not be exceeded.

2. Bubble-tight shutoff can not be attained at settings below 5 psig with fluoroelastomer O-ring seat.

Specifications

Orifice Types 289A and 289L: Aluminum Type 289H (2-inch Only): Brass or Stainless steel O-Ring Seat (Types 289H and 289HH Only):

Nitrile or Fluoroelastomer(2)

O-Ring Seat Holder and Washer (1-inch Types 289H and 289HH Only): Aluminum Seat Washer (2-inch Type 289H Only): Stainless steel Pitot Tube Types 289H and 289HH (1-inch), and 289L:

Aluminum Type 289H (2-inch): Brass or Stainless steel Gaskets Type 289L: Neoprene All Others: Composition Spring: Zinc-plated steel Diaphragm Plate Types 289A and 289U: Zinc All Others: Zinc-plated steel Closing Cap Type 289L: Plastic, Aluminum, or Zinc Type 289H (2-inch): Zinc

Material Temperature Capabilities(1)

With Nitrile and Neoprene Elastomers:

–20 to150°F (–29 to 66°C) With Fluoroelastomers: 20 to 300°F (–7 to 149°C) Available with Types 289H and 289HH only

Approximate Shipping Weight Types 289A and 289U: 0.75 lb (0.34 kg) Type 289H 1-inch Size: 4 lb (1.8 kg) 2-inch Size: 15 lb (6.8 kg) Type 289HH: 4 lb (1.8 kg) Type 289L: 1.5 lb (0.7 kg)

Options

• TFE diaphragm protector (Types 289A and

289U only)

• wire-seal on closing cap (1-inch Type 289L only)

Figure 2. Type 289U Relief Valve (Also Typical of Type 289A Relief Valve)

Figure 3. Type 289L Relief Valve

W1870-2 W0212-1

W1870-2 W0203-1

Figure 4. Capacity for 0.6 Specific Gas at 14.7 Psia and 60° F

1” TYPE 289H

VENT SCREEN INSTALLED

50 PSIG

1D745527142

40 PSIG

1D745527142

30 PSIG

1D745527142

20 PSIG

1D745527142

A

B

C

D

A—15 PSIG

1D751527022

B—10 PSIG

1D892327022

C—4 PSIG

D—1 PSIG

1F826927052

IN

L

E T

P R

E S

S U

R E

P

S

IG

0 10 20 30 40 50 60 70 80

0.6 SPECIFIC GRAVITY GAS FLOW RATE—

THOUSAND CUBIC FEET PER HOUR—14.7 PSIA AT 60°F

0.6 SPECIFIC GRAVITY GAS FLOW RATE—

THOUSAND CUBIC FEET PER HOUR—14.7 PSIA AT 60°F

IN

L

E T

P R

E S

S U

R E

P

S

IG

0 4 8 12 16 20 24 28 32 36 40 44 48 52 56 60 64

10 PSIG

1B536927052

7 PSIG

1B536827052

5 PSIG

1B536827052

2 PSIG

1B536627052

1 PSIG

1B536627052

1/2 PSIG

1B536527052

2” TYPE 289H

NO VENT RESTRICTION 1

NOTE:

1 LESS THAN 5% CAPACITY LOSS CAN BE EXPECTED WITH THE VENT SCREEN

INSTALLED ON THE 2-INCH TYPE 289H AT MAXIMU FLOW.

2. WHEN SELECTING ANY RELIEF VALVE FOR INSTALLATION DOWNATREAM OF A

REGULATOR, THE CAPACITY OF THE RELIEF VALVE SHOULD BE COMPARED WITH THE

WIDE-OPEN CAPACITY OF THE REGULATOR.

3. BUBBLE POINT RELIEF SETTING AND SPRING PART NUMBER ARE NOTED ON

EACH CURVE.

4. TO CONVERT TO EQUIVALENT CAPACITIES OF OTHER GASES, MULTIPLY VALUES

OBTAINED FROM CURVE BY THE FOLLOWING FACTORS: AIR–0.78, PROPANE–0.628,

BUTANE–0.548, NITROGEN–0.789

B2309

Figure 4.Capacity for 0.6 Specific Gas at 14.7 Psia and 60° F (Continued)

IN

L

E T

P R

E S

S U

R E

P

S

IG

0 10 20 30 40 50 60 70 80

0.6 SPECIFIC GRAVITY GAS FLOW RATE—

THOUSAND CUBIC FEET PER HOUR—14.7 PSIA AT 60°F

0.6 SPECIFIC GRAVITY GAS FLOW RATE—

THOUSAND CUBIC FEET PER HOUR—14.7 PSIA AT 60°F

IN

L

E T

P R

E S

S U

R E

P

S

IG

0 10 20 30 40 50 60 70 80 90 100 110 120

NOTE:

1. WHEN SELECTING ANY RELIEF VALVE FOR INSTALLATION DOWNATREAM OF A

REGULATOR, THE CAPACITY OF THE RELIEF VALVE SHOULD BE COMPARED WITH THE

WIDE-OPEN CAPACITY OF THE REGULATOR.

2. BUBBLE POINT RELIEF SETTING AND SPRING PART NUMBER ARE NOTED ON

EACH CURVE.

3. TO CONVERT TO EQUIVALENT CAPACITIES OF OTHER GASES, MULTIPLY VALUES

OBTAINED FROM CURVE BY THE FOLLOWING FACTORS: AIR–0.78, PROPANE–0.628,

BUTANE–0.548, NITROGEN–0.789

60 PSIG

50 PSIG

75 PSIG

1” TYPE 289HH

VENT SCREEN INSTALLED

SPRING 1D745527142

60 PSIG

50 PSIG

75 PSIG

1” TYPE 289HH

NO VENT RESTRICTION

SPRING 1D745527142

B2310

Figure 4. Capacity for 0.6 Specific Gas at 14.7 Psia and 60° F (Continued)

IN

L

E T

P R

E S

S U

R E

P

S

IG

0 100 200 300 400 500 600 700

0.6 SPECIFIC GRAVITY GAS FLOW RATE—

THOUSAND CUBIC FEET PER HOUR—14.7 PSIA AT 60°F

0.6 SPECIFIC GRAVITY GAS FLOW RATE—

THOUSAND CUBIC FEET PER HOUR—14.7 PSIA AT 60°F

IN

L

E T

P R

E S

S U

R E

P

S

IG

24 IN. WC

2 IN. WC

0F058227022

7 IN. WC

0V060227022

3 PSIG

0F058227022

NOTE:

1. WHEN SELECTING ANY RELIEF VALVE FOR INSTALLATION DOWNATREAM OF A

REGULATOR, THE CAPACITY OF THE RELIEF VALVE SHOULD BE COMPARED WITH THE

WIDE-OPEN CAPACITY OF THE REGULATOR.

2. BUBBLE POINT RELIEF SETTING AND SPRING PART NUMBER ARE NOTED ON

EACH CURVE.

3. TO CONVERT TO EQUIVALENT CAPACITIES OF OTHER GASES, MULTIPLY VALUES

OBTAINED FROM CURVE BY THE FOLLOWING FACTORS: AIR–0.78, PROPANE–0.628,

BUTANE–0.548, NITROGEN–0.789

TYPE 289U

2 PSIG

0F058227022

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10,000

IN

L

E T

P R

E S

S U

R E

IN

C H

E S

W .C

IN

L

E T

P R

E S

S U

R E

IN

C H

E S

W .C

1 PSIG

(28 IN. W.C.)

1B413727022

3/4” AND 1” TYPE 289L

VENT SCREEN INSTALLED

3/4” SIZE

1” SIZE

1/2 PSIG (14 IN. WC) 1B413627222

B2311

Installation

The 289 Series relief valves may be installed in any position. However, the outlet connection must be protected against the entrance of rain, snow, insects, or any other foreign material that may plug the outlet or affect the opening and closing of the valve (see figure 5). If it is necessary to pipe away the outlet, remove the outlet screen (if one is present).

Flow through the valve must be as indicated by the flow direction arrow on the body (inlet connection is marked on some sizes).

The spring case vent on the 2-inch Type 289H is tapped and plugged. This vent opening must remain plugged to allow the pitot tube booster to function.

Overpressure

Overpressure conditions in a regulating system may cause personal injury or equipment damage due to bursting of pressure-containing parts or explosion of accumulated gas. Check the system for damage if any of the maximum allowable relief (inlet) pressure ratings in table 1 are exceeded.

Ordering Information

When ordering, specify:

1. Type number and size

2. Relief pressure range and setting desired

3. Type of gas (natural gas, air, etc.); list any factors such as impurities in the gas that may affect compat-ibility of the gas with valve trim parts

4. Temperature and specific gravity of the gas

5. Maximum relief (inlet) pressure and flow rate desired

6. Line size and end connection size of adjacent piping

7. For Types 289H and 289HH, specify material of diaphragm and O-ring seat; for 2-inch Type 289H, specify material of orifice and pitot tube

8. Options desired, if any

Table 1. Spring Ranges and Maximum Allowable Relief (Inlet) Pressures

,SEZISYDOB

SEHCNI

EPYT

EGNARGNIRPS

)SGNITTESERUSSERPFEILER(

TRAPGNIRPS

REBMUN

ELBAWOLLAMUMIXAM

GNITTESFEILER )1(

ELBAWOLLAMUMIXAM

)TELNI(FEILER

ERUSSERP )2(

4/1 U982

.c.wsehcni-52ot5 gisp3ot.c.wsehcni-02

)rabm26ot21( )rab12.0otrabm05(

220722060V0 220722850F0

)rab12.0(gisp3 )rab96.0(gisp01

A982 gisp31ot3 gisp22ot11

)rab9.0ot12.0( )rab5.1ot67.0(

220723650Z0 220722862B1

)rab25.1(gisp22 )rab1.3(gisp54

1ro4/3 L982

.c.wsehcni-8ot3

.c.wsehcni-81ot5

.c.wsehcni-81ot01

.c.wsehcni-04ot21

)rabm02ot7( )rabm54ot21( )rabm54ot52( )rabm99ot03(

220725314B1 2100X2113N1 210X7197A31 210X6197A31

)rabm99(.c.wsehcni-04 )rab25.0(gisp7

1 H982 gisp5.4ot1 gisp51ot4 gisp02ot01 gisp05ot51

)rab3.0ot960.0( )rab0.1ot82.0( )rab4.1ot96.0(

)rab4.3ot0.1(

250729628F1 220723298D1 220725157D1 241725547D1

)rab4.3(gisp05 )rab9.6(gisp001

2 H982

.c.wsehcni-81ot7 gisp52.2ot5.0 gisp7ot57.1 gisp01ot4

54ot71( rabm ) )rab61.0ot430.0(

)rab25.0ot21.0( )rab96.0ot82.0(

250725635B1 250726635B1 250728635B1 250729635B1

)rab96.0(gisp01 )rab7.1(gisp52

1 HH982 gisp57ot54 )rab2.5ot1.3( 241725547D1 )rab2.5(gisp57 )rab9.6(gisp001

.elbaliavaegnargnirpstsehgihhtiW.1 .pudliubsulpgnitteserusserpfeilermumixaM.2

©Fisher Controls International, Inc., 1970, 1990; All Rights Reserved

Fisher and Fisher Regulators are marks owned by Fisher Controls International, Inc. The Emerson logo is a trade mark and service mark of Emerson Electric Co.

All other marks are the property of their respective owners.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

For information, contact Fisher Controls:

Marshalltown, Iowa 50158 USA 28320 Gallardon, France Sao Paulo 05424 Brazil Singapore 128461

Printed in U.S.A.

Bulletin 71.4:289

Regulatorswww.FISHERregulators.com

Figure 5. Typical Installation of a 289 Series Relief Valve

Figure 6. Dimensions

INCHES

(mm)

TYPE 289H AND 289HH (1-INCH) TYPE 289H (2-INCH)

1.88 (48)

1.78 (46)

8.69 (221)

0.38 (10)

4.12 (105)

2.12 (54)

3.56 (91)

7.12 (181)

8.94 (228)

TYPE 289L (3/4 AND 1-INCH)

4.88 (124)

5.38 (137)

1.94 (50)

1.25 (32)

TYPE 289A AND 289U (1/4-INCH)

3.06D (77.7)

0.38 (9.7)

2.25 (57.2)

1/4-18 NPT

11B6509-B

AL5113-B

AF8621-F

AU2493-B

A1393-2

PROTECTIVE VENT PIPE

WITH RAIN CAP

2” TYPE 289H

RELIEF VALVE

LARGE SERVICE

REGULATOR

AJ4698-C

A1947-1

Pressure and Vacuum Gauges 7-21-00.doc

Pressure and Vacuum Gauges

We use both standard gauges and liquid filled gauges from a variety of manufacturers.

Gauges are installed on our packages with gauge isolation valves (gauge cocks) part number BRS-VA-025-4F4M-BT. The gauge isolation valve can be used as a snubber while reading the gauge by opening it slightly. To protect gauges from damage due to shocks or pulsations in the system, gauge isolation valves should be closed except when the gauge is being read.

Liquid filled gauges may display incorrect readings due to variations in atmospheric pressure. To determine if a gauge is subject to this condition, the liquid filled cavity should be temporarily vented to atmosphere. Most liquid filled gauges have a seal plug in the liquid filled cavity. Remove this plug to allow the cavity to be vented to atmosphere.

In some instances the case can be lightly squeezed to burp it. Replace the plug.

J. E. GASHO & ASSOCIATES, INC.

Authorized Manufacturer’s Representative

Air / Gas Moving Equipment

460 W. GAY STREET

WEST CHESTER, PA 19380

PHONE: 610-692-5650 FAX: 610-692-5837

2 ½” Dia.

Gauge

Gauge Isolation Valve Shown in closed position

Liquid seal plug

¼” NPT

025 Series Options Material Options Brass Body, Nickel Plated Brass Ball, Teflon® Seats, Stainless Handle Screw

Seal Options Buna-N, Ethylene Propylene, Fluoroelastomer (Viton®), Neoprene

Body Options 1/4 Female x 1/4 Female NPT 1/4 Female x 11/16-16 Male 1/4 Female x 1/4 Male NPT 1/4 Female x 7/16-24 Female 1/4 Female x 1/8 Female NPT 1/4 Female x 1/4 Female Flare 1/4 Female x 1/8 Male NPT 1/4 Female x 3/8 Compression 1/4 Female x 1/4 Hose Barb

Handle Options Zinc Die Cast Lever (Standard), Zinc Die Cast Lever with Red Vinyl Sleeve, Steel Lever, Steel Lever, Round Handle, Steel Lever, Steel Lever with Red Vinyl Sleeve, Round Zinc Die Cast Handle, Black Nylon T-Handle, Blue Nylon Knob, .312 x 1” Stem, Screw Slot Headed Ball

Plating Options Electroless Nickel, Black Zinc

025 SERIES BALL VALVE

025 One-Way Ball Valve Design Considerations

The 025 Series One-Way Ball Valve compact design promotes multiple configurations to fit the exact end use application. The 025 Ball Valve Series is rated to 500 psi and will support flow and pressure only in the flow direction. The 025 Series has a one-piece body construction, stamped with directional flow arrows, to cover 1/4” NPT end configuration applications. The Zinc Die Cast Lever Handle is standard. Handles can be ordered Reversed - to lie over the outlet when the valve is in the open position. UL configurations are available and rated to 250 psi. UR configurations are available and rated to 500 psi.

Example: Inlet End Outlet End Seal Handle Plating 1/4 FNPT 1/4 MNPT Buna-N Steel ENP

SMC Part Number: 025-4F4M-B,SH,ENP

The handle will lie over the Inlet port when the valve is in the open position. SMC Part Numbers are a description of the valve as read left to right, Inlet to Outlet.

Example: 025-4F4M-B,SH,ENP = 1/4 FNPT Inlet x 1/4 MNPT Outlet

Maximum Operating Pressure - 500 psi Maximum Operating Temperature - 180 Degrees F Ball Through Hole Diameter - .218

SMC will quote alternate materials or customize our standard products when quantities ensure competitive pricing.

Contact Customer Service at (651) 653-0599, FAX - (651) 653-0989, E-Mail - info@specialtymfg.com

Moisture Seps. 6/11/08

Moisture Separators

Moisture separators are used to remove water and other liquids from air streams.

They are typically used on the inlet of vacuum systems to remove water and other contaminants before they enter the vacuum pump. The air volume of the moisture separator reduces the velocity of the air stream to allow liquids to precipitate. Up to 95% water removal is possible. The models GX-30 & GX-60 are rated for 29.9 in. Hg. vacuum.

Other moisture separators are rated to 18 in. Hg. higher vacuum ratings available.

Standard accessories include a sight gauge, drain valve, and a hand operated sludge pump.

Inside the top of the separator is a basket with “tri-packs®” demister material to promote condensation of vapors.

Options include: 1 to 3 level switches, automatic pump down systems, heat tracing, vacuum gauges, and thermometers.

Model Nominal Liquid Diameter Height Inlet Discharge Cleanout Weight Number Flow Rate Capacity (inches) (inches) Size Size Size

GX-30 250 8 16 47 3" 3" 4" 100

GX-60 500 22 20 57 4" 4" 4" 150

GX-90 1200 30 24 57 6" Flange 6" Flange 4" 240 GX-120 2000 40 24 70 8" Flange 8" Flange 4" 260 GX-200 2000 95 30 85 8" Flange 8" Flange 4" 350

Inlet

Outlet

Drain

Low level Switch port

JA

EG

ER Features

• Jaeger Tri-Packs® are hollow, spherical packings made of injection molded plastic, available in four diameters: 1”, 1 ¼ ”, 2”, and 3 ½ ”.

• Symmetrical geometry made from a unique network of ribs, struts, and drip rods.

• High active surface areas.

• Extremely low pressure drops.

• Extremely high operating capacities.

Benefits

• High mass and heat transfer rates.

• Excellent gas and liquid dispersion characteristics.

• Resist nesting, making removal easy.

• Installs to packed position - no settling.

• Available in a wide variety of plastics.

• Predictable performance.

Jaeger Tri-Packs®

Jaeger Tri-Packs®-PP are NSF Certified to ANSI/NSF Standard 61 when made in polypropylene.

TABLE OF CONTENTS

Features & Benefits 1

Physical Properties Jaeger Tri-Packs® 2

Optimizing Your Design 3

Performance Comparisons 4-8

Pressure Drop Curves 9-12

Flooding Curves 13

Liquid Holdups 14

Jaeger Tri-Packs® vs AIRSTRIP® 15-16

HTU FOR CO2 Desorption 17

Absorption/Scrubbing Data 18

Scaling, Fouling and Disinfection 19-20

Conversion Factors 21

Other Jaeger Packings 22

Properties Table

Size (in.) 1 1 1/4 2 3 1/2

Geometric Surface Area 85 70 48 38

(ft2/ft3)

Packing Factor 28 25 16 12 (1/ft)

Void Space 90 92 93.5 95

Bulk Density (lb/ft3) 6.2 5.6 4.2 3.3

(PP)

Materials.

Twelve standard, injection moldable plastics are available:

Polypropylene (PP) TopEx® (LCP) Polyethylene (PE) Kynar® (PVDF) Polypropylene Halar® (ECTFE)

Glass-Filled (PPG) Teflon® (PFA) Noryl® (PPO) Tefzel® (ETFE) Polyvinylchloride (PVC) Tefzel® Glass- CorzanTM (CPVC) Filled (ETFE-G)

Other plastics are available on request.

IMPORTANT NOTE:

Design data presented in this bulletin are for preliminary cal-culations only. Contact Jaeger before finalizing calculations.

JAEGER TRI-PACKS® is a Registered Trademark of

JAEGER PRODUCTS, INC.

Maximum Operating Temperatures for Plastic Jaeger Tri-Packs®

Jaeger Tri-Packs® are available in a variety of injection-molded plastics for different applications. The maximum operating tempera-tures for these different resins vary from material to material and are also affected by specific process variables. The data present-ed below correspond to maximum continuous operating temperatures at atmospheric pressure and systems that are essentially air and water. The presence of solvents, acids, free radicals, and oxidants needs to be considered. Furthermore, these temperatures correspond to the maximum recommended bed depth for each packing size and material. These maximum bed depths are different depending on the application. Consult with Jaeger in respect to the maximum bed depth for your particular application.

Maximum Temperature (Deg. F) Material (1 atm, air/water, at max. recommended depth) Bulk Density Factor

Polyvinyl Chloride (PVC) 140 1.50 Polyethylene (PE) 160 1.02 Polypropylene (PP) 180 1.00 CorzanTM (CPVC) 230 1.74 Chlorinated Polyvinyl Chloride (CPVC) 210 1.74 Polypropylene - Glass-Filled (10-30%) (PP-G) 210-230* 1.17-1.38* Noryl® (PPO) 230 1.24 Kynar® (PVDF) 280 1.98 Halar® (ECTFE) 290 1.86 Tefzel® (ETFE) 350 1.93 Teflon® (PFA) 400 2.45 Tefzel® - Glass Filled (25% Glass) (ETFE-G) 410 2.2

*Depending on glass content.

Specifications & Physical Properties

Product Bulletin-600

Plastic Jaeger Tri-Packs®

1611 Peachleaf St., Houston, Texas 77039 800-678-0345 Phone: 281-449-9500 Fax: 281-449-9400 www.jaeger.com

JAEGER

Generalized Flooding Curves

Product Bulletin-600

Ambient Air-Water Systems at 1 atm, 70oF

For Air/Water systems at 70oF & 1 atm: C-Factor x 7776.2 = lb/hr-ft2; gpm/ft2 x 499.7 = lb/hr-ft2

SRP - Separations Research Program, University of Texas at Austin.

9/99

1611 Peachleaf St., Houston, Texas 77039 800-678-0345 Phone: 281-449-9500 Fax: 281-449-9400 www.jaeger.com

JAEGER

Conversion Factors

Product Bulletin-600

FROM TO MULTIPLY BY ADD OFFSET

mg/ml ppmW 1.0 1/ft 1/m 3.2808 atm psia 14.696 atm psig 14.696 -14.696 atm torr 760 C F 1.8 32 C K 1 273.15 C-factor (air/water @70oF) ft/se lb/hr ft2 7776.2 F K .5556 255.3722 ft cm 30.48 ft m .3048 ft2/ft3 m2/m3 3.2808 ft3 gal (US) 7.4805 ft3 m3 .0283 g/cm3 lb/ft3 62.428 gm/cm3 kg/m3 1000 gpm/ft2 lb/hr ft2 (water @ 70oF) 499.7 hr sec 3600 in m .0254 in wc/ft dyne/cm3 81.5617 in wc/ft Pa/m 815.6168 kg gm 1000 kg lb 2.2046 kg/m2*sec lb/ft2*hr 737.3402 kg/sec lb/hr 7936.6829 kg mole/m2*sec lbmole/ft2*hr 737.3402 kW hp 1.341 lb gm 453.59 m2 cm2 10000 m2 ft2 10.7639 m2/m3 cm2/cm3 .01 m3 liters 1000 mg/l ppmW 1.0 Millions of Gallons/Day gpm 694.46 min sec 60 ppmW ppbW 1000

Oil-Rite Corporation 4325 Clipper Drive, P.O. Box 1207, Manitowoc, WI. 54221-1207 Telephone: (920) 682-6173 Fax: (920) 682-7699 E-Mail: sales@oilrite.com Web site: www.oilrite.com

Oil-Rite Corporation > B-1559-1

Item # B-1559-1, Level Gages Flush Channel - Steel larger image

Level Gages Flush Channel - Steel Level Gages Flush Channel - Steel can be mounted flush against the outside surface of a reservoir with only a small amount of protrusion. Liquid level gages for flush mounting are used for a multitude of applications, such as on tanks, reservoirs, packaged hydraulic equipment, large steel mill pumps, hydraulic presses, and for any other application where it is desirable to indicate fluid levels. These level gages are used to determine the liquid level inside a metal reservoir by visual observation of the level in a transparent sight. The clarity and condition of the liquid can also be checked. Models with a thermometer will show the temperature of the liquid as well. Extremely sturdy and rigid, these gages come with glass sights mounted inside the steel channel shield to provide maximum protection against breakage. Visibility of the liquid level is excellent through the large sight opening. A reflector enhances the visibility of the liquid level. Liquid level markings can be added on request. Back mounting gages are used on tanks permitting access to the inside, in order to fasten the nuts on the mounting studs inserted in drilled holes in reservoirs. Front mounting gages are used on reservoirs which do NOT permit access to the inside, therefore, the tanks must have two tapped holes, 1/2 - 20 N.F., to receive the mounting studs, which are fastened from the outside.

Specifications Style Plain

Pressure 125 P.S.I. Max.

Temperature 225° F. Max.

Centerline Distance Between Mtg.

Holes 3" to 60"

Body Steel, Plated (Optional Material Available)

Sight Red Line Gage Glass

Seals Buna-N

Mounting Shanks Steel, Plated 1/2-20 N.F.

GUZZLER® 400

HAND PUMP

930 Waterman Avenue East Providence, Rhode Island 02914

Ph: 888-438-1110 Fax: 401-438-2713 Web: www.thebosworthco.com Doc M-PCode-01.01-092807

Inlet & Outlet Ends & Sizes in cm Hose

(Smooth)

N.P.T.

Female (Tapped Inside)

N.P.T.

Male

(Threaded Outside)

Male (Threaded Outside) Garden Hose Barbed

1/2 1.27 •

3/4 1.91 • • • • • 1 2.54 S •

1 1/8 2.86 • • 1 1/4 3.18 •

(S: standard •: optional)

Pump Body Delrin (Gray)

Clamp Ring Delrin, Epoxy-coated Aluminum

Diaphragm Buna Nitrile (Buna N), Buna N Double Sided, Buna-N 3-Ply, Neoprene, Viton, EPDM, Urethane, Silicone

Valves Buna N, Neoprene, Viton, EPDM, Silicone (Silicone only available with umbrella valve)

Available Materials

Performance

Model GH-400

Description Hand pump for use with 1/2” to 1 1/4” hose. Available with either horizontal or vertical handle.

Features • Lightweight, economical

• Durable — tough Delrin® plastic

• Clamp ring adjusts to 12 different handle orientations

• Can be configured with either vertical or horizontal handle

Horizontal Handle

Consult factory for other options.

Vertical Handle

Other Options

Item Standard

Valves Flapper Duckbill Umbrella

Handle Style Horizontal (H) Vertical (V) (removable)

Other

Thru Deck Mounting Kit (only for vertical handle)

Internal Spring

Optional per Stroke per Minute

(@ 90 cycles/min)

0.44 Qt 0.42 L 10 Gals 37.9 L

Max Pressure 20 psi 1.4 kg/cm2

Max Head 12 ft 3.7 m

Max Lift 12 ft 3.7 m

Flow Rate

Dimensions

Length Height

Body incl. H.

Handle incl. V.

Handle incl. H.

Handle Up incl. V.

Handle Up in 10 1/4 12 3/4 12 5 1/2 12 13 5/8 cm 26.0 32.39 30.48 13.97 30.48 34.61

Mounting Holes 4

Weight Mounting Hole Diameter 1/4 in 0.64 cm

Bolt Circle Diameter 6 1/8 in 15.56 cm

1.70 lb 0.77 kg

Hole-to-Hole Distance 4 5/16 in 10.95 cm

Width

Hand-Operated Diaphragm Pumps A little elbow grease is all these pumps need to do their job. All pumps have a Delrin housing. Intake and discharge connections are unthreaded male slip-on style. All pumps have check valves, are self-priming, and can be run dry. Not for use with solids. Maximum discharge pressure is 12 feet of head (5 psi). Maximum viscosity is 100,000 centipoise (similar to toothpaste).

Temperature range is 33° to 140° F.

Common Compatible Chemicals Deionized Water, Diesel Fuel, Glycol, Kerosene, Methanol, Mineral Spirits, Salt Water, Water

Diaphragm Flow Rate, For Overall Size, Material oz/stroke Hose ID Ht. x Wd. x Dp.

Buna-N 14.08 1" 4 1/2" x 5 1/2" x 12 3/4" 4332K17 Buna-N 21.44 1 1/2" 4 1/2" x 5 1/2" x 13 3/8" 4332K18 Silicone 14.08 1" 4 1/2" x 5 1/2" x 12 3/4" 4332K37

930 Waterman Avenue East Providence, RI 02914

Ph: 401-438-1110 888-438-1110 Fax: 401-438-2713 www.thebosworthco.com

Guzzler® GH-400

Pin SetPS4-5

Flapper Valves14

Diaphragm13

TH1/4-20x1/2 (1) diaphragm

HN10-24 (18)

PPH10-24x1/2 (2) clamp ring

PPH10-24x3/4 (10) clamp ring

PPH10-24x5/8 (8) inlet/outlet

Hardware Set12

Vertical Actuator w/pin set11

Horizontal handle w/actuator & pin set9

Vertical Handle w/grip8

Clamp Ring6

Body5

Clevis4

Button3

Outlet Flange2

Inlet Flange1

PART NAMEITEM

PS4-5

PS4-5

IPG’s 64 series brass ball valves comply with the latest editions of these published standards:

• AGA Z21.15.CGA9.1 • ASME/ANSI B16.38

• AGA No. 3-88 • MSS SP-110

• ANSI B1.20.1 •UL Guide YSDT

• ANSI B16.18 •UL Guide YRPV

• CAN/CGA-3.16-M88 •UL Guide VQGU

• ASME/ANSI B16.33 •

A

B

C

D

A

B

C

D

Your local Conbraco distributor is:

Apollo®, RP&C and Conbraco are a registered trademarks of Conbraco Industries Inc. which reserves the right to change specifications without notice.©2002 Conbraco Industries Inc.

P.O. Box 247 Matthews, NC 28106

(704) 841-6000 Fax: (704) 841-6020 http://www.conbraco.com

Standards Compliance

Description Materials

1. Body Brass UNI 5705-65

2. Retainer Brass UNI 5705-65

3. Ball Brass UNI 5705-65

4. Seats PTFE

5. Stem Seals PTFE

6. O-Ring NBR 75 Shore A

7. Packing Gland Brass UNI 5705-65

8. Nut Plated Steel

9. Stem Brass UNI 5705-65 Cr Plated

10. Lever Handle Plated Steel 1/4" - 2" Models Aluminum 2 1/2" - 4" Models

Size Part No. A B C D (Cv)

1/4" NPT 64-101-01 0.39 2.02 1.75 3.85 6

3/8" NPT 64-102-01 0.39 2.02 1.75 3.85 7

1/2" NPT 64-103-01 0.59 2.44 1.88 3.85 19

3/4" NPT 64-104-01 0.78 2.71 2.28 4.80 34

1" NPT 64-105-01 0.98 3.07 2.44 4.80 50

1-1/4" NPT 64-106-01 1.25 3.42 3.07 6.02 104

1-1/2" NPT 64-107-01 1.57 3.89 3.34 6.02 268

2" NPT 64-108-01 1.96 4.33 3.79 6.37 309

2-1/2" NPT 64-109-01 2.56 5.59 5.02 8.07 629

3" NPT 64-100-01 3.15 6.45 5.45 8.07 1018

4" NPT 64-10A-01 3.94 7.60 6.34 10.23 1622

-20 0 50 100 150 200 250 300 350 400 Temperature (F˚)

P r e s s u r e

Materials of Construction

64-100 Dimensional Data Size Part No. A B C D (Cv) 1/2" 64-203-01 0.59 2.53 1.88 3.85 19 3/4" 64-204-01 0.78 2.99 2.28 4.80 34 1" 64-205-01 0.98 3.58 2.44 4.80 50 1-1/4" 64-206-01 1.25 4.09 3.07 6.02 104 1-1/2" 64-207-01 1.57 4.56 3.34 6.02 268 2" 64-208-01 1.96 5.43 3.79 6.37 309 2-1/2" 64-209-01 2.56 6.93 5.02 8.07 629 3" 64-200-01 3.15 8.09 5.45 8.07 1018

64-200 Dimensional Data

Optional Kits Valve Size Locking Handle Stem Extensions Balancing Stops 1/4", 3/8" & 1/2" 78-1659-01 78-1501-0 78-1506-01 3/4" & 1" 78-1660-01 78-1502-0 78-1507-01 1-1/4" & 1-1/2" 78-1661-01 78-1503-0 78-1508-01 2" 78-1662-01 78-1504-0 78-1509-01 2-1/2" & 3" - 78-1505-0 78-1510-01

PHFL64S 4/02

CG 7.5M Printed in U.S.A.

NOTE: Specify (-07) suffix for T-Handle i.e. 64-105-07.

64-100 Series

I n t e r n a t i o n a l A Division of Conbraco Industires, Inc.

Hazardous-Location Convection Heaters Approved for Class 1, Groups B, C, and D, Div. 1 and 2 for use in hazardous locations. Cabinet is steel with a gray finish and has NEMA 4 rating for indoor use and exposure to splashing liquids. Furnished with wall mounting bracket with four 3/8" dia.

mounting holes (fasteners not included). Have three 6" wire leads and operate on 60 Hz, single phase. UL listed.

Optional wall-mount thermostat adjusts from 50° to 90° F and is double pole, double throw (DPDT). Has one 3/4" NPT female conduit connection and two 1/4" dia.

mounting holes (fasteners not included). For 480 VAC or amps greater than 22 a contactor is required to work between the heater and thermostat; see pages 876-878.

Note: Contactors must be located outside the hazardous location.

Volts Watts Btu/Hr. Amps Ht. x Wd. x Dp.

120 VAC 1,800 6,143 15.0 18" x 34" x 9" 1752K71 208 VAC 1,800 6,143 8.7 18" x 34" x 9" 1752K72 208 VAC 3,600 12,286 17.3 18" x 34" x 9" 1752K74 208 VAC 7,600 25,938 36.5 18" x 58" x 9" 1752K77 240 VAC 1,800 6,143 7.5 18" x 34" x 9" 1752K73 240 VAC 3,600 12,286 15.0 18" x 34" x 9" 1752K75 240 VAC 7,600 25,938 31.7 18" x 58" x 9" 1752K78 480 VAC 3,600 12,286 7.5 18" x 34" x 9" 1752K76 480 VAC 7,600 25,938 15.8 18" x 58" x 9" 1752K79 Optional Wall-Mount Thermostat 1877K25

Rectangle

In addition to line voltage applications, these versatile thermostats also support systems with 24 volt controls. All are mercury free and have screw terminal wiring connections and built-in sensors. Come with mounting hardware (unless noted).

Style C has a NEMA 4 enclosure (for indoor/outdoor use; exposure to splashing liquids and dusty environments). The second stage can be adjusted to activate 3 1/2° to 18° F after the first stage.

Style C are UL listed. Enclosures are NEMA 7 (for indoor use; Class I, Group C and D for hazardous location duty) and NEMA 9 (for indoor use; Class II,…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.