Booster Pump Questions.pdf
PDF 59 KB Posted
- Attached to
- Battalion Complex (Amendment 8)
- Solicitation number
- W9123620R0001
View the file
Other files
Show 40 more
Latest 50 of 136 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A B C D E F G
Phase Section Paragraph
2 22 00 00 2.12.2
Oil filled drives is an older technology and not typically offered and/or supported by most booster pump manufacturers. Will electircal drives be acceptable for the booster pump system?
2 22 00 00 2.12.2
Please advise if noise suppression is required for electrical drives. If so, what type of noise suppression is required?
2 22 00 00 2.12.2
Telemetry is typically used in municipal applications. Is this required? If so, please provide specification.
2 Drawing P001
DWP-1 - Is the 220 gpm specified per pump flow or system flow? If it is system flow, can we assume a 33/33/33 split across all 3 pumps?
2 Drawing P001 DWP-1 - What is the minimum suction pressure?
2 Drawing P001
Will a 5HP Triplex Pumping system be acceptable given it meets design performance?
Date
Submitted
Pre-Proposal Inquiry Submission Form W9123620R001
Question
ReferenceSubmitted
By
LEAVE
BLANK
E4TEEZAG
Text Box System flow. Yes, 33/33/33 split across 3 pumps
E4TEEZAG
Text Box Design water pressure at water main entry is 65 PSI
E4TEEZAG
Text Box Acceptable provided it meets design parameters.
E4TEEZAG
Text Box Refer to amended specs 22 00 00