Booster Pump Questions.pdf

PDF 59 KB Posted

Attached to
Battalion Complex (Amendment 8)
Solicitation number
W9123620R0001
Issued by

View the file

Other files

File Type Posted
W9123620R0001P0008 - Amendment 8.pdf PDF
18245_ - AREA T - POWER.pdf PDF
A.07.24 - W9123620R0001(Amendment 7).pdf PDF
W9123620R0001 Amendment 6.pdf PDF
719_BC-PH2_SF423.pdf PDF
719_BC-PH2_MP121.pdf PDF
719_BC -PH2-A-601.pdf PDF
719_BC-PH2_SF600(Amend5).pdf PDF
720_BC-PH3-S504.pdf PDF
719_BC-PH2_26 20 00.pdf PDF
719_BC-PH2_MP111.pdf PDF
719_BC_PH2_Sheet A-200.pdf PDF
719_BC_Sheet - I-003.pdf PDF
719_BC-PH2_SF505.pdf PDF
719_BC-PH2_MP122.pdf PDF
720_BC-PH3-CS103.pdf PDF
719_BC-PH2_MP116.pdf PDF
719_BC-PH2_SF422.pdf PDF
719_BC_Sheet - I-223.pdf PDF
05 12 00.pdf PDF
22 00 00.pdf PDF
720_BC-PH3-CU102.pdf PDF
719_BC_PH2_Sheet A-412.pdf PDF
720_BC-PH3-S215 (1).pdf PDF
719_BC_FFE_PH2_Amendment 5 sheets(Amend5).pdf PDF
719_BC-PH2_SF420.pdf PDF
719_BC-PH2 Sheet EP404.pdf PDF
26 51 00.pdf PDF
719_BC-PH2_SF425.pdf PDF
10 28 13.pdf PDF
23 65 00.pdf PDF
28 31 76.pdf PDF
719_BC_Sheet - I-008.pdf PDF
AMEND005-719_BC-PH2_FA001-FA126.pdf PDF
719_BC-PH2_03 30 00.00 10.pdf PDF
719_BC-PH2_10 21 13.pdf PDF
PH1 TWS TWR piping routing.pdf PDF
720_BC-PH3-SF600.pdf PDF
720_BC_PH3_EL119-EL123_EL502.pdf PDF
719_BC-PH2_FA001_FA111-FA114.pdf PDF
719_BC_Sheet - I-124.pdf PDF
719_BC -PH2-A- 603.pdf PDF
719_BC_PH2_Sheet A-411.pdf PDF
720_BC_PH3_FP001_FP140-FP143.pdf PDF
719_BC-PH2_SF421.pdf PDF
719_BC-PH2_SB106.pdf PDF
720_BC_PH3_A-605.pdf PDF
719_BC-PH2_MP113.pdf PDF
719_BC-PH2_11 46 01.06.pdf PDF
719_BC-PH2_S-001(Amend5).pdf PDF
Show 40 more

Latest 50 of 136 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A B C D E F G

Phase Section Paragraph

2 22 00 00 2.12.2

Oil filled drives is an older technology and not typically offered and/or supported by most booster pump manufacturers. Will electircal drives be acceptable for the booster pump system?

2 22 00 00 2.12.2

Please advise if noise suppression is required for electrical drives. If so, what type of noise suppression is required?

2 22 00 00 2.12.2

Telemetry is typically used in municipal applications. Is this required? If so, please provide specification.

2 Drawing P001

DWP-1 - Is the 220 gpm specified per pump flow or system flow? If it is system flow, can we assume a 33/33/33 split across all 3 pumps?

2 Drawing P001 DWP-1 - What is the minimum suction pressure?

2 Drawing P001

Will a 5HP Triplex Pumping system be acceptable given it meets design performance?

Date

Submitted

Pre-Proposal Inquiry Submission Form W9123620R001

Question

ReferenceSubmitted

By

LEAVE

BLANK

E4TEEZAG

Text Box System flow. Yes, 33/33/33 split across 3 pumps

E4TEEZAG

Text Box Design water pressure at water main entry is 65 PSI

E4TEEZAG

Text Box Acceptable provided it meets design parameters.

E4TEEZAG

Text Box Refer to amended specs 22 00 00