ABBREVIATIONS
ABBREVIATION
AB
AFF
ANR
APPROX
ARCH
ATFP
BC
BEJ
BM
BOC
BOS
BRG
BP
BRP
CFMF
CFS
CJ
CL
CLR
CMU
COL
CONN
CONC
CONT
COORD
DE
DIA
DIAG
DIM
DN
EA
EF
EJ
ELEV, EL
EOS
EQ
EW
EXT
FDN
FFE
FOB
FS
FTG
GA
HORIZ
HS
HSS
JBE
JS
JST
KB
KIPS (k)
LG
LLH
LLV
LSH
LSV
MAX
MCJ
MECH
MFR
MIN
MOW
N/A
NIC
NO
NOM
OC
OPP
PCL
PJF
PL
PLF
PSF
PSI
REINF
REJ
SC
SCHED
SDS
SF
SHT
SIM
SPA
STD
T&B
TOC
TOF
TOM
TOS
TOW
TS
TYP
UON
VERT
WF
WP
WWF
WT
DESCRIPTION
ANCHOR BOLT
ABOVE FINISHED FLOOR
ANCHOR
APPROXIMATELY
ARCHITECTURAL
ANTI-TERRORISM AND FORCE
PROTECTION
BOTTOM CHORD
BUILDING EXPANSION JOINT
BEAM
BOTTOM OF CONCRETE
BOTTOM OF STEEL
BEARING
BEARING OR BASE PLATE
BRICK RELIEF PLATE
COLD-FORMED METAL
FRAMING
COLD-FORMED STEEL
CONTROL JOINT
CENTER LINE
CLEAR
CONCRETE MASONRY UNIT
COLUMN
CONNECTION
CONCRETE
CONTINUOUS
COORDINATE
DECK EDGE
DIAMETER
DIAGONAL
DIMENSION
DOWN
EACH
EACH FACE
EXPANSION JOINT
ELEVATION
EDGE OF SLAB
EQUAL
EACH WAY
EXTENSION
FOUNDATION
FINISHED FLOOR ELEVATION
FACE OF BRICK
FOOTING STEP
FOOTING
GAGE
HORIZONTAL
HIGH STRENGTH
HOLLOW STRUCTURAL SHAPE
JOIST BEARING ELEVATION
JOIST SUBSTITUTE
JOIST
KNUCKLED BEAM
1000 POUNDS
LONG
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
MAXIMUM
MASONRY CONTROL JOINT
MECHANICAL
MANUFACTURER
MINIMUM
MIDDLE OF WALL
NOT APPLICABLE
NOT IN CONTRACT
NUMBER
NOMINAL
ON CENTER
OPPOSITE
PRE-CAST COMPOSITE LINTEL
PREMOLDED JOINT FILLER
PLATE
POUNDS PER LINEAR FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
REINFORCEMENT
ROOF EXPANSION JOINT
STUB COLUMN
SCHEDULE
SELF DRILLING SCREW
SPREAD FOOTING
SHEET
SIMILAR
SPACES/SPACED
STANDARD
TOP AND BOTTOM
TOP OF CONCRETE
TOP OF FOOTING/FOUNDATION
TOP OF MASONRY
TOP OF STEEL
TOP OF WALL
THICKENED SLAB
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
WALL FOOTING
WORKING POINT
WELDED WIRE FABRIC
WEIGHT
COLD-FORMED METAL FRAMING CONSTRUCTION
NOTES
1. COLD-FORMED STEEL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE
AMERICAN IRON AND STEEL INSTITUTE (AISI) "COLD-FORMED STEEL DESIGN MANUAL",
2002 EDITION, INCLUDING THE TRUSS DESIGN MANUAL AND THE NORTH AMERICAN
SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS, 2001
EDITION INCLUDING 2004 SUPPLEMENT.
2. ALL MATERIAL MUST BE 18 GAGE OR GREATER IN THICKNESS AND SHALL HAVE A MINIMUM
YIELD STRENGTH OF Fy = 50 KSI.
5. MEMBER DESIGNATIONS SHALL BE AS FOLLOWS:A B C - D
A = WEB DEPTH (DECIMAL INCHES) X 100
B = SECTION TYPE
C = FLANGE WIDTH (DECIMAL INCHES) X 100
D = BASE METAL THICKNESS (MILS)
SECTION TYPES (B):
S = STUD AND JOIST SECTION WITH FLANGE STIFFENING RETURN LIPS
T = TRACK SECTIONS (NO STIFFENING RETURN LIPS)
U = CHANNEL AND CHANNEL STUDS (NO STIFFENING RETURN LIPS)
F = FURRING CHANNEL
EXAMPLES:
MEMBER WEB SECTION FLANGE BASE METAL
DESIGNATION DEPTH TYPE WIDTH THICKNESS
362S162-33 3-5/8" S 1-5/8" 33 MILS
400T125-68 4" T 1-1/4" 68 MILS
MINIMUM CONNECTION REQUIREMENTS FOR COLD-FORMED WALL MEMBERS ARE AS
FOLLOWS, UNLESS OTHERWISE NOTED:
CONDITION CONNECTION
STUD TO TRACK (2) #10-16 SDS EACH TRACK FLANGE WITH STUD SECURELY
SEATED INTO TRACK
TRACK TO STEEL BEAM 1/8" WELD EACH SIDE, 2" LONG SPACED AT 32" OC OR
(2) 0.145" DIAMETER POWDER ACTUATED FASTENERS
AT 16" OC
EXTERIOR TRACK AISI 1021 3/16" DIAMETER CONCRETE SCREWS @ 2'-8" MAX
TO CONCRETE SLAB OR THROUGH TRACK. SCREW SHALL HAVE A MINIMUM ULTIMATE
FOUNDATION SHEAR CAPACITY OF 900 LBS. PROVIDE 1 1/2" MINIMUM
CONCRETE EMBEDMENT. MINIMUM SCREW SPACING = 4".
MINIMUM SCREW CONCRETE EDGE DISTANCE = 3"
STUD TO STUD (2) #10-16 SDS SPACED AT 1'-4" OC MAX UON
STEEL DECK TO TRACK (2) #10-16 SDS SPACED AT 0'-6" OC MAX UON
6. DEFLECTION OF WALL STUD SPANS FOR LATERAL LOADS SHALL NOT EXCEED A LIMIT OF
L/600.
7. ALL CONNECTION SCREWS SHALL BE ZINC COATED.
8. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3, "STRUCTURAL WELDING CODE -
SHEET STEEL."
9. CONTRACTOR TO PROVIDE TEMPORARY BRACING AND GUYING OF COLD-FORMED METAL
FRAMING TO PROVIDE FOR THE SAFETY OF THE STRUCTURE AND WORK PERSONNEL.
BRACING SHALL REMAIN UNTIL NO LONGER REQUIRED FOR SAFE SUPPORT OF FRAMING.
10. FIELD MODIFICATIONS OF COLD-FORMED STEEL SYSTEMS SHALL NOT BE ALLOWED
WITHOUT PRIOR WRITTEN APPROVAL OF THE ENGINEER OF RECORD.
11. MAINTAIN 3/4" MINIMUM DISTANCE BETWEEN CENTERS OF CONNECTION SCREWS AND
3/4" MINIMUM DISTANCE FROM THE CENTER OF SCREW TO EDGE OF CONNECTED PART.
INSTALL FASTENERS FROM THINNER THROUGH THICKER MATERIAL.
12. MECHANICAL BRIDGING SHALL BE PLACED AT A MINIMUM OF THIRD POINTS ALONG STUD
SPAN FOR ALL LOAD BEARING, SHEAR AND EXTERIOR WALLS LESS THAN 15 FEET TALL,
BUT NOT GREATER THAN 4'-0" OC. BRIDGING SHALL BE IN PLACE PRIOR TO PLACING ANY
LOADS ON THE STUD WALLS.
13. THE CONNECTION OF NONSTRUCTURAL COLD-FORMED STEEL FRAMING SHALL BE
PROVIDED WITH SLIP TYPE CONNECTION WHICH WILL ALLOW FOR DEFLECTION OF THE
BUILDING FRAME - SEE "TYPICAL DEFLECTION TRACK" DETAIL ON SHEET SF503.
14. TYPICAL LOAD BEARING CFMF WALL STUD SHALL BE 8" DEEP UON.
15. LOAD BEARING WALL FRAMING AND X BRACE FRAMING SHALL ALIGN WITH FRAMING ON
THE BUILDING STORY ABOVE/BELOW.
16. CONTINUOUS HSS PROVIDED AT HI ROOF BEARING SERVES AS A CONTINUOUS BEARING
ELEMENT FOR STEEL JOIST FRAMING - SEE ROOF FRAMING PLANS.
CONCRETE CONSTRUCTION NOTES
1. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF
THE AMERICAN CONCRETE INSTITUTE (ACI)
2. CAST-IN-PLACE CONCRETE SHALL ATTAIN THE MINIMUM COMPRESSIVE
STRENGTHS (f'c) OF:
4000 PSI AT 28 DAYS, ALL CONCRETE UON
4000 PSI AT 28 OR 56 DAYS, MASS CONCRETE UON
5000 PSI AT 28 DAYS, ALL SLABS ON GRADE UON
7500 PSI AT 28 DAYS, 8" THICK SLAB ON GRADE
3. CONCRETE DENSITY SHALL BE NORMAL WEIGHT UON ON DRAWINGS
4. CONCRETE REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM
A615/A615M, GRADE 60.
5. WELDED WIRE REINFORCEMENT SHALL CONFORM TO ASTM A185. PROVIDE SHEET-
TYPE WWR. SHEET LAPS SHALL BE TIED AND LAPPED ONE FULL MESH SPACING.
6. CONCRETE REINFORCING STEEL SHALL BE CONTINUOUS UNLESS OTHERWISE
INDICATED. CONTINUOUS REINFORCING STEEL SHALL BE LAPPED WITH TYPE "B"
SPLICES IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 318.
7. MINIMUM CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS INDICATED. IN NO
CASE SHALL REINFORCEMENT COVER BE LESS THAN THE REQUIREMENTS OF ACI 301.
A. CONCRETE DEPOSITED AGAINST THE GROUND: 3"
B. CONCRETE EXPOSED TO EARTH OR WEATHER: 2"
C. INTERIOR CONCRETE UON 2"
D. INTERIOR ELEVATED FLOOR: TOP 3/4"
BOT 1 1/2"
E. SLAB ON GRADE REINF. DEPTH 1-1/2" FROM TOP OF SLAB
8. CONCRETE REINFORCING STEEL MARKED STANDARD HOOK SHALL HAVE A 90-DEGREE
HOOK UNLESS OTHERWISE NOTED. STIRRUP, TIE AND 180-DEGREE HOOKS AND 90-
DEGREE HOOKS SHALL CONFORM TO THE REQUIREMENTS OF ACI 318.
9. PROVIDE 1/2" WIDE ISOLATION JOINT WITH PRE-MOLDED JOINT FILLER MATERIAL WHERE
SLABS ON GRADE ABUT VERTICAL SURFACES.
10. ALL EMBEDDED ITEMS SHALL BE PROPERLY PLACED, ACCURATELY POSITIONED, AND
MAINTAINED SECURELY IN PLACE PRIOR TO AND DURING CONCRETE PLACEMENT.
ALL PIPING PASSING THROUGH ELEVATED FLOOR SLABS AND WALLS SHALL BE SLEEVED
TO ALLOW FOR MAINTENANCE AND REPLACEMENT.
11. REINFORCING STEEL SHALL BE SPREAD AT SLEEVES, TIEBACKS, RECESSES AND
OTHER EMBEDDED ITEMS UNLESS OTHERWISE INDICATED. REINFORCEMENT SHALL NOT
BE CUT TO FACILIATE PLACEMENT OF EMBEDDED ITEMS.
12. NO CONCRETE SHALL BE PLACED UNTIL THE CONTRACTING OFFICER OR THE
CONTRACTING OFFICER'S DESIGNATED REPRESENTATIVE HAS INSPECTED ALL
EMBEDDED WORK, INCLUDING REINFORCEMENT.
13. ALL EXPOSED CONCRETE EDGES SHALL BE CHAMFERED 3/4" UON
14. ALUMINUM SHALL NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE UNLESS
EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CONCRETE REACTION AND
ELECTROLYTIC ACTION BETWEEN ALUMINUM AND STEEL.
15. CONSTRUCTION LOADS SHALL NOT BE APPLIED TO CONCRETE STRUCTURAL MEMBERS
UNTIL THE MIXTURE PROPORTIONING STUDY OR TEST RECORD DATA FOR THAT MEMBER
INDICATES THE CONCRETE STRENGTH HAS REACHED A MINIMUM OF 75% OF THE
SPECIFIED COMPRESSIVE STRENGTH f'c FOR THAT MEMBER.
DESIGN CRITERIA
1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES AND
SPECIFICATIONS:
A. 2015 INTERNATIONAL BUILDING CODE
B. ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES
C. AISC 360-10 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
D. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
E. SJI "STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS, K-SERIES", EFFECTIVE
MARCH 1, 2015
F. UFC 4-010-01 CHANGE 1 DoD MINIMUM ANTITERRORISM STANDARDS FOR
BUILDINGS (2013)
G. UFC 3-310-04 SEISMIC DESIGN OF BUILDINGS (2013)
H. UFC 3-301-01 CHANGE 3 STRUCTURAL ENGINEERING (2016)
2. DESIGN LOAD CRITERIA:
A. RISK CATEGORY II
B. LIVE LOADS:
ROOF 20 PSF
CORRIDOR (SERVING GATHERING AREA) 100 PSF
CORRIDOR UON 80 PSF
KITCHEN 250 PSF
KITCHEN DRY STORAGE 200 PSF
ELECTRICAL/TELECOM ROOMS 150 PSF
MECHANICAL ROOMS - HVAC 125 PSF
MECHANICAL ROOMS - OTHER 100 PSF
LIGHT STORAGE AREAS 125 PSF
PRIMARY GATHERING AREAS, DATA CENTERS,
KITCHEN SERVERY AND PREP ROOM 100 PSF
RESTROOM AND JANITORIAL SPACES 75 PSF
OFFICE, OTHER AREAS UON MIN 50 PSF (‡)
(‡) MOVABLE PARTITION LOAD INCLUDED FOR ALL OCCUPANCIES UNDER
80 PSF LIVE LOAD EXCEPT RESTROOM AREAS
C. SNOW LOAD:
GROUND SNOW LOAD, Pg 15 PSF
SNOW LOAD IMPORTANCE FACTOR, I 1.0
SNOW EXPOSURE FACTOR, Ce 1.0 THERMAL FACTOR, Ct 1.0
ROOF SNOW LOAD 15 PSF
D. WIND LOADS:
WIND IMPORTANCE FACTOR, I 1.0
BASIC WIND SPEED, V 115 MPH
WIND EXPOSURE CATEGORY C
INTERNAL PRESSURE COEFFICIENTS, GCpi +/-0.18
E. SEISMIC LOADS:
SEISMIC IMPORTANCE FACTOR, I 1.0
SPECTRAL RESPONSE ACCELERATION, Ss 0.11g SPECTRAL RESPONSE ACCELERATION, S1 0.05g
SITE CLASS D
DESIGN SPECTRAL ACCELERATION, SDs 0.117g DESIGN SPECTRAL ACCELERATION, SD1 0.080g
SEISMIC DESIGN CATEGORY B
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
BASIC SEISMIC-FORCE-RESISTING SYSTEMS:
BUILDING I (HIGH BAY)
ORDINARY REINFORCED CONCRETE SHEAR WALL
RESPONSE MODIFICATION FACTOR, R 4.0
BUILDING II (2-STORY)
LOWER STORY: ORDINARY REINFORCED MASONRY SHEAR WALL
RESPONSE MODIFICATION FACTOR, R 2.0
UPPER STORY: LIGHT FRAME (COLD FORMED) W/ FLAT STRAP BRACING
RESPONSE MODIFICATION FACTOR, R 4.0
F. FROST DEPTH 14"
GENERAL NOTES
1. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL OTHER DRAWINGS. COORDINATE
THE WORK OF OTHER TRADES INCLUDING, BUT NOT LIMITED TO THE REQUIREMENTS FOR
SLEEVES, INSERTS, HOLES, HANGERS AND ANCHORS.
2. ELEVATIONS ON THE STRUCTURAL DRAWINGS ARE DENOTED AS [+/-X'-X"] REFERENCED TO
THE FINISHED FLOOR TOP OF SLAB ELEVATION DATUM SET AT +0'-0". THIS DATUM IS EQUIVALENT
TO THE TOP OF SLAB ELEVATION INDICATED ON THE CIVIL DRAWINGS.
3. THE CONTRACTOR SHALL REPORT DISCREPANCIES IN DIMENSIONS BETWEEN DIFFERENT
DRAWINGS TO THE CONTRACTING OFFICER PRIOR TO BEGINNING WORK IN AREAS THAT WILL
BE AFFECTED.
4. DETAILS ENTITLED OR NOTED AS "TYPICAL" APPLY NOT ONLY WHERE SPECIFICALLY
INDICATED OR REFERENCED, BUT ALSO IN ALL OTHER CASES WHERE THE NATURE OF THE
CONSTRUCTION REQUIRES THEIR USE. DETERMINE APPLICABILITY OF TYPICAL DETAILS FROM
DESCRIPTIVE TITLES OR FROM THE SIMILARITY OF A CONSTRUCTION CONDITION TO ANOTHER
CONDITION WHERE THE DETAIL IS SPECIFICALLY INDICATED OR REFERENCED.
5. THE STRUCTURAL DRAWINGS CONTAINED HEREIN REPRESENT THE FINISH STRUCTURE.
CONTRACTOR TO PROVIDE ALL TEMPORARY GUYING AND BRACING REQUIRED TO ERECT AND
HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL ALL STRUCTURAL WORK, INCLUDING
CONNECTIONS, IS COMPLETE. THE ANALYSIS, DESIGN, SAFETY, ADEQUACY AND INSPECTION OF
ERECTION BRACING, SHORING, AND OTHER TEMPORARY SUPPORTS ARE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR.
6. CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND SUPERVISION OF THE
WORK ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR UON.
7. REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP DRAWINGS UNDER
ANY CIRCUMSTANCES.
GEOTECHNICAL & FOUNDATION NOTES
1. GEOTECHNICAL INFORMATION - REFER TO GEOTECHNICAL ENGINEERING REPORT TITLED
"REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING SERVICES,
AVIATION COMPLEX PHASE 1 - VERTICAL", DATED FEBRUARY 2, 2016, PREPARED BY GET
SOLUTIONS INC. AND ADDENDUM "AVIATION COMPLEX PHASE II AND III, SUPPLEMENTAL
GEOTECHNICAL REPORT", DATED JULY 12, 2018, PREPARED BY US ARMY CORPS OF ENGINEERS
NORFOLK DISTRICT.
2. REMOVAL AND BACKFILLING OPERATIONS OF UNCONTROLLED FILL AND OVER EXCAVATION
SHALL BE PERFORMED UNDER THE SUPERVISION OF A PROFESSIONAL ENGINEER LICENSED
IN THE COMMONWEALTH OF VIRGINIA. THE PROFESSIONAL ENGINEER OVERSEEING THESE
OPERATIONS SHALL CERTIFY TO THE GOVERNMENT THAT ALL UNCONTROLLED FILL HAS
BEEN REMOVED AND REPLACED WITH PROPERLY COMPACTED STRUCTURAL FILL MEETING
THE PROJECT REQUIREMENTS.
3. REFER TO THE GOVERNMENT GEOTECHNICAL REPORT FOR NON-EXPANSIVE FILL, SELECT
FILL, AND SELECT CLAY FILL MATERIAL DEFINITIONS AND REQUIREMENTS, AND FOR
COMPLETE FILL AND SUB-GRADE PREPARATION MINIMUM REQUIREMENTS.
4. THE FOUNDATIONS CONSIST OF A PRECAST CONCRETE PILE DEEP FOUNDATION SYSTEM
WITH CONCRETE PILE CAPS AND GRADE BEAMS. GROUND FLOOR CONCRETE SLABS
SHALL BE GRADE SUPPORTED.
5. NET ALLOWABLE DESIGN BEARING PRESSURE FOR SLABS: 3,000 PSF
6. DO NOT CONSTRUCT FOUNDATIONS UNTIL FOUNDATION WORK HAS BEEN COORDINATED
WITH UNDERGROUND UTILITIES AND STRUCTURES.
7. COORDINATE AND VERIFY ALL FOOTING LOCATIONS WITH CIVIL, PLUMBING, AND ELECTRICAL
DRAWINGS.
8. ALL SLABS ON GRADE SHALL REST ON A 10 MIL VAPOR BARRIER OVER A MINIMUM 6" DEEP
LAYER OF COMPACTED #57 STONE POROUS FILL UPON THE PREPARED SUB-GRADE.
MASONRY CONSTRUCTION NOTES
1. ALL MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH "BUILDING CODE
REQUIREMENTS FOR MASONRY STRUCTURES" (ACI 530.1-08/ASCE 6-08/TMS 402-08).
2. DESIGN MASONRY ASSEMBLAGE STRENGTH, f'm = 1500 PSI. NET AREA COMPRESSIVE
STRENGTH OF CONCRETE MASONRY UNITS SHALL BE A MINIMUM OF 1900 PSI.
3. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 AND BE MANUFACTURED WITH
LIGHT WEIGHT AGGREGATE.
4. GROUT SHALL CONFORM TO ASTM C476 AND SHALL NOT CONTAIN ADMIXTURES. GROUT
SHALL ATTAIN A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2000 PSI.
5. GROUT POURS SHALL BE STOPPED 1-1/2 INCHES BELOW THE TOP OF A COURSE TO FORM A
KEY AT POURED JOINTS.
6. REINFORCEMENT SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60
AND SHALL HAVE FABRICATION TOLERANCES IN ACCORDANCE WITH ACI 315. SHOP
FABRICATE REINFORCING BARS WHICH ARE INDICATED TO BE BENT OR HOOKED.
7. LOCATE WIRE JOINT REINFORCEMENT 16 INCHES ON CENTER VERTICALLY.
8. PLACE PIPES AND CONDUITS PASSING HORIZONTALLY THROUGH MASONRY IN STEEL, PVC
SLEEVES OR CORED HOLES UON ON THE DRAWINGS.
9. ALUMINUM CONDUITS, PIPES, AND ACCESSORIES SHALL NOT BE EMBEDDED IN MASONRY
GROUT, OR MORTAR, UNLESS EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-
CEMENT CHEMICAL REACTION OR ELECTROLYTIC REACTION BETWEEN ALUMINUM AND
STEEL.
10. UON OR DETAILED, CENTER WALL REINFORCEMENT IN BLOCK CELLS. A MINIMUM OF 1/2"
CLEARANCE IS TO BE PROVIDED BETWEEN REINFORCEMENT AND BLOCK CELL WALL. USE
GALVANIZED "Z" TYPE BAR POSITIONERS AT A MAXIMUM SPACING OF 2'-0" OC TO SECURE
THE VERT REINF STEEL PRIOR TO GROUTING THE CELL.
11. PROVIDE DOWEL REINFORCEMENT FROM FOUNDATION OF SAME SIZE AND SPACING AS
VERTICAL WALL REINFORCEMENT. LAP WALL REINFORCEMENT A MINIMUM OF 72 BAR
DIAMETERS.
12. PROVIDE INSPECTION OPENINGS AT THE BOTTOM OF ALL GROUTED CELL LOCATIONS.
13. UON, ALL CMU SHALL BE 12", REINFORCED WITH #4 VERT @ 24" O.C. MIN. PROVIDE
CONTINUOUS (2)-#5 REINFORCED BOND BEAM AT ROOF, TOP OF WALL, FLOOR, AND
INTERMEDIATE AT 8'-0" OC MAX VERTICAL SPACING. PROVIDE LINTEL
ABOVE ALL CMU OPENINGS IN ACCORDANCE WITH NOTES ON SF401 AND TYPICAL DETAIL
ON SHEET SF504.
14. IN ANY LOCATION WHERE A BOND BEAM IS SHOWN ATOP A PARTIAL HEIGHT COURSE, A
TALLER BOND BEAM CUT FROM 16" HIGH BLOCK MAY BE SUBSTITUTED AT CONTRACTOR'S
OPTION.
STEEL CONSTRUCTION NOTES
1. FABRICATION AND ERECTION OF STRUCTURAL STEEL AND DESIGN OF CONNECTIONS SHALL
BE IN ACCORDANCE WITH THE AISC "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
2010 EDITION AND THE AISC "CODE OF STANDARD PRACTICE FOR BUILDINGS AND
BRIDGES", 2010 EDITION.
2. UNLESS OTHERWISE NOTED, STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE
ABOVE LISTED AISC SPECIFICATION AND THE FOLLOWING:
A. SQUARE AND RECTANGULAR HSS ASTM A500, GRADE B, Fy = 46 KSI B. ROUND HSS ASTM A500, GRADE B, Fy = 42 KSI
C. WIDE-FLANGE SHAPES AND TEES ASTM A992
D. CHANNELS AND S-SHAPES ASTM A36/A36M
E. PLATES AND ANGLES ASTM A36/A36M
F. HIGH STRENGTH BOLTS ASTM 325
G. ANCHOR RODS W/ NUT AND WASHER ASTM F1554, GRADE 36 UON
H. THREADED ROD ASTM A36/A36M
3. ALL SHOP AND FIELD WELDING SHALL BE BY CERTIFIED WELDERS AND SHALL CONFORM
TO AWS STANDARDS. USE E70XX ELECTRODES UNLESS NOTED OTHERWISE. CURRENT
AWS CERTIFICATIONS SHALL BE AVAILABLE AT THE JOB SITE FOR REVIEW BY THE
CONTRACTING OFFICER'S REPRESENTATIVE.
4. UNLESS OTHERWISE NOTED MINIMUM WELD SIZE TO BE 1/4" FILLET WELD
5. CONFORM DIMENSIONAL TOLERANCES FOR WELDED CONSTRUCTION, DETAILS OF WELDS,
AND QUALITY OF WELDS WITH THE APPLICABLE REQUIREMENTS OF AWS D1.1 AND THE
CONTRACT DRAWINGS. CONTRACTOR SHALL VISUALLY INSPECT 100 PERCENT OF WELDS.
IN ADDITION, A MINIMUM OF 20 PERCENT OF WELDS SHALL BE RANDOMLY SELECTED AND
TESTED BY LIQUID PENETRANT. ALSO, 100 PERCENT OF FULL MOMENT WELDS ARE TO BE
TESTED BY ULTRASONIC METHODS.
6. ALL BOLTED CONNECTIONS, UON, SHALL USE HIGH STRENGTH BOLTS WITH HARDENED
CARBON STEEL WASHERS AS REQUIRED FOR THE CONNECTON LOADS.
7. FIELD CUTTING OF STRUCTURAL STEEL MEMBERS BY ANY TRADE SHALL NOT BE PERMITTED.
BOLT HOLES SHALL NOT BE CUT OR ENLARGED BY FLAME CUTTING IN THE FIELD.
8. ALL FIELD BOLTED SHEAR CONNECTIONS SHALL BE FULLY TENSIONED CONNECTIONS,
THREADS INCLUDED IN THE SHEAR PLANE.
9. CONNECTION DETAILING IS DELEGATED TO THE CONTRACTOR. THE FABRICATOR SHALL
SUBMIT DETAILS AND CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER IN THE STATE
OF VIRGINIA TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO DOING ANY WORK OR
ORDERING MATERIALS.
10. CONNECTIONS FOR AXIAL, SHEAR AND BENDING FORCES SHALL BE DESIGNED FOR THE
FACTORED CAPACITY OF THE CONNECTED MEMBER.
11. THE MINIMUM BOLT DIAMETER SHALL BE 3/4" UNLESS OTHERWISE NOTED.
12. SHOP OR FIELD SPLICES OF STRUCTURAL STEEL MEMBERS ARE PROHIBITED EXCEPT AS
SPECIFICALLY PERMITTED IN THE SPECIFICATIONS, AS INDICATED ON APPROVED
SUBMITTALS, AND AS SPECIFICALLY APPROVED ON SHOP DRAWINGS PRIOR TO FABRICATION.
13. PAINT ALL STEEL BELOW GRADE WITH TWO COATS OF COAL TAR EPOXY IN ACCORDANCE
WITH SSPC PAINT 16.
14. CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING MISCELLANEOUS STEEL
REQUIRED TO SUPPORT DRAINS, FAN CURBS, OVERFLOW DRAINS, ACCESS HATCHES,
ACCESS PANELS, ETC. COORDINATE WITH ARCHITECTURAL DRAWINGS.
15. ANCHOR BOLTS SHALL BE ASTM A1554 GRADE 36 OR APPROVED EQUAL UON. SEE NOTES
ON SF502 FOR DIFFERENT AB GRADE REQUIREMENT FOR CFMF X BRACED FRAMES.
ANCHORS MAY BE CAST IN PLACE AS SHOWN IN DETAILS, OR ALTERNATELY MAY BE
POST INSTALLED UNDERCUT OR EPOXY ADHESIVE TYPE. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. ANCHORS SHALL WITHSTAND LOAD EQUIVALENT TO THE CAST
IN PLACE ANCHOR BOLTS SHOWN. CONTRACTOR TO SUBMIT MANUFACTURER'S ANALYSIS
AND DESIGN DATA, INCLUDING ICC REPORT, SHOWING THAT POST INSTALLED ANCHOR BOLT
SYSTEMS MEET THE ANCHOR FORCE REQUIREMENTS IN ACCORDANCE WITH ACI 318 WITH
APPENDIX D.
STEEL JOIST CONSTRUCTION NOTES
1. K-SERIES AND LH-SERIES OPEN WEB STEEL JOISTS SHALL BE IN ACCORDANCE WITH
SJI 100 - 2015. JOISTS SHALL BE HANDLED AND ERECTED IN ACCORDANCE WITH SJI
TECHNICAL DIGEST #9 THIRD EDITION DATED MARCH 2008.
2. JOIST BRIDGING SHALL CONFORM TO SJI SPECIFICATIONS, INCLUDING BRIDGING
REQUIRED FOR UPLIFT RESISTANCE. CROSS BRIDGING IS REQUIRED AT CHANGES IN
JOIST DEPTHS AND WHERE BRIDGING LINES ARE INTERRUPTED BY STRUCTURAL
STEEL BEAMS SPANNING PARALLEL TO THE JOISTS. WHERE BRIDGING TERMINATES
INTO A WALL, PROVIDE HORIZONTAL BRIDGING IN THE SPACE BETWEEN THE WALL AND
FIRST JOIST.
3. NO LOADS ARE PERMITTED TO BE SUPPORTED FROM JOIST BRIDGING.
4. JOISTS WITH CONCENTRATED LOADS ON THE TOP OR BOTTOM CHORDS NOT
LOCATED AT A PANEL POINT SHALL BE REINFORCED WITH A FIELD INSTALLED MEMBER.
THE FIELD INSTALLED MEMBER SHALL BE LOCATED AT THE CONCENTRATED LOAD AND
SHALL BRACE THE CHORD BACK TO A PANEL POINT IN ACCORDANCE WITH TYPICAL DETAIL
ON SHEET SF501.
5. SECOND FLOOR AND MEZZANINE (NO SLOPE) JOIST SEAT IS TO BE 5" DEEP UON FOR BOTH
LH- AND K-SERIES JOISTS.
6. ROOF (LOW AND MEDIUM SLOPE) JOIST SEAT IS TO BE 8" DEEP AT GRID/WALL CENTERLINE
UON FOR BOTH LH- AND K-SERIES JOISTS.
SLOPE SLOPE DIRECTION
DECK SPAN
INDICATES ELEVATION
REFERENCED TO
FINISH FIRST FLOOR
GRID REFERENCE LINE
STEEL
BRICK
CONCRETE MASONRY
UNIT
CONCRETE
GROUT
CAPILLARY WATER
BARRIER
EARTH FILL
CFMF OVER-FRAMING
LOAD BEARING CFMF
WALL
STRUCTURAL LEGEND
SYMBOL DESCRIPTION
[+/-X'-X"]
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
'D
D
AT
E
TI
M
E
ST
AM
P:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
PR
O
JE
C
T N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
PROPERTY OF UNITED STATES GOVERNMENT, FOR OFFICIAL USE ONLY (FOUO). COPYING, DISSEMINATION, AND DISTRIBUTION TO UNAUTHORIZED INDIVIDUALS PROHIBITED.
4/
/2
5:
:3
PM
S-001
PHASE 2
G
EN
ER
AL
S
TR
U C
TU
R
AL
N
O
TE
S, D
ES
IG
N L
O
AD
S
AB
BR
EV
IA
TI
O
N S
B
AT
TA
LI
O N
C O
M
PL
EX
N
O R
FO
LK
D
IS
TR
IC
T N
O R
FO
LK
, V A
J.
J
O N
ES
C . S
AN
D
ER
S
C . S
AN
D
ER
S
W . M
IL
LE
R
JA
N
U
AR
Y
R
TA
S U
BM
IT
TA
L
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AM
E N D
M
EN
T
-0 4-
1 4
AM
E N
D M
EN
T
-0
4- 2 2
| Sheets |
| S-001 - GENERAL STRUCTURAL NOTES, DESIGN LOADS & ABBREVIATIONS |