26 51 00.pdf
PDF 73 KB Posted
- Attached to
- Battalion Complex (Amendment 8)
- Solicitation number
- W9123620R0001
View the file
Other files
Show 40 more
Latest 50 of 136 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BATTALION COMPLEX PH 3 720ACPH3
RTA SUBMITTAL
SECTION 26 51 00
INTERIOR LIGHTING
05/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 189.1 (2014) Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings
ASHRAE 90.1 - IP (2013) Energy Standard for Buildings Except Low-Rise Residential Buildings
ASTM INTERNATIONAL (ASTM)
ASTM A1008/A1008M (2016) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM A580/A580M (2018) Standard Specification for Stainless Steel Wire
ASTM A641/A641M (2009a; R 2014) Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A653/A653M (2017) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B164 (2003; R 2014) Standard Specification for Nickel-Copper Alloy Rod, Bar, and Wire
ASTM B633 (2015) Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM D4674 REV A (2002; R 2010) Standard Practice for Accelerated Testing for Color Stability of Plastics Exposed to Indoor Office Environments
CALIFORNIA ENERGY COMMISSION (CEC)
CEC Title 24 (2016) Building Energy Efficiency
SECTION 26 51 00 Page 1
Standards For Residential and Nonresidential Buildings
ILLUMINATING ENGINEERING SOCIETY (IES)
IES HB-10 (2011; Errata 2015) IES Lighting Handbook
IES LM-79 (2008) Electrical and Photometric Measurements of Solid-State Lighting Products
IES LM-80 (2015) Measuring Lumen Maintenance of LED Light Sources
IES RP-16 (2010; Addendum A 2008; Addenda B 2009;
Addendum C 2016) Nomenclature and Definitions for Illuminating Engineering
IES TM-21 (2011; Addendum B 2015) Projecting Long Term Lumen Maintenance of LED Light Sources
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA ANSLG C78.377 (2017) Electric Lamps— Specifications for the Chromaticity of Solid State Lighting Products
NEMA C82.77 (2002) Harmonic Emission Limits - Related Power Quality Requirements for Lighting Equipment
NEMA ICS 2 (2000; R 2005; Errata 2008) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA SSL 1 (2010) Electronic Drivers for Led Devices, Arrays, or Systems
NEMA SSL 3 (2011) High-Power White LED Binning for General Illumination
SECTION 26 51 00 Page 2
NEMA SSL 7A (2015) Phase-Cut Dimming for Solid State Lighting: Basic Compatibility
NEMA WD 1 (1999; R 2015) Standard for General Color Requirements for Wiring Devices
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2018; TIA 18-1; TIA 18-2; TIA 18-3) Life Safety Code
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14) National Electrical Code
U.S. DEPARTMENT OF DEFENSE (DOD)
DOD 8500.01 (2014) Cybersecurity
DOD 8510.01 (2014; Change 1-2016; Change 2-2017) Risk Management Framework (RMF) for DoD Information Technology (IT)
UNDERWRITERS LABORATORIES (UL)
UL 1472 (2015) UL Standard for Safety Solid-State Dimming Controls
UL 1598 (2008; Reprint Oct 2012) Luminaires
UL 20 (2010; Reprint Feb 2012) General-Use Snap Switches
UL 2043 (2013) Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces
UL 508 (2018) UL Standard for Industrial Control Equipment
UL 844 (2012; Reprint Mar 2016) UL Standard for Safety Luminaires for Use in Hazardous (Classified) Locations
UL 8750 (2015; Reprint Feb 2018) UL Standard for Safety Light Emitting Diode (LED) Equipment for Use in Lighting Products
UL 916 (2007; Reprint Aug 2014) Standard for Energy Management Equipment
UL 924 (2016; Reprint May 2018) UL Standard for Safety Emergency Lighting and Power Equipment
UL 94 (2013; Reprint Sep 2017) UL Standard for
SECTION 26 51 00 Page 3
Safety Tests for Flammability of Plastic Materials for Parts in Devices and Appliances
1.2 RELATED REQUIREMENTS
Materials not considered to be luminaires or luminaire accessories are specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Luminaires and accessories mounted on exterior surfaces of buildings are specified in Section 26 56 00 EXTERIOR LIGHTING.
1.3 DEFINITIONS
a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, must be as defined in IEEE 100 and IES RP-16 .
b. For fluorescent, HID and induction luminaire light sources, "Average Rated Life" is the time after which 50 percent of a large group of light sources will have failed and 50 percent will have survived under normal conditions.
c. For LED luminaire light sources, "Useful Life" is the operating hours before reaching 70 percent of the initial rated lumen output (L70) with no catastrophic failures under normal operating conditions. This is also know as 70 percent "Rated Lumen Maintenance Life" as defined in IES LM-80 .
d. For fluorescent, HID and induction luminaires, "Luminaire Efficacy Rating" (LER) is the appropriate measure of energy efficiency, measured in lumens/watt. Specifically it is the luminaire's efficiency multiplied by the total rated light source lumens and the ballast factor, divided by the luminaire input watts.
e. For LED luminaires, "Luminaire Efficacy" (LE) is the appropriate measure of energy efficiency, measured in lumens/watt. This is gathered from LM-79 data for the luminaire, in which absolute photometry is used to measure the lumen output of the luminaire as one entity, not the source separately and then the source and housing together.
f. Total harmonic distortion (THD) is the root mean square (RMS) of all the harmonic components divided by the total fundamental current.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Data, drawings, and reports must employ the terminology, classifications and methods prescribed by the IES HB-10 as applicable, for the lighting system specified. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Luminaire Drawings; G
Occupancy/Vacancy Sensor Coverage Layout; G
SECTION 26 51 00 Page 4
SD-03 Product Data
Luminaires; G
Light Sources; G
Drivers; G
LED Luminaire Warranty; G
Luminaire Design Data; G
Vacancy Sensors; G
Dimming Controllers (Dimmers); G
Lighting Contactor; G
Timeswitch; G
Exit Signs; G
Emergency Lighting Unit (EBU); G
Occupancy Sensors; G
Ambient Light Level Sensor ; G
SD-06 Test Reports
LED Luminaire - IES LM-79 Test Report; G
LED Light Source - IES LM-80 Test Report; G
LED Light Source - IES TM-21 Test Report; G
Occupancy/Vacancy Sensor Verification Tests; G
Energy Efficiency; G
SD-07 Certificates
Luminaire Useful Life Certificate; G
LED Driver and Dimming Switch Compatibility Certificate; G
1.5 QUALITY CONTROL
1.5.1 Luminaire Drawings
Include dimensions, accessories, and installation and construction details. Photometric data, including zonal lumen data, average and minimum ratio, aiming diagram, and computerized candlepower distribution data must accompany shop drawings.
1.5.2 Occupancy/Vacancy Sensor Coverage Layout
Provide floor plans showing coverage layouts of all devices using manufacturer's product information.
SECTION 26 51 00 Page 5
1.5.3 LED Driver and Dimming Switch Compatibility Certificate
Submit certification from the luminaire, driver, or dimmer switch manufacturer that ensures compatibility and operability between devices.
1.5.4 Luminaire Design Data
a. Provide safety certification and file number for the luminaire family that must be listed, labeled, or identified per the NFPA 70 (NEC).
Applicable testing bodies are determined by the US Occupational Safety Health Administration (OSHA) as Nationally Recognized Testing Laboratories (NRTL) and include: CSA (Canadian Standards Association), ETL (Edison Testing Laboratory), and UL (Underwriters Laboratories).
b. Provide long term lumen maintenance projections for each LED luminaire in accordance with IES TM-21 . Data used for projections must be obtained from testing in accordance with IES LM-80 .
1.5.5 LED Luminaire - IES LM-79 Test Report
Submit test report on manufacturer's standard production model luminaire.
Include all applicable and required data as outlined under "14.0 Test Report" in IES LM-79 .
1.5.6 LED Light Source - IES LM-80 Test Report
Submit report on manufacturer's standard production LED light source (package, array, or module). Include all applicable and required data as outlined under "8.0 Test Report" in IES LM-80 .
1.5.7 LED Light Source - IES TM-21 Test Report
Submit test report on manufacturer's standard production LED light source (package, array or module). Include all applicable and required data, as well as required interpolation information as outlined under "7.0 Report" in IES TM-21 .
1.5.8 Occupancy/Vacancy Sensor Verification Tests
Submit test report outlining post-installation coverage and operation of sensors.
1.5.9 Test Laboratories
Test laboratories for the IES LM-79 and IES LM-80 test reports must be one of the following:
a. National Voluntary Laboratory Accreditation Program (NVLAP) accredited for solid-state lighting testing as part of the Energy-Efficient Lighting Products laboratory accreditation program for both LM-79 and LM-80 testing.
b. One of the qualified labs listed on the Department of Energy - LED Lighting Facts Approved Testing Laboratories List at for LM-79 testing.
c. One of the EPA-Recognized Laboratories listed at for LM-80 testing.
SECTION 26 51 00 Page 6
1.5.10 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, installation, and workmanship must be in accordance with the mandatory and advisory provisions of NFPA 70 , unless more stringent requirements are specified or indicated.
1.5.11 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products must have been in satisfactory commercial or industrial use for two years prior to bid opening. The two-year period must include applications of equipment and materials under similar circumstances and of similar size. The product must have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the two-year period. Where two or more items of the same class of equipment are required, these items must be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.5.11.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.5.11.2 Material and Equipment Manufacturing Date
Products manufactured more than six months prior to date of delivery to site must not be used, unless specified otherwise.
1.5.11.3 Energy Efficiency
Submit data indicating lumens per watt efficacy and color rendering index of light source.
1.6 WARRANTY
Support all equipment items by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.6.1 LED Luminaire Warranty
a. Provide a written 5 year on-site replacement warranty for material, fixture finish, and workmanship. On-site replacement includes transportation, removal, and installation of new products.
(1) Include finish warranty to include failure and substantial deterioration such as blistering, cracking, peeling, chalking, or fading.
SECTION 26 51 00 Page 7
(2) Material warranty must include:
(a) All drivers.
(b) Replacement when more than 10 percent of LED sources in any lightbar or subassembly(s) are defective or non-starting.
b. Warranty period must begin on date of beneficial occupancy. Provide the Contracting Officer with signed warranty certificates prior to final payment.
1.6.1.1 Provide Luminaire Useful Life Certificate
Submit certification from the manufacturer indicating the expected useful life of the luminaires provided. The useful life must be directly correlated from the IES LM-80 test data using procedures outlined in IES TM-21 . Thermal properties of the specific luminaire and local ambient operating temperature and conditions must be taken into consideration.
PART 2 PRODUCTS
2.1 PRODUCT COORDINATION
Products and materials not considered to be luminaires, luminaire controls, or associated equipment are specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Luminaires, luminaire controls, and associated equipment for exterior applications are specified in Section
26 56 00 EXTERIOR LIGHTING.
2.2 LUMINAIRES
UL 1598 , NEMA C82.77 , and UL 8750 . Provide luminaires as indicated in luminaire schedule and NL plates or details on project plans. Provide luminaires complete with light sources of quantity, type, and wattage indicated. Provide all luminaires of the same type by the same manufacturer. Luminaires must be specifically designed for use with the driver, ballast or generator and light source provided.
2.2.1 LED Luminaires
Provide luminaires complete with power supplies (drivers) and light sources. Provide design information including lumen output and design life in luminaire schedule on project plans for LED luminaires. LED luminaires must meet the minimum requirements in the following table:
LUMINAIRE TYPE MINIMUM LUMINAIRE
EFFICACY (LE)
MINIMUM COLOR RENDERING INDEX
(CRI)
LED TROFFER -
1 x 4 2 x 2 2 x 4
90 LPW 80
LED Downlight 50 LPW 90
LED Track or Accent 40 LPW 80
LED Low Bay/High Bay 80 LPW 70
SECTION 26 51 00 Page 8
LUMINAIRE TYPE MINIMUM LUMINAIRE
EFFICACY (LE)
MINIMUM COLOR RENDERING INDEX
(CRI)
LED Linear Ambient 80 LPW 80
LED luminaires must also meet the following minimum requirements:
a. Luminaires must have a minimum 5 year manufacturer's warranty.
b. Luminaires must have a minimum L70 lumen maintenance value of 50,000 hours as calculated by IES TM-21 , with data obtained per IES LM-80 requirements.
c. Luminaire drive current value must be identical to that provided by test data for luminaire in question.
d. Luminaires must be tested to IES LM-79 and IES LM-80 standards, with the results provided as required in the Submittals paragraph of this specification.
e. Luminaires must be listed with the DesignLights Consortium 'Qualified Products List' when falling into category of "General Application" luminaires, i.e. Interior Directional, Display Case, Troffer, Linear Ambient, or Low/High Bay. Requirements are shown in the Designlights Consortium "Technical Requirements Table" at https://data.energystar.gov/dataset/EPA-Recognized-Laboratories-For- Lighting-Products/jgwf-7qrr .
f. Provide Department of Energy 'Lighting Facts' label for each luminaire.
2.2.2 Luminaires for Hazardous Locations
In addition to requirements stated herein, provide LED, luminaires for hazardous locations which conform to UL 844 or which have Factory Mutual certification for the class and division indicated.
2.3 DRIVERS
2.3.1 LED Drivers
NEMA SSL 1, UL 8750 . LED drivers must be electronic, UL Class 1, constant-current type and comply with the following requirements:
a. Output power (watts)and luminous flux (lumens) as shown in luminaire schedule for each luminaire type to meet minimum luminaire efficacy (LE) value provided.
b. Power Factor (PF) greater than or equal to 0.9 over the full dimming range when provided.
c. Current draw Total Harmonic Distortion (THD) of less than 20 percent.
d. Class A sound rating.
e. Operable at input voltage of 120-277 volts at 60 hertz.
f. Minimum 5 year manufacturer's warranty.
g. RoHS compliant.
SECTION 26 51 00 Page 9
h. Integral thermal protection that reduces or eliminates the output power if case temperature exceeds a value detrimental to the driver.
i. UL listed for dry or damp locations typical of interior installations.
j. Fully-dimmable using 0-10V control as indicated in luminaire schedule.
2.4 LIGHT SOURCES
NEMA ANSLG C78.377 , NEMA SSL 3. Provide type and wattage as indicated in luminaire schedule on project plans.
2.4.1 LED Light Sources
a. Correlated Color Temperature (CCT) of 4000 degrees K.
b. Minimum Color Rendering Index (CRI) R9 value of 80.
c. High power, white light output utilizing phosphor conversion (PC) process.
d. RoHS compliant.
2.5 LIGHTING CONTROLS
ASHRAE 90.1 - IP ASHRAE 189.1 . Provide network certification for all networked lighting control systems and devices per requirements of DOD 8500.01 and DOD 8510.01 .
2.5.1 Toggle Switches
Provide line-voltage toggle switches as specified in Section 26 20 00
INTERIOR DISTRIBUTION SYSTEM.
2.5.2 Dimming Controllers (Dimmers)
UL 1472 , UL 20 , IEEE C62.41 , NEMA SSL 7A. 120/277 V 0-10 V dimmers must provide flicker-free, continuously variable light output throughout the dimming range. Provide radio frequency interference suppression integral to device. Provide dimmers utilizing pulse width modulation (PWM).
Provide device with a vertical slider, paddle, rotary button, or toggle (with adjacent vertical slider) type control, with finish to match switches and outlets in same area. Provide back box in wall with sufficient depth to accommodate body of switch and wiring. Devices must be capable of operating at their full rated capacity regardless of being single or ganged-mounted, and be compatible with three-way and four-way switching scenarios. Dimmers must be capable of controlling 0-10 volt fluorescent ballasts or LED drivers. Ensure compatibility of dimmer with separate power packs when utilized for lighting control. Dimmers and the ballasts or drivers they control, must be provided from the same manufacturer, or tested and certified as compatible for use together.
Provide NEMA SSL 7A-compliant devices.
2.5.3 Sensors for Lighting Control
IEEE C62.41 , NEMA WD 1, UL 94 , UL 916 , UL 508 , ASTM D4674 REV A .
SECTION 26 51 00 Page 10
Carole Polygon
2.5.3.1 Occupancy Sensors
Provide occupancy sensors with coverage patterns as indicated on project plans. Provide no less quantity of sensors as shown on plans, but add additional sensors when required to fulfill coverage requirement for the specific model sensor provided. Sensor must be provided with an adaptive learning function that automatically sets sensor in optimum calibration in a set period of time after installation and a non-volatile memory that saves settings after a power outage. Provide sensors designed for ceiling, wall or wall-box installation as indicated. Operating voltage must be 120/277 volts. Operating voltage must be 24V in conjunction with a control system or separate power pack which interacts with luminaire being controlled. Provide housing of high-impact, injection-molded thermoplastic with a multi-segmented lens for PIR and dual technology sensors. Sensor operation requires movement to activate luminaires controlled, and turns luminaires off after a set time of inactivity.
2.5.3.1.1 Passive Infrared (PIR) Sensors
Provide ceiling or wall-mounted PIR sensors meeting the following requirements:
a. Temperature compensated, dual element sensor and a multi-element fresnel lens (Poly IR4 material).
b. Technology to optimize automatic time delay to fit occupant usage patterns.
c. No minimum load requirement for line voltage sensors and be capable of switching from zero to 800 W at 120 VAC, 50/60 Hz and from zero to 1200 W at 277 VAC, 50/60 Hz. Control voltage sensors must not exceed a maximum load requirement of 20 mA at 24VDC.
d. Time delay of five to 30 minutes in increments of five minutes with a walk through and test mode set by DIP switch.
e. LED indicator that remains active during occupancy.
f. Built-in light level sensor that is operational from 8 to 180 foot-candles.
g. Coverage pattern tested to NEMA WD 7 standards.
h. Standard five year warranty and be UL listed
i. No leakage current to load when in the off mode.
2.5.3.1.2 Ultrasonic Sensors
Provide ceiling-mounted ultrasonic sensors meeting the following requirements:
a. Operate at an ultrasonic frequency of 25 kHz.
b. LED on exterior of device to indicate occupant detection.
c. Adjustable time delay period of 15 seconds to 15 minutes.
d. UL listed with minimum five year warranty.
SECTION 26 51 00 Page 11
e. Provide with isolated relay for integrating control of HVAC or other automated systems.
2.5.3.1.3 Dual Technology Sensors
Provide dual technology sensors that meet the requirements for PIR sensors and ultrasonic sensors indicated above. If either the passive infrared or ultrasonic sensing registers occupancy, the luminaires must remain on.
2.5.3.1.4 Power Packs for Sensors
UL 2043 , CEC Title 24 , ASHRAE 90.1 - IP . Power packs used to provide power to one or more lighting control sensors must meet the following requirements:
a. Input voltage - 120-277 VAC; output voltage - 24 VDC at 225 mA.
b. Plenum-rated, high-impact thermoplastic enclosure.
c. Utilizes zero-crossing circuitry to prevent damage from inrush current.
d. Maximum load rating of 16 amps for electronic lighting loads.
e. RoHS compliant.
2.5.3.2 Vacancy Sensors
Provide vacancy sensors as indicated above under paragraph OCCUPANCY SENSORS, but with requirement of a manual operation to activate luminaires controlled. Provide automatic operation to turn luminaires off after a set period of inactivity.
2.5.4 Lighting Contactor
NEMA ICS 2 . Provide an electrically mechanically-held lighting contactor housed in a NEMA 1 enclosure conforming to NEMA ICS 6. Provide contactor with one normally-open(NO), single pole contacts, rated 600 volts, 30 amps. Provide coil operating voltage of 120 volts.
2.5.5 Timeswitch
Provide electronic type timeswitch with a astronomicprogramming function that changes on/off settings according to seasonal variations of sunset and sunrise, providing a total of 56 on/off set points. Provide 12 hour AM/PM type digital clock display format. Provide power outage back-up for switch for a minimum of seven days. Provide switch capable of controlling a minimum of 2 channels or loads. Rate contacts at 30 amps at 120/277 volts for general purpose loads. Provide contacts in a SPST, normally-open (NO) configuration. Provide switch with function that allows automatic control to be skipped on certain selected days of the week manual bypass or remote override control.
House timeswitch in a surface-mounted, lockable, NEMA 1 enclosure constructed of painted steel or plastic polymer conforming to NEMA ICS 6 .
2.5.6 Local Area Lighting Controller
CEC Title 24 and ASHRAE 90.1 - IP compliant. Provide controller designed
SECTION 26 51 00 Page 12 for single area or room with the following requirements:
a. 120/277 volt input, designed for fluorescent or LED lighting loads.
b. 2 zone, with 1 relays rated 20 amps each.
c. Provide daylight harvesting capability with full-range dimming control.
d. Inputs for occupancy sensor, photocell, and low-voltage wall switch.
e. Provide full 'OFF' function with input from external time clock input.
2.6 EXIT AND EMERGENCY LIGHTING EQUIPMENT
UL 924 , NFPA 101 , and NFPA 70 compliant.
2.6.1 Exit Signs
Provide exit signs consuming a maximum of five watts total.
2.6.1.1 LED Self-Powered Exit Signs
Provide in UV-stable, thermo-plastic housing with configured for ceiling wall end mounting. Provide 6 inch high, 3/4 inch stroke red lettering on face of sign. Provide chevrons on either side of lettering to indicate direction. Provide double face. Equip with automatic power failure device, test switch, and pilot light, and fully automatic high/low trickle charger in a self-contained power pack. Battery must be sealed, maintenance free nickel-cadmium type, and must operate unattended for a period of not less than five years. Emergency run time must be a minimum of 1 1/2 hours. LEDs must have a minimum rated life of 10 years.
2.6.2 Emergency Lighting Unit (EBU)
Provide in UV-stable, thermo-plasticpainted housing with UL wet label as indicated. Emergency lighting units must be rated for 12 volts, except units having no remote-mounted lamps and having no more than two unit-mounted light sources may be rated six volts. Equip units with brown-out sensitive circuit to activate battery when input voltage falls to 75 percent of normal. Equip with two LED, type light sources, automatic power failure device, test switch, and pilot light, and fully automatic high/low trickle charger in a self-contained power pack.
Battery must be sealed, maintenance free lead-calcium type, and must operate unattended for a period of not less than five years. Emergency run time must be a minimum of 1 1/2 hours. LEDs must have a minimum rated life of 10 years.
2.7 LUMINAIRE SUPPORT HARDWARE
2.7.1 Wire
ASTM A641/A641M ; Galvanized, soft tempered steel, minimum 0.11 inches in diameter, or galvanized, braided steel, minimum 0.08 inches in diameter.
2.7.2 Wire for Humid Spaces
ASTM A580/A580M ; Composition 302 or 304, annealed stainless steel, minimum
0.11 inches in diameter.
SECTION 26 51 00 Page 13
ASTM B164; UNS NO4400, annealed nickel-copper alloy, minimum 0.11 inches in diameter.
2.7.3 Threaded Rods
Threaded steel rods, 3/16 inch diameter, zinc or cadmium coated.
2.7.4 Straps
Galvanized steel, one by 3/16 inch, conforming to ASTM A653/A653M , with a light commercial zinc coating or ASTM A1008/A1008M with an electrodeposited zinc coating conforming to ASTM B633, Type RS.
2.8 EQUIPMENT IDENTIFICATION
2.8.1 Manufacturer's Nameplate
Each item of equipment must have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.8.2 Labels
Provide labeled luminaires in accordance with UL 1598 requirements. All luminaires must be clearly marked for operation of specific light sources and ballasts, generators or drivers. Note the following light source characteristics in the format "Use Only _____":
a. Correlated color temperature (CCT) and color rendering index (CRI) for all luminaires.
All markings related to light source type must be clear and located to be readily visible to service personnel, but unseen from normal viewing angles when light sources are in place. Ballasts, generators or drivers must have clear markings indicating multi-level outputs and indicate proper terminals for the various outputs.
2.9 FACTORY APPLIED FINISH
Provide all luminaires and lighting equipment with factory-applied painting system that as a minimum, meets requirements of NEMA 250 corrosion-resistance test.
2.10 RECESS- AND FLUSH-MOUNTED LUMINAIRES
Provide access to lamp and ballast from bottom of luminaire. Provide trim and lensesfor the exposed surface of flush-mounted luminaires as indicated on project drawings and specifications.
2.11 SUSPENDED LUMINAIRES
Provide hangers capable of supporting twice the combined weight of luminaires supported by hangers. Provide with swivel hangers to ensure a plumb installation. Provide cadmium-plated steel with a swivel-ball tapped for the conduit size indicated. Hangers must allow fixtures to swing within an angle of 45 degrees. Brace pendants 4 feet or longer to limit swinging. Single-unit suspended luminaires must have twin-stem hangers. Multiple-unit or continuous row luminaires must have a tubing or
SECTION 26 51 00 Page 14 stem for wiring at one point and a tubing or rod suspension provided for each unit length of chassis, including one at each end. Provide rods in minimum 0.18 inch diameter.
PART 3 EXECUTION
3.1 INSTALLATION
Electrical installations must conform to IEEE C2 , NFPA 70 , and to the requirements specified herein. Install luminaires and lighting controls to meet the requirements of ASHRAE 90.1 - IP and ASHRAE 189.1 . To encourage consistency and uniformity, install luminaires of the same manufacture and model number when residing in the same facility or building.
3.1.1 Light Sources
When light sources are not provided as an integral part of the luminaire, deliver light sources of the type, wattage, lumen output, color temperature, color rendering index, and voltage rating indicated to the project site and install just prior to project completion, if not already installed in the luminaires from the factory.
3.1.2 Luminaires
Set luminaires plumb, square, and level with ceiling and walls, in alignment with adjacent luminaires and secure in accordance with manufacturers' directions and approved drawings. Installation must meet requirements of NFPA 70 . Mounting heights specified or indicated must be to the bottom of the luminaire for ceiling-mounted luminaires and to center of luminaire for wall-mounted luminaires. Obtain approval of the exact mounting height on the job before commencing installation and, where applicable, after coordinating with the type, style, and pattern of the ceiling being installed. Recessed and semi-recessed luminaires must be independently supported from the building structure by a minimum of four wires, straps or rods per luminaire and located near each corner of the luminaire. Ceiling grid clips are not allowed as an alternative to independently supported luminaires. Round luminaires or luminaires smaller in size than the ceiling grid must be independently supported from the building structure by a minimum of four wires, straps or rods per luminaire, spaced approximately equidistant around. Do not support luminaires by acoustical tile ceiling panels. Where luminaires of sizes less than the ceiling grid are indicated to be centered in the acoustical panel, support each independently and provide at least two 3/4 inch metal channels spanning, and secured to, the ceiling tees for centering and aligning the luminaire. Provide wires, straps, or rods for luminaire support in this section. Luminaires installed in suspended ceilings must also comply with the requirements of Section 09 51 00 ACOUSTICAL CEILINGS.
3.1.3 Suspended Luminaires
Provide suspended luminaires with 45 degree swivel hangers so that they hang plumb and level. Locate so that there are no obstructions within the 45 degree range in all directions. The stem, canopy and luminaire must be capable of 45 degree swing. Pendants, rods, or chains 4 feet or longer excluding luminaire must be braced to prevent swaying using three cables at 120 degree separation. Suspended luminaires in continuous rows must have internal wireway systems for end to end wiring and must be properly aligned to provide a straight and continuous row without bends, gaps, SECTION 26 51 00 Page 15 light leaks or filler pieces. Utilize aligning splines on extruded aluminum luminaires to assure minimal hairline joints. Support steel luminaires to prevent "oil-canning" effects. Luminaire finishes must be free of scratches, nicks, dents, and warps, and must match the color and gloss specified. Match supporting pendants with supported luminaire.
Aircraft cable must be stainless steel. Canopies must be finished to match the ceiling and must be low profile unless otherwise shown. Maximum distance between suspension points must be 10 feet or as recommended by the manufacturer, whichever is less.
3.1.4 Ballasts, Generators and Power Supplies
Typically, provide ballasts, generators, and power supplies (drivers) integral to luminaire as constructed by the manufacturer.
3.1.5 Exit Signs and Emergency Lighting Units
Wire exit signs and emergency lighting units ahead of the local switch, to the normal lighting circuit located in the same room or area.
3.1.6 Photocell Switch Aiming
Aim switch according to manufacturer's recommendations.
3.1.7 Occupancy/Vacancy Sensors
Provide testing of sensor coverage in all spaces where sensors are placed. This should be done only after all furnishings (carpet, furniture, workstations, etc.) have been installed. Provide quantity of sensor units indicated as a minimum. Provide additional units to give full coverage over controlled area. Full coverage must provide hand and arm motion detection for office and administration type areas and walking motion for industrial areas, warehouses, storage rooms and hallways.
Locate the sensor(s) as indicated and in accordance with the manufacturer's recommendations to maximize energy savings and to avoid nuisance activation and deactivation due to sudden temperature or airflow changes and usage.
3.1.8 Daylight or Ambient Light Level Sensor
Locate sensor as indicated and in accordance with the manufacturer's recommendations. Adjust sensor for 30 foot-candlesor for the indicated light level measured at the work plane for that particular area.
3.2 FIELD APPLIED PAINTING
Paint lighting equipment as required to match finish of adjacent surfaces or to meet the indicated or specified safety criteria. Provide painting as specified in Section 09 90 00 PAINTS AND COATINGS.
-- End of Section --
SECTION 26 51 00 Page 16
| DIVISION 26 - ELECTRICAL |
| 26 51 00 - INTERIOR LIGHTING |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 RELATED REQUIREMENTS |
| 1.3 DEFINITIONS |
| 1.4 SUBMITTALS |
| 1.5 QUALITY CONTROL |
| 1.5.1 Luminaire Drawings |
| 1.5.2 Occupancy/Vacancy Sensor Coverage Layout |
| 1.5.3 LED Driver and Dimming Switch Compatibility Certificate |
| 1.5.4 Luminaire Design Data |
| 1.5.5 LED Luminaire - IES LM-79 Test Report |
| 1.5.6 LED Light Source - IES LM-80 Test Report |
| 1.5.7 LED Light Source - IES TM-21 Test Report |
| 1.5.8 Occupancy/Vacancy Sensor Verification Tests |
| 1.5.9 Test Laboratories |
| 1.5.10 Regulatory Requirements |
| 1.5.11 Standard Products |
| 1.5.11.1 Alternative Qualifications |
| 1.5.11.2 Material and Equipment Manufacturing Date |
| 1.5.11.3 Energy Efficiency |
| 1.6 WARRANTY |
| 1.6.1 LED Luminaire Warranty |
| 1.6.1.1 Provide Luminaire Useful Life Certificate |
| PART 2 PRODUCTS |
| 2.1 PRODUCT COORDINATION |
| 2.2 LUMINAIRES |
| 2.2.1 LED Luminaires |
| 2.2.2 Luminaires for Hazardous Locations |
| 2.3 DRIVERS |
| 2.3.1 LED Drivers |
| 2.4 LIGHT SOURCES |
| 2.4.1 LED Light Sources |
| 2.5 LIGHTING CONTROLS |
| 2.5.1 Toggle Switches |
| 2.5.2 Dimming Controllers Dimmers |
| 2.5.3 Sensors for Lighting Control |
| 2.5.3.1 Occupancy Sensors |
| 2.5.3.1.1 Passive Infrared PIR Sensors |
| 2.5.3.1.2 Ultrasonic Sensors |
| 2.5.3.1.3 Dual Technology Sensors |
| 2.5.3.1.4 Power Packs for Sensors |
2.5.3.2 Vacancy Sensors
| 2.5.4 Lighting Contactor |
| 2.5.5 Timeswitch |
| 2.5.6 Local Area Lighting Controller |
| 2.6 EXIT AND EMERGENCY LIGHTING EQUIPMENT |
| 2.6.1 Exit Signs |
| 2.6.1.1 LED Self-Powered Exit Signs |
2.6.2 Emergency Lighting Unit EBU
| 2.7 LUMINAIRE SUPPORT HARDWARE |
| 2.7.1 Wire |
| 2.7.2 Wire for Humid Spaces |
| 2.7.3 Threaded Rods |
| 2.7.4 Straps |
| 2.8 EQUIPMENT IDENTIFICATION |
| 2.8.1 Manufacturer's Nameplate |
| 2.8.2 Labels |
| 2.9 FACTORY APPLIED FINISH |
| 2.10 RECESS- AND FLUSH-MOUNTED LUMINAIRES |
| 2.11 SUSPENDED LUMINAIRES |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.1.1 Light Sources |
| 3.1.2 Luminaires |
| 3.1.3 Suspended Luminaires |
| 3.1.4 Ballasts, Generators and Power Supplies |
| 3.1.5 Exit Signs and Emergency Lighting Units |
| 3.1.6 Photocell Switch Aiming |
| 3.1.7 Occupancy/Vacancy Sensors |
| 3.1.8 Daylight or Ambient Light Level Sensor |
3.2 FIELD APPLIED PAINTING
File details come from the government source that posted it. Updated .