719_BC-PH2 Sheet EP602.pdf

PDF 88 KB Posted

Attached to
Battalion Complex (Amendment 8)
Solicitation number
W9123620R0001
Issued by

View the file

Other files

File Type Posted
W9123620R0001P0008 - Amendment 8.pdf PDF
18245_ - AREA T - POWER.pdf PDF
A.07.24 - W9123620R0001(Amendment 7).pdf PDF
W9123620R0001 Amendment 6.pdf PDF
719_BC-PH2_SF423.pdf PDF
719_BC-PH2_MP121.pdf PDF
719_BC -PH2-A-601.pdf PDF
719_BC-PH2_SF600(Amend5).pdf PDF
720_BC-PH3-S504.pdf PDF
719_BC-PH2_26 20 00.pdf PDF
719_BC-PH2_MP111.pdf PDF
719_BC_PH2_Sheet A-200.pdf PDF
719_BC_Sheet - I-003.pdf PDF
719_BC-PH2_SF505.pdf PDF
719_BC-PH2_MP122.pdf PDF
720_BC-PH3-CS103.pdf PDF
719_BC-PH2_MP116.pdf PDF
719_BC-PH2_SF422.pdf PDF
719_BC_Sheet - I-223.pdf PDF
05 12 00.pdf PDF
22 00 00.pdf PDF
720_BC-PH3-CU102.pdf PDF
719_BC_PH2_Sheet A-412.pdf PDF
720_BC-PH3-S215 (1).pdf PDF
719_BC_FFE_PH2_Amendment 5 sheets(Amend5).pdf PDF
719_BC-PH2_SF420.pdf PDF
719_BC-PH2 Sheet EP404.pdf PDF
26 51 00.pdf PDF
719_BC-PH2_SF425.pdf PDF
10 28 13.pdf PDF
23 65 00.pdf PDF
28 31 76.pdf PDF
719_BC_Sheet - I-008.pdf PDF
AMEND005-719_BC-PH2_FA001-FA126.pdf PDF
719_BC-PH2_03 30 00.00 10.pdf PDF
719_BC-PH2_10 21 13.pdf PDF
PH1 TWS TWR piping routing.pdf PDF
720_BC-PH3-SF600.pdf PDF
720_BC_PH3_EL119-EL123_EL502.pdf PDF
719_BC-PH2_FA001_FA111-FA114.pdf PDF
719_BC_Sheet - I-124.pdf PDF
719_BC -PH2-A- 603.pdf PDF
719_BC_PH2_Sheet A-411.pdf PDF
720_BC_PH3_FP001_FP140-FP143.pdf PDF
719_BC-PH2_SF421.pdf PDF
719_BC-PH2_SB106.pdf PDF
720_BC_PH3_A-605.pdf PDF
719_BC-PH2_MP113.pdf PDF
719_BC-PH2_11 46 01.06.pdf PDF
719_BC-PH2_S-001(Amend5).pdf PDF
Show 40 more

Latest 50 of 136 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S D

R

AW

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

'D

D

AT

E

TI

M

E

ST

AM

P:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

PR

O

JE

C

T N

O

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

PROPERTY OF UNITED STATES GOVERNMENT, FOR OFFICIAL USE ONLY (FOUO). COPYING, DISSEMINATION, AND DISTRIBUTION TO UNAUTHORIZED INDIVIDUALS PROHIBITED.

4/

/2

:3 7:

P

M

EP602

PHASE 2

PA

N

EL

BO

AR

D

S C

H

ED

U

LE

S

B

AT

TA

LI

O N

C O

M

PL

EX

N

O R

FO

LK

D

IS

TR

IC

T N

O R

FO

LK

, V A

R . K

U

ST

O W

SK

I

E.

M

O R

TO

N

R . N

AG

EL

R . K

U

ST

O W

SK

I

JA

N

U

AR

Y

R

TA

S U

BM

IT

TA

L

NOTES:

RECEPTACLE 32140 VA 65.56% 21070 VA

MOTORS (CONTINUOUS) 0 VA 0.00% 0 VA

MOTORS 0 VA 0.00% 0 VA

MISCELLANEOUS 5243 VA 65.00% 3408 VA TOTAL EST. DEMAND: 87 A

LIGHTING 13120 VA 100.00% 13120 VA TOTAL CONN. CURRENT: 113 A

KITCHEN EQUIPMENT 438 VA 65.00% 285 VA TOTAL EST. DEMAND: 72298 VA

HVAC 43093 VA 80.00% 34474 VA TOTAL CONN. LOAD 94027 VA

COMPUTER 210 VA 70.00% 147 VA

LOAD CLASSIFICATION CONNECT LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 113 A 112 A 114 A

TOTAL LOAD: 31241 VA 31096 VA 31692 VA

-- -- -- 17296 0 20 A SPARE 42

-- -- -- 17405 0 20 A SPARE 40

37,39,41 TG-1134 125 A SEE FEEDER SCHEDULE 17558 0 -- -- SPACE 38

35 SPARE 20 A 0 0 -- -- SPACE 36

33 SPARE 20 A 0 0 -- -- SPACE 34

31 SPACE -- -- 0 0 -- -- SPACE 32

29 SPACE -- -- 0 0 -- -- SPACE 30

27 SPACE -- -- 0 4476 -- -- --

25 WAHP-1117 15 A 2#10, 1#10 GND, 1/2"C 2493 4476 -- -- --

23 WAHP-1140A 15 A 2#12, 1#12 GND, 1/2"C 2493 4476 3#12, 1#12 GND, 3/4"C 20 A WAHP-1135 24,26,28 21 WAHP-1113 15 A 2#12, 1#12 GND, 1/2"C 803 803 2#12, 1#12 GND, 1/2"C 15 A WAHP-1112 22 19 WAHP-1123 15 A 2#12, 1#12 GND, 1/2"C 803 803 2#12, 1#12 GND, 1/2"C 15 A WAHP-1116 20 17 WAHP-1127 15 A 2#12, 1#12 GND, 1/2"C 803 803 2#12, 1#12 GND, 1/2"C 15 A WAHP-1126 18 15 WAHP-1215 15 A 2#12, 1#12 GND, 1/2"C 803 803 2#12, 1#12 GND, 1/2"C 15 A WAHP-1132 16 13 WAHP-1222 15 A 2#12, 1#12 GND, 1/2"C 803 803 2#12, 1#12 GND, 1/2"C 15 A WAHP-1218 14 11 WAHP-1140B 15 A 2#12, 1#12 GND, 1/2"C 3027 942 2#12, 1#12 GND, 1/2"C 15 A WAHP-1115 12 9 INV-1134 20 A 2#12, 1#12 GND, 1/2"C 3047 300 2#12, 1#12 GND, 1/2"C 20 A LIGHTING CONTROL PNL 1134 10 7 LIGHTING RM 1002 20 A 2#10, 1#10 GND, 1/2"C 1193 658 2#12, 1#12 GND, 1/2"C 20 A EXTERIOR LIGHTING 8 5 LIGHTING RM 1127 20 A 2#10, 1#10 GND, 1/2"C 1007 935 2#12, 1#12 GND, 1/2"C 20 A LIGHTING RM 1126 6 3 LIGHTING RM 1003 20 A 2#12, 1#12 GND, 1/2"C 650 2126 2#10, 1#10 GND, 1/2"C 20 A LIGHTING RM 1133 4 1 LIGHTING RM 1134 20 A 2#12, 1#12 GND, 1/2"C 1071 732 2#12, 1#12 GND, 1/2"C 20 A LIGHTING RM 1140 2

CKT CIRCUIT DESCRIPTION TRIP

WIRE AND CONDUIT SIZE A B C A B C WIRE AND CONDUIT SIZE

TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 225 A

SUPPLY FROM: SBG-1134 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELEC 1134 VOLTS: 480/277 Wye A.I.C RATING: 42 KAIC

BRANCH PANEL: HG1-1134

NOTES:

RECEPTACLE 0 VA 0.00% 0 VA

MOTORS (CONTINUOUS) 0 VA 0.00% 0 VA

MOTORS 3991 VA 65.00% 2594 VA

MISCELLANEOUS 0 VA 0.00% 0 VA TOTAL EST. DEMAND: 325 A

LIGHTING 0 VA 0.00% 0 VA TOTAL CONN. CURRENT: 407 A

KITCHEN EQUIPMENT 0 VA 0.00% 0 VA TOTAL EST. DEMAND: 270298 VA

HVAC 334630 VA 80.00% 267704 VA TOTAL CONN. LOAD 338621 VA

COMPUTER 0 VA 0.00% 0 VA

LOAD CLASSIFICATION CONNECT LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 407 A 407 A 407 A

TOTAL LOAD: 112874 VA 112874 VA 112874 VA

41 SPARE 20 A 0 0 20 A SPARE 42

39 SPARE 20 A 0 0 20 A SPARE 40

37 SPACE -- -- 0 0 -- -- SPACE 38

35 SPACE -- -- 0 0 -- -- SPACE 36

33 SPACE -- -- 0 0 -- -- SPACE 34

31 SPACE -- -- 0 0 -- -- SPACE 32

-- -- -- 1330 5127 -- -- -- -- -- -- 1330 5127 -- -- --

25,27,29 JOCKEY PUMP CONTROLLER 15 A 3#12, 1#12 GND, 3/4"C 1330 5127 3#10, 1#10 GND, 3/4"C 50 A SSF-1 26,28,30 -- -- -- 5265 609 -- -- -- -- -- -- 5265 609 -- -- --

19,21,23 DWP-1 50 A 3#10, 1#10 GND, 3/4"C 5265 609 3#12, 1#12 GND, 3/4"C 15 A CP-1 20,22,24 -- -- -- 31593 31593 -- -- -- -- -- -- 31593 31593 -- -- --

13,15,17 DOAS-1 125 A 3#1/0, 1#6 GND, 2"C 31593 31593 3#1/0, 1#6 GND, 2"C 125 A DOAS-2 14,16,18 11 -- -- 0 1330 -- -- -- 9 -- -- 0 1330 -- -- -- 7 FUTURE 3 POLE SPACE FOR P-3 -- -- 0 1330 3#12, 1#12 GND, 3/4"C 15 A EF-1 8,10,12

-- -- -- 18013 18013 -- -- -- -- -- -- 18013 18013 -- -- --

1,3,5 P-1 175 A 3#3, 1#6 GND, 1-1/2"C 18013 18013 3#3, 1#6 GND, 1-1/2"C 175 A P-2 2,4,6

CKT CIRCUIT DESCRIPTION TRIP

WIRE AND CONDUIT SIZE A B C A B C WIRE AND CONDUIT SIZE

TRIP CIRCUIT DESCRIPTION CKT

100% RATED MAIN CB

NOTES:

ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 400 A

SUPPLY FROM: SBG-1134 PHASE: 3 MAINS TYPE: MCB

LOCATION: MECH./FP 1136 VOLTS: 480/277 Wye A.I.C RATING: 35 KAIC

BRANCH PANEL: HG1-1136

NOTES:

RECEPTACLE 17265 VA 78.96% 13633 VA

MOTORS (CONTINUOUS) 0 VA 0.00% 0 VA

MOTORS 696 VA 65.00% 452 VA

MISCELLANEOUS 26131 VA 65.00% 16985 VA TOTAL EST. DEMAND: 83 A

LIGHTING 8828 VA 100.00% 8828 VA TOTAL CONN. CURRENT: 109 A

KITCHEN EQUIPMENT 8445 VA 65.00% 5489 VA TOTAL EST. DEMAND: 68680 VA

HVAC 24063 VA 80.00% 19250 VA TOTAL CONN. LOAD 90854 VA

COMPUTER 4630 VA 70.00% 3241 VA

LOAD CLASSIFICATION CONNECT LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 174 A 159 A 153 A

TOTAL LOAD: 48081 VA 43731 VA 42268 VA

-- -- -- 18176 0 20 A SPARE 42

-- -- -- 20354 0 20 A SPARE 40

37,39,41 TG-1202 125 A SEE FEEDER SCHEDULE 19450 0 -- -- SPACE 38

35 SPARE 20 A 0 14410 -- -- --

33 SPARE 20 A 0 14410 -- -- --

31 SPACE -- -- 0 14410 3#4, 1#6 GND, 1-1/4"C 150 A CBU-1203 (ELEVATOR (EA1)) 32,34,36

29 SPACE -- -- 0 0 -- -- SPACE 30

27 SPACE -- -- 0 0 -- -- SPACE 28

25 SPACE -- -- 0 0 -- -- SPACE 26

-- -- -- 1635 0 -- -- SPACE 24

-- -- -- 1635 0 -- -- SPACE 22

19,21,23 WAHP-1205 15 A 3#12, 1#12 GND, 3/4"C 1635 1635 -- -- --

17 WAHP-1106 15 A 2#12, 1#12 GND, 1/2"C 803 1635 -- -- --

15 WAHP-1210 15 A 2#12, 1#12 GND, 1/2"C 803 1635 3#12, 1#12 GND, 3/4"C 15 A WAHP-1100 16,18,20 13 WAHP-1104 15 A 2#12, 1#12 GND, 1/2"C 2019 3795 2#10, 1#10 GND, 1/2"C 25 A WAHP-1211 14 11 WAHP-1102 15 A 2#12, 1#12 GND, 1/2"C 941 2019 2#12, 1#12 GND, 1/2"C 15 A WAHP-1133 12 9 WAHP-1204 15 A 2#12, 1#12 GND, 1/2"C 2493 803 2#12, 1#12 GND, 1/2"C 15 A WAHP-1201 10 7 WAHP-1105 15 A 2#12, 1#12 GND, 1/2"C 803 1939 2#12, 1#12 GND, 1/2"C 20 A INV-1202 8 5 LIGHTING RM 1351 20 A 2#12, 1#12GND, 1/2"C 396 2297 2#10, 1#10 GND, 1/2"C 20 A LIGHTING RM 1203 6 3 LIGHTING CONTROL PNL RM 1202 20 A 2#12, 1#12 GND, 1/2"C 300 1363 2#12, 1#12GND, 1/2"C 20 A LIGHTING RM 1210 4 1 LIGHTING RM 1010 20 A 2#12, 1#12 GND, 1/2"C 1066 1443 2#12, 1#12 GND, 1/2"C 20 A LIGHTING RM 1202 2

CKT CIRCUIT DESCRIPTION TRIP

WIRE AND CONDUIT SIZE A B C A B C WIRE AND CONDUIT SIZE

TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 225 A

SUPPLY FROM: SBG-1134 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELEC 1202 VOLTS: 480/277 Wye A.I.C RATING: 22 KAIC

BRANCH PANEL: HG1-1202

NOTES:

RECEPTACLE 32760 VA 65.26% 21380 VA

MOTORS (CONTINUOUS) 0 VA 0.00% 0 VA

MOTORS 0 VA 0.00% 0 VA

MISCELLANEOUS 58346 VA 65.00% 37925 VA TOTAL EST. DEMAND: 133 A

LIGHTING 26222 VA 100.00% 26222 VA TOTAL CONN. CURRENT: 181 A

KITCHEN EQUIPMENT 5376 VA 65.00% 3494 VA TOTAL EST. DEMAND: 110763 VA

HVAC 24161 VA 80.00% 19329 VA TOTAL CONN. LOAD 150354 VA

COMPUTER 3620 VA 70.00% 2534 VA

LOAD CLASSIFICATION CONNECT LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 193 A 192 A 165 A

TOTAL LOAD: 52375 VA 52156 VA 45824 VA

-- -- -- 30359 0 20 A SPARE 42

-- -- -- 30665 0 20 A SPARE 40

37,39,41 TG-1220 150 A SEE FEEDER SCHEDULE 30994 0 -- -- SPACE 38

35 SPARE 20 A 0 0 -- -- SPACE 36

33 SPARE 20 A 0 0 -- -- SPACE 34

31 SPACE -- -- 0 0 -- -- SPACE 32

29 SPACE -- -- 0 0 -- -- SPACE 30

-- -- -- 2771 3048 -- -- -- -- -- -- 2771 3048 -- -- --

23,25,27 WAHP-1226 15 A 2#12, 1#12GND, 1/2"C 2771 3048 3#10, 1#10 GND, 3/4"C 30 A AC-1 24,26,28

21 WAHP-1221B 15 A 2#12, 1#12 GND, 1/2"C 2493 2522 -- -- --

19 WAHP-1335 15 A 2#12, 1#12 GND, 1/2"C 803 2522 -- -- --

17 WAHP-1327 15 A 2#12, 1#12 GND, 1/2"C 2493 2522 3#12, 1#12 GND, 3/4"C 15 A WAHP-1325B 18,20,22 15 LIGHTING RM 1341 20 A 2#10, 1#10 GND, 1/2"C 2532 2493 2#12, 1#12 GND, 1/2"C 15 A WAHP-1328 16 13 LIGHTING 2 GYM CANOPY B 20 A 2#12, 1#12 GND, 1/2"C 413 7479 2#8, 1#10 GND, 3/4"C 35 A INV-1220 14 11 LIGHTING RM 1310 20 A 2#10, 1#10 GND, 1/2"C 2268 453 2#12, 1#12 GND, 1/2"C 20 A EXTERIOR LIGHTING 12 9 LIGHTING CONTROL PNL RM 1220 20 A 2#12, 1#12 GND, 1/2"C 300 2268 2#10, 1#10 GND, 1/2"C 20 A LIGHTING RM 1310 10

7 1522 2#10, 1#10GND, 1/2"C 20 A LIGHTING RM1315 8

5 LIGHTING RM 1314 20 A 2#12, 1#12GND, 1/2"C 318 1709 2#10, 1#10GND, 1/2"C 20 A LIGHTING RM 1219 6 3 LIGHTING RM 1312 20 A 2#10, 1#10GND, 1/2"C 1745 1394 2#10, 1#10GND, 1/2"C 20 A LIGHTING RM 1220 4 1 LIGHTING RM 1007 20 A 2#10, 1#10 GND, 1/2"C 1342 1662 2#10, 1#10GND, 1/2"C 20 A LIGHTING RM 1226 2

CKT CIRCUIT DESCRIPTION TRIP

WIRE AND CONDUIT SIZE A B C A B C WIRE AND CONDUIT SIZE

TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 225 A

SUPPLY FROM: SBG-1134 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELEC 1220 VOLTS: 480/277 Wye A.I.C RATING: 18 KAIC

BRANCH PANEL: HG1-1220

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AM

E N D

M

EN

T

AP

R

2 0

Sheets
EP404 - ENLARGED PLANS
EP602 - PANELBOARD SCHEDULES