Questions 17-63.xlsx

XLSX spreadsheet 19 KB Posted

Attached to
Building 420 Renovation Federal contract opportunity
Solicitation number
W50S98-21-B-0001
Issued by
Department of the Army Tennessee Army National Guard

About this file

This document contains questions and answers related to a construction contract solicitation for renovations to Building 420 at McGhee Tyson Air National Guard Base in Tennessee. The solicitation is for repair and upgrades to the dining and medical training facility, with a project magnitude between $5-10 million. The work includes kitchen equipment replacement, elevator upgrades, roof repairs, window and curtainwall replacements, and other renovations. The pre-bid conference was to be held on-site, and bids were due from small businesses only with a NAICS code of 236220 and size standard of $39.5 million in average annual receipts. Funding may become available by September 30, 2021, and award will be to the responsible bidder providing the most advantageous price.

View the file

Other files for this federal contract opportunity

Other files attached to Building 420 Renovation, newest first.
File Type Posted
W50S9821B0001 Abstract 1419.pdf PDF
Amendment 6 B420 Revised.pdf PDF
Amendment 6 B420.pdf PDF
McGhee Tyson ANG_5.12.20-QF101.pdf PDF
Amendment 5 420 PreBid Questions.xlsx XLSX spreadsheet
B420 Geotechnical Report.pdf PDF
Amendment 5 B420.pdf PDF
Amendment 4 B420.pdf PDF
21B0001P0001 Solicitation Amendment Conformed Copy.pdf PDF
21B0001P0001 Solicitation Amendment.pdf PDF
Amendment 3 B420.pdf PDF
Wage Determination TN20210077 1 Jan 2021.pdf PDF
Amendment 2 B420.pdf PDF
Amendment 1 B420.pdf PDF
Old Addition Drawings.pdf PDF
Old Original Facility Drawings.pdf PDF
Questions 11-16.pdf PDF
Question 1-9 Corrected.pdf PDF
Building 420 A4.0.pdf PDF
Question 10.pdf PDF
S1-1.PDF PDF
Building 420 A3.2.pdf PDF
Building 420 A4.1.pdf PDF
Building 420 S1.2.pdf PDF
Pre-Bid Sign in Sheet.pdf PDF
Pre-Bid Slides.pdf PDF
Pre-Bid Minutes W50S98-21-B-0001.pdf PDF
Questions 1-9.pdf PDF
Construction PWS PSXE162007 Repair Dining- Medical Training Facility-Bldg 420.pdf PDF
Repair B420 - Type B-3 - Vol 2 Drawings (Half Size).pdf PDF
Repair B420 - Type B-3 - Vol 3 Specs (Div 01-11) V2.pdf PDF
Repair B420 - Type B-3 - Vol 4 Specs (Div 12-33).pdf PDF
W50S98-21-B-0001 Solicitation.pdf PDF
Show all 33

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

QuestionResponse
17We have a 2nd floor demo plan, but I do not see a lower level ceiling demo plan. What is the extent of the ceiling demo on the 2nd floor?Note G on AD101 indicates all ceilings are to be removed at the first level.
18Sheet A201, Keynote #13 directs us to provide windows that meet the ATFP design standards. I have not found these standards defined in specifications 08.41.13 or 08.44.00. What are the requirements?Glazing required to meet AT/FP requirements will be 1/4-inch laminated glass consisting of two nominal 1/8-inch glass panes bonded together with a minimum of a 0.030 inch interlayer of a material designed for blast resistance. The innermost pane of insulated glass units (IGU) will comply with this requirement. Glazing frame bite will be in accordance with ASTM F 2248.
19Are the construction drawings for the existing building available?Yes, they have been posted for reference only. Accuracy can not be confirmed.
20There are two specifications listed for the metal roof system, 074113 metal roofing and 076114 standing seam roofing. Please clarify the scope associated with each of these specifications.07 41 13 is for the pre-engineered canopies. 07 61 14 applies to the building roof.
21Several locations show new HVAC duct running parrallel or diagonally over existing walls to remain (see attached sketch). Do these walls currently extend to the deck? How will the existing walls need to be modified to accomodate this condition?Drawing A003 Indicates which new walls are full or partial height. Existing building drawings A.01 and A.02 identify existing fire rated walls. Obtain existing drawings from the base. New duct penetrations through full height existing walls will require demolition to frame out and seal these openings.
22What is to be included in ABI 04 Kitchen Equipment compared to the Base bid? Demo, storage, cleaning, installation, new equipment, etc...?The bulk of equipment as directed per AD-120 is to be removed. ABI #4 includes:

1. Only new equipment to replace equipment being removed and not put back later.

The Base Bid encompasses everything else, including:

1. New freezers and coolers (per specification 11 41 11 and drawing M-703). Note: the comment in parenthesis at title of Equipment Schedule on sheet Q-120 stating that the freezers and coolers are GFCI is in error.

2. Equipment to be removed, cleaned, stored, and reinstalled at completion per drawings A-120 and Q-120 and UFC 02 41 00. Note: some keynotes on sheet A-120 mark the location of new equipment for information and coordination purposes only for Base Bid, and are labeled N.I.C.

3. The remaining balance of all removed equipment to be salvaged and turned over to the Government per drawing AD-120 and section 3.3.3c of UFC 02 41 00.

23C101 shows a new 8'x12' metal canopy and refers us to architectural and structural plans for details. I have found no reference to this canopy on the architectural or structural plans. Please clarify the requirements.Construct slab according to B2/S504. Provide a pre-engineered aluminum, open canopy with metal roof in accordance with site canopy drawing: A-560/Canopy Plans, Elevation and Details. .
24C101 directs us to remove and replace the existing handrails on the ramp and refers us to detail B1/C501. There no ramp rails shown in this detail. Please clarify the requirements.The handrails shown in the detail B1/C-501 are representative of the style, material, color, as well as the attachment requirements for all locations around the building including ramps.
25There is a 9 ft elevation change between the top of the footing at the mechanical room addition and the adjacent grade (the road). The work requires us to demolish a portion of the existing retainaing wall and build a new retaining wall. OSHA regulations require that the bank be laid back or shored during constuciton to protect the workers from an open excavation. Is road closure an option or will you require that the bank be temorarily shored to keep the road open.?A temporary road closure is acceptable so the excavation can be properly laid back. The contractor would be repsonsible when taking this approach for road repairs.
26Curtainwall spec 084400 para 1.3.5.5 calls out an “opaque” U-factor of no greater than 0.29. Glazing spec 088100 para 2.2 calls out a U-factor of 0.4 or less for the insulated glass units. Drawing A003 thermal shielding table lists fixed glass windows as having a U-factor of 0.40. Is it correct to assume that the entire curtainwall system (glazing + framing) should have a U-factor of 0.40 or less, and glazing should be selected as required to meet this overall system thermal performance?Yes, assume U-factor of 0.40 or less, and glazing should be selected as required to meet this overall system thermal performance
27Could micropiles be used in place of helical piles? Please adviseThe helical piers are designed and specified based on a site-specific geotechnical investigation, use helical piers as specified.
28The IG unit specified in glazing spec 088100 para 2.2 last paragraph lists an IG unit makeup of bronze tint (uncoated) on the exterior lite, and clear(uncoated) on the interior lite, with argon fill. Are low-E coatings on the IG units acceptable to improve the thermal performance of the IG units in order to meet the overall window system U-value requirements?Yes, low-E coatings are acceptable
29Doors are listed as impact resistant in para 2.2 of spec 084113. Are there any requirements for impact resistance on the storefront and curtainwall not associated with doors?The glazing needs to meet AT/FP requirements. Glazing required to meet AT/FP requirements will be 1/4-inch laminated glass consisting of two nominal 1/8-inch glass panes bonded together with a minimum of a 0.030 inch interlayer of a material designed for blast resistance. The innermost pane of insulated glass units (IGU) will comply with this requirement. Glazing frame bite will be in accordance with ASTM F 2248.
30B1/C501 shows a (2) line aluminum handrail with a powercoat finish for site ramps and stairs. Details on sheet A540 show a steel handrail with pickets and a field painted finish. These details appear to conflict, please clarify the requirements.Railings will be aluminum with powder coat finish, Dove Gray.
31In the responses to Questions, the response to Question #11 references a site specific geotechnical investigation. It does not appear that the geotechnical information or a subsequent report with recommendations is currently provided in the bidding documents. Please provide this information.We defer to the Gov't to supply the geotechnical report.
32Specification Section 31 32 26 (Polyurethane Foam Injection Grouting) lists three unit items which will be the basis of payment for work performed under this specification. Those unit items are Drilling Injection Holes, Polyurethane materials, and Injection (with units of measure being linear foot, pounds, and pounds, respectively). We cannot identify where units for bidding have been provided. Please provide details on bid units.This is a fixed price contract, include all work in proposal. Disregard the unit price requirements of this specification.
33The existing steel structure has spray on fire proofing but the new structure does not. Will modifications to the existing structure require patching the fire proofing?Yes, any existing fireproofing that is damaged will require repair.
34Specification 01.91.00 calls for a 3rd party commission agent to be paid for by the Contractor. Typically, commissioning is performed by the owner. Please confirm that the cost of commisioning is to be included in the base bid.The cost of commissioning is to be included in the base bid. The Govt is the owner and will not do this.
35Will the contents of the building (furniture, etc...) be removed by others prior to start of construction?The Governmemt will remove, store and protect existing contents to include furniture, pictures, personal items, and other items UNO in construction documents. Include scope of items to be included, scheduling and coordination of removal of these items with the Base in the Demolition/Deconstruction Plan required in section 1.2.2 of specification 02 41 00 Demolition.
36Drawings AD-120 calls for the contractor to remove kitchen equipment that is not shown on sheet Q-120. Sheet A-120 states that this kitchen equipment is not in contract. Should the equipment scheduled for removal be disposed of by the contractor or turned over to the Owner?Equipment scheduled for removal not to be replaced shall be deemed salvageable and turned over as property of the Government as described in section 3.3.3c of UFC 02 41 00 Demolition.
37Kitchen equipment subcontractors are asking for the manufacture of the Owner furnished and contractor installed freezers and coolers. This can affect the installation cost due to manufactures requirements?The contractor will demo the existing freezers and coolers and provide new per specification 11 41 11 and drawing M-703.

Note: the comment in parenthesis at title of Equipment Schedule on sheet Q-120 stating that the freezers and coolers are GFCI is in error. They are to be included in the Base Bid.

38Kitchen equipment subcontractors are asking if there is any new equipment furnished by contractor?For the Base Bid the contractor will demo the existing freezers and coolers and provide new per specification 11 41 11 and drawing M-703.
39Is all kitchen equipment as shown on bid documents to be priced in Option # 4?ABI #4 includes:

1. Only new equipment to replace equipment being removed and not put back later.

40Suppliers are asking for a manufacture for the aluminum insulated wall panels. They are saying they can find metal but not aluminum.07 42 13 specifies aluminum sheet metal wall panels, not insulated metal wall panels.
41Sheet AD-130 calls for the loading dock roof to remain. Sheet A-130 calls for a new loading dock roof. Which sheet is correct?The loading dock roof will be demolished and replaced by the new pre-engineered loading dock canopy.
42Sheet Q-120 is for the kitchen equipment. Are we to price this sheet only in Option 4? If not what is to be priced in Option 4?Q-120 and specification spec 11 41 11 cover the kitchen equipment.
43Please confirm that UFC 4-010-01 (Antiterrorism standards) do not apply.UFC 4-010-01 applies to this project.
44Does the elevator as shown in Option # 2 go from a 2 stop elevator to a 3 stop elevator?Yes, the base bid is a 2 stop elevator, bid option #2 adds a 3rd stop for roof access.
45Can the government be more specific on how the contractor is to repair brick where settlement has occurred? The bid documents state to replace brick as required or repoint brick. The government should tells us what to price so all contractors will be on the same page.Drawing AD102 identifies the affected area with keynote #2. Photos of this area are provided on this drawing to show the brick damage.
46On the roof support columns, are there any as-built designs for the footers for those columns?This has been posted for reference only. Accuracy can not be confirmed.
47Sheet A120, Keynote #16 references Details C5/A-411. However, there is no Detail C5 on sheet A-411. Please provide details for Keynote #16.This is an error. Sheet A-120, keynote #16 should point to detail D1/A-411. Additionally, sheet A-120 keynote #17 should point to detail D1/A-411 as well. Detail D1/A-411 will be updated to show 20 ga 307 stainless steel panels adhered with adhesive.
48The Door Hardware schedule shows electric hardware for several doors, but there is not a spec section. Is this “Security by Owner?” If not, please provide a spec section.All door hardware to be provided by contractor.
49Please provide information on the type of control system (brand and model #) of your current access control system.The ACS brand and model is determined by the Base. The design is for infrastructure only (conduit pathways, door pathways, backboxes for card readers, etc). The Base Security Contractor will provide the system and ACS wiring.
50The Equipment schedule on sheet A Q-120 states that the Freezer/Coolers are GFCI. However, Sheet M-703 states to provide Freezers and Coolers. Can you please clarify who is providing the Freezers and Coolers?The contractor will demo the existing freezers and coolers and provide new per specification 11 41 11 and drawing M-703.

Note: the comment in parenthesis at title of Equipment Schedule on sheet Q-120 stating that the freezers and coolers are GFCI is in error. They are to be included in the Base Bid.

51Item No#0006, Option 4, is for Kitchen equipment. Can you please clarify which Kitchen Equipment this is referring to?Q-120 and specification spec 11 41 11 cover the kitchen equipment.
52Can you please extend the bid due date to 2/24/21?The bid due date has been extended past this date.
53Mechanical drawing M-703 has a freezer / cooler schedule and there is a specification section (23 63 00.00 10) that full describes the freezers and coolers. If they are furnished by the Owner and installed by the contractor, why are they so clearly specified on the mechanical drawings and specifications?New freezers and coolers shall be provided per specifications 11 41 11, 23 63 00.00 10 and drawing M-703. Note: the comment in parenthesis at title of Equipment Schedule on sheet Q-120 stating that the freezers and coolers are GFCI is in error.
54The lumber for the wooden clouds scheduled for the dining facility weighs approximately 48,000 lbs plus hardware and lighting. There is no support system / cabling designed and will your roof structure support the added weight?The weight of the ceiling system identified in specification 09 54 26 was checked against roof capacity with current framing and sheathing removed and was acceptable.
55The 2 stop base bid we can provide the hydraulic elevator design. For the alternate of 3 stops at 37’ 10” of rise the hydraulic design cannot accommodate this. the design will need to be changed to the EVO 200 traction elevator design. This will change the hoistway dimensions, pit, overhead, and electrical. Now we can provide the traction design for the 2 stop and the 3 stop. If they are think about adding the 3rd landing for a future the traction is the only option.Basis-of-Design is Thyssenkrup MRL Hydraulic elevator: 2-stage for Base Bid 2-stop version, and 3-stage 3-stop version with 1'-0" added to the pit depth, 5'-0" total.
56Keynote #3 on Sheet AC110 refers to Detail D1/AC111. However, Detail D1/AC111 shows a detail for the reflected Ceiling Plan at the Check-In area. Please provide a detail for the Gypsum Board Soffit area in the Corridor 130Keynote #3 is in error. See details D4 & D5/A-410, similar.
57Is the Wing Element for the Upper Floor a design-build or is there a specific manufacturer that will create this element?This is a design build element, shop drawings should be submitted for review and approval prior to fabrication.
58The Finish Schedule includes a couple of Walk Off Mats. Please provide the sizes of these mats for the 102 & 202 Entry Vestibules and 227 Vestibule.Vestibule 102: 8'-0"wide (parallel with and centered on entry doors) x 6'-0" deep

Vestibule 202: 6'-0"wide (parallel with entry doors) x 7'-0"deep Vestibule 227: 6'-0"wide (parallel with entry doors) x 8'-0"deep

59Wall Types on sheet A003 are listed as not to scale. However, they do not call out a size for the Metal Studs. Please provide size information for the Metal Studs.Provide min. 20ga, 3-1/2 metal studs for all non-load bearing interior walls that are not constrained as part of existing wall infill or matching, or UNO.
60Sheet A110, shows two W7 windows by the elevator (office 143 & conference 146). Are they considered “Southeast elevation” and are therefore part of ABI #1 or are they part of the base bid?Windows tagged W7 at Office 143 & 146 are part of Base Bid
61Sheet A-560 shows the details for the canopy. However, there is not a spec section. Please provide a spec section for this canopy.Basis-of-Design for the canopy is Mapes Super Lumideck, Post Supported; refer to Mapes Super Lumideck Specification for typical specification that describes to meet or exceed level of quality and construction: www.mapescanopies.com
62The drawings and specs call for American Olean Tile. Please provide the series for the 4 x 12 wall tile and the 24 x 48 floor tile.24 x 48 floor tile to be Americal Olean IDEOLOGY, matte finish. Change 4 x 12 tile to 12 x 24 American Olean MINIMUM, matte finish.
63As here is not machine room on the drawings, can you please confirm that the hydraulic elevator is a Machine Room Less Elevator?The elevator is a machine room-less hydraulic type elevator.