This document contains plumbing schedules and details for Repair Building 113 at the Tennessee Army National Guard McGhee Tyson Air Base in Alcoa, Tennessee. It specifies plumbing fixtures such as an emergency shower/eyewash, electric water cooler, floor drain, undercounter lavatory, washing machine outlet box, and floor-mount water closet. It also includes schedules for electric water heaters located in various buildings and for a breathing air compressor system in Building 134. Product manufacturers and models are identified for most fixtures. Installation details are provided for items such as the emergency shower/eyewash, pipe penetrations, and electric water heaters. Notes cover requirements for exposed piping, P-traps and supplies, insulation, and vent and drainage sizes. The related federal contract opportunity is solicitation number W50S98 for Building 113 repairs with an option to demolish Buildings 110 and 111, issued by the Department of the Army Tennessee Army National Guard.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF 1419 Abstract.pdf | ||
| OF 1419 Abstract.pdf | ||
| Sign in Sheet - 23 Aug 2022 10am.pdf | ||
| B 113 As Built Drawings.pdf | ||
| W50S98-22-B-000100002.pdf | ||
| Demo 110_110 Drawings GC002 003 004 005.pdf | ||
| BLDG 111 Asbestos Info.pdf | ||
| 05 40 00 Cold-formed Metal Framing 20220805.pdf | ||
| Demo Drawings CS503-506.pdf | ||
| REGISTER-upate 07292022.pdf | ||
| 1190113_TNANG_B113_ELEC-ADDENDUM 1-072622.pdf | ||
| W50S98-22-B-000100001.pdf | ||
| 1190113_TNANG_B113_FIRE-ADDENDUM 1-072622.pdf | ||
| 28 31 76 - updated.pdf | ||
| Pre-Bid Slides B113.pdf | ||
| Pre-Bid Sign in Sheet B113.pdf | ||
| MTANG Demo 110 and 111 drawings.pdf | ||
| W50S98-22-B-0001 21 July 2022.pdf | ||
| Repair Building 113 Spec. Volume 1.pdf | ||
| Repair Building 113 Drawings.pdf | ||
| Repair Building 113 Spec. Volume 2.pdf |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LAVATORY
WATER HEATER
MOUNTED ON
WALL
BELOW LAVATORY
CW SUPPLY VALVE
CW
HW
FAUCET
NOTE: COORDINATE WITH ELECTRICAL
ON POWER CONNECTION.
NOTE:
PIPE PENETRATIONS
AT
FIRE RATED WALLS
SHALL BE A UL LISTED
ASSEMBLY
FINISHED WALL
SEALANT-JOINT 1/4"
WIDE MIN. BY 3/8"
DEEP.
METAL JACKET
SLEEVE
INTERIOR SIDE
ESCUTCHEON
PIPE WITHOUT
INSULATION
PIPE WITH
INSULATION
INSULATION
BACKUP MATERIAL
PIPE
ANSI COMPLIANT
IDENTIFICATION
SIGN
TEMPERED
WATER SUPPLY
INLET, 70 DEG F
DELUGE TYPE
EMERGENCY
SHOWER
PULL HANDLE
FOR SHOWER
PUSH PLATE
FOR EYE
WASH
SUPPORT BASE,
SECURE TO FLOOR
PER MANUFACTURER'S
REQUIREMENTS
FINISHED FLOOR
DRAIN TO
FLOOR
EMERGENCY EYE WASH
ALARM HORN
FLOW SWITCH
FINISHED WALLSTAY-OPEN VALVE
STAY-OPEN VALVE
STROBE LIGHT
NOTE:
1. EMERGENCY EYEWASH/SHOWERS SHALL CONNECT TO THE FIRE ALARM SYSTEM.
2. PROVIDE MOVABLE CURTAIN FOR PRIVACY.
DRAIN VALVE (TYP)
BALL VALVE (TYP)
UNION (TYP)
CHECK VALVE (TYP)
EWH
T&P RELIEF
VALVE
1-1/4"CW SUPPLY
1-1/4" TEMPERED WATER
CONNECTION DIRECTLY
TO EMERGENCY EYEWASH
AND SHOWER
EWH IN NEMA 4 EXPLOSION
PROOF CABINET
1. MOUNTING HEIGHT 24" AFF.
NOTES:
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y L a n e
S u it e
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
/1
/2
:3
:5
B
IM
/1
T N
A N
G R e p a ir
B ld g
F u e l C e ll/
T
N A
N G
B v
M P
F P
.r v t
P-601
100% REVISED
P L U
M B
IN
G
S C
H E
D U
L E
S A
N D
S C
H E
D U
L E
S
R E
P A
IR
B
U
IL
D
IN
G
T
H T
E N
N E
S S
E E
A
IR
N A
T
IO
N A
L G
U A
R D
M c G
H E
E T
Y S
O N
A N
G B
A S
E A
L C
O A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
IR
N A
T
IO
N A
L G
U A
R D
A L C
O A
T
E N
N E
S S
E E
J O
B N
O
J N
A
IZ
E R
J F
L Y
N N
J L E
D Y
A R
D
M
A R
C H
S O
L -X
X -X
-X X
X X
W L -1
-D
-0
X X
-X -X
X X
X G
K
E R
R
PLUMBING FIXTURE SCHEDULE
TAG FIXTURE TYPE
CW PIPE
SIZE
HW PIPE
SIZE
WASTE
PIPE SIZE
VENT PIPE
SIZE
FLOW
RESTRICTION
BASIS OF DESIGN
MANUFACTURER MODEL DESCRIPTION
ESEW EMERGENCY
SHOWER/FACEWASH
1-1/4" 1-1/4" -- -- 20 GPM GUARDIAN G1696 FREE-STANDING, STAINLESS STEEL HEAD, #G3800LF THERMOSTATIC
MIXING VALVE TO DELIVER 70°F TEPID WATER. PROVIDE #AP275-200
ELECTRIC FLASHING LIGHT, FIRE ALARM, AND LOCAL ALARM HORN.
EWC-1 ELECTRIC WATER COOLER 1/2" -- 2" 1-1/2" -- MATCH
EXISTING
MATCH
EXISTING
ADA, STAINLESS STEEL, SINGLE WALL-MOUNT WATER COOLER WITH
ENHANCED EZH2O BOTTLE FILLING STATION, ZURN #Z1225 SUPPORT.
FD-1 FLOOR DRAIN -- -- 3" 2" -- ZURN Z1400 CAST IRON FLOOR DRAIN WITH 8" CAST IRON GRATE, CAST IRON
SEDIMENT BUCKET, MEMBRANE CLAMP, AND TRAP PRIMER CONNECTION.
LV-1 UNDER-COUNTER MOUNT
LAVATORY
1/2" 1/2" 2" 1-1/2" 0.5 GPM MATCH
EXISTING
MATCH
EXISTING
PROVIDE WITH P-TRAP (KOHLER K-8998) AND DRAIN COVER. MOUNT TO
COUNTER AS SHOWN PER ARCHITECTURAL DRAWINGS. PROVIDE
HARDWIRED SENSOR FAUCET AND THERMOSTATIC MIXING VALVE.
WB-1 WASHING MACHINE
OUTLET BOX
1/2" 1/2" 2" 2" -- SIOUX CHIEF 696-2313MF FULLY RECESSED WASHING MACHINE SUPPLY BOX WITH COVER.
PROVIDE 1/4 TURN BALL VALVES AND WATER HAMMER ARRESTORS IN
BOX. PROVIDE A 2” TRAPPED STANDPIPE IN CONCEALED WALL SPACE.
WC-1 FLOOR-MOUNT WATER
CLOSET
1" -- 4" 2" 1.28 GPF MATCH
EXISTING
MATCH
EXISTING
PROVIDE WITH ELONGATED OPEN END SEAT. PROVIDE WITH HARDWIRED
SENSOR FLUSH VALVE.
ELECTRIC WATER HEATER SCHEDULE
TAG
LOCATION BASIS OF DESIGN
TYPE
HEATING DATA
FLA MCA MOCP VOLTS PH REMARKSNAME NO. MANUFACTURER MODEL NO.
HEATING
CAPACITY (KW)
MAX TEMP RISE
(°F)
EWH-1 HANGAR BAY 101 EEMAX AP048480 EFD N4 INSTANT 48 16 58 72.5 175 480 3 1 - 3
EWH-2 HANGAR BAY 101 EEMAX AP048480 EFD N4 INSTANT 48 16 58 72.5 175 480 3 1 - 3
EWH-3 FUEL CELL TANK MAINTENANCE 126 EEMAX AP048480 EFD N4 INSTANT 48 16 58 72.5 175 480 3 1 - 3
NOTES:
1. PROVIDE WITH NON-FUSED DISCONNECT BY ELECTRICAL.
2. HEATER MUST COMPLY WITH ANSI Z358.1. PROVIDE WITH INTEGRAL RELIEF AND MIXING VALVE INSIDE EXPLOSION-PROOF NEMA 4 ENCLOSURE.
3. UNIT TO BE WALL-MOUNTED PER MANUFACTURER'S RECOMMENDATION.
NOTES:
1. AUTOMATIC DRIP DRAIN.
2. PROVIDE REFRIGERATED AIR DRYER. BASIS OF DESIGN: CHAMPION CRPC200
3. PROVIDE AIR FILTER. BASIS OF DESIGN: LT CAT RP200.
4. PROVIDE ASME RATED, SECTION VII, RECEIVER TANKS, STAINLESS STEEL TANK. BASIS OF DESIGN: QUINCY T400-200.
5. PROVIDE WITH MANUFACTURER STARTER.
6. DISCONNECT TO BE FURNISHED AND INSTALLED BY ELECTRICAL.
BREATHING AIR COMPRESSOR SCHEDULE
MARK LOCATION MODEL NO. TYPE
TOTAL AIR
(CFM)
PRESSURE
(PSIG)
RECIEVER
CAPACITY
(GAL)
ELECTRICAL DATA
WEIGHT
(LB) COMMENTS
MOTOR
(HP) VOLTAGE PHASE
BC-1 134 MECH CHAMPION L29 BREATHING AIR COMPRESSOR 173 125 400 40 480 3 1501 1, 4, 5, 6
BC-1b 134 MECH CHAMPION CRPC200 AIR DRYER 480 3 438 1, 2, 5, 6
BC-1c 134 MECH LT CAT RP200. AIR FILTER 115 1 125 1, 3
SCALE: N.T.S.C1
TANKLESS ELECTRIC WATER HEATER DETAIL
SCALE: N.T.S.A4
PIPE PENETRATION DETAIL
SCALE: N.T.S.A1
ESEW DETAIL
SCALE: N.T.S.A2
TANKLESS ELECTRIC WATER HEATER DETAIL
NOTES:
1. ALL EXPOSED PIPING AT PLUMBING FIXTURES SHALL BE CHROME PLATED WITH CHROME PLATED ESCUTCHEONS AT WALL PENETRATION.
2. PROVIDE CHROME PLATED BRASS P-TRAP AND SUPPLIES WITH STOP VALVES AT ALL SINKS, LAVATORIES AND DRINKING FOUNTAINS.
3. PROVIDE INSULATION FOR P-TRAP AND SUPPLIES AT ALL HANDICAPPED SINKS AND LAVATORIES.
4. CONNECTION SIZES SHOWN ARE MINIMUM SIZES.
5. SEE PLANS FOR COMMON VENT SIZES.
6. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.