Repair Building 113 Drawings.pdf
PDF 35 MB Posted
- Attached to
- B113 Solicitation Federal contract opportunity
- Solicitation number
- W50S98
About this file
This solicitation is for repair and maintenance services for Building 113 at the Tennessee Army National Guard. The solicitation number is W50S98 and is seeking either repair of Building 113 or demolition of Buildings 110 and 111 as an option. The issuing agency is the Department of the Army Tennessee Army National Guard. Interested parties should respond to this solicitation for repair and maintenance services or the optional demolition work by the specified deadline. The awarded contract will support maintenance and upkeep of facilities at the Tennessee Army National Guard.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF 1419 Abstract.pdf | ||
| OF 1419 Abstract.pdf | ||
| Sign in Sheet - 23 Aug 2022 10am.pdf | ||
| B 113 As Built Drawings.pdf | ||
| Demo 110_110 Drawings GC002 003 004 005.pdf | ||
| BLDG 111 Asbestos Info.pdf | ||
| 05 40 00 Cold-formed Metal Framing 20220805.pdf | ||
| Demo Drawings CS503-506.pdf | ||
| W50S98-22-B-000100002.pdf | ||
| P-601_REVISED.pdf | ||
| REGISTER-upate 07292022.pdf | ||
| 1190113_TNANG_B113_ELEC-ADDENDUM 1-072622.pdf | ||
| W50S98-22-B-000100001.pdf | ||
| 1190113_TNANG_B113_FIRE-ADDENDUM 1-072622.pdf | ||
| 28 31 76 - updated.pdf | ||
| Pre-Bid Sign in Sheet B113.pdf | ||
| Pre-Bid Slides B113.pdf | ||
| MTANG Demo 110 and 111 drawings.pdf | ||
| Repair Building 113 Spec. Volume 2.pdf | ||
| W50S98-22-B-0001 21 July 2022.pdf | ||
| Repair Building 113 Spec. Volume 1.pdf |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
SCALE: N.T.S.
1 2 3 4 5
A
B
C
D
3500 Parkway Lane, Suite 500 Norcross, GA 30092 Phone (678) 336-7740 Fax (678) 336-7744
SHEET ID
P a rk w a y L a n e
S u it e
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
/1
/2
:3
:0
A
M B
IM
/1
T N
A N
G R e p a ir
B ld g
F u e l C e ll/
T
N A
N G
B v
A rc h
-I n t.
rv t
G-001
100% REVISED
McGHEE TYSON ANG BASE
ALCOA, TENNESSEE
REPAIR BUILDING 113 FOR FUEL CELL
134TH AIR REFUELING WING
W9133L-15-D-0001
100% REVISED
15 MARCH 2022
C O
V E
R S
H E
E T
R E
P A
IR
B
U
IL
D
IN
G
F
O R
F U
E L C
E L L
T
H A
IR
R
E F
U E
L
IN
G W
IN
G
M c G
H E
E T
Y S
O N
A N
G B
A S
E A
L C
O A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
IR
N A
T
IO
N A
L G
U A
R D
A L C
O A
T
E N
N E
S S
E E
J O
B N
O
P O
N D
P ro je c t
N u m b e r>
A D
H
A D
H
J A
M
M
A R
C H
S O
L -X
X -X
-X X
X X
W L -1
-D
-0
X X
-X -X
X X
X
BASE MAP
SCALE: N.T.S.
PROJECT LOCATIONPROJECT LOCATION
PROJECT #: PSXE152020
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y L a n e
S u it e
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
/1
/2
:3
:1
A
M B
IM
/1
T N
A N
G R e p a ir
B ld g
F u e l C e ll/
T
N A
N G
B v
A rc h
-I n t.
rv t
G-002
100% REVISED
S H
E E
T I
N D
E X
R E
P A
IR
B
U
IL
D
IN
G
F
O R
F U
E L C
E L L
T
H A
IR
R
E F
U E
L
IN
G W
IN
G
M c G
H E
E T
Y S
O N
A N
G B
A S
E A
L C
O A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
IR
N A
T
IO
N A
L G
U A
R D
A L C
O A
T
E N
N E
S S
E E
J O
B N
O
P O
N D
P ro je c t
N u m b e r>
A D
H
A D
H
J A
M
M
A R
C H
S O
L -X
X -X
-X X
X X
W L -1
-D
-0
X X
-X -X
X X
X
SHEET INDEX
SHEET
NUMBER SHEET NAME
PLUMBING
P-001 PLUMBING GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS
PD101 OVERALL PLUMBING DEMOLITION PLAN
P-101 OVERALL PLUMBING NEW WORK PLAN
P-401 PLUMBING ENLARGED PLANS
P-402 PLUMBING ENLARGED PLANS
P-601 PLUMBING SCHEDULES AND SCHEDULES
P-901 PLUMBING RISER DIAGRAMS
MECHANICAL
M-001 MECHANICAL GENERAL NOTES AND ABBREVIATIONS
M-002 MECHANICAL LEGENDS AND HVAC DESIGN CRITERIA
MD101 OVERALL MECHANICAL DEMOLITION PLAN
MD101A MECHANICAL DEMOLITION PLAN - AREA A
MD101B MECHANICAL DEMOLITION PLAN - AREA B
MD101C MECHANICAL DEMOLITION PLAN - AREA C
MD101D MECHANICAL DEMOLITION PLAN - AREA D
M-101 OVERALL MECHANICAL PLAN
M101A MECHANICAL PLAN - AREA A
M101B MECHANICAL PLAN - AREA B
M101C MECHANICAL PLAN - AREA C
M101D MECHANICAL PLAN - AREA D
M-102 MECHANICAL PLAN - LOWER ROOF AND BAY
M-301 MECHANICAL SECTION VIEWS
M-302 MECHANICAL SECTION VIEWS
M-401 MECHANICAL ENLARGED PLANS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-505 MECHANICAL DETAILS
M-506 MECHANICAL DETAILS
M-507 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-701 MECHANICAL CONTROLS
M-702 MECHANICAL CONTROLS
M-703 MECHANICAL CONTROLS
M-704 MECHANICAL CONTROLS
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES AND ABBREVIATIONS
E-002 ELECTRICAL LEGEND
ED101 ELECTRICAL DEMOLITION PLAN
E-101 LIGHTING PLAN
E-102 PHOTOMETRIC PLAN
E-103 PHOTOMETRIC PLAN
E-111 POWER PLAN
E-121 MECHANICAL POWER PLAN
E-122 MECHANICAL POWER PLAN - LOWER ROOF AND BAY
E-131 GROUNDING PLAN
E-141 HAZARDOUS CLASSIFICATION PLAN
E-142 HAZARDOUS CLASSIFICATION PLAN ELEVATIONS
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-503 ELECTRICAL DETAILS
E-600 ELECTRICAL FEEDER SCHEDULES
E-601 DEMO ELECTRICAL ONE-LINE DIAGRAM
E-602 NEW ELECTRICAL ONE-LINE DIAGRAM
E-603 LUMINAIRE AND MECHANICAL EQUIPMENT
SCHEDULE
E-604 PANELBOARD SCHEDULES
E-605 PANELBOARD SCHEDULES
SHEET INDEX
SHEET
NUMBER SHEET NAME
GENERAL
G-001 COVER SHEET
G-002 SHEET INDEX
G-101 LIFE SAFETY PLAN
G-102 BUILDING CODE SUMMARY
CIVIL
C-001 GENERAL CIVIL NOTES, ABBREVIATIONS AND
LEGEND
C-002 FIRE PROTECTION CODE COMPLIANCE SITE PLAN
C-003 HAUL ROUTE
CD-101 DEMOLITION PLAN
C-110 CIVIL SITE AND UTILITY PLAN
C-501 CONSTRUCTION DETAILS
C-502 CONSTRUCTION DETAILS
C-503 CONSTRUCTION DETAILS
C-504 CONSTRUCTION DETAILS
STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES
S-002 GENERAL STRUCTURAL NOTES
S-003 WIND DIAGRAMS
S-004 SCHEDULE OF SPECIAL INSPECTIONS
S-101 FIRST FLOOR PLAN
S-151 ROOF PLAN
S-301 SECTIONS AND DETAILS
S-302 SECTIONS AND DETAILS
S-501 STRUCTURAL DETAILS
S-502 STEEL DETAILS
S-503 MASONRY DETAILS
ARCHITECTURAL
A-001 GENERAL NOTES, ABBREVIATIONS & SYMBOLS
A-002 PARTITION TYPES & DETAILS
AD101 ARCHITECTURAL DEMOLITION PLAN
AD201 EXTERIOR ELEVATION - DEMOLITION
A-101 FIRST FLOOR PLAN
A-111 ENLARGED PLANS & INT. ELEVATION
A-131 REFLECTED CEILING PLAN
A-151 ROOF PLAN
A-201 EXTERIOR ELEVATION & DETAILS
A-301 WALL SECTIONS
A-501 ARCHITECTURAL DETAILS
A-571 ADA MOUNTING HEIGHTS & DETAILS
A-601 DOOR SCHEDULE & DETAILS
A-602 DOOR DETAILS
A-603 HANGAR DOOR DETAILS
A-604 HANGAR DOOR DETAILS
A-605 ENTRANCE SIGN PLANS & DETAILS
INTERIORS
IG101 SIGNAGE PLAN
IG601 SIGNAGE DETAILS &SCHEDULE
I-101 INTERIOR FINISH PLAN
I-601 ROOM FINISH SCHEDULE & GENERAL NOTES
FIRE PROTECTION
F-001 FIRE PROTECTION GENERAL NOTES AND LEGEND
FD101 FIRE PROTECTION DEMOLITION PLAN
F-101 FIRE PROTECTION PLAN
FA001 FIRE ALARM & MASS NOTIFICATION GENERAL NOTES
AND LEGEND
FA101 FIRE ALARM & MASS NOTIFICATION PLAN
FA501 FIRE ALARM & MASS NOTIFICATION DETAILS
REF.REF.REF.REF.
GENERAL LIFE SAFETY SHEET NOTES:
1. DEVICES HAVE BEEN SHOWN; BUT THE CONTRACTOR SHALL ENSURE
THE INSTALLATION OF ALL LIFE SAFETY DEVICES INDICATED ON THE
ENGINEERING DRAWINGS.
2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ANY EXISTING
FIRE RATED WALLS. ANY WORK DONE AROUND EXISTING FIRE RATED
WALLS SHALL BE DONE WITH CARE SO AS NOT TO COMPROMISE THE
RATING'S INTEGRITY. ANY DAMAGE SHALL BE REPAIRED
IMMEDIATELY.
3. CONTRACTOR SHALL FIELD VERIFY HANGAR FLOOR PEDESTRIAN
DOORS ARE 1 HOUR FIRE RATED.
4. THE EXISTING WALLS SEPARATING THE HANGAR BAY
FROM THE OTHER AREAS OF THE BUILDING ARE 1-HOUR RATED.
150 SF
100 100
NEW 1-HR. RATED WALLS
LIFE SAFETY PLAN LEGEND
45'-0"
TRAVEL DISTANCE
EXIT SIGN - SEE ELECT. DWGS.
EGRESS CLEAR WIDTH
CAPACITY/NO. OF OCCUPANTS
EXISTING 1-HR RATED WALLS
ROOM AREA
OCCUPANT LOAD
AREA PER OCCUPANT
36" 100/100
EXISTING WALLS
S ACCESSORY STORAGE AREAS, MECHANICAL
AND EQUIPMENT ROOMS (300 GROSS)
AH AIRCRAFT HANGER (500 GROSS)
AU ASSEMBLY-UNCONCENTRATED
(TABLES & CHAIRS) (15 NET)
BUSINESS (100 GROSS)B
INDUSTRIAL AREAS (100 GROSS)IN
FLOOR AREA ALLOWANCES: FUNCTION
(OCCUPANT LOAD FACTOR)
45 DOOR FIRE RATING INDICATOR
(FIRE-RATING INDICATED IN MINUTES)
LAUNDRY
109A
HANGAR BAY
MECH.
FUEL CELL TANK
MAINTENANCE
UNISEX
MECH.
ACCESSORIES
SUPERVISOR
CORRIDOR
COMM.
MECH.
114A
FUEL CELL
SUPERVISOR
MECH.
102A
MECH.
T D
T D
TD=42'
T D
T D
T D
T D
43500 21284
18100
13100
10100
14100
162178
WELDING SHOP
OFFICE
MACHINE SHOP
BREAK ROOM
UNISEX
CORRIDOR
SUPPLY
CSO OFFICE
COMM.
BREAK ROOM
FUEL CELL OFFICE
CORR.
NOSE BAY
101A
MECH.
CORRIDOR
MEN'S LOCKER
ROOM
JANITOR
MEN'S RESTROOM
WOMEN'S
RESTROOM
WOMEN'S LOCKER
ROOM
TOOL CRIB
CLOSET
S
S
S
AU
S
S
S
AU
B
AH
AH
S
S
B
BIN
S
IN
S
IN
IN
IN
45 45 45
B
B
VEST.
ELEC.
UNISEX
T D
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y L a n e
S u it e
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
/1
/2
:3
:1
A
M B
IM
/1
T N
A N
G R e p a ir
B ld g
F u e l C e ll/
T
N A
N G
B v
A rc h
-I n t.
rv t
G-101
100% REVISED
L
IF
E S
A F
E T
Y P
L A
N
R E
P A
IR
B
U
IL
D
IN
G
F
O R
F U
E L C
E L L
T
H A
IR
R
E F
U E
L
IN
G W
IN
G
M c G
H E
E T
Y S
O N
A N
G B
A S
E A
L C
O A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
IR
N A
T
IO
N A
L G
U A
R D
A L C
O A
T
E N
N E
S S
E E
J O
B N
O
P O
N D
P ro je c t
N u m b e r>
A D
H
A D
H
J A
M
M
A R
C H
S O
L -X
X -X
-X X
X X
W L -1
-D
-0
X X
-X -X
X X
X
SCALE: 3/32" = 1'-0"A1
LIFE SAFETY PLAN
SCALE: = 1'-0"3/32"
0 8 16 248
BUILDING CODE SUMMARY - TENNESSEE AIR NATIONAL GUARD, McGHEE TYSON ANG BASE - REPAIR BLDG 113 EXIT REQUIREMENTS (PER NFPA 101 LSC):
MINIMUM REQUIRED EGRESS WIDTH: EGRESS COMPONENTS OTHER THAN STAIRS - 0.2" PER OCCUPANT SERVED (NFPA 101 TABLE 7.3.3.1)
EGRESS REQUIRED: 117 OCCUPANTS X 0.2" = 23" EGRESS REQUIRED
EGRESS PROVIDED: 36" EGRESS PROVIDED
EGRESS DOORS: MINIMUM CLEAR WIDTH OF NOT LESS THAN 32 INCHES (NFPA 101 PER 7.2.1.2.3) EXCEPT FOR DOORS SERVING CLOSET SPACES
LESS THAN 10 SQUARE FEET SHALL NOT BE LIMITED BY THE MINIMUM WIDTH.
MINIMUM HEIGHT IS 80 INCHES (NFPA 101 PER 7.1.5)
LOCATION OF EXITS: WHERE TWO EXITS, EXIT ACCESSES, OR EXIST DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF** OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT ACCESSES, OR EXIT DISCHARGES.EXIT DOORS OR
EXIT ACCESS DOORWAYS. (NFPA 101 PER 7.5.1.3.2)**
**PER NFPA 101, 7.5.1.3.3, IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED SUPERVISED AUTOMATIC SPRINKLER SYSTEM, THE MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT DISCHARGES SHALL BE NO LESS THAN ONE-THIRD THE LENGTH OF THE
MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED.
EXIT CORRIDORS: MINIMUM CORRIDOR WIDTH IS NOT LESS THAN 44 INCHES CLEAR (NFPA 101 PER 39.2.3.2)
MAXIMUM TRAVEL DISTANCE: HANGAR BAY EGRESS - 150 FEET (NFPA 101 PER TABLE A.7.6, AND PER 42.6)
ALL EXITS MUST DISCHARGE DIRECTLY TO THE EXTERIOR OF THE BUILDING AT GRADE LEVEL OR PROVIDE DIRECT ACCESS TO GRADE (NFPA 101, 7.7.1)
MAXIMUM COMMON PATH OF TRAVEL: OCCUPANCY GROUP, (S-1) STORAGE; WITH SPRINKLER SYSTEM - 100 FEET (NFPA 101 PER TABLE A.7.6)
MAXIMUM DEAD-END CORRIDOR: OCCUPANCY GROUP, (S-1) STORAGE; WITH SPRINKLER SYSTEM - 50 FEET (NFPA 101 PER TABLE A.7.6)
MINIMUM NUMBER OF PLUMBING FIXTURES: IBC, TABLE 2902.1
TOTAL OCCUPANTS: 254 ACTUAL OCCUPANTS (BOTH MEN & WOMEN)
WATER CLOSET:
LAVATORIES:
DRINKING FOUNTAIN:
OTHER:
PLUMBING FIXTURE COUNT:
PROJECT
TNANG AIR NATIONAL GUARD, McGHEE TYSON ANG BASE.
RENOVATION AND REPAIR - HANGAR BUILDING B113
SCOPE
PROJECT PROVIDES FOR THE RENOVATION AND REPAIR OF HANGAR BUILDING 113 FOR A FUEL CELL HANGAR.
NUMBER OF LEVELS: 1 (EXISTING)
GROSS AREA: 36,908 SF (EXISTING)
TOTAL HEIGHT: VARIES. RANGES FROM: 12'-0" - 50'-4" (EXISTING)
LIST OF APPLICABLE CODES:
INTERNATIONAL CODE COUNCIL (ICC), INTERNATIONAL BUILDING CODE (IBC), 2015 EDITION UNIFIED FACILITIES CRITERIA (UFC) 1-200-01, GENERAL BUILDING REQUIREMENTS –20 JUNE 2016 UNIFIED FACILITIES CRITERIA (UFC) 3-420-01, PLUMBING SYSTEMS - 25 OCTOBER 2004, INCL. CHANGE 10, 26 OCTOBER 2015 UNIFIED FACILITIES CRITERIA (UFC) 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES – 8 AUGUST 2016 UFC 3-601-02, OPERATIONS AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS – 8
SEPTEMBER 2010
UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARD FOR BUILDINGS, 9 FEBRUARY 2012
UFC 4-021-01, DESIGN AND O&M: MASS NOTIFICATION SYSTEMS – CHANGE 1, JANUARY 2010
UFC 4-211-01, AIRCRAFT MAINTENANCE HANGARS, 13 APRIL 2017 - CHANGE 1, NOVEMBER 2017
NFPA 1, FIRE CODE – 2015 EDITION
NFPA 101, NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), LIFE SAFETY CODE, 2015 EDITION
NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS – 2013 EDITION
NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS – 2016 EDITION
NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION
NFPA 70, NATIONAL ELECTRICAL CODE, 2017 EDITION
NFPA 72, FIRE ALARM AND SIGNALING CODE, 2016 EDITION
NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATION SYSTEMS, 2012 EDITION NFPA 241, SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS – 2013 EDITION
ABA - ARCHITECTURAL BARRIERS ACT FOR FEDERAL FACILITIES
OCCUPANCY CLASSIFICATION:
THIS BUILDING IS CLASSIFIED AS A MIXED USE NONSEPERATED OCCUPANCY IN THE INTERNATIONAL BUILDING CODE.
PRIMARY OCCUPANCY: MODERATE-HAZARD STORAGE, GROUP S-1 - AIRCRAFT HANGAR (STORAGE & REPAIR) (SEC 311.2), BUSINESS
GROUP B, BUSINESS AREAS ARE AN ACCESSORY OCCUPANCY (SEC 304.1) F-1 (306.1),
TYPE OF CONSTRUCTION: IBC, TABLE 503; SECTION 504
TYPE IIB WITH AUTOMATIC FIRE SPRINKLER SYSTEM
FIRE RESISTIVE RATINGS: IBC, TABLE 601; SECTION 602.2
STRUCTURAL FRAME
EXT. BEARING WALLS
INT. BEARING WALLS
INT. NON-BEARING WALLS AND PARTITIONS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
ALLOWABLE HEIGHT:
STORAGE (S-1) (MOST RESTRICTIVE)
55'-0" + 20'-0" FOR AUTOMATIC SPRINKLER INCREASE = 75FT/ 3 STORIES (AS PER IBC 504.3)
ALLOWABLE AREA:
STORAGE (S-1) (MOST RESTRICTIVE)
BASED ON IBC TABLE 506.2 - (S-1) 52,500 SF/FLR
OCCUPANCY TYPE: MIN. OCCUPANT LOAD: FLOOR AREA/OCC.: OCCUPANT LOAD:
HANGAR BAY 101 - (AH) 1 OCCUPANT PER 500 SQUARE FEET 21,284 S.F. /500 43 OCCUPANTS
NOSE BAY 101A - (AH) 1 OCCUPANT PER 500 SQUARE FEET 594 S.F. /500 2 OCCUPANTS
TOOL CRIB 102 - (S) 1 OCCUPANT PER 500 SQUARE FEET 762 S.F. /500 2 OCCUPANTS
MECH. 102A - (S) 1 OCCUPANT PER 300 SQUARE FEET 50 S.F. /300 1 OCCUPANTS
MECH. 103 - (S) 1 OCCUPANT PER 300 SQUARE FEET 967 S.F. /300 4 OCCUPANTS
JANITOR 108 - (S) 1 OCCUPANT PER 500 SQUARE FEET 25 S.F. /500 1 OCCUPANTS
FUEL CELL OFFICE 111 - (AU) 1 OCCUPANT PER 15 SQUARE FEET 1,133 S.F. /15 76 OCCUPANTS FUEL CELL SUPER 113 - (B) 1 OCCUPANT PER 100 SQUARE FEET 309 S.F. /100 3 OCCUPANTS
MECH. 114A - (S) 1 OCCUPANT PER 300 SQUARE FEET 77 S.F. /300 1 OCCUPANTS
BREAK ROOM 115 - (AU) 1 OCCUPANT PER 15 SQUARE FEET 722 S.F. /15 48 OCCUPANTS
COMM. 116 - (S) 1 OCCUPANT PER 500 SQUARE FEET 44 S.F. /500 1 OCCUPANTS
COMM. 117 - (S) 1 OCCUPANT PER 500 SQUARE FEET 117 S.F. /500 1 OCCUPANTS
ACCESSORIES SUPER 118 - (B) 1 OCCUPANT PER 100 SQUARE FEET 391 S.F. /100 4 OCCUPANTS
MECH. 120 - (S) 1 OCCUPANT PER 300 SQUARE FEET 96 S.F. /300 1 OCCUPANTS
CSO OFFICE 121 - (B) 1 OCCUPANT PER 100 SQUARE FEET 146 S.F. /100 2 OCCUPANTS
SUPPLY 122 - (B) 1 OCCUPANT PER 100 SQUARE FEET 531 S.F. /100 5 OCCUPANTS
FUEL CELL TANK
MAINTENANCE 126 - (IN) 1 OCCUPANT PER 100 SQUARE FEET 1,368 S.F. /100 14 OCCUPANTS
MECH. 128 - (S) 1 OCCUPANT PER 300 SQUARE FEET 153 S.F. /300 1 OCCUPANTS
COMP. TRAINING 129 - (B) 1 OCCUPANT PER 100 SQUARE FEET 170 S.F. /100 2 OCCUPANTS
ROOM 130 - (IN) 1 OCCUPANT PER 100 SQUARE FEET 1,735 S.F. /100 18 OCCUPANTS
ROOM 130A - (IN) 1 OCCUPANT PER 100 SQUARE FEET 982 S.F. /100 10 OCCUPANTS
OFFICE 131 - (B) 1 OCCUPANT PER 100 SQUARE FEET 181 S.F. /100 2 OCCUPANTS
OFFICE 132 - (B) 1 OCCUPANT PER 100 SQUARE FEET 163 S.F. /100 2 OCCUPANTS
ROOM 133 - (IN) 1 OCCUPANT PER 100 SQUARE FEET 546 S.F. /100 6 OCCUPANTS
MECH. 134 - (S) 1 OCCUPANT PER 300 SQUARE FEET 979 S.F. /300 3 OCCUPANTS
VEST. 135 - (B) 1 OCCUPANT PER 100 SQUARE FEET 112 S.F. /100 1 OCCUPANTS
STORAGE, S-1:
MALE: 1 FIXTURE PER 100
FEMALE: 1 FIXTURE PER 100
NUMBER OF WATER CLOSETS PROVIDED = 8
NUMBER OF URINALS PROVIDED = 6
STORAGE, S-1:
MALE: 1 FIXTURE PER 100
FEMALE: 1 FIXTURE PER 100
NUMBER OF LAVATORIES PROVIDED = 8
STORAGE, S-1:
1 FIXTURE PER 1,000 1
NUMBER OF WATER COOLERS PROVIDED = 1
STORAGE, S-1:
1 SERVICE SINK
NUMBER OF SERVICE SINKS PROVIDED = 1
0 HR.
0 HR.
0 HR.
0 HR.
0 HR.
0 HR.
TOTAL: 33,622 S.F. 254 OCCUPANTS
OCCUPANCY LEGEND:
(AH) - AIR HANGAR, (AU) - ASSEMBLY - UNCONCENTRATED, (B) - BUSINESS, (IN) - INDUSTRIAL AREAS,
(S) - ACCESSORY STORAGE AREAS, MECHANICAL AND EQUIPMENT ROOMS
OCCUPANT LOADS: (NFPA 101 PER TABLE 7.3.1.2)
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y L a n e
S u it e
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
/1
/2
:3
:1
A
M B
IM
/1
T N
A N
G R e p a ir
B ld g
F u e l C e ll/
T
N A
N G
B v
A rc h
-I n t.
rv t
G-102
100% REVISED
B U
IL
D
IN
G
C O
D E
S U
M M
A R
Y
R E
P A
IR
B
U
IL
D
IN
G
F
O R
F U
E L C
E L L
T
H A
IR
R
E F
U E
L
IN
G W
IN
G
M c G
H E
E T
Y S
O N
A N
G B
A S
E A
L C
O A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
IR
N A
T
IO
N A
L G
U A
R D
A L C
O A
T
E N
N E
S S
E E
J O
B N
O
P O
N D
P ro je c t
N u m b e r>
A D
H
A D
H
J A
M
M
A R
C H
S O
L -X
X -X
-X X
X X
W L -1
-D
-0
X X
-X -X
X X
X
GENERAL NOTES
1. THE CONTRACTOR SHALL COMPLY WITH ALL CITY, COUNTY,
STATE, AND FEDERAL REGULATIONS APPLICABLE TO
CONSTRUCTION OF THIS SITE.
2.
3.
4.
5.
ALL LABOR, MATERIALS, AND METHODS OF CONSTRUCTION
SHALL BE IN STRICT ACCORDANCE WITH THE MINIMUM
ENGINEERING AND CONSTRUCTION STANDARDS ADOPTED BY
THE U.S. AIR NATIONAL GUARD (ANG). SUBSTITUTIONS AND
DEVIATION FROM PLANS AND SPECIFICATIONS SHALL BE
PERMITTED ONLY WHEN WRITTEN APPROVAL HAS BEEN ISSUED
BY THE CONTRACTING OFFICER (KO). ALL DIMENSIONS ARE
TAKEN FROM/TO FENCE LINES, CENTERLINE OF UTILITY,
CENTER OF MANHOLE OR CATCH BASIN, CENTERLINE OF ROAD,
FACE OF BUILDING, FACE OF CURB, FACE OF WALL, OR
CENTERLINE OF STRIPING UNLESS OTHERWISE NOTED.
EXISTING CONDITIONS SHOWN ARE BASED UPON GOOGLE
EARTH INFORMATION AND BASE PROVIDED GIS INFORMATION.
ALL EXISTING UTILITY INFORMATION SHOULD BE CONSIDERED
APPROXIMATE AND MUST BE VERIFIED BY THE CONTRACTOR
PRIOR TO CONSTRUCTION OR ORDERING MATERIALS.
ALL REQUIRED EROSION AND SEDIMENT CONTROL MEASURES
SHALL BE PROVIDED, INSTALLED, AND MAINTAINED AS SHOWN
WITHIN THESE CONSTRUCTION DOCUMENTS.
6. CONTRACTOR TO MOVE ALL CONSTRUCTION DEBRIS OFF THE
AIR NATIONAL GUARD BASE PROPERTY AND DISPOSE DEBRIS
AT A LEGAL, PERMITTED LANDFILL CONSISTENT WITH ALL
LOCAL, STATE, AND FEDERAL REQUIREMENTS.
7. NO BURNING IS ALLOWED ON AIR RESERVE BASE PROPERTY.
8. CONTRACTOR TO ENSURE ALL EXISTING TOPS OF MANHOLES
AND VALVE BOXES ARE RAISED OR LOWERED TO BE FLUSH
WITH FINISHED GRADES, UNLESS NOTED OTHERWISE.
9. ALL NEW PAVEMENT AND SIDEWALKS SHALL BE CONSTRUCTED
FLUSH WITH EXISTING, WITH NO PONDING OF STORMWATER,
UNLESS NOTED OTHERWISE.
10. CONTRACTOR SHALL GRADE ALL DISTURBED AREAS TO
ENSURE POSITIVE DRAINAGE AWAY FROM ALL BUILDINGS AND
TO DRAINAGE STRUCTURES OR DITCHES. NATURAL FLOW OF
SURROUNDING WATERS SHALL NOT BE DISTURBED DURING
CONSTRUCTION, UNLESS SHOWN OTHERWISE.
11. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS,
COORDINATES, AND DIMENSIONAL INFORMATION PRIOR TO
CONSTRUCTION. THE CONTRACTOR SHALL BRING ALL
DISCREPANCIES TO THE ATTENTION OF THE COR PRIOR TO
STARTING CONSTRUCTION.
12. ALL TRAFFIC SIGNS AND PAVEMENT MARKINGS SHALL BE IN
ACCORDANCE WITH THE "MANUAL ON UNIFORM TRAFFIC
CONTROL DEVICES" (MUTCD), LATEST EDITION.
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATING INSTALLATION OF ALL NEW UTILITIES WITH
THOSE THAT ARE EXISTING. IF EXISTING UTILITIES ARE IN
CONFLICT WITH NEW UTILITIES, THE SITE CONTRACTOR SHALL
NOTIFY THE COR BEFORE PROCEEDING WITH CONSTRUCTION.
14. ALL TOPSOIL AND EXCAVATED MATERIAL SHALL BE
STOCKPILED IN AN APPROVED AREA DURING CONSTRUCTION.
EXCESS OR UNUSABLE TOPSOIL SHALL BE DISPOSED OF
OFF-SITE IN A MANNER THAT IS LEGAL AND CONSISTENT WITH
ALL LOCAL, STATE, AND FEDERAL REQUIREMENTS.
15. THE LOCATION OF ALL EXISTING UTILITIES AND STORM
DRAINAGE SHOWN ON THE PLANS HAVE BEEN DETERMINED
FROM THE BEST INFORMATION AVAILABLE AND ARE GIVEN FOR
THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER
ASSUMES NO RESPONSIBILITY FOR INACCURACY. PRIOR TO
THE START OF ANY CONSTRUCTION ACTIVITY IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE VARIOUS
UTILITIES AND TO MAKE THE NECESSARY ARRANGEMENTS FOR
ANY RELOCATION OF THESE UTILITIES WITH THE COR OF THE
UTILITY. THE CONTRACTOR SHALL EXERCISE CAUTION WHEN
CROSSING UNDERGROUND UTILITIES, WHETHER SHOWN ON
THE PLAN OR LOCATED BY THE UTILITY COMPANY. ALL
UTILITIES WHICH INTERFERE WITH THE PROPOSED
CONSTRUCTION SHALL BE BROUGHT TO THE ATTENTION OF
THE CONTRACTING OFFICER'S REPRESENTATIVE (COR). ANY
FEES ASSOCIATED WITH UTILITY RELOCATIONS SHALL BE
BORNE BY THE CONTRACTOR IN ACCORDANCE WITH
RESPECTIVE UTILITY COMPANY STANDARDS. THE
CONTRACTOR SHALL COORDINATE DISCONNECTION OF
EXISTING UTILITIES WITH THE APPROPRIATE UTILITY PROVIDER.
16. UTILITIES INDICATED SHALL BE CONSTRUCTED IN
ACCORDANCE WITH THE APPLICABLE PROVISIONS OF THE
SPECIFICATIONS. GRADING SHALL BE AS INDICATED, AND
SHALL PRODUCE A FINISHED SURFACE WITH NO PONDING OF
WATER, READY TO RECEIVE PLANTING MATERIALS OR
GRASSING.
17. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
ENSURE THAT ALL REQUIRED PERMITS ARE OBTAINED AND IN
HAND BEFORE BEGINNING ANY CONSTRUCTION. NO
CONSTRUCTION OR FABRICATION OF ANY ITEM SHALL BEGIN
UNTIL THE CONTRACTOR HAS RECEIVED ALL PLANS AND ANY
OTHER DOCUMENTATION FROM ALL OF THE PERMITTING AND
ANY OTHER REGULATORY AUTHORITIES. ANY PENALTIES,
STOP WORK ORDERS OR ADDITIONAL WORK RESULTING FROM
THE CONTRACTOR BEING IN VIOLATION OF THE ABOVE
REQUIREMENTS, SHALL BE FULLY BORNE BY THE
CONTRACTOR.
18. ALL CONTRACTORS/SUBCONTRACTORS THAT WILL BE
ENGAGED IN LAND DISTURBING ACTIVITIES SHALL COMPLY
WITH ALL EROSION, SEDIMENTATION AND POLLUTION CONTROL
AND STORMWATER POLLUTION PREVENTION REQUIREMENTS
CONTAINED THROUGHOUT THE DRAWINGS, SPECIFICATIONS,
AND PERMITS.
19. AREAS DISTURBED BY THE CONTRACTOR, WHICH ARE NOT
PART OF THIS PROJECT, SHALL BE RETURNED TO ORIGINAL OR
BETTER CONDITION PRIOR TO THE COMPLETION OF THE
PROJECT AS DETERMINED BY THE COR.
20. THE CONTRACTOR'S MEANS, METHODS, SEQUENCE,
TECHNIQUES OR PROCEDURES IN PERFORMING THE WORK IS
SOLELY THE RESPONSIBILITY OF THE CONTRACTOR, WHO IS
ALSO RESPONSIBLE FOR COMPLYING WITH ALL HEALTH AND
SAFETY PRECAUTIONS AS REQUIRED BY THE APPLICABLE
REGULATORY AGENCY.
21. THE DESIGN ADEQUACY AND SAFETY OF ALL BRACING,
SHORING AND TEMPORARY SUPPORTS, ETC. ARE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR.
22. PROTECT ALL EXISTING FEATURES AND EXISTING
LANDSCAPING THAT WILL REMAIN. ANY ITEM DAMAGED DURING
THE PERFORMANCE OF THE WORK WILL BE RESTORED TO
ORIGINAL CONDITION, OR REPLACED WITH NEW AT THE
CONTRACTOR'S EXPENSE. CONTRACTOR SHALL TAKE
PRECAUTIONS TO AVOID OVERLOADING PAVEMENTS WHICH
WILL REMAIN.
23. EACH SHEET IS PART OF A MULTI-SHEET SET OF
CONSTRUCTION PLANS AND SHALL BE READ WITH THE FULL
SET TO BEST ENSURE PROPER INTERPRETATION.
24. SHEET KEYNOTES ON THE PLANS ARE SPECIFIC TO THAT
SHEET ONLY. MISSING SEQUENTIAL NUMBERS DO NOT APPLY
TO THAT SHEET.
CIVIL DEMOLITION NOTES
1. "DEMOLISH" SHALL MEAN TO REMOVE AN OBJECT IN ITS
ENTIRETY. RESTORE GRADES AND SURFACE IMPROVEMENTS
TO MATCH EXISTING CONDITIONS OR PER REQUIREMENTS OF
NEW WORK, WHICHEVER IS APPLICABLE.
2. EROSION AND SEDIMENTATION CONTROL MEASURES AND
TEMPORARY CONSTRUCTION FENCING SHALL BE IN PLACE
PRIOR TO COMMENCEMENT OF DEMOLITION WORK.
3. CONTRACTOR SHALL ESTABLISH SURVEY CONTROL NETWORK
OUTSIDE LIMITS OF DEMOLITION PRIOR TO COMMENCEMENT
OF WORK. THIS WORK MUST BE PERFORMED BY LICENSED &
REGISTERED TENNESSEE LAND SURVEYOR.
4. ALL DEMOLITION WORK SHALL BE COORDINATED WITH
CONTRACTOR'S SCHEDULE AND LOGISTICS PLAN (APPROVED
BY COR) PRIOR TO WORK.
CIVIL SITE NOTES
1. CONTRACTOR SHALL FURNISH AND MAINTAIN ANY AND ALL
NECESSARY BARRICADES AROUND THE WORK AND PROVIDE
PROTECTION AGAINST WATER DAMAGE AND SOIL EROSION.
2. ALL BUILDING DIMENSIONS SHALL BE VERIFIED AND
COORDINATED WITH THE ARCHITECTURAL PLANS.
3. PAVEMENT MARKINGS, INCLUDING ANY STANDARD HANDICAP
SYMBOLS, PARKING STRIPING AND TRAFFIC ARROWS, SHALL BE
PAINTED ON PAVEMENT AT LOCATIONS SHOWN.
4. ALL SIGNAGE SHALL CONFORM TO THE MOST RECENT TDOT
AND MUTCD STANDARDS AND SPECIFICATIONS.
GRADING AND DRAINAGE NOTES
1. POSITIVE DRAINAGE SHALL BE MAINTAINED AT ALL TIMES TO
PREVENT SATURATION OF EXPOSED SOILS IN CASE OF SUDDEN
RAINS, AND FOR ALL FINISHED GRADING. CONTRACTOR SHALL
LOCATE ALL EXISTING UTILITIES PRIOR TO ANY EXCAVATION.
2. CONTRACTOR SHALL INSTALL ALL PERIMETER EROSION AND
SEDIMENT CONTROL MEASURES PRIOR TO ANY SITE CLEARING
OR EXCAVATION. CONTRACTOR SHALL INSPECT ALL SEDIMENT
AND EROSION CONTROL MEASURES DAILY AND DURING
PROLONGED PERIODS OF CONTINUOUS RAINFALL EVENTS TO
ENSURE THAT ALL CONTROLS ARE FUNCTIONING PROPERLY.
DAMAGED CONTROLS SHALL BE REPLACED BY THE END OF THE
WORKDAY.
3. ALL BACKFILL AND FILL MATERIAL SHALL BE FREE OF ORGANIC
MATTER AND WASTE.
4. THE CONTRACTOR SHALL REMOVE ALL EROSION CONTROL
FENCING FROM THE SITE PRIOR TO FINAL PROJECT
ACCEPTANCE, AND SHALL SMOOTH THE GROUND SURFACE
WHERE THE FENCE WAS REMOVED THEN MULCH OR SEED &
STRAW (SEASON APPROPRIATE GRASS) THE RESTORED
SURFACE AS SUNLIGHT CONDITIONS WARRANT.
5. CONTRACTOR SHALL MARK, PRESERVE AND PROTECT ALL
SURVEY BENCHMARKS. IF BENCHMARK MUST BE DEMOLISHED
FOR CONSTRUCTION, CONTRACTOR SHALL RELOCATE
BENCHMARK AND PROVIDE NEW DATA ON AS-BUlLTS.
6. ALL CUT AND FILL SLOPES SHALL BE 2:1 OR FLATTER (SEE
PLANS).
7. ALL SPOT ELEVATIONS NOTED ARE FINISH GRADE.
ABBREVIATIONS
@ AT
& AND
Ø DIAMETER
APPR APPROVED
APPROX APPROXIMATELY
BLDG BUILDING
BM BENCHMARK
BOT BOTTOM
CL CENTERLINE
CF CUBIC FEET
CONC CONCRETE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
DI DROP INLET
DIA DIAMETER
DB DUCTBANK
DIP DUCTILE IRON PIPE
DS DOWNSPOUT
E EASTING
EG EXISTING GRADE
ELEV ELEVATION
EP EDGE OF PAVEMENT
ESMT EASEMENT
EX EXISTING
FFE FINISHED FLOOR ELEVATION
FG FINISHED GRADE
FH FIRE HYDRANT
FT FEET
GAB GRADED AGGREGATE BASE
GIS GEOGRAPHIC INFORMATION SYSTEM
HDPE HIGH DENSITY POLYETHYLENE PIPE
HORZ HORIZONTAL
HT HEIGHT
HW HEADWALL
IBW INSIDE BOTTOM OF WALL
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCH
INC INCORPORATED
INV INVERT
IPF IRON PIN FOUND
IPS IRON PIN SET
JB JUNCTION BOX
LF LINEAR FEET
LOD LIMITS OF DISTURBANCE
LP LIGHTING PROTECTION
MAX MAXIMUM
M.E. MATCH ELEVATION
MECH MECHANICAL
MES MITERED END SECTION
MIN MINIMUM
MON MONUMENT
N NORTHING
N/F NOW OR FORMERLY
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER
OCEW ON CENTER EACH WAY
OD OUTSIDE DIAMETER
OWS OIL/WATER SEPARATOR
PIV POST INDICTOR VALVE
POL PETROLEUMS, OILS, AND LUBRICANTS
PROP PROPOSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
QC QUALITY CONTROL
RCP REINFORCED CONCRETE PIPE
R/W RIGHT OF WAY
SD STORM DRAIN
SF SQUARE FEET
SPEC SPECIFICATIONS
SQ SQUARE
SS SANITARY SEWER
SSMH SANITARY SEWER MANHOLE
STD STANDARD
TBM TEMPORARY BENCHMARK
TYP TYPICAL
VERT VERTICAL
WM WATER METER
WV WATER VALVE
WWF WELDED WIRE FABRIC
W/ WITH
W/C WATER TO CEMENT
YR YEAR
LODLOD
H
Y
D
W W
SHEET NAMING CONVENTION
C-001
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DESCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
LEGEND
DESCRIPTION EXISTING PROPOSED
BOLLARD N/A
FENCE N/A
LIMITS OF DISTURBANCE N/A
FIRE HYDRANT N/A
SLOPE N/A N/A
PAVEMENT PATCH N/A
WATER LINE
STORM PIPE N/A
SILT FENCE N/A
ST
3 4 5
A
B
C
100% REVISED
SHEET ID
R E
P A
I R
B
U I L
D I N
G
M c G
H E
E
T
Y S
O N
A
N G
S
E
T
H
T
E N
N E
S S
E
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E
P a r k w a y
L a n e
S u i t e
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I L
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
C H
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
T
O
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
D
M
C
A D
C
D
W G
G E
N E
R A
L
C
I V
T
E S
A B
B R
E V
I A
T I O
N S
A
G
E N
D
C-001
BASE ACCESS NOTES
1. CONSTRUCTION ACTIVITIES REQUIRE CONTRACTORS TO
GAIN ACCESS TO THE INSTALLATION USING ONE OF THE
FOLLOWING METHODS:
1.1. CONTRACTOR BADGING - REQUIRED FOR ACCESS > 72
HOURS. COMPLETE CONTRACTOR/VENDOR/STATE!
EMPLOYEE ID BADGE APPLICATION (134ARW FORM 5).!
NAME OF SUPERVISOR/EMPLOYER IS A SUPERVISING!
REPRESENTATIVE OF THE GENERAL CONTRACTOR.!
NAME OF SPONSOR IS A REPRESENTATIVE FROM BASE!
CIVIL ENGINEERING WORK CONTROL. TAKE COMPLETED!
FORM 5 TO SECURITY FORCES (BLDG 120) BETWEEN THE!
HOURS OF 0800-1600 ON MONDAY THRU FRIDAY FOR!
PRODUCTION OF PHOTO ID BADGE. FOR FURTHER!
DETAILS CONTACT SECURITY FORCES AT (865) 336-3276.!
ONE DAY VISITOR PASS IS REQUIRED TO GAIN ACCESS!
FOR BADGING.
1.2. FULL-TIME MILITARY ESCORT (LIMITED AVAILABILITY) -
CONTACT COR TO SCHEDULE AN ESCORT. PROVIDE
NAME, COMPANY NAME, DRIVER'S LICENSE, AND
REASON FOR ESCORT. ARRIVE AT FRONT GATE, AS
SCHEDULED, AND WAIT FOR GUARD TO VERIFY. MEET
WITH ESCORT.
1.3. VISITOR PASSES - REQUEST FOR PASS MUST BE
SUBMITTED TO COR 72 HOURS IN ADVANCE OF ARRIVAL.
VALID DRIVERS LICENSE, VEHICLE REGISTRATION, AND
NAME OF BASE CIVIL ENGINEERING REPRESENTATIVE
REQUIRED AT FRONT GATE. SCHEDULE 15 MINUTES
MINIMUM FOR BACKGROUND CHECK AT FRONT GATE.
2. ALL DELIVERIES AND DAY TO DAY CONSTRUCTION TRAFFIC
SHALL USE FRONT GATE ENTRANCE LOCATED OFF OF AIR
BASE ROAD.
3. ALL CONTRACT WORKERS DRIVING ON BASE SHALL HAVE
VALID DRIVER LICENSE, VEHICLE REGISTRATION AND
PROOF OF INSURANCE.
4. CONTRACTOR SHALL COORDINATE TRAFFIC CONTROL
WITH THE CONTRACTING OFFICER'S REPRESENTATIVE
(COR).
5. CONTRACTOR PARKING SHALL BE COORDINATED WITH THE
COR.
6. CONTRACTOR SHALL PROTECT EXISTING ROADWAY AND
PARKING LOTS AND REPAIR AS REQUIRED BY THE COR.
7. CONTRACTOR MATERIAL STAGING SHALL BE LIMITED TO
THE DESIGNATED AREA UNLESS OTHERWISE APPROVED BY
COR.
Y
D
U
E
3 4 5
A
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
GENERAL NOTES:
1. REFER TO C-001 FOR GENERAL CIVIL NOTES,
ABBREVIATIONS, AND LEGEND.
2. KEYNOTES INDICATED WITH .
3. BACKGROUND INFORMATION IS TAKEN FROM BASE
PROVIDED GIS INFORMATION. CONTRACTOR TO VERIFY
INFORMATION PRIOR TO CONSTRUCTION.
4. THIS PLAN HAS BEEN CREATED TO SHOW COMPLIANCE WITH
UFC 3-600-01 "FIRE PROTECTION ENGINEERING FOR
FACILITIES" SECTION 1-7.2.4.2.
5. THE FOLLOWING ITEMS AS INDICATED IN UFC 3-600-01
SECTION 1-7.2.4.2 CODE COMPLIANCE SITE PLAN ARE NOT
APPLICABLE TO THIS PROJECT:
-LINE OF ENCROACHMENT IDENTIFYING PROPERTY LINES
· FACILITY IS LOCATED WITHIN MCGHEE TYSON AIR
NATIONAL GUARD BASE.
-BUILDING PERIMETER USED FOR FRONTAGE INCREASE
· FACILITY IS WITHIN THE ALLOWABLE AREA WITHOUT A
FRONTAGE INCREASE.
-HAZARDOUS MATERIAL SPILL CONTAINMENT TANKS
· NO HAZARDOUS MATERIAL SPILL CONTAINMENT TANKS
PRESENT AT THIS FACILITY.
-ANTI-TERRORISM/FORCE PROTECTION (ATFP) MEASURES
· NO ATFP MEASURES PRESENT AT THIS FACILITY.
-BACKFLOW PREVENTION ASSEMBLY
· BACKFLOW PREVENTION LOCATED INSIDE FIRE PUMP
ROOM.
HANGAR BUILDING 113
(PROJECT LOCATION)
AIR NATIONAL
GUARD FIRE
DEPARTMENT
C1
FIRE DEPARTMENT ACCESS
SCALE: N.T.S.
F I R
E
P
R O
T E
C T
I O
N
C
O D
E
C O
M P
L I A
N C
E
S
I T
E
P
L A
N
C-002
HANGAR BUILDING 113
KEY # KEYNOTE DESCRIPTION
FIRE DEPARTMENT ACCESS WITHIN 33' OF
BUILDING
2 FIRE LANE APPROACH
INTENDED FIRE DEPARTMENT MAIN
ENTRANCE.
4 FIRE DEPARTMENT CONNECTION
5 FIRE HYDRANT.
6 FIRE PUMP ROOM.
7 FIRE AND DOMESTIC WATER TANK.
KEYNOTES
SCALE: 1" = 20'
0 20' 40' 60'10'
A1
FIRE PROTECTION CODE COMPLIANCE SITE PLAN
3 4 5
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
H A
U
T E
C-003
HAUL ROUTE
BASE MAIN ENTRANCE
HANGAR BUILDING 113
DEMOLISH ASPHALT PAVEMENT
CONSTRUCTION FENCE
DEMOLISH EXISTING FENCE FABRIC
3 4 5
A
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
D E
M O
L I T
I O
N
P
L A
N
CD101
LEGEND
GENERAL NOTES:
1. SEE SHEET C-001 FOR GENERAL CIVIL NOTES, ABBREVIATIONS,
AND LEGEND.
2. KEYNOTES INDICATED WITH .
3. BACKGROUND INFORMATION PROVIDED BY THE OWNER BASED
ON AS-BUILT INFORMATION FROM C2RL, INC. ENGINEERS
DATED 03/01/2018.
KEY # KEYNOTE DESCRIPTION
EXISTING HANGAR DOOR TO BE
REFURBISHED. REFER TO ARCHITECTURAL
PLANS FOR ADDITIONAL INFORMAITON.
EXISTING EXTERIOR APRON PAVEMENT TO
REMAIN.
3 EXISTING FLIGHT LINE FENCE.
4 DEMOLISH EXISTING PERSONNEL GATE.
CLEANLY SAWCUT AND DEMOLISH
ASPHALT PAVEMENT.
PROVIDE TEMPORARY CONSTRUCTION
FENCING WITH STANDS AROUND FACILITY,
AS DELINEATED. COORDINATE WITH COR
ON FINAL LOCATION OF TEMPORARY
FENCING PRIOR TO CONSTRUCTION.
PROVIDE SILT FENCE PRIOR TO
COMMENCEMENT OF CONSTRUCTION. (SEE
DETAIL A1/C-504)
DEMOLISH EXISTING 6'-HIGH FENCE FABRIC.
CONTRACTOR TO ENSURE CONTINUITY OF
AIRFIELD PERIMETER SECURITY FENCE
DURING CONSTRUCTION.
KEYNOTES
SCALE: 1" = 20'
0 20' 40' 60'10'
A1
DEMOLITION PLAN
Y
D
S
C O
C
O
C O
U
E
~50'
A0
A1
A2
A3
E L
E V
A T
I O
N
E L
E V
A T
I O
N
STATION
SANITARY SEWER A PROFILE
HORZ. SCALE 1"= 20'
VERT. SCALE 1"= 5'
0+00
S S
M
T O
P
S
S M
H
U
S
A
S
S M
H
D
S
T O
P
A
A
T O
P
A
A
T O
P
A
6" PVC
20LF @ 1.00%
6" P
VC
7LF @
.2 6%
6" PVC
4LF @ 1.00%
HANGAR BUILDING 113
3 4 5
A
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
SCALE: 1" = 20'
0 20' 40' 60'10'
C I V
S
T
E
A
I L
I T
Y
P
L A
N
C-110
A1
CIVIL SITE AND UTILITY PLAN
GENERAL NOTES:
1. SEE SHEET C-001 FOR GENERAL CIVIL NOTES, ABBREVIATIONS,
AND LEGEND.
2. KEYNOTES INDICATED WITH .
3. BACKGROUND INFORMATION PROVIDED BY THE OWNER BASED
ON AS-BUILT INFORMATION FROM C2RL, INC. ENGINEERS
DATED 03/01/2018.
4. CONTRACTOR TO PROVIDE THRUST BLOCKING ON ALL
HORITZONTAL AND VERTICAL BENDS,TEES, AND WYES IN
ACCORDANE WITH DETAIL B1/C-501.
KEY # KEYNOTE DESCRIPTION
12" X 6" TAPPING SLEEVE AND VALVE. (SEE DETAIL A4/C-501)
6" C900 PVC WATER LINE.
FIRE HYDRANT ASSEMBLY. (SEE DETAIL C3/C-501) CONTRACTOR TO
PROVIDE HYDRANT NUMBER ON HYDRANT IN WHITE STENCIL.
COORDINATE WITH COR REGARDING HYDRANT NUMBER.
PIPE BOLLARD (SEE DETAIL A2/C-501). PROVIDE SPACING AROUND FIRE
HYDRANT PER DETAIL A3/C-501.
ASPHALT PAVEMENT PATCH. (SEE DETAIL A1/C-501)
RESTRIPE PAVEMENT TO MATCH EXISTING STRIPING PATTERN.
NORTH PERSONNEL GATE. (SEE DETAIL A1/C-502)
SOUTH PERSONNEL GATE. (SEE DETAIL A1/C-503)
ENTRANCE SIGN LOCATION REFER TO ARCHITECTURAL AND
STRUCTURAL PLANS FOR DETAILS.
PROVIDE 6'-HIGH FENCE FABRIC ON EXISTING FENCE POSTS AND RAILS.
FENCE FABRIC TO MATCH EXISTING GAUGE, DIMENSIONS, AND
KNUCKLING. REFER TO C-502 FOR ADDITIONAL INFORMATION.
SANITARY SEWER LINE. REFER TO PROFILE ON THIS SHEET FOR PIPE
SIZING AND INVERTS.
REFER TO P-101 FOR SANITARY SEWER CONTINUATION.
EXISTING GAS LINE. REFER TO P-101 FOR METER REPLACEMENT.
SANITARY SEWER CLEANOUT. (SEE DETAIL B3/C-504)
SANITARY SEWER MANHOLE. (SEE DETAIL A4/C-504)
ELECTRICAL CONDUIT DUCTBANK. REFER TO ELECTRICAL DRAWINGS.
CONTRACTOR TO REPLACE DECORATIVE ROCK IN LIKE KIND UPON
COMPLETION OF WORK.
CONTRACTOR TO SEAL PARKING LOT AND RESTRIPE IN THE EXISTING
CONFIGURATION. PROVIDE WHITE TRAFFIC STRIPING.
RESTRIPE EXISTING ADA SPACE.
PROVIDE 2'X2' 4" THICK CONCRETE PAD UNDERNEATH NEMA ENCLOSED
CIRCUIT BREAKERS. REFER TO E-111 FOR THE LOCATION OF THE
BREAKERS AND COORDINATE THE PAD ACCORDINGLY.
KEYNOTES
SCALE: 1" = 20'
0 20' 40' 60'10'
A5
SANITARY SEWER PROFILE
HORZ.
SCALE: 1" = 5'
0 2.5' 5' 10' 15'
VERT.
LEGEND
LIMITS OF RESEALING
PARKING LOT
COMPACTED BACKFILL
SOIL (TYP.)
PIPE
UNDISTURBED
OF REMOVAL (TYP.)
SAWCUT AT LIMITS
EXISTING BASE
1'-0" (MIN.)
EXISTING PAVEMENT
A1
ASPHALT PAVEMENT PATCH
TIE TO EXISTING
ASPHALT PAVEMENT
7'-6"
3'-0"
1'-6"
18"Ø CONC. BASE
UNDISTURBED
EARTH
CONCRETE CAP
6" STANDARD PIPE
FILLED WITH
CONCRETE. PROVIDE
YELLOW BOLLARD
COVER.
FINISH PAVEMENT
6"
4'-0"
A2
PIPE BOLLARD
ASPHALT PAVEMENT SECTION
MATCH EXISTING
NOTES:
1. CLEAN SURFACES OF DIRT, CLAY AND OTHER OBJECTIONABLE MATERIAL.
2. SAWCUT EXISTING PAVEMENT TO PROVIDE STRAIGHT VERTICAL JOINT.
3 4 5
A
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
1' (TYP)
B1
THRUST BLOCK
THRUST BLOCK NOTES:
1. KEEP CONCRETE CLEAR OF JOINT AND JOINT ACCESSORIES.
2. CONCRETE THRUST BLOCKING SHALL BE POURED AGAINST UNDISTURBED EARTH.
3. THRUST BLOCKS FOR VERTICAL BENDS HAVING DOWNWARD RESULTANT THRUSTS
SHALL BE THE SAME AS FOR HORIZONTAL BENDS.
4. BEARING AREAS, VOLUMES, AND SPECIAL BLOCKING DETAILS SHOWN ON PLANS
TAKE PRECEDENCE OVER THIS STANDARD.
5. TAPPING VALVES SHALL HAVE THRUST BLOCKING AS SPECIFIED FOR TEES.
6. CONTRACTOR SHALL PROVIDE RESTRAINT AT ALL PRESSURE LINE FITTINGS USING
EITHER CONCRETE BLOCKING OR TIE ROD ASSEMBLIES.
7. CONCRETE FOR THRUST BLOCKS SHALL BE 4000 PSI MINIMUM STRENGH.
8. ANCHOR BLOCKS FOR VERTICAL BENDS SHALL BE SIZED AS 90° BENDS REGARDLESS
OF ANGLE.
0.4
0.7
1.0
2.0
2.6
4.0
1.5
WYE
0.6
1.4
3.9
2.5
1.2
4.6
7.1
6"
4"
8"
10"
0.8
1.9
5.0
3.3
9.7
7.5
15.1
13.7
17.8
27.5
#6
#4
#8
#10
14"
16"
20"
8" THRU 10"
4" THRU 6"
20" THRU 24"
12" THRU 18"
19.6
12.7
9.7
10.17.212" 5.5
0.7
7.8
5.0
3.9
2.0
2.9
1.3
SEE NOTE 8
UNDISTURBED EARTH (TYP.)
BEARING AREA (TYP.)
POURED CONCRETE BLOCKS (TYP.)
VERTICAL BEND
2.6
MIN. DEPTH OF BURY
AS SPECIFIED (TYP.)
DOUBLE ANCHOR
GALVANIZED RODS
BITUMASTIC COATED
AND EMBEDDED 30" IN
CONCRETE
PIPE
FITTING
SIZES
TEE &
END
90°
BEND
45° BENDS
& WYES
22 1/2°
BEND
11 1/4°
BEND
ANCHOR ROD SIZE
PIPE SIZE ROD SIZE
BEARING AREA OF BLOCK IN SQ.FT.
PLACE DOUBLE LAYER OF TAR PAPER
BETWEEN CONCRETE BLOCKING AND
PLUG TO PERMIT EASY REMOVAL FOR
FUTURE EXTENSION OF WATER MAIN
(TYP.)
8"
NOTE: SET CONCRETE COLLAR
AND TOP OF VALVE BOX
FLUSH WITH FINISHED
GRADE IN PAVED AREAS.
#3 BAR ALL AROUND
(W/ 6" OVERLAP)
WATER
LINE
GRADE
TIE VALVE TO
CONCRETE
BLOCK
C3
FIRE HYDRANT ASSEMBLY
STENCIL "WATER" ON COVER
ROUND CONCRETE COLLAR
M
I N
M
A X
M
I N
6" DIA.
7.0 CU FT CRUSHED
ROCK (57/67)
GRAVEL (TYP)
No. 12 TYPE TW WIRE
No. 10 BAR ALL AROUND
(w/ 6" OVERLAP)
ROUND CONCRETE
COLLAR
ANODE TEST
STATION (SEE DETAIL B2/C-504)
24" MIN
SQ CONC
BLOCK
FINISHED GRASS
GRADE
ROUND VALVE
BOX CONCRETE
COLLAR
VALVE BOX (SEE DTL)
No. 10 TW
BOND WIRE
VALVE
No. 10 TYPE TW WIRE
THERMITE WELD
No. 10 BAR ALL AROUND
(w/ 6" OVERLAP)
WATER MAIN
20 LB PACKAGED ANODE
(AS SPECIFIED)
No. 12 TW LEAD WIRE
No. 12 TW WIRE
CONCRETE THRUST BLOCKING.
SIZE AS TEE. SEE DETAIL THIS
SHEET FOR THRUST BLOCKING
DIMENSIONS.
EDGE OF
PAVEMENT
A3
FIRE HYDRANT
BOLLARD SPACING
PLAN
ELEVATION
SEE BOLLARD
DETAIL A1/C-502
M
N
NOTES
1. SEE DETAIL A3/C-501 FOR BOLLARD SPACING REQUIREMENT.
2. SEE DETAIL A2/C-504 FOR THERMITE WELD.
3. FIRE HYDRANT SHALL BE NUMBERED IN ACCORDANCE WITH FIRE DEPARTMENT REQUIREMENTS. CONTRACTOR TO
COORDINATE WITH COR ON FIRE HYDRANT NUMBER AND STENCIL FIRE HYDRANT NUMBER IN WHITE PAINT.
4. COLOR OF THE FINISH PAINT ABOVE THE GROUND LINE SHALL BE YELLOW.
5. CONTRACTOR SHALL PERFORM A FIRE FLOW TEST ONCE HYDRANT IS INSTALLED. CONTRACTOR SHALL PAINT
HYDRANT CAP IN ACCORDANCE WITH NFPA 291 COLOR CODE REQUIREMENTS LISTED BELOW. CONTRACTOR TO
VERIFY COLOR SELECTION WITH COR.
CLASS AA 1500 GPM OR GREATER LIGHT BLUE
CLASS B 1000-1499 GPM GREEN
CLASS C 500-999 GPM ORANGE
CLASS D 500 GPM OR LESS RED
BOLLARD, TYP.
(SEE DETAIL A1\2/C-501)
FIRE
HYDRANT
24" MIN.
No. 12 TW LEAD WIRE
20 LB PACKAGED ANODE
(AS SPECIFIED)
C O
N S
T R
U C
T I O
N
D
E T
A I L
S
C-501
2'-0" SQUARE CONC.
TYPICAL ALL VALVE BOXES
4" MIN.
SLIP-TYPE
ADJUSTABLE
VALVE BOX
BRICK
TAPPING VALVE
TEST TAP
& PLUG
SEE NOTES FOR TAPPING
SLEEVE LENGTH
MIN. 24"
EXIST.
WATER
MIN. 18"
THRUST
BLOCK
SEE NOTE 4
HOLLOW CONCRETE BLOCK AND/OR
BRICK FOR TEMPORARY SUPPORT.
SET WITH HOLLOW CORE HORIZONTAL.
WRAP-UP BLOCKS IN CONCRETE POUR.
MAKE SURE CONCRETE FILLS HOLLOW
PORTION OF BLOCKS.
NOTES:
THOROUGHLY
TAMP DITCH TO
SPECIFICATION
REQUIREMENTS
MAXIMUM TAPPING SLEEVE LENGTH
8in x 6in
MAIN & TAP
(IN. NOMINAL)
21in
LENGTH
(ALONG RUN)
1. TEMPORARILY SUPPORT TAPPING SADDLE AND VALVE AND APPLY STANDARD HYDROSTATIC TEST.
2. IF NO LEAKS, POUR INDICATED PERMANENT CONCRETE BLOCK AND SUPPORT PAD.
3. MAKE TAP, LINE EXTENSION AND BACKFILL.
4. COVER GLANDS AND BOLTS WITH HEAVY POLYETHYLENE SHEETING TO KEEP CONCRETE FROM BONDING. TYPICAL WHENEVER BOLTS
OR GLANDS MAY BE "WRAPPED-UP" IN CONCRETE.
5. COAT TAPPING SLEEVE AND BOLTS WITH AN APPROVED BITUMASTIC COATING BEFORE POURING CONCRETE. TYPICAL FOR ALL STEEL
INCLUDING RODS, COUPLINGS, STRAPS, AND OTHER BURIED STEEL. COAT WITH ROYSTON LABORATORIES, INC. ROSKOTE PLASTIC N0. A
939 OR KOPPERS CO. , INC. BITUMASTIC SUPERSERVICE BLACK OR APPROVED EQUIVALENT.
6. ALL TAPPING SLEEVES AND VALVES SHALL BE HYDROSTATICALLY TESTED PRIOR TO TAP.
7. WORKMEN INSTALLING TAPPING SLEEVE AND VALVE SHALL FOLLOW MANUFACTURER'S INSTALLATION PROCEDURES AND BASE
STANDARDS.
CONNECT DIP
FITTING WITH HPDE
MECHANICAL JOINT
ADAPTER IN
ACCORDANCE WITH
MANUFACTURER'S
INSTALLATION
INSTRUCTIONS. SEE
MECHANICAL JOINT
ADAPTER
CONNECTION
DETAIL BELOW (TYP)
MECHANICAL JOINT ADAPTER CONNECTION
MECHANICAL JOINT CONNECTION TO GATE VALVE
WITH MECHANICAL JOINT ENDS
MECHANICAL JOINT ADAPTER CONNECTION TO
DUCTILE IRON FITTING
MECHANICAL
JOINT
ADAPTER
6" C900 PVC
PIPE
A4
TAPPING SLEEVE AND VALVE
5" STORZ CONNECTION
SCALE: N.T.S.
SCALE: N.T.S.
SCALE: N.T.S.SCALE: N.T.S.
SCALE: N.T.S. SCALE: N.T.S.
NOTES:
1. ALL NEW EXTERIOR BOLLARDS SHALL
HAVE A 52" YELLOW PLATIC BOLLARD
COVER WITH TWO RED REFLECTIVE
STRIPES. CONTRACTOR SHALL SUBMIT
CUT SHEET TO COR FOR APPROVAL
PRIOR TO PROCUREMENT.
1" CROWN
NORTH MAIN GATE WITH CIPHER LOCK
3 4 5
A
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
CIPHER LOCK NOTES:
PUBLIC SIDE
SECURE SIDE
PLAN VIEW
WARNING
CONTROLLED AREA
ELEVATION VIEW FROM PUBLIC SIDE
ANG
FENCING NOTES:
ELEVATION VIEW FROM SECURE SIDE
C O
N S
T R
U C
T I O
N
D
E T
A I L
S
C-502
SOUTH MAIN GATE WITH CIPHER LOCK
3 4 5
A
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
FENCING NOTES:
WARNING
CONTROLLED AREA
WARNING
CONTROLLED AREA
ELEVATION VIEW FROM PUBLIC SIDE
CIPHER LOCK NOTES:
PUBLIC SIDE
SECURE SIDE
NEW POST DETAIL ELEVATION VIEW FROM SECURE SIDE
PLAN VIEW
C O
N S
T R
U C
T I O
N
D
E T
A I L
S
C-503
3 4 5
B
C
100% REVISED
SHEET ID
R E
P A
I L
D I N
G
M c G
H E
E
T
Y S
O N
A
S
E
T
H
T
E N
N E
S S
T
I O
N A
L
G
U A
R D
A L
C O
A
T
E N
N E
S S
E E
T E
N N
E S
S E
E
A
T
I O
N A
L
G
U A
R D
A L C
O A
T
E N
N E
S S
E E r k w a y
L a n e
S u i
P e a c h t r e e
C o r n e r s
G
A
P h o n e
F a x
J O
B
N
O
S I Z
E
A N
S I
D
F I
M
E
S U
B M
I T
T E
D
B
Y
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
C D
M
C D
M
J A
S
I S
S U
E
D
A T
E
M
A R
S O
L I C
I T
A T
I O
N
N
O
C O
N T
R A
W L D
F I
N
B E
R
D A
T E
D E
S C
R I P
T I O
N M
A R
K
1 2
D
G K
A
M X
F
Y C
M
C
A D
C
D
W G
C O
N S
T R
U C
T I O
N
D
E T
A I L
S
C-504
B2
ANODE TEST STATION
20-LB MAGNESIUM
ANODE (TYP. 2)
TOP OF ANODES
MUST BE BELOW
CENTERLINE OF
PIPE
METALLIC
FITTING OR
VALVE
REFERENCE
ELECTRODE
(AS REQUIRED)
# 12 CABLE (TYP. PER ANODE)
TWO (2) #10
AWG THHN
WIRES TO PIPE
FLUSH TO GRADE TEST
STATION W/ CAST IRON LID
12"x12"x4" CONCRETE PAD IN
UNPAVED AREAS ONLY
0.01 Ω SHUNT
(2) ANODE LEAD WIRES
TERMINAL BOARD
REF
PIPE
PIPE
TERMINAL BOARD
LAYOUT
THERMITE
WELD
(SEE C2/C-506)
SP 2888 REPAIR COATING
INSIDE STRUCTURE WALL
(IF REQUIRED)
EXOTHERMIC WELD
COPPER SLEEVE
STRUCTURE COATING
LEAD WIRE
EXOTHERMIC WELDING INSTRUCTIONS
1. REMOVE PIPE COATING APPROXIMATELY 4" DIAMETER SPOT FROM
STRUCTURE.
2. CLEAN AREA APPROXIMATELY 2" DIAMETER TO BRIGHT METAL.
3. REMOVE 1-1/4" OF INSULATION FROM END OF WIRE.
4. WELD CONDUCTOR TO PIPE. USE APPROPRIATE GRAPHITE MOLD AND
CARTRIDGE CHARGE SIZE.
5. TEST THE EXOTHERMIC WELD CONNECTION BY STRIKING THE
CONNECTION SEVERAL BLOWS ON THE SIDE USING A ONE POUND
HAMMER. TOP OF WELD MAY BE HAMMERED FLAT IF REQUIRED.
6. REFER TO MANUFACTURER FOR RECOMMENDED CARTRIDGE SIZE.
A2
THERMITE WELD
NOTES:
1. INSPECTION: INSPECT SILT FENCE BEFORE ANTICIPATED STORM EVENTS
(OR SERIES OF STORM EVENTS SUCH AS INTERMITTENT SHOWERS OVER
ONE OR MORE DAYS) AND WITHIN 24 HOURS AFTER THE END OF A STORM
EVENT OF 0.5 INCHES OR GREATER, AND AT LEAST ONCE EVERY
FOURTEEN CALENDAR DAYS. WHERE SITES HAVE BEEN FINALLY OR
TEMPORARILY STABILIZED, SUCH INSPECTIONS MAY BE CONDUCTED
ONLY ONCE PER MONTH.
2. MAINTENANCE: SEDIMENT SHOULD BE REMOVED ONCE IT HAS
ACCUMULATED TO ONE-HALF THE ORIGINAL HEIGHT OF THE BARRIER.
FILTER FABRIC SHOULD BE REPLACED WHENEVER IT HAS DETERIORATED
TO SUCH AN EXTENT THAT THE EFFECTIVENESS OF THE FABRIC IS
REDUCED (APPROXIMATELY SIX MONTHS). SILT FENCE SHOULD REMAIN IN
PLACE UNTIL DISTURBED AREAS HAVE BEEN PERMANENTLY STABILIZED.
ALL SEDIMENT ACCUMULATED AT THE FENCE SHOULD BE REMOVED AND
PROPERLY DISPOSED OF BEFORE THE FENCE IS REMOVED.
3. MATERIAL SPECIFICATIONS:
3.1. TYPE: TYPE B
3.2. TENSILE STRENGHT (LBS MIN.): WARP 120
3.3. ELONGATION (% MAX): 40
3.4. APPARENT OPENING SIZE: #30
3.5. FLOW RATE (GAL/MIN/SQ FT) = 25
3.6. UV SENSITIVTY (ASTM D-4632): 80
3.7. BURSTING STRENGHT (PSI MIN.): 175
3.8. MIN. FABRIC WIDTH (IN.): 22
4. INFORMATION AND DETAIL BASED ON TENNESSEE EROSION & SEDIMENT
CONTROL HANDBOOK, SECOND EDITION (MARCH 2002)
A1
SILT FENCE
A4
SANITARY SEWER MANHOLE
C.I. FRAME & COVER
2'-0" Ø OPENING
PRECAST SECTION. FLAT
TOP SECTION MAY BE
USED FOR STRUCTURES
4' OR LESS IN DEPTH.
C.I. FRAME & COVER
RATED FOR HS-20
LOADING
11"
PLAN VIEW
6" AGGREGATE BASE
UNDISTURBED SOIL
PRECAST
BASE SECTION
COMPRESSIBLE
GASKET (TYP)
4' Ø RISER SECTIONS
(AS NECESSARY)
SECTION B-B
2'-0"2'-0"
31 1/2"
24"
25'-1/4"
SEWER
MACHINED
SURFACES
"0" RING SEAL IN A
DOVE-TAIL GROOVE
FINISH FRAME AND COVER WITH
ONE COAT ASPHALT PAINT
A
FLOW
SEWER
LINE (TYP.)
FORMED
CONCRETE
INVERT
MANHOLE
SECTION
CONCRETE
BASE
S
L
O
P
E
F
T
3"
MIN
RUBBERIZED
BOOT SEAL
AND CLAMP
FORMED
CONCRETE
INVERT
B O
X
T
Y P
L
C
O V
E R
C
F
R A
M E
C
C
J U
N C
T I O
N
L
T
Y P
C
PIPE BEDDING
BASE SECTION
PLAN VIEW
2 NON-PENETRATING
PICK HOLES
NOTES
1. PRECAST MANHOLE SECTIONS REINFORCING SHALL CONFORM TO ASTM C478.
2. MANHOLE FRAME AND GRATE BASIS OF DESIGN: NEENAH FOUNDRY R-1574
3. SCARIFY AND COMPACT 12" OF SUBGRADE TO 95% MODIFIED PROCTOR.
PLUG IF LINE DOES
DIRECTION OF FLOW
NOT CONTINUE
FINISHED
GRADE
VARIES
B3
CLEANOUT
PE LINE
18"X18"X12" DEEP CONC.
PAD UNLESS CLEANOUT
IS IN CONC. PAVEMENT
45° BEND
CLEANOUT
NOTES:
1. FOR CLEANOUTS USED ON SANITARY SEWER LINES,
STENCIL "SEWER" ON CLEANOUT CAP.
SCALE: N.T.S.
AWG #12 THW (TYP.
PER ANODE)
SCALE: N.T.S.
SCALE: N.T.S. SCALE: N.T.S.
GENERAL STRUCTURAL NOTES:
A. GENERAL:
1. THE CONTRACTOR SHALL REVIEW ALL SUBMITTALS BEFORE THEY ARE PROVIDED TO THE
CONTRACTING OFFICER. THE CONTRACTOR’S REVIEW SHALL BE DOCUMENTED WITHIN THE
SUBMITTAL. THE CONTRACTING OFFICER RESERVES THE RIGHT TO REJECT SUBMITTALS THAT
HAVE NOT BEEN FIRST REVIEWED BY THE CONTRACTOR. THE ACCURACY AND COMPLETENESS OF
THE SUBMITTALS IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR, INCLUDING ALL ERRORS
AND OMISSIONS. IN ADDITION, THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL MEANS,
METHODS, AND SEQUENCING OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL BE EXPERIENCED AND
QUALIFIED TO PERFORM THE TYPE OF CONSTRUCTION REQUIRED TO COMPLETE THE WORK
PRESCRIBED BY THE CONTRACT DOCUMENTS. THE CONTRACT DOCUMENTS WERE PREPARED AS
A COMPLETE SET OF PROJECT DRAWINGS AND SPECIFICATIONS. IT IS THE GENERAL
CONTRACTOR’S RESPONSIBILITY TO COORDINATE ALL INFORMATION PROVIDED IN THE CIVIL,
ARCHITECTURAL, INTERIOR, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION
DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER
IMMEDIATELY OF ANY CONFLICTS, OMISSIONS, OR DISCREPANCIES. THIS COORDINATION SHALL
BE PERFORMED BEFORE THE PROCUREMENT OF MATERIALS AND/OR FABRICATION OF ANY
PROJECT COMPONENTS.
3. WHERE SECTION IS SHOWN AND DETAILED, OTHER SECTIONS OF SIMILAR CONDITION SHALL BE
DETAILED THE SAME OR OPPOSITE HAND, WHETHER SPECIFICALLY NOTED OR NOT.
4. CONTRACTOR SHALL VERIFY EXISTING DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE
BEGINNING CONSTRUCTION. NOTIFY CONTRACTING OFFICER OF ANY DISCREPANCIES.
5. COORDINATE SIZES AND LOCATIONS OF ALL FLOOR AND ROOF PENETRATIONS WITH PLUMBING, MECHANICAL, AND ARCHITECTURAL REQUIREMENTS.
6. CONTRACTING OFFICER APPROVAL MUST BE SECURED FOR ALL SUBSTITUTIONS. SUCH
APPROVAL MAY ALSO BE WITHHELD AT THE SOLE DISCRETION OF THE CONTRACTING OFFICER.
7. THE STRUCTURES HAVE BEEN DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF THE
FOLLOWING:
a. INTERNATIONAL BUILDING CODE, 2015 EDITION (IBC 2015).
b. AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMUM DESIGN LOADS FOR BUILDINGS AND
OTHER STRUCTURES," 2010 EDITION (ASCE 7-10).
c. UNIFIED FACILITIES CRITERIA (UFC), "STRUCTURAL ENGINEERING," 2013 EDITION WITH
CHANGE 3, 12 SEPTEMBER 2016 (UFC 3-301-01).
8. THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING REQUIRED TO ERECT
AND HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL PERMANENT SUPPORTS AND LATERAL
BRACING ARE IN PLACE.
9. DO NOT SCALE DRAWINGS, USE DIMENSIONS.
10. DESIGN LOADS USED IN THE DESIGN OF THE STRUCTURAL SYSTEMS IN THIS PROJECT ARE AS
FOLLOWS:
a. RISK CATEGORY II
b. DEAD LOAD:
ROOF (NOT INCLUDING FRAMING SELF WT.) 7.5 psf
c. LIVE LOAD:
ROOF 20 psf (REDUCIBLE) HANGAR SLAB-ON-GRADE 250 psf NON-HANGAR INTERIOR SLAB-ON-GRADE 100 psf
d. ROOF SNOW LOAD:
GROUND SNOW LOAD, pg 10 psf SNOW EXPOSURE FACTOR, Ce 1.0 IMPORTANCE FACTOR, Is 1.0 THERMAL FACTOR, Ct 1.0 FLAT ROOF SNOW LOAD, pf 7 psf FROST PENETRATION DEPTH 18 in
e. WIND DESIGN CRITERIA:
EXPOSURE CATEGORY B IN TRANSVERSE DIR
C IN LONGITUDINAL DIR
BASIC WIND SPEED, V 115 mph (FACTORED, ULTIMATE LOAD)
89.1 MPH (UNFACTORED, SERVICE LOAD)
INTERNAL PRESSURE COEFFICIENT, GCp ± 0.55 PARTIALLY ENCLOSED HANGAR BAY
± 0.18 ENCLOSED OFFICE/SHOP SPACES
INTERIOR WIND LOADING (PARTITIONS) 10 psf (UNFACTORED, SERVICE LOAD)
(SEE S-003 FOR WIND LOAD DIAGRAMS)
f. SEISMIC DESIGN CRITERIA:
SPECTRAL RESPONSE ACCELERATION:
Ss (SHORT PERIOD (0.2 SECOND)) 0.423 g S1 (LONG PERIOD (1.0 SECOND)) 0.126 g SDS (SHORT PERIOD (0.2 SECOND)) 0.338 g SD1 (LONG PERIOD (1.0 SECOND)) 0.141 g
SITE CLASS CLASS C
SEISMIC DESIGN CATEGORY C
LATERAL FORCE RESISTING SYSTEM BUILDING FRAME STRUCTURE, STEEL SYSTEM
NOT SPECIFICALLY DETAILED FOR SEISMIC
RESISTANCE
IMPORTANCE FACTOR, Ie 1.0
RESPONSE MODIFICATION COEFFICIENT, R 3
SEISMIC RESPONSE COEFFICIENT, Cs 0.113
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
11. ALL VERTICAL ELEVATIONS ARE BASED ON THE CONTROL ELEVATION FROM SURVEY BY OTHERS.
1. FOUNDATIONS AND EARTH RETAINING STRUCTURES HAVE BEEN DESIGNED FOR A MAXIMUM
ALLOWABLE SOIL BEARING PRESSURE OF 2000 psf BASED ON REQUIREMENTS OF IBC WHEN A
GEOTECHNICAL ENGINEER'S REPORT HAS NOT BEEN PROVIDED.
2. REFER TO THE GEOTECHNICAL REPORT AND SPECIFICATION SECTION 31 23 00.00 20 FOR
REQUIREMENTS FOR REMOVAL OF UNSATISFACTORY MATERIAL UNDER FOOTINGS, SLABS, AND
FOUNDATIONS AND FOR THE BACKFILLING, COMPACTION, AND TESTING OF SATISFACTORY
MATERIAL TO REPLACE IT. REFER TO GEOTECHNICAL REPORT FOR ALL ADDITIONAL
PREPARATION REQUIREMENTS.