1190113_TNANG_B113_ELEC-ADDENDUM 1-072622.pdf

PDF 1000 KB Posted

Attached to
B113 Solicitation Federal contract opportunity
Solicitation number
W50S98
Issued by
Department of the Army Tennessee Army National Guard

About this file

This document package includes electrical drawings and panel schedules in support of Solicitation Number W50S98 for repair work at Building 113 of the Tennessee Army National Guard. The scope of work includes replacing panels and transformers with new energy efficient models, upgrading receptacles and light fixtures to meet hazardous location requirements, installing new magnetic door locks and controls, and modifying power and lighting as shown on the plans. Panel schedules provide specifications for existing and proposed panels to support the upgrades.

View the file

Other files for this federal contract opportunity

Other files attached to B113 Solicitation, newest first.
File Type Posted
OF 1419 Abstract.pdf PDF
OF 1419 Abstract.pdf PDF
Sign in Sheet - 23 Aug 2022 10am.pdf PDF
B 113 As Built Drawings.pdf PDF
Demo 110_110 Drawings GC002 003 004 005.pdf PDF
BLDG 111 Asbestos Info.pdf PDF
05 40 00 Cold-formed Metal Framing 20220805.pdf PDF
Demo Drawings CS503-506.pdf PDF
W50S98-22-B-000100002.pdf PDF
P-601_REVISED.pdf PDF
REGISTER-upate 07292022.pdf PDF
W50S98-22-B-000100001.pdf PDF
1190113_TNANG_B113_FIRE-ADDENDUM 1-072622.pdf PDF
28 31 76 - updated.pdf PDF
Pre-Bid Sign in Sheet B113.pdf PDF
Pre-Bid Slides B113.pdf PDF
MTANG Demo 110 and 111 drawings.pdf PDF
Repair Building 113 Spec. Volume 2.pdf PDF
W50S98-22-B-0001 21 July 2022.pdf PDF
Repair Building 113 Spec. Volume 1.pdf PDF
Repair Building 113 Drawings.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:

A. NFPA 70-2017 (NATIONAL ELECTRICAL CODE)

B. ANSI C2-2017 (NATIONAL ELECTRICAL SAFETY CODE)

C. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.

2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40%

FULL.

3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LIGHTING

FIXTURES AND CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL

DESCRIPTIONS INDICATED.

5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.

6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.

7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE

RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.

8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE

ROUGHING-IN.

9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA

COMPENSATION WILL BE GRANTED.

10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM THE

EXISTING SHALL BE REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.

11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.

12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND

SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE

CONTRACTOR'S RESPONSIBILITY.

14. ALL CONDUCTORS ARE COPPER.

15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY

MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.

16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/8” IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN

WITH AN INDELIBLE MARKER.

17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.

ABBREVIATIONS

A OR AMP

ACC

AC

AC

AF

AFF

AFG

AHU

AIC

AL

AM

ASYM

AT

ATS

AUTO

AWG

B

BC

BCW

BFF

BFG

BLDG

C

CAT

CB

CCT

CCTV

CFCI

CH

CHWCP

CHWP

CHWSP

CKT

CMH

CP

CPT

CRAC

CRI

CT

CT

CU

CWP

D

DC

DF

DH or DUH

DHWCP

DISC

DOAS

DPST

DPDT

DSCU

DSHP

DSS

DWBP

DX

EC

EF

ELEC

EMH

EMT

E or EMER

EPA

EQUIP

ERV

ERU

EXIST or EX

EUH

EXP

EWC

EWH

F

FACP

FCU

FLEX

FWE

G OR GND

GFGI

GFI

GRS

GUH

GWH

H or HT

HAC

HOA

HP

HP

HT

HVU

HWCP

HWP

AMPERE(S)

AIR COOLED CHILLER

ALTERNATING CURRENT

AIR COMPRESSOR / AIR CURTAIN

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AMMETER

ASYMMETRICAL

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AMERICAN WIRE GAUGE

BOILER

BRANCH CONTROLLER

BARE COPPER WIRE

BELOW FINISHED FLOOR

BELOW FINISHED GRADE

BUILDING

CONDUIT

CATEGORY

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CHILLER

CHILLED WATER CIRCULATING PUMP IN A

PRIMARY-SECONDARY SYSTEM

CHILLED WATER PUMP

CHILLED WATER SUPPLY PUMP IN A PRIMARY-

SECONDARY SYSTEM

CIRCUIT

COMMUNICATIONS MANHOLE

CONDENSATE PUMP

CONTROL POWER TRANSFORMER

COMPUTER ROOM AC UNIT

COLOR RENDERING INDEX

CURRENT TRANSFORMER

COOLING TOWER

COPPER OR CONDENSING UNIT

CONDENSER WATER PUMP

DEPTH

DIRECT CURRENT

DESTRATIFICATION FAN

DUCT HEATERS

DOMESTIC HOT WATER CIRCULATING PUMP

DISCONNECT SWITCH

DEDICATED OUTSIDE AIR SYSTEM (UNIT)

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

DUCTLESS SPLIT CONDENSING UNIT (POWERS

THE DSS INDOOR UNIT)

DUCTLESS SPLIT HEAT PUMP (POWERS THE

DSS INDOOR UNIT)

DUCTLESS SPLIT SYSTEM (INDOOR UNIT)

DOMESTIC WATER BOOSTER PUMP

DIRECT EXPANSION (DX) COOLING COIL

EMPTY CONDUIT

EXHAUST FAN

ELECTRICAL

ELECTRICAL MANHOLE

ELECTRICAL METALLIC TUBING

EMERGENCY

EFFECTIVE PROJECTED AREA

EQUIPMENT

ENERGY RECOVERY VENTILATOR

ENERGY RECOVERY UNIT

EXISTING

ELECTRIC UNIT HEATER

EXPLOSION PROOF

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FUSE

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FLEXIBLE

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GROUND FAULT INTERRUPTER

GALVANIZED RIGID STEEL CONDUIT

GAS UNIT HEATER

GAS WATER HEATER

HEIGHT

HEATED AIR CURTAIN

HAND-OFF AUTOMATIC

HORSE POWER

HEAT PUMP (OUTDOOR PORTION OF SPLIT

SYSTEM HEAT PUMP, USE CU FOR

STANDARD DX OUTDOOR UNIT)

HEAT TRACKING

HEATING/VENTILATING UNIT

HEATING WATER CIRCULATING PUMP IN A

PRIMARY-SECONDARY SYSTEM

HEATING WATER SUPPLY IN A PRIMARY-ONLY

SYSTEM

HWRP

HWSP

HWUH

HZ

IDS

IMC

IRH

J OR JB

K

KAIC

KCM OR KCMIL

KEF

KH

KV

KVA

KW

KWHR

L

LA

LAN

LAV

LTG

MAU

MAX

MCA

MCB or MB

MCC

MGB

MH

MIN

MLO

MOD

MT or MTD

MRS

N

NEC

NEMA

NFPA

NC

NESC

NO

NTS

P

PA

PDU

PF

PH

PIU

PMT

PNL

PTAC

PVC

RECEPT or RECP

RF

RH

RMC

RMS

RTU

RVNR

SA

SCCR

SD

SF

S/N

SP

SPD

SPDT

SPEC

SPST

SWBD

SWGR

TMGB

TOL

TP

TYP

U

UH

UG

UIO

UL

UTP

V

VA

VAV

VEF

VM

VRF

W

WC

WEF

WH

WHDM

WSHP

WP

XFMR

Z

HOT WATER RECIRCULATION PUMP

HEATING WATER SUPPLY PUMP IN A PRIMARY-

SECONDARY SYSTEM

HOT WATER UNIT HEATER

HERTZ

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

INFRARED HEATER

JUNCTION BOX

KILO

THOUSAND AMPERE INTERRUPTING CAPACITY

THOUSAND OF CIRCULAR MILS

KITCHEN EXHAUST FAN

KITCHEN HOOD

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

KILOWATT-HOUR

LENGTH

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

LAVATORY

LIGHTING

MAKE-UP AIR UNIT

MAXIMUM

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN GROUND BAR

MANHOLE or MOUNTING HEIGHT

MINIMUM

MAIN LUGS ONLY

MOTOR OPERATED DAMPER

MOUNT or MOUNTED

MOTOR RATED SWITCH

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NORMALLY CLOSED

NATIONAL ELECTRICAL SAFETY CODE

NORMALLY OPEN

NOT TO SCALE

POLE(S) or PUMP

PUBLIC ADDRESS

POWER DISTRIBUTION UNIT

POWER FACTOR

PHASE

VAV TERMINAL UNIT WITH PARALLEL OR

SERIES FAN (PRIMARY INDUCTION UNIT)

PAD MOUNTED TRANSFORMER

PANEL OR PANELBOARD

PACKAGED THRU-WALL AIR CONDITIONER

POLYVINYL CHLORIDE

RECEPTACLE

RETURN FAN

RADIANT HEATERS (ELECTRIC)

RIGID METAL CONDUIT

ROOT MEAN SQUARE

ROOF TOP UNIT

REDUCED VOLTAGE NON-REVERSING

SURGE ARRESTOR

SHORT CIRCUIT CURRENT RATING

SMOKE DAMPER

SUPPLY FAN

SOLID NEUTRAL

SUMP PUMP

SURGE PROTECTIVE DEVICE

SINGLE POLE DOUBLE THROW

SPECIFICATIONS

SINGLE POLE SINGLE THROW

SWITCHBOARD

SWITCHGEAR

TELECOMMUNICATIONS MAIN GROUNDING

BUSBAR

THERMAL OVERLOAD

TWISTED PAIR

TYPICAL

URINAL

UNIT HEATER

UNDERGROUND

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

VAV TERMINAL UNIT

VEHICLE EXHAUST FAN

VOLTMETER

VARIABLE REFRIGERANT FLOW SYSTEM

WATTS or WIRE or WIDTH

WATER CLOSET

WELDING EXHAUST FAN

WATER HEATER

WATTHOUR DEMAND METER

WATER SOURCE HEAT PUMP

WEATHERPROOF

TRANSFORMER

IMPEDANCE

SHEET NAMING CONVENTION

E-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DESCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

/2

/2

:4

:0

P

M B

IM

/1

T N

A N

G R e p a ir B ld g

F u e l C e ll/

T

N A

N G

B v

E le c .r v t

E-001

100% REVISED

E L E

C T

R

IC

A L G

E N

E R

A L N

O T

E S

A N

D A

B B

R E

V

IA

T

IO

N S

R E

P A

IR

B

U

IL

D

IN

G

T

H T

E N

N E

S S

E E

A

IR

N A

T

IO

N A

L G

U A

R D

M c G

H E

E T

Y S

O N

A N

G B

A S

E A

L C

O A

T

E N

N E

S S

E E

T E

N N

E S

S E

E

A

IR

N A

T

IO

N A

L G

U A

R D

A L C

O A

T

E N

N E

S S

E E

J O

B N

O

T E

H

T C

G

T E

H

M

A R

C H

S O

L -X

X -X

-X X

X X

W L -1

-D

-0

X X

-X -X

X X

X G

L K

NOTE:

1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS

PROJECT.

WIRE SIZE FOR ALL 277V, 20A

CIRCUITS, UIO:

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 170 FT,

PROVIDE 2#12 & 1#12G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 280 FT

AND GREATER THAN OR EQUAL TO 170 FT, PROVIDE 2#10 & 1#10G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 440 FT

AND GREATER THAN OR EQUAL TO 280 FT, PROVIDE 2#8 & 1#8G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 700 FT

AND GREATER THAN OR EQUAL TO 440 FT, PROVIDE 2#6 & 1#6G,

3/4"C.

WIRE SIZE FOR ALL 120V, 20A

CIRCUITS, UIO:

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,

PROVIDE 2#12 & 1#12G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT

AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT

AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT

AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,

3/4"C.

NOTES:

1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.

ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,

DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT

IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF

EACH:

EXISTING EQUIPMENT

NEW OR RELOCATED EQUIPMENT

HATCH INDICATES EQUIPMENT TO BE DEMOLISHED

/2

/2

A

D D

E N

D U

M

HendersonZ Snapshot

1/2

B

W

S B

S W

M

MOD

2/60/40/1

60/40/3/3R

40/3/3R

CB

T

M

EM

J J

J

G

G4

LP

A

AE

M

X X

C

D a b

LUMINAIRES

LUMINAIRE AND OUTLET BOX. LETTER INDICATES

LUMINAIRE TYPE. SEE LIGHTING FIXTURE

SCHEDULE.

LUMINAIRE AND OUTLET BOX WIRED FOR

MULTILEVEL SWITCHING, LOWER CASE LETTER

INDICATES SWITCHLEG DESTINATION.

LUMINAIRE AND OUTLET BOX, WITH PROVISIONS

FOR EMERGENCY LIGHTING. LETTER INDICATES

LUMINAIRE TYPE. SEE LIGHTING FIXTURE

SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LIGHTING FIXTURE SCHEDULE.

CEILING OR WALL MOUNTED EXIT SIGN AND

OUTLET BOX. PROVIDE NUMBER OF ARROWS

AND FACES INDICATED. LETTER INDICATES

LUMINAIRE TYPE. SEE LIGHTING FIXTURE

SCHEDULE. WALL MT AT 96" AFF.

RECESSED OR PENDANT MOUNTED LUMINAIRE

AND OUTLET BOX. LETTER INDICATES LUMINAIRE

TYPE. SEE LIGHTING FIXTURE SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LIGHTING FIXTURE SCHEDULE.

CEILING OR WALL MOUNTED LUMINAIRE AND

OUTLET BOX WITH PROVISIONS FOR

EMERGENCY LIGHTING.

EMERGENCY LIGHT UNIT

REMOTE HEAD OR FLOOD LUMINAIRE

WALL WASH DOWNLIGHT

POLE MOUNTED TYPE

POST-TOP OR BOLLARD TYPE

CEILING FAN

EQUIPMENT

MOTOR, HORSEPOWER AS INDICATED

MOTORIZED DAMPER

3-POLE COMBINATION MAGNETIC MOTOR

STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/

NEMA ENCLOSURE) NF = NONFUSED

DISCONNECT SWITCH, (SWITCH AMPS/ FUSE

SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-

FUSED

INDIVIDUALLY MOUNTED CIRCUIT BREAKER, (CB

SIZE/ POLES/ NEMA ENCLOSURE)

DRY TYPE TRANSFORMER, KVA AS INDICATED

METER

ELECTRONIC METER

PANELBOARD, SEE SCHEDULES

DISTRIBUTION PANELBOARD

EQUIPMENT AS INDICATED

CEILING OR WALL MOUNTED JUNCTION BOX

PULL OR JUNCTION BOX

CEILING MOUNTED BLUE LIGHT SYSTEM

ROTATING BEACON

WHITE NOISE PLENUM SPEAKER; MT ABOVE

DROP CEILING

BLUE LIGHT LOCAL CONTROL SWITCH; MT 48"

AFF, UIO

WHITE NOISE ROTARY VOLUME CONTROL; MT

48" AFF, UIO

CR

ST

TR

M

R

LA-1,3,5

WIRING

CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5

ADJACENT TO ARROW INDICATES HOMERUN OF

CIRCUITS, 1,3,5 TO PANEL LA. MARKS ACROSS

RACEWAY INDICATE THE NUMBER OF PHASE

CONDUCTORS AND NEUTRAL IN RACEWAY.

GROUND CONDUCTORS ARE INDICATED BY

LONGER HASHMARKS. NO MARKS ACROSS

RACEWAY INDICATES 2#12 CONDUCTORS AND 1#

12 GROUND CONDUCTOR. CONDUCTOR SIZE #12

UNLESS INDICATED OTHERWISE. MINIMUM

RACEWAY SIZE SHALL BE 3/4"

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR

ABOVE FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW

GRADE OR CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

PLUG-IN BUSWAY, UIO

SURFACE METAL RACEWAY OR MULTIOUTLET

ASSEMBLY AS INDICATED

CABLE TRAY (SIZE AS INDICATED ON PLAN)

DUCTBANK, TEXT INDICATES QUANTITY AND SIZE

OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)

LIGHTNING PROTECTION

3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG

GROUND CONNECTION

BARE COPPER GROUND CONDUCTOR, 1/0 UIO.

4/0 BARE COPPER GROUND CONDUCTOR

LIGHTNING PROTECTION SYSTEM AIR TERMINAL

LIGHTNING PROTECTION ROOF CONDUCTOR

ELECTRICAL CONNECTION

3/4'' X 10'-0'' COPPER CLAD STATIC GROUND ROD,

18'' BFG

STATIC DISCHARGE TOUCH PLATE

ONE-LINE

TRANSFORMER

CURRENT TRANSFORMER

FUSE

ELECTRICAL CONNECTION

CIRCUIT BREAKER

SWITCH

SURGE ARRESTORS

SEPARABLE CONNECTION

DRY TYPE TRANSFORMER, K-4 RATED, KVA AS

INDICATED

GROUND

2W4"

WIRING DEVICES

SIMPLEX RECEPTACLE NEMA 5-20R, MT 18" AFF,

UIO

DUPLEX RECEPTACLE NEMA 5-20R, MT 18" AFF,

UIO

DUPLEX RECEPTACLE, NEMA 5-20R, MT 48" AFF

OR ABOVE COUNTER TOP/BACKSPLASH

DUPLEX GFI RECEPTACLE NEMA 5-20R, MT 18"

AFF, UIO

DUPLEX GFI RECEPTACLE NEMA 5-20R, MT 48"

AFF OR ABOVE COUNTER TOP/BACKSPLASH

DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R, MT

18" AFF, UIO

SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,

MT 18" AFF, UIO

SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,

MT 48" AFF OR ABOVE COUNTER

TOP/BACKSPLASH

SWITCHED DUPLEX GFI RECEPTACLE NEMA

5-20R, MT 18" AFF, UIO

SWITCHED DUPLEX GFI RECEPTACLE NEMA

5-20R, MT 48" AFF OR ABOVE COUNTER

TOP/BACKSPLASH

DOUBLE-DUPLEX GFI RECEPTACLE, NEMA

5-20R, MOUNTED CONCEALED BEHIND ELECTRIC

WATER COOLER

FLOOR BOX WITH DUPLEX RECEPTACLE NEMA

5-20R. PROVIDE FIRE RATED POKE THRU

DEVICES ON ALL FLOORS ABOVE GROUND

LEVEL.

SPECIAL RECEPTACLE, NEMA TYPE AS

INDICATED, MT 18" AFF UIO

CEILING BOX WITH DUPLEX RECEPTACLE, NEMA

5-20R

RECEPTACLE WP = IN-USE WEATHER PROOF

SUBSCRIPTS TR = TAMPER RESISTANT

TV = TELEVISION, MOUNT AT 60" AFF

AFCI = ARC FAULT CIRCUIT INTERRUPTER

CR = CORD REEL

FLOOR BOX SUITABLE FOR CONCRETE FLOOR

POUR; TWO COMPARTMENTS - POWER AND

TELECOMMUNICATIONS; FLUSH COVER/FLANGE

WITH HINGED ACCESS TO RECEPTACLES AND

JACKS RECESSED BELOW COVER IN FLOOR

BOX. PROVIDE 8" FIRE RATED POKE THRU

ABOVE GROUND FLOOR.

WALL SWITCH, AC TYPE, SPST, MOUNT 48" AFF

WALL SWITCH, AC TYPE, DPDT, MOUNT 48" AFF

3-WAY WALL SWITCH, MOUNT 48" AFF

4-WAY WALL SWITCH, MOUNT 48" AFF

SLIDE DIMMER, MT 48" AFF

3-WAY DIMMING WALL SWITCH, MOUNT 48" AFF

WALL MOUNTED, DUAL TECHNOLOGY

OCCUPANCY SWITCH WITH DIMMING, MT 48" AFF

MOTOR RATED DISCONNECT SWITCH WITH

THERMAL OVERLOADS, SPST, MT. ON UNIT, UIO.

WALL MOUNTED SPEAKER VOLUME SWITCH, MT.

48" AFF

WALL MOUNTED, DUAL TECHNOLOGY

OCCUPANCY SWITCH, MT. 48" AFF

LOW VOLTAGE ON/OFF WALL SWITCH, WALL MT.

48" AFF. PROVIDE DIMMER CONTROL WITH

DIMMABLE FIXTURES INTEGRAL WITH SWITCH.

CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR

CEILING MOUNTED DAYLIGHT SENSOR

LEGEND

D

M

V

O

LV

OS

DS

5-30R

EWC

SCHEMATIC

PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)

CONTROL RELAY COIL

SHUNT TRIP COIL

TIME DELAY RELAY COIL

MOTOR STARTER COIL

S

SDP

TV

COMMUNICATIONS

COAXIAL CATV OUTLET WALL MOUNTED 60" AFF,

UIO

COMMUNICATIONS COMBINATION VOICE/DATA

OUTLET (TWO VOICE & TWO DATA JACKS)

MOUNT 18" AFF, UIO

COMMUNICATIONS VOICE OUTLET MT 48" AFF,

UIO

COMMUNICATIONS DATA OUTLET, MT 18" AFF,

UIO

FLOOR BOX SUITABLE FOR CONCRETE FLOOR

POUR; TWO COMPARTMENTS - POWER AND

TELECOMMUNICATIONS; FLUSH COVER/FLANGE

WITH HINGED ACCESS TO RECEPTACLES AND

JACKS RECESSED BELOW COVER IN FLOOR

BOX. PROVIDE 8" FIRE RATED POKE THRU

ABOVE GROUND FLOOR.

ELECTRONIC SECURITY

MAGLOCK

REQUEST TO EXIT PUSHBUTTON REX

ML

3D

DO

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

/2

/2

:4

:0

P

M B

IM

/1

T N

A N

G R e p a ir B ld g

F u e l C e ll/

T

N A

N G

B v

E le c .r v t

E-002

100% REVISED

E L E

C T

R

IC

A L L

E G

E N

D

R E

P A

IR

B

U

IL

D

IN

G

T

H T

E N

N E

S S

E E

A

IR

N A

T

IO

N A

L G

U A

R D

M c G

H E

E T

Y S

O N

A N

G B

A S

E A

L C

O A

T

E N

N E

S S

E E

T E

N N

E S

S E

E

A

IR

N A

T

IO

N A

L G

U A

R D

A L

C O

A

T E

N N

E S

S E

E

J O

B N

O

T E

H

T C

G

T E

H

M

A R

C H

S O

L -X

X -X

-X X

X X

W

L

-1

-D -0

X X

-X -X

X X

X G

L K

NOTE:

1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.

/2

/2

A D

D E

N D

U M

J J

J

J

J J J J

M

J

J

REX

REXREX

REX

REX

REX

REX

REX

REX

REX

REX

REX

J

J

JJ

J

J

J

J

J

J

JREX

ML ML

ML

ML

ML ML

ML

ML

ML ML

ML

ML

J

J

J

A

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

B

C

D

E

F

G

H

J

K

L

M

LAUNDRY

109A

HANGAR BAY

MECH.

FUEL CELL TANK

MAINTENANCE

UNISEX

MECH.

ACCESSORIES

SUPERVISOR

CORRIDOR

COMM.

MECH.

114A

FUEL CELL

SUPERVISOR

MECH.

102A

MECH.

CR

CR

CR

CR

CR

CR

CR

CR CR

CR

LE

LF1LF2

LD3

LD2

LD1

HD

LA1

LA2HDP1

HB

LB1

LB2

LC

LP

OFFICE

MACHINE SHOP

WELDING SHOP

BREAK ROOM

CORRIDOR

SUPPLY

CSO OFFICE

COMM.

NOSE BAY

101A

BREAK ROOM

FUEL CELL OFFICE

CORRIDOR

MEN'S LOCKER

ROOM

MEN'S RESTROOM

WOMEN'S

RESTROOM

WOMEN'S LOCKER

ROOM

MECH.

TOOL CRIB

DRYER

WASHER

SWBD

(TYP.)

T

T-LA

T-LB

T-LC

T-LD

T-LE/LF

(TYP.)

M

(TYP.)

OPEN SHOP

133A

UNISEX

VEST.

LA1-28

LA1-8

LC-2

LC-4

LC-8

LB2-25,27

LB1-19

LB1-25

MGB

LA2-2,4 LA2-7

M

JANITOR

J

FACP

WP

WP

WP

WP WP WP

WP

ELEC.

UNISEX

LC-24

LC-18

LF2-9

LF2-7

LF2-6

LF2-11

LA2-9

(TYP.)

SEE E-600 AND E-601 FOR INFORMATION ON

CONDUCTOR AND CONDUIT SIZES

E11

E12

E23

E25

E27

E25

E25

E19

E19

E25

E26 E21

E21

E25 E24

E25

E14

E15

E17E20

E22

E27

E25

E25

E13

E13

E16

E16

E18

E34 E34

E34E34

E34

E34

E34

E34

E34 E34

E34

E35

LF2-24

E34

LC-46

LB1-18

LA1-15

LC-47

E36 E36

E36

M

EXISTING

E38

E39

E40 E40

E39

E40

LC-48

E41

NEW CONDUIT SHALL TRANSISTION FROM

UNDERGROUND TO ABOVE GRADE AND RISE UP

THROUGH CHASE TO BOTTOM OF ROOF STRUCTURE

SE RATED 100A, 3P, 4W, NEMA 3R

ENCLOSED CIRCUIT BREAKER

100A, 4 POLE NEMA 3R MTS

MTS

E34

E16

GENERATOR TAP BOX

E42

E42

E42

E42

E42

E42

E42

E42

E42

E45

E45

DOE

LA2-10E46

E46

KEYNOTES:

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

/2

/2

:4

:1

P

M B

IM

/1

T N

A N

G R e p a ir B ld g

F u e l C e ll/

T

N A

N G

B v

E le c .r v t

E-111

100% REVISED

P O

W E

R P

L A

N

R E

P A

IR

B

U

IL

D

IN

G

T

H T

E N

N E

S S

E E

A

IR

N A

T

IO

N A

L G

U A

R D

M c G

H E

E T

Y S

O N

A N

G B

A S

E A

L C

O A

T

E N

N E

S S

E E

T E

N N

E S

S E

E

A

IR

N A

T

IO

N A

L G

U A

R D

A L

C O

A

T E

N N

E S

S E

E

J O

B N

O

T E

H

T C

G

T E

H

M

A R

C H

S O

L -X

X -X

-X X

X X

W

L

-1

-D -0

X X

-X -X

X X

X G

L K

SCALE: 3/32" = 1'-0"A1

POWER PLAN

GENERAL NOTES:

1. REFER TO E-001 & E-002 FOR

ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

2. ALL EXISTING POWER,

TELECOMMUNICATIONS, AND

LIGHTING DEVICES ARE

EXISTING TO REMAIN UNLESS

INDICATED OTHERWISE.

3. THE EXISTING SPEAKER

SYSTEM, MICROPHONE PLUG-

IN, PROJECTOR, AND OTHER

AV SYSTEMS ARE EXISTING TO

REMAIN.

SCALE: = 1'-0"3/32"

0 8 16 248

KEY # KEYNOTE DESCRIPTION

E26 PROVIDE A 30A/30AF/3/3R DISCONNECT FOR THE MOTORIZED HANGAR DOOR. MOUNT

BOTTOM OF DISCONNECT AT 48" AFF.

E27 PROVIDE 120V POWER FOR EMERGENCY EYEWASH ALARM.

E34 PROVIDE MOMENTARY REQUEST TO EXIT PUSHBUTTON FOR MAGNETIC DOOR LOCK

RELEASE.

E35 ADD CONTROL MODULE AS NECESSARY TO INTEGRATE NEW MAGNETIC DOOR LOCKS WITH

EXISTING ADVANTOR ACCESS CONTROL SYSTEM. PROVIDE ALL WIRING AND ACCESSORIES

NECESSARY FOR A COMPLETE, FUNCTIONAL SYSTEM. THE ADVANTOR SYSTEM SHALL

RELEASE ALL MAGNETIC LOCKS IN THE EVENT OF AN EMERGENCY.

E36 PROVIDE A DEDICATED 911 COPPER LINE. FED FROM ROOM 116.

E38 JUNCTION BOX ABOVE HANGAR DOOR FOR DISTRIBUTION TO DOOR MOUNTED HANGAR

DOOR CONTROLLERS/OPERATORS.

E39 PROVIDE 120V POWER FOR WATER CLOSET SENSOR FLUSH VALVE.

E40 PROVIDE 120V POWER FOR LAVATORY SENSOR FAUCET.

KEY # KEYNOTE DESCRIPTION

E17 NEW VOICE/DATA OUTLET FED FROM COMM 116.

E18 ALL OUTLETS AND EQUIPMENT IN THE FUEL CELL TANK MAINTENANCE ROOM SHALL BE

CLASS 1 DIVISION 2 RATED.

E19 WASHER AND DRYER OUTLETS SHALL BE SIZED FOR THE COMMERCIAL VERSIONS. DRYER

IS A 25A 120V/1PH CIRCUIT.

E20 DOE PANEL IS TO REMAIN FUNCTIONAL. ALL THE CIRCUITS THAT THIS PANEL FEEDS ARE TO

REMAIN FUNCTIONAL.

E21 CONNECT TO EXISTING CIRCUIT. CONTRACTOR SHALL VERIFY THAT EXISTING CIRCUIT IS

BEING FED FROM THE CIRCUIT INDICATED.

E22 NEW STOVE RECEPTACLE.

E23 EXISTING 1000KVA UTILITY TRANSFORMER.

E24 CONNECT TO EXISTING CORRIDOR RECEPTACLE CIRCUIT.

E25 RELOCATE RECEPTACLES IN COMMUNICATING SPACES TO 48" AFF. SEE E-141 FOR

HAZARDOUS CLASSIFICATION.

KEY # KEYNOTE DESCRIPTION

E11 REPLACE HANGAR BAY OUTLETS WITH CLASS 1, DIVISION 2 EXPLOSION PROOF FOR ALL

RECEPTACLES. RELOCATE OUTLETS MOUNTED LOWER THAN 48'' TO A MINIMUM HEIGHT OF

48''. REPAIR WALL LOCATIONS AFFECTED. RECONNECT TO EXISTING CIRCUITRY. TYPICAL

ALL LOCATIONS.

E12 REPLACE EXISTING OVERHEAD CORD REELS WITH CLASS 1 DIVISION 2 RATED CORD REELS.

REUSE EXISTING CIRCUITRY.

E13 REPLACE OVERHEAD DOOR IN FUEL CELL ROOM WITH MOTORIZED OVERHEAD DOOR,

SUITABLE FOR CLASS 1 DIVISION 2 SPACE. SEE ARCHITECTURAL DRAWINGS FOR MORE

DETAILS ON THE DOOR.

E14 REPLACE EXISTING PANELS WITH NEW PANELS OF EQUAL AMPERAGE AND RATING. REFER

TO E-602 FOR SIZING.

E15 ALL EXISTING DRY-TYPE TRANSFORMERS SHALL BE REPLACED IN KIND WITH NEW ENERGY

EFFICIENT DOE 2016 COMPLIANT TRANSFORMERS. REFER TO E-602 FOR SIZING.

E16 OVERHEAD DOOR MANUFACTURER PROVIDED DOOR CONTROLS. PROVIDE ALL WIRING,

CONDUIT, AND INTERCONNECTIONS NEEDED FOR A COMPLETE AND FUNCTIONAL SYSTEM.

KEY # KEYNOTE DESCRIPTION

E41 NEW OVERHEAD DOOR.

PROVIDE 120V POWER FOR DOOR

CONTROLS AND MAG LOCK.

CONDUIT SHALL BE ROUTED TIGHT

TO BOTTOM OF STRUCTURE UP TO

DISCONNECT WHERE IT SHALL RUN

DOWN WALL TO DISCONNECT. ON

SECONDARY SIDE OF DISCONNECT,

CONDUIT SHALL RUN UP WALL TO

BOTTOM OF STRUCTURE AND

CONTINUE TO HANGAR DOOR

CONTROLLER/OPERATOR.

PROVIDE 120V POWER FOR FIRE

DETECTION PANEL.

E42

E45

E46

/2

/2

A D

D E

N D

U M

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

/2

/2

:4

:1

P

M B

IM

/1

T N

A N

G R e p a ir B ld g

F u e l C e ll/

T

N A

N G

B v

E le c .r v t

E-604

100% REVISED

P A

N E

L B

O A

R D

S C

H E

D U

L E

S

R E

P A

IR

B

U

IL

D

IN

G

T

H T

E N

N E

S S

E E

A

IR

N A

T

IO

N A

L G

U A

R D

M c G

H E

E T

Y S

O N

A N

G B

A S

E A

L C

O A

T

E N

N E

S S

E E

T E

N N

E S

S E

E

A

IR

N A

T

IO

N A

L G

U A

R D

A L

C O

A

T E

N N

E S

S E

E

J O

B N

O

T E

H

T C

G

T E

H

M

A R

C H

S O

L -X

X -X

-X X

X X

W

L

-1

-D -0

X X

-X -X

X X

X G

L K

NOTES:

TOTAL LOAD: 45.67 45.82 39.92 TOTAL CONNECTED LOAD: 158.1 A

41 SPARE 20 A 1 0.00 0.00 -- -- SPACE 42

39 LTG 124, 126 20 A 1 1.13 0.00 -- -- SPACE 40

37 LTG 119, 130, 131, 132, 136 20 A 1 2.79 0.00 -- -- SPACE 38

35 -- -- -- 3.05 3.05 -- -- -- 36

33 -- -- -- 3.05 3.05 -- -- -- 34

31 EF-1 30 A 3 3.05 3.05 3 30 A EF-2 32

29 -- -- -- 0.00 15.08 -- -- -- 30

27 -- -- -- 0.00 19.83 -- -- -- 28

25 TVSS 30 A 3 0.00 18.57 3 100 A T-LB 26

23 -- -- -- 3.05 3.05 -- -- -- 24

21 -- -- -- 3.05 3.05 -- -- -- 22

19 MAU-1 25 A 3 3.05 3.05 3 25 A MAU-3 20

17 LTG 110, 118, 120, 121, 122, 123 20 A 1 0.75 3.05 -- -- -- 18

15 LTG 111, 112, 113, 114, 114A 20 A 1 0.83 3.05 -- -- -- 16

13 LTG 115 & 116 20 A 1 0.34 3.05 3 25 A MAU-2 14

11 -- -- -- 2.11 2.33 -- -- -- 12

9 -- -- -- 2.11 2.33 -- -- -- 10

7 AHU-3 20 A 3 2.11 2.33 3 15 A HP-3 8

5 -- -- -- 2.11 2.33 -- -- -- 6

3 -- -- -- 2.11 2.33 -- -- -- 4

1 AHU-2 20 A 3 2.11 2.33 3 15 A HP-2 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: SWBD VOLTAGE: 480/277 Wye

LOCATION: CORR. 112 MAINS RATING: 225A MLO MINIMUM BREAKER SCCR: MATCH EXISTING

PANELBOARD SCHEDULE HB

NOTES:

TOTAL LOAD: 149.11 145.65 141.38 TOTAL CONNECTED LOAD: 524.6 A

41 -- -- -- 62.87 42.51 -- -- -- 42

39 -- -- -- 65.11 44.54 -- -- -- 40

37 T-LE/LF 175 A 3 66.22 46.89 3 175 A T-LD 38

35 -- -- -- 1.67 5.89 -- -- -- 36

33 -- -- -- 1.67 5.89 -- -- -- 34

31 EH-3 20 A 3 1.67 5.89 3 20 A AHU-6 32

29 -- -- -- 1.86 0.00 -- -- -- 30

27 -- -- -- 1.86 0.00 -- -- -- 28

25 AHU-6 60 A 3 1.86 0.00 3 20 A SPARE 26

23 -- -- -- 4.18 2.11 -- -- -- 24

21 -- -- -- 4.18 2.11 -- -- -- 22

19 HP-6 40 A 3 4.18 2.11 3 20 A AHU-4 20

17 -- -- -- 0.00 9.15 -- -- -- 18

15 -- -- -- 0.00 9.15 -- -- -- 16

13 SPARE 15 A 3 0.00 9.15 3 45 A AIR COMPRESSOR 14

11 SPARE 20 A 1 0.00 9.15 -- -- -- 12

9 SPARE 20 A 1 0.00 9.15 -- -- -- 10

7 SPARE 20 A 1 0.00 9.15 3 45 A AIR COMPRESSOR 8

5 -- -- -- 2.00 0.00 -- -- -- 6

3 -- -- -- 2.00 0.00 -- -- -- 4

1 EXISTING LOAD - BIG ASS FANS 20 A 3 2.00 0.00 3 15 A WATER JET TABLE 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: SWBD VOLTAGE: 480/277 Wye

LOCATION: ELEC. 137 MAINS RATING: 400A MLO MINIMUM BREAKER SCCR: 65,000

PANELBOARD SCHEDULE HD

NOTES:

TOTAL LOAD: 84.40 84.02 80.77 TOTAL CONNECTED LOAD: 299.7 A

41 -- -- -- 0.00 16.00 -- -- -- 42

39 -- -- -- 0.00 16.00 -- -- -- 40

37 SURGE PROTECTION 30 A 3 0.00 16.00 3 150 A EWH-1 38

35 -- -- -- 16.00 0.42 -- -- -- 36

33 -- -- -- 16.00 0.42 -- -- -- 34

31 EWH-2 150 A 3 16.00 0.42 3 20 A BC-1b 32

29 -- -- -- 1.00 14.41 -- -- -- 30

27 -- -- -- 1.00 14.41 -- -- -- 28

25 TAIL DOOR 20 A 3 1.00 14.41 3 100 A BC-1 26

23 -- -- -- 7.21 16.00 -- -- -- 24

21 -- -- -- 7.21 16.00 -- -- -- 22

19 PAU-1 45 A 3 7.21 16.00 3 150 A EWH-3 20

17 LTG 102, 102A, 103, 103A 20 A 1 0.61 0.00 -- -- -- 18

15 LTG 104-110 20 A 1 0.88 0.00 -- -- -- 16

13 EXIT LIGHTS EGRESS 20 A 1 2.75 0.00 3 100 A COMPRESSOR 14

11 SPARE 20 A 1 0.00 0.00 1 20 A SPARE (OFF) 12

9 SPARE 20 A 1 0.00 3.00 1 20 A EH-1 (OFF) 10

7 SPARE 20 A 1 0.00 3.00 1 20 A EH-1 (OFF) 8

5 -- -- -- 7.06 2.25 -- -- -- 6

3 -- -- -- 7.06 2.25 -- -- -- 4

1 LP 100 A 3 5.45 2.25 3 20 A EH-2 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: SWBD VOLTAGE: 480/277 Wye

LOCATION: FIRE PUMP 103A MAINS RATING: 400A MCB MINIMUM BREAKER SCCR: 65,000

PANELBOARD SCHEDULE HDP1

NOTES:

TOTAL LOAD: 25.28 23.94 26.03 TOTAL CONNECTED LOAD: 208.8 A

41 -- -- -- 0.44 0.44 -- -- -- 42

39 -- -- -- 0.44 0.44 -- -- -- 40

37 EF-9 20 A 3 0.44 0.44 3 20 A EF-10 38

35 -- -- -- 1.00 0.44 -- -- -- 36

33 ZAMBONI CHARGER 20 A 2 1.00 0.44 -- -- -- 34

31 ICE MAKER 20 A 1 1.00 0.44 3 20 A EF-8 32

29 WATER HEATER 20 A 1 1.00 1.00 1 20 A RECEPT ROOM 102 30

27 RECEPT CORRIDOR 109 20 A 1 1.00 0.54 1 20 A RECEPT ROOM 102 & 102A 28

25 EF-1 20 A 1 1.00 1.00 1 20 A RECEPT ROOM 102 26

23 RECEPT MENS LOCKER ROOM 20 A 1 1.00 1.00 1 20 A CORD REEL - HANGAR 24

21 CORD REEL - HANGAR 20 A 1 1.00 1.00 1 20 A CORD REEL - HANGAR 22

19 RECEPT ROOM 108 20 A 1 1.00 1.00 1 20 A CORD REEL - HANGAR 20

17 CORD REEL - HANGAR 20 A 1 1.00 1.00 1 20 A RECEPT ROOM 102 18

15 SECURITY POWER 20 A 1 0.36 1.00 1 20 A RECEPT ROOM 102 16

13 RECEPT WOMENS RESTROOM 20 A 1 1.00 1.00 1 20 A RECEPT ROOM 102 14

11 RECEPT WOMENS RESTROOM 20 A 1 1.00 1.00 1 20 A HW RECIRC PUMP 12

9 RECEPT WOMENS RESTROOM 20 A 1 1.00 0.55 1 20 A EF-3 10

7 WATER FOUNTAIN - HANGAR 20 A 1 1.00 0.54 1 20 A RECEPT ROOM 103 & 103A 8

5 RECEPT MENS RESTROOM 20 A 1 1.00 1.00 1 20 A FOAM CONTROL PANEL 6

3 RECEPT MENS RESTROOM 20 A 1 1.00 1.00 1 20 A HVAC CONTROL PANEL 4

1 RECEPT MENS RESTROOM 20 A 1 1.00 1.00 1 20 A FACP 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: T-LA VOLTAGE: 120/208 Wye

LOCATION: FIRE PUMP 103A MAINS RATING: 225A MCB MINIMUM BREAKER SCCR: 65,000

PANELBOARD SCHEDULE LA1

NOTES:

TOTAL LOAD: 13.41 13.16 13.70 TOTAL CONNECTED LOAD: 111.8 A

29 -- -- -- 1.00 1.00 1 20 A RECEPT - RADIO TOWER 30

27 AIR DRYER 20 A 2 1.00 0.74 -- -- -- 28

25 BLUE STROBE LIGHT SYSTEM 20 A 1 0.11 0.74 2 20 A HP-1 26

23 EF-6 20 A 1 1.00 1.12 1 20 A HR-1 24

21 DAMPER 20 A 1 1.00 0.14 -- -- -- 22

19 GAS SOLENIDO VALVE 20 A 1 1.00 0.14 2 50 A AHU-1 20

17 HR-6 & HR-7 40 A 1 2.24 2.50 -- -- -- 18

15 HR-4 & HR-5 40 A 1 2.24 2.50 2 70 A EUH-2 16

13 HR-3 20 A 1 1.12 2.50 -- -- -- 14

11 HR-2 20 A 1 1.12 2.50 2 70 A EUH-1 12

9 EMERGENY EYEWASH ALARM 20 A 1 0.18 0.36 1 20 A FIRE DETECTION PANELS 10

7 DRYER ROOM 109A 25 A 1 2.30 0.50 1 15 A BC-1c 8

5 -- -- -- 1.00 0.22 1 20 A CONDENSATE PUMP 102A 6

3 -- -- -- 1.00 4.00 -- -- -- 4

1 LS-1 30 A 3 1.00 4.00 2 20 A WASHER ROOM 109A 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: LA1 VOLTAGE: 120/208 Wye

LOCATION: FIRE PUMP 103A MAINS RATING: 225A MLO MINIMUM BREAKER SCCR: 65,000

PANELBOARD SCHEDULE LA2

NOTES:

TOTAL LOAD: 18.57 19.83 15.08 TOTAL CONNECTED LOAD: 148.4 A

29 RECEPT - HANGAR FWD ZONE 20 A 1 1.00 1.00 1 20 A RECEPT - HANGAR FWD ZONE 30

27 RECEPT - HANGAR FWD ZONE 20 A 1 1.00 1.54 -- -- -- 28

25 RECEPT ROOM 113 & 114A 20 A 1 0.54 1.54 2 20 A DSA-2 26

23 RECEPT ROOM 114 20 A 1 1.00 1.00 -- -- -- 24

21 RECEPT ROOM 113 20 A 1 1.00 1.00 -- -- -- 22

19 RECEPT ROOM 113 20 A 1 0.54 0.00 3 30 A REPLACED NOSE BAY DOOR 20

17 RECEPT ROOM 116 20 A 1 1.00 0.54 1 20 A SECURITY POWER 18

15 RECEPT - HANGAR WEST 20 A 1 1.00 0.00 -- -- -- 16

13 RECEPT ROOM 113 20 A 1 1.00 0.00 -- -- -- 14

11 RECEPT ROOM 113 20 A 1 1.00 0.00 3 30 A EXISTING SURGE SUPRESSION 12

9 RECEPT ROOM 111 20 A 1 1.00 1.00 1 20 A RECEPT ROOM 115 10

7 RECEPT ROOM 111 20 A 1 1.00 1.00 1 20 A RECEPT ROOM 115 8

5 RECEPT ROOM 111 20 A 1 1.00 1.00 1 20 A POLE LIGHTS - EAST PARKING... 6

3 RECEPT ROOM 111 20 A 1 1.00 2.25 -- -- -- 4

1 RECEPT ROOM 111 20 A 1 1.00 2.25 2 30 A EWH-1 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: T-LB VOLTAGE: 120/208 Wye

LOCATION: CORR. 112 MAINS RATING: 225A MCB MINIMUM BREAKER SCCR: 65,000

PANELBOARD SCHEDULE LB1

NOTES:

TOTAL LOAD: 9.70 9.04 6.54 TOTAL CONNECTED LOAD: 70.2 A

59 (SHUNT TRIP) 20 A 1 0.00 0.00 1 20 A RECEPT RM 111 - CEILING 60

57 -- -- -- 2.50 1.00 -- -- -- 58

55 STOVE TOP 50 A 2 2.50 1.00 2 125 A PANEL DOE 56

53 SPARE 20 A 1 0.00 1.00 1 20 A RECEPT RM 115 54

51 -- -- -- 0.00 1.00 1 20 A RECEPT RM 115 52

49 -- -- -- 0.00 1.00 1 20 A RECEPT RM 115 50

47 EXISTING SURGE SUPRESSION 30 A 3 0.00 1.00 1 20 A RECEPT RM 115 48

45 SPARE 20 A 1 0.00 1.00 1 20 A RECEPT RM 115 46

43 CONDENSATE PUMPS 114A 20 A 1 0.44 1.00 1 20 A RECEPT RM 115 44

41 RECEPT RM 115 - VENDING 20 A 1 1.00 1.00 1 20 A RECEPT RM 115 42

39 RECEPT RM 115 - VENDING 20 A 1 1.00 1.00 1 20 A RECEPT RM 115 40

37 RECEPT RM 115 - VENDING 20 A 1 1.00 1.00 1 20 A RECEPT RM 115 38

35 -- -- -- 1.54 1.00 1 20 A RECEPT RM 115 36

33 DSC-2 30 A 2 1.54 0.00 1 20 A MOTORIZED DAMPER 34

31 RECEPT - HANGAR NOSE BAY 20 A 1 1.00 0.76 1 20 A EF-4 AND EF-14 32

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: LB1 VOLTAGE: 120/208 Wye

LOCATION: CORR. 112 MAINS RATING: 225A MLO MINIMUM BREAKER SCCR: 65,000

PANELBOARD SCHEDULE LB2

NOTES:

TOTAL LOAD: 12.42 12.53 10.44 TOTAL CONNECTED LOAD: 98.2 A

53 SPACE -- -- 0.00 0.00 -- -- SPACE 54

51 SPACE -- -- 0.00 0.00 -- -- SPACE 52

49 SPACE -- -- 0.00 0.00 -- -- SPACE 50

47 EMERGENCY EYEWASH ALARM 20 A 1 0.18 0.36 1 20 A SECURITY POWER 48

45 -- -- -- 0.00 0.36 1 20 A SECURITY POWER 46

43 DSA-1 30 A 2 0.00 1.00 1 20 A POLE LIGHTS N PARKING LOT 44

41 SPARE (ON) 20 A 1 0.00 1.36 1 20 A DSC-1 42

39 RECEPT RM 125 20 A 1 1.00 1.54 -- -- -- 40

37 CONDENSATE PUMPS 120, 128 20 A 1 0.44 1.54 2 20 A DSA-1 38

35 SECURITY PANEL 20 A 1 1.00 0.00 -- -- -- 36

33 RECEPT RM 101 PROJECTOR 20 A 1 1.00 0.00 -- -- -- 34

31 EXISTING LOAD - RECEPT 20 A 1 1.00 0.00 3 30 A EXISTING SURGE SUPRESSION 32

29 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A RECEPT HANGAR DROP CORD 30

27 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A RECEPT HANGAR DROP CORD 28

25 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A RECEPT RM 125 26

23 EXISTING LOAD - RECEPT 20 A 1 1.00 0.18 1 20 A POWER ROOM 124 24

21 EXISTING LOAD - RECEPT 20 A 1 1.00 0.91 1 20 A EF-5 & EF-7 22

19 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A RECEPT RM 101 20

17 EXISTING LOAD - RECEPT 20 A 1 1.00 0.36 1 20 A AUTO SENSORS ROOM 124 18

15 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A RECEPT RM 123 16

13 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A RECEPT RM 119 14

11 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A RECEPT RM 120 12

9 EXISTING LOAD - RECEPT 20 A 1 1.00 1.00 1 20 A EXISTING LOAD 10

7 EXISTING LOAD - RECEPT 20 A 1 1.00 0.72 1 20 A RECEPT RM 126 8

5 -- -- -- 0.00 1.00 1 20 A OVER HEAD DOOR 6

3 -- -- -- 0.00 0.72 1 20 A RECEPT RM 126 4

1 MAIN BREAKER 100 A 3 0.00 0.72 1 20 A RECEPT RM 126 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: T-LC VOLTAGE: 120/208 Wye

LOCATION: CORRIDOR 123 MAINS RATING: 100A MCB MINIMUM BREAKER SCCR: MATCH EXISTING

PANELBOARD SCHEDULE LC

1115 A

NOTES: 927.3 kVA

9 PANEL HDP1 3 400 A 249.2 kVA

8 SPARE 3 400 A 0.0 kVA

7 SPARE 3 400 A 0.0 kVA

6 PANEL HD 3 400 A 436.1 kVA

5 PANEL HB 3 400 A 131.4 kVA

4 SURGE SUPPRESSION 3 60 A 0.0 kVA

3 PHASE GENERATOR 3 125 A 0.0 kVA

2 T-LC 3 40 A 35.4 kVA

1 T-LA 3 150 A 75.2 kVA

CKT CIRCUIT DESCRIPTION # OF POLES TRIP RATING Load

SCCR RATING: 50,000

WIRES: 4

ENCLOSURE: NEMA 3R PHASES: 3

MOUNTING: SURFACE VOLTAGE: 480/277 Wye

LOCATION: MAINS RATING: 1200A MCB

DISTRIBUTION PANEL: SWBD

EXTERIOR

* FACP AND FOAM SYSTEM BREAKER SHALL BE PROVIDED WITH A RED LOCKING CLIP.

GENERAL NOTES:

1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. PANEL SCHEDULE INFORMATION WAS TAKEN FROM AS BUILT DRAWINGS AND ON SITE PANEL

INFORMATION. CONTRACTOR TO CONFIRM CIRCUITS ARE AVAILABLE.

/2

/2

A D

D E

N D

U M

Sheets
E-001 - ELECTRICAL GENERAL NOTES AND ABBREVIATIONS
E-002 - ELECTRICAL LEGEND
E-111 - POWER PLAN
E-604 - PANELBOARD SCHEDULES

File details come from the government source that posted it. Updated .