E-612 - ELECTRICAL SCHEDULES.pdf
PDF 330 KB Posted
- Attached to
- Entry Control Facility Federal contract opportunity
- Solicitation number
- W50S8N21B0001
- Issued by
- Department of the Army National Guard
About this file
This document provides details for a construction contract opportunity with the Department of the Army National Guard. The solicitation is for Project No. HAAW139030 to construct a new Entry Control Facility complex, including a gate house, guard booth, vehicle canopies, pavements, fencing, gates, active denial barriers, site lighting, and site drainage. Demolition of the existing Entry Control Facility is also required. The work must be completed in accordance with the contract, plans, and technical specifications. This opportunity is set aside as a total Service Disabled Veteran Owned Small Business opportunity. The NAICS code is 236220 for commercial and institutional building construction with a size standard of $39.5M average annual revenue. The project magnitude is between $1M and $5M. Attendance at the pre-bid conference and site visit is highly encouraged for those intending to submit a bid. Bids must include all items or they will be rejected. Award will be made based on the responsible bidder with the most advantageous price.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y L a n e
S u it e
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
ORIGINAL SHEET SIZE: 22" X 34"
M A
/2
/2
:5
:2
A
M B
IM
/1
N
Y A
N G
S Y
R E n tr y C o n tr o l/ N
Y A
N G
S
Y R
M
E P
F
P v .r v t
E-612
B3 - 100% SUBMITTAL
E L E
C T
R
IC
A L S
C H
E D
U L E
S
C O
N S
T R
U C
T E
N T
R Y
C O
N T
R O
L F
A C
IL
IT
Y T
H A
T T
A C
K W
IN
G
H A
N C
O C
K F
IE
L D
A N
G B
M A
T T
Y D
A L E
N
E W
Y O
R K
N E
W Y
O R
K
A
IR
N A
T
IO
N A
L G
U A
R D
H A
N C
O C
K F
IE
L D
A N
G B
N
E W
Y O
R K
J O
B N
O
D T
B
D T
B
T E
H
J
U L Y
W P
Q F
X X
-X -X
X X
SHEET NOTES:
NOTES:
1. ALL CONDUCTORS FOR MECHANICAL AND PLUMBING EQUIPMENT SHALL BE COPPER. THE USE OF ALUMINUM CONDUCTORS TO FEED THIS
EQUIPMENT IS NOT PERMITTED.
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
UNIT VOLTAGE
NUMBER
OF
POLES KVA FLA HP STARTER DISCONNECT FEEDER SIZE PANEL CIRCUIT NOTES
AHU-1 120 V 1 0.80 kVA 6.70 A 0.33 BY DIVISION 23 MRS 2#12 & 1#12(G) IN 3/4" C. NP21B 14 1
CU-1 208 V 2 2.70 kVA 13.00 A 0.13 BY DIVISION 23 30/NF/2/4X 2#10 & 1#10(G) IN 3/4" C. NP21B 13,15 1
EF-1 120 V 1 0.37 kVA 3.10 A 0.17 BY DIVISION 23 MRS 2#12 & 1#12(G) IN 3/4" C. NP21B 16 1
EUH-1 208 V 2 3.02 kVA 14.50 A N/A - FWE 2#10 & 1#10(G) IN 3/4" C. NP21B 17,19 1
EUH-2 120 V 1 1.50 kVA 12.50 A N/A - FWE 2#12 & 1#12(G) IN 3/4" C. NP21B 18 1
EWH-1 120 V 1 1.65 kVA 13.75 A N/A - MRS 2#10 & 1#10(G) IN 3/4" C. NP21B 20 1
IRH-1 120 V 1 0.08 kVA 0.70 A N/A - NEMA 5-20R 2#12 & 1#12(G) IN 3/4" C. NP21B 12 1
IRH-2 120 V 1 0.08 kVA 0.70 A N/A - NEMA 5-20R 2#12 & 1#12(G) IN 3/4" C. NP21B 12 1
PTAC-1 208 V 2 3.18 kVA 15.30 A N/A BY DIVISION 23 MRS 2#12 & 1#12(G) IN 3/4" C. NP1 3,5 1
NOTES:
TOTAL EST. DESIGN CURRENT: 13 A
TOTAL LOAD: 1.10 1.95 1.59 TOTAL CONNECTED CURRENT: 13 A
11 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 12
9 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 10
7 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 8
-- 5 -- -- -- 1.59 0.00 1 20 A SPARE 6
3 PTAC-1 20 A 2 1.59 0.36 1 20 A RECP - GENERAL PURPOSE 4
1 RECP - GUARD BOOTH A-105 20 A 1 1.08 0.02 1 20 A LTG GUARD BOOTH A-105 2
CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT
CONNECTED LOAD KVA
ENCLOSURE: NEMA 1 WIRES: 4
MOUNTING: SURFACE PHASES: 3
SUPPLY FROM: NP21A VOLTAGE: 208Y/120
LOCATION: GUARD BOOTH A-105 MAINS RATING: 100A MCB MINIMUM BREAKER SCCR: 10,000
PANELBOARD SCHEDULE: NP1
NOTES:
TOTAL EST. DESIGN CURRENT: 28 A
TOTAL LOAD: 2.81 3.07 TOTAL CONNECTED CURRENT: 28 A
-- 17 SPACE -- -- 0.00 0.00 -- -- SPACE 18 --
-- 15 SPACE -- -- 0.00 0.00 -- -- SPACE 16 --
13 COMPUTERS RM 100,101 20 A 1 0.36 0.00 -- -- SPACE 14 --
11 RECP - POLE MOUNT CAMERAS 20 A 1 0.36 0.00 -- -- SPACE 12 --
9 SECURITY CAMERA MONITORS 20 A 1 1.02 0.36 1 20 A RECP - POLE MOUNT CAMERAS 10
7 TELECOM CABINET RM 101 20 A 1 1.92 0.36 1 20 A TELECOM RECP RM 101 8
5 BASE ANTENNA - RM 100 20 A 1 0.25 0.54 1 20 A RECP - POLE MOUNT CAMERAS 6
3 DURESS ALARM - RM 100 20 A 1 0.18 0.25 1 20 A LANE SIGNAL CNTRL PNL - RM 100 4
1 LANE TRAFFIC SIGNALS 20 A 1 0.03 0.25 1 20 A AVB CNTRL SYSTM - RM 100 2
CKT CIRCUIT DESCRIPTION TRIP POLE A B POLE TRIP CIRCUIT DESCRIPTION CKT
CONNECTED LOAD KVA
ENCLOSURE: NEMA 1 WIRES: 3
MOUNTING: SURFACE PHASES: 1
SUPPLY FROM: UPS VOLTAGE: 208/120
LOCATION: ELEC / MECH ROOM 104 MAINS RATING: 50A MCB MINIMUM BREAKER SCCR: 10,000
PANELBOARD SCHEDULE: UP2A
BUILDING EXTERIOR
RECP - SPECIFIC APPLIANCE OR LOAD 2.10 kVA 2.10 kVA Total Est. Design Current: 251 A
RECP - GENERAL PURPOSE 8.58 kVA 8.58 kVA Total Est. Demand Current: 251 A
MISC 56.24 kVA 56.24 kVA Total Conn. Current: 246 A
LTG 8.23 kVA 10.28 kVA Total Est. Demand Load: 90.53 kVA
HVAC 13.38 kVA 13.38 kVA Total Conn. Load: 88.48 kVA
Load Classification Connected Load Estimated Demand Panel Totals
NOTES: *PROVIDE CIRCUIT BREAKER WITH 30mA GFI PROTECTION.
TOTAL LOAD: 29.13 28.92 30.44
-- 53 SPACE -- -- 0.00 0.00 -- -- -- 54 --
-- 51 SPACE -- -- 0.00 0.00 -- -- -- 52 --
49 CANOPY LIGHTING 20 A 1 0.79 0.00 3 30 A SURGE PROTECTION DEVICE 50
47 CANOPY LIGHTING 20 A 1 0.59 0.00 -- -- SPACE 48 --
-- 45 -- -- -- 0.98 0.00 -- -- SPACE 46 --
43 SITE LIGHTING 20 A 2 0.98 0.00 -- -- SPACE 44 --
-- 41 -- -- -- 0.56 0.00 -- -- SPACE 42 --
39 SITE LIGHTING 20 A 2 0.56 0.00 -- -- SPACE 40 --
-- 37 -- -- -- 0.98 0.00 -- -- SPACE 38 --
35 SITE LIGHTING (ROUTE THRU INVERTER) 20 A 2 0.98 0.00 1 20 A SPARE 36
-- 33 -- -- -- 0.56 0.00 1 20 A SPARE 34
31 SITE LIGHTING (ROUTE THRU INVERTER) 20 A 2 0.56 0.00 1 20 A SPARE 32
-- 29 -- -- -- 3.13 0.00 1 20 A SPARE 30
-- 27 -- -- -- 3.13 0.00 1 20 A SPARE 28
25 PUMP LIFT STATION 45 A 3 3.13 0.00 1 20 A SPARE 26
-- 23 -- -- -- 3.07 0.00 1 20 A SPARE 24
21 8 kVA UPS 50 A 2 2.81 0.50 1 20 A AVB WRONG WAY DETECTION 22
-- 19 -- -- -- 2.08 0.50 1 20 A AVB WRONG WAY DETECTION 20
17 *AVB-2 HEAT TRACE 30 A 2 2.08 0.83 -- -- -- 18 --
-- 15 -- -- -- 2.08 0.83 2 20 A MOTOR GATE OPERATOR (BID OPTION 2) 16
13 *AVB-1 HEAT TRACE 30 A 2 2.08 0.00 1 20 A SPARE 14
-- 11 -- -- -- 4.20 9.22 -- -- -- 12 --
-- 9 -- -- -- 4.20 7.14 -- -- -- 10 --
7 AVB-2 POWER 60 A 3 4.20 8.56 3 200 A PANEL NP21B 8
-- 5 -- -- -- 4.20 1.59 -- -- -- 6 --
-- 3 -- -- -- 4.20 1.95 -- -- -- 4 --
1 AVB-1 POWER 60 A 3 4.20 1.10 3 100 A PANEL NP1 2
CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT
CONNECTED LOAD KVA
ENCLOSURE: NEMA 4X WIRES: 4
MOUNTING: SURFACE PHASES: 3
SUPPLY FROM: VOLTAGE: 208Y/120
LOCATION: MAINS RATING: 400A MLO MINIMUM BREAKER SCCR: 22,000
PANELBOARD SCHEDULE: NP21A
UTILITY
NOTES: *PROVIDE CIRCUIT BREAKER WITH 30mA GFI PROTECTION.
TOTAL EST. DESIGN CURRENT: 80 A
TOTAL LOAD: 8.56 7.14 9.22 TOTAL CONNECTED CURRENT: 69 A
41 SPARE 20 A 1 0.00 0.00 -- -- SPACE 42 --
39 SPARE 20 A 1 0.00 0.00 -- -- SPACE 40 --
37 SPARE 20 A 1 0.00 0.00 -- -- SPACE 38 --
35 SPARE 20 A 1 0.00 0.00 -- -- SPACE 36 --
33 SPARE 20 A 1 0.00 0.00 -- -- SPACE 34 --
31 SPARE 20 A 1 0.00 0.00 -- -- SPACE 32 --
29 SPARE 20 A 1 0.00 0.00 -- -- SPACE 30 --
27 SPARE 20 A 1 0.00 0.00 -- -- SPACE 28 --
-- 25 -- -- -- 1.15 0.00 1 20 A SPARE 26
23 *GUTTER HEATER ELEMENT 20 A 2 1.15 1.02 -- -- -- 24 --
21 *GUTTER HEATER ELEMENT 20 A 1 1.04 1.02 2 20 A *GUTTER HEATER ELEMENT 22
-- 19 -- -- -- 1.51 1.65 1 20 A EWH-1 20
17 EUH-1 25 A 2 1.51 1.50 1 20 A EUH-2 18
-- 15 -- -- -- 1.35 0.37 1 20 A EF-1 16
13 CU-1 25 A 2 1.35 0.80 1 20 A AHU-1 14
-- 11 -- -- -- 2.08 0.16 1 20 A IRH-1, IRH-2 12
9 4 kVA LIGHITNG INVERTER 30 A 2 2.08 0.40 1 20 A SIGN LIGHTING 10
7 RECP - ELEC / MECH ROOM 104 20 A 1 0.54 0.28 1 20 A LIGHTING - GATE HOUSE 8
5 WP RECP & RECP RM 1O1, 1O3 20 A 1 0.90 0.90 1 20 A RECP - RM 100,101,102 6
3 DOM WTR SPPLY HEATER RCPT 20 A 1 0.18 0.70 1 20 A RECP - REFRIGERATOR 4
1 DOM WTR SPPLY HEATER RCPT 20 A 1 0.18 1.10 1 20 A RECP - MICROWAVE 2
CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT
CONNECTED LOAD KVA
ENCLOSURE: NEMA 4X WIRES: 4
MOUNTING: SURFACE PHASES: 3
SUPPLY FROM: NP21A VOLTAGE: 208Y/120
LOCATION: MAINS RATING: 200A MCB MINIMUM BREAKER SCCR: 22,000
PANELBOARD SCHEDULE: NP21B
BUILDING EXTERIOR
M A
R K
D E
S C
R
IP
T I O
N D
A T
E
A
D D
E N
D U
M
R E
V
IS
E D
D R
A W
I N G
S /2
/2