A3 Covered Parking Drawings 20240702 (Unlocked PDF).pdf
PDF 18 MB Posted
- Solicitation number
- W50S8K26QA002
About this file
This document is a comprehensive construction drawing set for a covered parking canopy structure at Jefferson Barracks Air National Guard, Building 41, located at 41 May Road, St. Louis, Missouri 63125. The project involves new construction of an exterior parking canopy covering approximately 6,100 square feet, designed to accommodate 10 parking stalls per canopy structure with provisions for photovoltaic (PV) solar panels.
The structural design features steel framing with HSS (Hollow Structural Section) columns and beams, including a roof framing plan with 1½" wide rib galvanized roof decking attached to the structure. Foundation design consists of straight-shaft drilled piers on highly weathered limestone capable of supporting 10 ksf end bearing, with concrete footings extending to elevation 453'-3". The electrical system includes a 122.4 kW grid-interactive photovoltaic system with monocrystalline or thin-film solar cells mounted on the canopy structure, four 25 kW three-phase string inverters (CPS SCA 25KTL-DO/US-208), and connections to Building 41's service entrance at 208V-3 phase. The project incorporates four alternates: (1) not used, (2) waterproof duplex receptacles at columns, (3) deletion of PV panel system in favor of standing seam metal roof, and (4) addition of gutters and downspouts. Design compliance requires adherence to the Department of Defense Building Code 2021 (IBC 2021), NFPA standards, and 2010 ADA Standards for Accessible Design. The drawing set is prepared at 100% construction document level dated July 2, 2024, with design by ACI Boland Architects, structural by Bob D. Campbell & Co., civil by BHC, and MEP by BranchPattern.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.N.O. UNLESS NOTED OTHERWISE
T. TREAD
STAINLESS STEELST.STL.
ST. STAINED
SCREWSCR.
SYSTEMSYS.
S.C. SEALED CONCRETE
SHG. SHEATHING
R.O. ROUGH OPENING
RE.
RB. RESILIENT BASE
REFER TO
PLASTIC LAMINATEPLAM.
OVERHEAD DOORO.H.D.
FV. FIELD VERIFY
LB. POUND
ELEV. ELEVATOR
CHANNEL
ANGLE
ACOUSTIC CEILING TILE/PANELACT
AFF ABOVE FINISH FLOOR
W.W. WINDOW WALL
LOC. LOCATION
V. VENT
RADIUS
REGISTER
REQUIRED
REVISION
RISER, RISERS
ROOF DRAIN
ROOFING
ROOM
ROUGH
ROUND
SCHEDULE
SECTION
SELECT
SHEET
SIDING
SIMILAR
SLIDING
SMOOTH
SPECIFICATION
SQUARE
STANDARD
STRUCTURE
SUSPENDED
SWITCHBOARD
TOP OF CURB
TOP OF
TOP OF STEEL DECK
TYPICAL
VERTICAL
VERTICAL GRAIN
VESTIBULE
VINYL COMPOSITION TILE
VITREOUS CLAY PIPE
WELDED WIRE MESH
WATER CLOSET
WATER HEATER
WIDE FLANGE
WITH
WITHOUT
WOOD
WINDOW
GAUGE
GALVANIZED STEEL
GLASS / GLAZING
GRADE
GRAM
GRILLE
GRID
GROUND
GYPSUM
GYPSUM BOARD
HAND RAIL
HARDENER
HARDWARE
HARDWOOD
HEATER
HEIGHT
HIGH POINT
HOLLOW METAL
HORIZONTAL
HOSE BIB
HOT WATER
INCH / INCHES
INSIDE DIAMETER
INSULATION
INTERIOR
INVERT
JANITOR
JOINT
JOIST
KICK PLATE
LAMINATED
LANDING
LATH
LAVATORY
LENGTH
LIGHT
LIGHT WEIGHT CONCRETE
LOUVER
MASONRY OPENING
MATERIAL
MANUFACTURER
MAXIMUM
MECHANICAL
METAL
METAL LATH
METER
MINIMUM
MOLDING
MULLION
NATURAL GRADE
NOMINAL
NOT IN CONTRACT
NOT TO SCALE
NUMBER
OBSCURE
ON CENTER
OPENING
OVERALL
OUTSIDE DIAMETER
OVERFLOW SCUPPER
OVERFLOW DRAIN
PAINTED
PAGE
PAIR
PANEL
PARTITION
PENNY
PLATE
PLUMBING
PLYWOOD
POINT
POUNDS PER SQ. IN.
POUNDS PER SQ. FT.
PRECAST
PROPERTY LINE
WDW.
WD.
W/O
W/ W.F.
W.H.
W.C.
W.W.M.
VCP
V.C.T.
VEST.
V.G.
VERT.
TYP.
T.S.D.
T.O.
T.C.
SW.BD.
SUSP.
STRUC.
S.S. /
STD.
SQ.
SPL.SPEC.
SM.
SLDG.
SIM.
SDG.
SHT.
SEL.
SECT.
SCHED.
RND.
RGH.
RM.
RF'G.
R.D.
R.
REV.
REQ'D.
REG.
RAD.
P.L.
P.C.
P.S.F.
P.S.I.
PT.
PLYWD.
PLBG.
PL
d
PTN.
PNL.
PR.
PG.
PTD.
O.F.D.
O.F.S.
O.D.
O.A.
OPN'G.
O.C.
OBS.
NO. / #
N.T.S.
N.I.C.
NOM.
N.G.
MULL.
MLDG.
MIN.
M.
M.L.
MTL.
MECH.
MAX.
MFR.
MAT'L..
M.O.
LVR.
L.W.C.
LT.
LG.
LAV.
LTH.
LDG.
LAM.
K.P.
JST.
JT.
JAN.
INV.
INT.
INSUL.
I.D.
IN.
H.W.
H.B.
HORIZ.
H.M.
H.P.
HT.
HTR.
HDWD.
HDW.
HDN.
H.R.
GWB/G.B.
GYP.
GND.
GRD.
GRL.
G.
GD.
GL.
G.S.
GA.
CONSTRUCTION JOINT
BASEMENT
BEAM
BENCHMARK
BLOCKING
BOARD
BOTTOM OF
BUILDING
CABINET
CAST IN PLACE
CATCH BASIN
CEILING
CEMENT/CEMENTITIOUS
CENTIGRAM
CENTIMETER
CENTER LINE
CERAMIC
CERAMIC TILE
CHANNEL
CLEAR
CLEAN OUT
CLOSET
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTROL JOINT
CONTINUOUS
CONTRACTOR
CORRUGATED
COUNTER
COUNTERSUNK
CONCRETE MASONRY UNIT
DAMP PROOFING
DECIBEL
DIAGONAL
DIAMETER
DIMENSION
DISPENSER
DOWEL
DOWN
DOWNSPOUT
DRAWING
EACH
ELECTRIC
ELECTRIC WATER COOLER
ELEVATION
EQUAL
EQUIPMENT
EXHAUST
EXPANSION
EXPANSION JOINT
EXISTING
EXTERIOR
FEET / FOOT
FINISH
FIXTURE
FLASHING
FLOOR
FLOOR DRAIN
FLUORESCENT
FOOTING
FOUNDATION
FRAME
FIRE HOSE CAB.F.H.C.
FR.
FND.
FTG.
FLOR.
F.D.
FLR.
FL.
FIXT.
FIN.
FT.
EXT.
EXIST.
E.J.
EXPAN.
EXH.
EQUIP.
EQ.
EL.
E.W.C.
ELEC
EA.
DWG.
D.S.
DN.
DWL.
DISP.
DIM.
DIAM.
DIAG.
DB.
D.P.
C.M.U.
CTSK.
CTR.
COR'G.
CONTR.
CONT.
C.J.
CONST.
CONN.
CONC.
COL.
CLOS.
C.O.
CLR.
CHAN.
C.T.
CER.
CL.
CM
CG.
CEM.
CLG.
C.B.
C.I.P.
CAB'T.
BLDG.
B.O.
BD.
BLKG.
B.M.
BM.
BSMT.
ACOUSTIC/ACOUSTICAL
ADDENDUM
ADDITION
AGGREGATE BASE COURSE
AGGREGATE
AIR CONDITIONING
ALUMINUM
ALTERNATE
ANCHOR BOLT
AND
ARCHITECT
ASPHALT
AT@
ASP.
ARCH.
A.B.
ALT.
AL.
A/C
AGG.
ABC
ADD'N.
ADD.
AC.
T.G. TEMPERED GLASS
LOC. LOCATION
T.W. TEACHERS WARDROBE
MB. MARKER BOARD
ABBREVIATIONS
A101
SIM
A101
SIM
A101
SIM
DETAIL BUBBLE
EXAMPLES
ROOM NAME AND
NUMBER SYMBOL
DOOR TAG WINDOW
TAG
WALL
TYPE
SYMBOL
SPOT
ELEVATION
REVISION
SYMBOL
A101
SIM
DETAIL SYMBOL BUILDING SECTION SYMBOL SECTIONAL DETAIL SYMBOL
A101
1 Ref
R e f
1 Ref
R e f
EXTERIOR ELEVATION SYMBOL INTERIOR ELEVATION
SYMBOL
NORTH ARROW SYMBOL DETAIL TITLE SYMBOL
A
VIEW NAME
1 1/2" = 1'-0"
KEYNOTE SYMBOLSSTANDARD VIEW TITLE
E-0
EQUIPMENT
TAG
Room Name
POWER ACTUATOR PROX READER
AA1t
WALL SECTION SYMBOL
1 Ref
A101
SIM
1 Ref
A101
SIM
1 Ref
A101
SIM
A101
SIM
A1
VIEW NAME
1/8" = 1'-0"
REVISION CLOUD
EXAMPLE
PROX READER
W/ POWER
ACTUATOR
MAGNETIC
DOOR HOLD
D H
TA-0
TOILET
ACCESSORY
TAG
NORTH
CODE SUMMARY
PROJECT CONSTRUCTION PURPOSE:
NEW CONSTRUCTION OF EXTERIOR PARKING CANOPY
OWNER:
JEFFERSON BARRACKS / AIR NATIONAL GUARD
DESIGNER:
ACI BOLAND ARCHITECTS
17107 CHESTERFIELD AIRPORT RD. SUITE 110
CHESTERFIELD, MO 63005
PHONE: (314) 991-9993
LOCAL AUTHORITY:
JEFFERSON BARRACKS / AIR NATIONAL GUARD
CODE INFORMATION:
DEPARTMENT OF DEFENSE BUILDING CODE 2021 (IBC 2021 WITH AMENDMENTS)
DEPARTMENT OF DEFENSE PLUMBING CODE 2018 (IPC 2018 WITH AMENDMENTS)
DEPARTMENT OF DEFENSE MECHANICAL CODE 2018 (IMC 2018 WITH AMENDMENTS)
DEPARTMENT OF DEFENSE ELECTRICAL CODE 2017 (NFPA 70, 2017)
DEPARTMENT OF DEFENSE ENERGY CODE 2021 (IECC 2021)
DEPARTMENT OF DEFENSE FIRE CODE 2021 (NFPA 1, 2021)
DEPARTMENT OF DEFENSE LIFE SAFETY CODE (NFPA 101, 2021)
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN / AMERICANS WITH DISABILITIES ACT OF 1990
2009 ICC/ANSI A117.1
NOTE: IF CODE REQUIREMENTS OVERLAP, THE MOST STRINGENT SHALL APPLY.
TYPE OF CONSTRUCTION: II-B
OCCUPANCY GROUP: U - UTILITY & MISCELLANEOUS (NON-ENCLOSED PARKING CANOPY)
OCCUPANT LOAD: N/A (NON-ENCLOSED PARKING CANOPY)
AREA OF CONSTRUCTION:
+/- 6,100 SF
REQUIRED FIRE RESISTANCE RATINGS (IN HOURS)
PER NFPA 101 A.8.2.1.2:
EXTERIOR BEARING WALLS 0 HR
INTERIOR BEARING WALLS 0 HR
PRIMARY STRUCTURAL FRAME 0 HR
FLOOR CONSTRUCTION 0 HR
ROOF CONSTRUCTION 0 HR
INTERIOR NON-BEARING WALLS 0 HR
LIST OF ALTERNATES
ALTERNATE 1: (NOT USED)
ALTERNATE 2: PROVIDE WATERPROOF DUPLEX RECEPTACLE AT EACH COLUMN, TYP.; SEE
ELECTRICAL
ALTERNATE 3: DELETE PV PANEL SYSTEM AND ADD STANDING SEAM METAL ROOF
ALTERNATE 4: ADD GUTTER AND DOWNSPOUTS
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
P R
O J E
C T
N A
M E
TM
TM
07/02/2024
A000
COVER SHEET
100% CD
KM
J E
F F
E R
S O
N B
A R
R A
C K
S C
O V
E R
E D
P A
R K
IN
G
B
U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
5SHEET INDEX
SHEET NUMBER SHEET NAME
CIVIL
C1.0 SITE PLAN
C2.0 CONSTRUCTION DETAILS
ARCHITECTURE
A110 OVERALL ARCHITECTURAL SITE PLAN
A120 ENLARGED ARCHITECTURAL SITE PLAN
A510 OVERALL EXTERIOR ELEVATIONS
A600 BUILDING SECTIONS
STRUCTURAL
S001 STRUCTURAL GENERAL NOTES
S100 FOUNDATION PLAN
S101 ROOF FRAMING PLAN
S300 FRAMING DETAILS
ELECTRICAL
E001 ELECTRICAL SYMBOLS LEGEND
E101 OVERALL ELECTRICAL SITE PLAN
E201 ENLARGED ELECTRICAL PLANS
1/4" = 1'-0"
SYMBOLS
LOCATION PLAN
JB ANG COVERED PARKING
BUILDING 41
41 MAY ROAD
ST. LOUIS, MO 63125
P R O J E C T T E A M
MEP
BRANCHPATTERN
PHONE 816.531.2121
1508 Grand Boulevard Kansas City, MO 64108
ARCHITECT
ACI BOLAND, INC.
17107 Chesterfield Airport Road, Ste 110 Chesterfield, MO 63005
314.991.9993PHONE
STRUCTURAL
BOB D. CAMPBELL & CO.
PHONE 816.531.4144
4338 Belleview Ave.
Kansas City, MO 64111
CIVIL
BHC
PHONE 913.663.1900
7101 College Blvd., Ste. 400 Overland Park, KS 66210
NORTH
PROJECT AREA
Description Date
D ou gl as
B L ov el an d
A rc hi te ct M
O A
-2
77/
2/
2 45
451.67 TE
451.85 TE
451.06 TE
452.09 TE
448.05 TP
447.87 TP
452.53 TP452.66 TP
450.95 TE
451.24 TE
451.84 TE
452.36 TE
449.31 TP
450.04 TP
.1
6' 9.
110.00'
9.
30.0020.00 40.00
9.47'14.16'
5.
14.16' 9.47'
5.
.0
.0
.0
.0
8.50 8.50 8.50 8.50
449.60 TP
449.98 TP
450.37 TP
450.68 TP
450.99 TP
451.15 TP
450.70 TP
450.34 TP 449.90 TP 449.22 TP 448.73 TP
448.24 TP
448.39 TP
.0
.0
.1
6'
.1
6'
110.00'
20.00
9.00
.9
61.53
63.09
.6
2.
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
PR
O
JE
C
T N
AM
E:
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
Description Date
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
N
GRADING LEGEND
EXISTING GRADE MAJOR CONTOURS
EXISTING GRADE MINOR CONTOURS 982
DETAILED GRADING LEGEND
TOP OF EXISTING PAVEMENT ELEVATION0000.00 TP
TOP ELEVATION OF EXISTING STRUCTURE0000.00 TE
01 PROPOSED CANOPY; REFER TO STRUCTURAL PLANS.
02 PROPOSED 36" DIA. COLUMNS, TYP.; REFER TO STRUCTURAL PLANS.
03 EXISTING FENCE, DO NOT DISTURB.
04 LEAD FREE, WATER-BORNE EMULSION BASED TRAFFIC PAINT FOR PARKING LOT STRIPING
(WHITE ON ASPHALT & YELLOW ON CONCRETE).
CONSTRUCTION NOTES
SITE LEGEND
EXISTING ASPHALT PAVEMENT
EXISTING BUILDING
EXISTING PCC PAVEMENT
EXISTING
BUILDING
PROPOSED CANOPY
1. All existing parking striping under proposed canopies are to be removed and repainted as shown.
2. Project Survey was created using meters & converted into feet with a factor of 1 meter = 3.28084 feet
3. All utilities are to remain & not to be disturbed.
4. All striping locations were estimated using Google Earth, Contractor to repaint lines if needed.
5. All existing stalls are 10' x 20'
SITE NOTES
EXISTING
BUILDING
POINT OF SCALING TO
CONVERT FROM METERS
TO FEET
03 000
SEE CONSTRUCTION DETAILS - SHEETS C2.0
017 STEEL/CONCRETE BOLLARD; CONTRACTOR TO COORDINATE WITH OWNER ON LOCATION.
023 CONCRETE WHEEL STOP
DETAILS
JE
FF
ER
SO
N B
AR
R
AC
KS
C O
VE
R
ED
P
AR
KI
N G
BU
IL
D
IN
G
M
AY
R
O
AD
ST
. L
O U
IS
, M
O
C1.0
SITE PLAN
DM
DM
07/02/2024
100% CD
AKL
040220
07/12/2024
NOTE:
1. SUBMIT ALTERNATIVE WHEELSTOP
DESIGNS FOR APPROVAL BY
ARCHITECT/ ENGINEER
1'-0" 2'-0" 1'-0" 2'-0" 1'-0" 7'-0"
8" Min.
6 12" Min.
(2) #3 BARS
34" ∅ x 30" SMOOTH STEEL BAR DRIVEN
INTO 1" ∅ HOLE DRILLED THRU PAVEMENT
(TYPICAL OF 3 AT EACH WHEELSTOP)
Not to Scale Concrete Wheelstop023
FRONT ELEVATION END SECTION
3' -0
4'
-0
15"
6" DIAMETER STEEL PIPE
PAINTED YELLOW FILLED
W/CONCRETE
APPLY EXPANSION JOINT MATERIAL
(FOR BOLLARDS IN HEAVY DUTY
CONCRETE AREAS ONLY)
CONCRETE
BACKFILL
Not to Scale Steel/Concrete Bollard017
3" M
IN
MOUND CONCRETE
TO FORM CAP
1" M
IN
FINISH
GRADE
GENERAL NOTES:
1. CONSTRUCTED OF STEEL NOT LESS THAN 4" IN DIAMETER AND
CONCRETE FILLED.
2. SET NOT LESS THAN 3' DEEP IN A CONCRETE FOOTING OF NOT LESS
THAN A 15" DIAMETER.
3. SET WITH THE TOP OF THE POST NOT LESS THAN 4' ABOVE GROUND.
4. LOCATED NOT LESS THAN 3' FROM THE PROTECTED OBJECT.
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
PR
O
JE
C
T N
AM
E:
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
Description Date
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
C2.0
CONSTRUCTION
DETAILS
DM
DM
07/02/2024
100% CD
AKL
040220
JE
FF
ER
SO
N B
AR
R
AC
KS
C O
VE
R
ED
P
AR
KI
N G
BU
IL
D
IN
G
M
AY
R
O
AD
ST
. L
O U
IS
, M
O
07/12/2024
A120
B
B
C
C
G
G
F
F
E
E
D
D
A
A
'-8
'-0
'-0
'-0
'-0
'-0
23'-0"
23'-0"
23'-0"
23'-0"
23'-0"
6'-0 1/4"
A120
EXTENTS OF NEW CANOPY
EXTENTS OF NEW CANOPY
EXISTING PARKING TO REMAIN
A120
Sim
A120
Sim
BUILDING 41
'-5
/4 www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
P R
O J E
C T
N A
M E
TM
TM
07/02/2024
A110
OVERALL
ARCHITECTURAL SITE
PLAN
100% CD
KM
J E
F F
E R
S O
N B
A R
R A
C K
S C
O V
E R
E D
P A
R K
IN
G
B
U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
3/32" = 1'-0"1 SITE PLAN
NORTH
Description Date
D ou gl as
B L ov el an d
A rc hi te ct M
O A
-2
77/
2/
A600
1/ A510
A
3 8654
/4
1'-11 1/4" 23'-0" 23'-0" 23'-0" 23'-0" 23'-0" 1'-11 1/4"
118'-10 1/2"
/2
9" +/-
/2
1'-11 1/4"
EXISTING
POWER POLE
TO REMAIN;
PROTECT
DURING
CONSTRUCTION
EXISTING
POWER POLE
TO REMAIN;
PROTECT
DURING
CONSTRUCTION
NOTE: VERIFY OVERALL
ROOF DIMENSIONS WITH
FINAL SOLAR PANEL
INSTALL DIMENSIONS
PV PANEL,
TYP.; SEE
ELECTRICAL
ALTERNATE 3 :
DELETE PV
PANEL SYSTEM
AND ADD
STANDING SEAM
METAL ROOF
ALTERNATE 4:
ADD GUTTER
AND
DOWNSPOUTS
NOTE: SOLAR PANEL
INSTALLER TO PROVIDE
AND INSTALL
MANUFACTURER-
RECOMMENDED
MOUNTING HARDWARE.
FOUR SYMMETRICAL
MOUNTING POINTS PER
PANEL, MIN.
A600
1/ A510
A
3 8654
/4
1'-11 1/4" 23'-0" 23'-0" 23'-0" 23'-0" 23'-0" 1'-11 1/4"
118'-10 1/2"
/2
9" +/-
/2
T Y
P
TYP.
3'-0"
TYP.
10'-0"
RELOCATE
WHEEL STOP
FOR NEW
PARKING LINE
LAYOUT, TYP.
EXTENT OF
CANOPY
ABOVE
ALTERNATE 2:
PROVIDE
WATERPROOF
DUPLEX
RECEPTACLE
AT SECOND
AND FIFTH
COLUMNS,
TYP.; SEE
ELECTRICAL
EXISTING
POWER POLE
TO REMAIN;
PROTECT
DURING
CONSTRUCTION
EXISTING
POWER POLE
TO REMAIN;
PROTECT
DURING
CONSTRUCTION
REMOVE FORMER
STRIPING IN
AREAS OF NEW
CANOPIES; PAINT
NEW STRIPING
AS SHOWN; TYP.
SAW CUT
EXISTING
ASPHALT AND
EXCAVATE FOR
NEW FOOTINGS
AS REQUIRED
TO
ACCOMMODATE
NEW WORK;
TYP.
NOTE: INCLUDE COSTS TO
SAW CUT, EXCAVATE, AND
PATCH AS REQUIRED TO
ACCOMMODATE NEW
ELECTRICAL WORK.
10 PARKING STALLS PER
CANOPY, TYP.
ALTERNATE 4:
ADD GUTTER
AND
DOWNSPOUTS
PAINT EXPOSED
CONCRETE
FOOTINGS
SAFETY
YELLOW, TYP.
EXPOSED
STEEL TO BE
AESS3, PRIMED
AND PAINTED,
TYP.
A600
A
3 8654
TYP.
11'-6"
TYP.
11'-6"
MOUNT LED LIGHT
TO PURLIN, TYP.;
SEE ELECTRICAL
EXPOSED
STEEL TO BE
AESS3, PRIMED
AND PAINTED,
TYP.
GENERAL PLAN NOTES
1. WORK SHALL BE PERFORMED IN ACCORDANCE WITH ADA REQUIREMENTS AND
APPLICABLE LOCAL, STATE, AND FEDERAL BUILDING CODES AND REGULATIONS.
2. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING NECESSARY BUILDING PERMITS.
3. THE GENERAL CONTRACTOR AND SUBCONTRACTORS SHALL FIELD VERIFY EXISTING
CONDITIONS AND NOTIFY THE ARCHITECT OF ANY INCONSISTENCIES OR DISCREPANCIES
WITH THE PROJECT DOCUMENTS. ACCESS TO THE SITE AND/OR SPACE UNDER
CONSTRUCTION DURING BIDDING AND CONSTRUCTION SHALL BE COORDINATED WITH THE
OWNER.
4. UPON VERIFICATION OF THE EXISTING CONDITIONS, THE CONTRACTOR SHALL DETERMINE
AND RECOMMEND THE BEST ACTION TO MINIMIZE THE EXTENT OF REMOVAL WORK FOR
INSTALLATION OF NEW WORK.
5. IF MATERIAL SUSPECTED OF CONTAINING HAZARDOUS MATERIALS ARE ENCOUNTERED,
DO NOT DISTURB. IMMEDIATELY NOTIFY ARCHITECT AND OWNER. OWNER SHALL
COORDINATE WITH CONTRACTOR ON THE REMOVAL OF SUCH ITEMS. WORK MAY PROCEED
AFTER HAZARDOUS MATERIAL HAS BEEN REMOVED.
6. CONTRACTOR TO PROVIDE ALL REQUIRED LABOR, MATERIAL, AND EQUIPMENT
NECESSARY TO MEET AND COMPLETE THE REQUIREMENTS OF THE NEW CONSTRUCTION.
7. EXISTING CONSTRUCTION TO REMAIN SHALL BE PATCHED, REPAIRED, AND PREP AS
REQUIRED FOR NEW FINISH APPLICATION.
8. DO NOT CLOSE OR OBSTRUCT WALKWAYS, EXITS, OR OTHER FACILITIES USED BY
OCCUPANTS OF BUILDINGS WITHOUT WRITTEN PERMISSION FROM AUTHORITIES HAVING
JURISDICTION
9. CONDUCT OPERATIONS IN A SAFE WORKING MANNER TO PREVENT DAMAGE OR INJURY TO
ADJACENT SPACES, BUILDING, STRUCTURE, OTHER FACILITIES, AND PERSONS.
10. REFER TO GENERAL NOTES, LEGENDS & SYMBOLS SHEET FOR ADDITIONAL GENERAL
NOTES AS APPLICABLE.
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
P R
O J E
C T
N A
M E
TM
TM
07/02/2024
A120
ENLARGED
ARCHITECTURAL SITE
PLAN
100% CD
KM
J E
F F
E R
S O
N B
A R
R A
C K
S C
O V
E R
E D
P A
R K
IN
G
B
U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
1/8" = 1'-0"3 NORTH CANOPY ROOF PLAN
1/8" = 1'-0"1 NORTH CANOPY PARKING PLAN
1/8" = 1'-0"2 NORTH CANOPY REFLECTED CEILING PLAN
NORTH
NORTH
NORTH
Description Date
D ou gl as
B L ov el an d
A rc hi te ct M
O A
-2
77/
2/
A600
CLEARANCE
HEIGHT
463'-6"
2 3 8654
T.O. FOOTING
453'-3"
N. GRADE HIGH
451'-0 101/256"
N. GRADE LOW
448'-4 37/256"
T.O. COLUMN
465'-9"
/2
ALTERNATE 2: PROVIDE
WATERPROOF DUPLEX
RECEPTACLE AT SECOND
AND FIFTH COLUMNS,
TYP.; SEE ELECTRICAL
EXPOSED
STEEL TO BE
AESS3, PRIMED
AND PAINTED,
TYP.
ALTERNATE 4:
ADD GUTTER
AND
DOWNSPOUTS
PAINT EXPOSED
CONCRETE
FOOTINGS
SAFETY
YELLOW, TYP.
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
P R
O J E
C T
N A
M E
Designer
Author
07/02/2024
A510
OVERALL EXTERIOR
ELEVATIONS
100% CD
Checker
J E
F F
E R
S O
N B
A R
R A
C K
S C
O V
E R
E D
P A
R K
IN
G
B
U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
1/4" = 1'-0"1 NORTH CANOPY - SOUTH ELEVATION
Description Date
D ou gl as
B L ov el an d
A rc hi te ct M
O A
-2
77/
2/
S. GRADE - LOW
449'-1"
S. GRADE - HIGH
451'-6"
CLEARANCE
HEIGHT
463'-6"
A
T.O. FOOTING
453'-3"
N. GRADE HIGH
451'-0 101/256"
N. GRADE LOW
448'-4 37/256"
T.O. COLUMN
465'-9"
B.O. FOOTING
443'-3"
(S E
E S
T R
U C
T U
R A
L
(S O
U T
H C
A N
O P
Y M
IN
IM
U M
C L
E A
R A
N C
E
(N O
R T
H C
A N
O P
Y M
IN
IM
U M
C L E
A R
A N
C E
/2
2 1/8"
12"
A600
A600
24'-0"
23'-7 1/2" +/-
NOTE: VERIFY OVERALL
ROOF DIMENSIONS WITH
FINAL SOLAR PANEL
INSTALL DIMENSIONS
ALTERNATE 4: ADD GUTTER AND
DOWNSPOUTS; 6" STYLE "A"
GUTTER, 4" DOWNSPOUT AT
EACH COLUMN, PROVIDE AND
INSTALL BRACKETS AS
REQUIRED, PREFINISHED TO
MATCH STEEL PAINT
ALTERNATE 3: DELETE PV
PANEL SYSTEM AND ADD
STANDING SEAM METAL ROOF;
PROVIDE INSTALLATION SHOP
DRAWINGS
EXPOSED STEEL TO BE AESS3,
PRIMED AND PAINTED, TYP.
ALTERNATE 2: PROVIDE
WATERPROOF DUPLEX
RECEPTACLE AT SECOND AND
FIFTH COLUMNS, TYP.; SEE
ELECTRICAL
PAINT EXPOSED CONCRETE
FOOTINGS SAFETY YELLOW,
TYP.
CLEARANCE
HEIGHT
463'-6"
ALTERNATE 4: ADD GUTTER AND
DOWNSPOUTS; 6" STYLE "A"
GUTTER, 4" DOWNSPOUT AT
EACH COLUMN, PROVIDE AND
INSTALL BRACKETS AS
REQUIRED, PREFINISHED TO
MATCH STEEL PAINT
ALTERNATE 3: DELETE PV
PANEL SYSTEM AND ADD
STANDING SEAM METAL ROOF;
PROVIDE INSTALLATION SHOP
DRAWINGS
SEE STRUCTURAL
A
T.O. COLUMN
465'-9"
3'-0"
1'-9 1/4"
3'-0"2
/2
6"
2 1/2"
/2
6"
2 1/2"
6"
6"
R 2'-0"
R
'-0
1/4" END CAP
PLATE, TYP.
SEE STRUCTURAL
FOR CONNECTION
DETAILS AND
MATERIAL
GAUGES
SEE STRUCTURAL
ALTERNATE 3: DELETE
PV PANEL SYSTEM AND
ADD STANDING SEAM
METAL ROOF; PROVIDE
INSTALLATION SHOP
DRAWINGS
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
P R
O J E
C T
N A
M E
TM
TM
07/02/2024
A600
BUILDING SECTIONS
100% CD
KM
J E
F F
E R
S O
N B
A R
R A
C K
S C
O V
E R
E D
P A
R K
IN
G
B
U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
1/2" = 1'-0"1 Section 4
1" = 1'-0"3 LOWER ROOF EDGE DETAIL
1" = 1'-0"2 COLUMN BRACKET DETAIL
Description Date
D ou gl as
B L ov el an d
A rc hi te ct M
O A
-2
77/
2/
GENERAL NOTES - STRUCTURAL
1. General Information
A. The contractor shall verify dimensions and conditions before construction and notify the engineer of any discrepancies, inconsistencies, or difficulties affecting the work before proceeding.
B. The contractor shall coordinate all disciplines, verifying size and location of all openings, whether shown on structural drawings or not, as called for on architectural, mechanical, or electrical drawings. In the case of work in an existing building the contractor shall scan existing structure to locate all rebar in the area of the new core/opening using ground penetrating radar and notify the engineer of record for review prior to coring/cutting. Conflicts, inconsistencies, or other difficulties affecting structural work shall be called to the architect or engineer's attention for direction before proceeding.
C. All design and construction work for this project shall conform to the requirements of the following governing design codes:
1. International Building Code (IBC 2018) and referenced standards as amended by the city of St. Louis, MO
2. Minimum Design Loads for Buildings and Other Structures (ASCE7-16)
3. Specification for Structural Steel Buildings (AISC 360-16)
Member Design Basis is Allowable Stress Design (ASD) Connection Design Basis is Allowable Stress Design (ASD)
4. Structural Welding Code (AWS D1.4/D1.4M - 2017)
5. Building Code Requirements for Structural Concrete (ACI 318-14)
6. Building Code Requirements for Masonry Structures (TMS 402-16)
7. North American Specification for the Design of Cold-Formed Steel Structural
Members (AISI S100-16)
8. National Design Specification (NDS) for Wood Constriction with 2018
Supplements (ANSI/AWC NDS-2018)
9. Special Design Provisions for Wind and Seismic (AWC SDPWS-2015)
D. These drawings are for this specific project and no other use is authorized.
2. Structural Load Design Criteria
3. Concrete
A. All concrete shall have a minimum design compressive strength of 4500 psi in 28 days, with not less than 560 pounds of cement per cubic yard of concrete, not over 5 gallons of water per 100 pounds of cement, with 6% +/- 1% air entrainment, and a maximum of 4 inches of slump.
B. The preceding minimum mix requirements may have water-reducing admixtures conforming to ASTM C494 added to the mix at manufacturer's dosage rates for improved workability.
C. The preceding minimum mix requirements may have up to 15% maximum of the cement content replaced with an approved ASTM C618 Class C fly ash, provided the total minimum cementitious content is not reduced.
D. Combined aggregate (coarse plus fine) for all concrete shall be well graded from coarsest to finest with no more than 18 percent and not less than 8 percent retained on an individual sieve, except that less than 8 percent may be retained on coarsest sieve and on No. 50 and finer sieves. Submit this gradation report with the concrete mix design shop drawings.
E. All concrete is reinforced concrete unless specifically called out as unreinforced.
Reinforce all concrete not otherwise shown with same steel as in similar sections or areas. Any details not shown shall be detailed per ACI 315 and meet requirements of ACI 318, current editions.
F. Contractor shall verify that all concrete inserts, reinforcing and embedded items are correctly located and rigidly secured prior to concrete placement.
G. No aluminum items shall be embedded in any concrete.
4. Reinforcing Steel
A. All reinforcing steel shall conform to the requirements of ASTM A615 or A706 grade 60 steel. Welded plain wire fabric shall be supplied in sheets and conform to the requirements of ASTM A185.
B. Clear coverage of concrete over reinforcing steel shall be as follows:
1. Concrete placed against earth: 3"
2. Formed concrete against earth: 2"
3. Slabs: 1"
4. Beams or Columns: 1-1/2"
5. Other 2" All coverage shall be nominal bar diameter minimum.
C. All dowels shall be the same size and spacing as adjoining main bars (splice lap 48 bar diameters or 24" minimum unless noted otherwise).
D. Bars marked continuous and all vertical steel shall be lapped 48 bar diameters (2'-0" minimum) at splices and embedments, unless shown otherwise. Splice top bars near midspan and splice bottom bars over supports, unless noted otherwise.
E. Accessories shall be as specified in latest edition of the ACI Detailing Handbook and the concrete Reinforcing Steel Institute Design Handbook. Maximum accessory spacing shall be 4'-0" on center, and all accessories on exposed surfaces are to have plastic coated feet.
5. Structural Steel
A. All structural steel beams and columns shall be ASTM A992, grade 50 steel and all miscellaneous steel shall be ASTM A36 grade steel (except at moment connections where plates shall be ASTM A572, grade 50). Hollow Structural Sections (HSS) shall be ASTM A500, grade C. Fabrication and erection shall be in accordance with AISC 303 "Code of Standard Practice for Steel Buildings and Bridges" in the referenced edition of the AISC Steel Construction Manual.
B. All welding shall conform to the recommendations of the AWS.
C. All exterior steel and connections shall be hot-dip galvanized.
D. All bolts not otherwise specified shall be 3/4" diameter high strength (ASTM A325-N).
All bolts shall be fully pretensioned. All beam connections shall be designed per the AISC Manual of Steel Construction "Framed Beam Connections" for the indicated reactions or at least 0.4 x beam total shear capacity, Vn/Omega, shown in the maximum total uniform load tables, whichever is greater; and, shall account for eccentricity when the bolt line is more than 2" from the center of the support. All connections must be two bolt minimum. Additional connection elements may not be specifically shown in the conceptual details in this set but may be required by the final connection design, such as stiffener plates, doubler plates, supplement/reinforcing plates or other connection material. Connection design and shop drawing preparation shall be completed under the direct supervision of a professional engineer licensed in the state the project is located and shop drawings and connection calculations shall bear his/her seal.
E. All anchor bolts shall be 3/4" diameter, ASTM F1554, Grade 36 unless noted otherwise.
Plate washers of minimum size and thickness for the given anchor diameter in Table 14-2 of the AISC Steel Construction Manual shall be provided at every column anchor bolt. Plate washers shall have a standard size hole for the anchor bolt. At braced frames, plate washers shall be welded all around to the column base plate with 3/16” fillet weld.
F. Design and installation of steel decking shall comply with the recommendations of the Steel Deck Institute (SDI). All decking shall be galvanized unless noted otherwise.
G. Allow 1.0 tons of structural steel to be used as directed in the field for special conditions by the engineer of record. Cost for shop drawings, fabrication, delivery, detailing, and erection to be included. 50% of structural steel allowance shall be bid as miscellaneous galvanized angle and plate.
6. Post-installed Anchors
A. Post-installed anchors shall be used only where specified on the drawings unless approved in writing by the engineer of record. See drawings for anchor diameter, spacing and embedment. Performance values of the anchors shall be obtained for specified products using appropriate design procedures and/or standards as required by the governing building code. Anchors installed in concrete shall have an ICC-ES Evaluation Service Report. Special inspection is required for all post installed anchors.
The contractor shall coordinate an on-site meeting with the post installed anchor manufacturer field representative to educate the construction team on the anchor installation guidelines and requirements.
B. Mechanical anchors used in cracked and uncracked concrete shall have been tested and qualified for use in accordance with ACI 355.2 and ICC-ES AC193. All anchors shall be installed per the anchor manufacturer's written instructions.
C. Adhesive anchors used in cracked and uncracked concrete shall have been tested and qualified for use in accordance with ICC-ES AC308. All anchors shall be installed per the anchor manufacturer's written instructions.
D. Mechanical anchors used in solid grouted masonry shall have been tested and qualified for use in accordance with ICC-ES AC01. All anchors shall be installed per the anchor manufacturer's written instructions.
E. Adhesive anchors used in solid grouted masonry shall have been tested and qualified for use in accordance with ICC-ES AC58. All anchors shall be installed per the anchor manufacturer's written instructions.
F. Anchors used in hollow concrete masonry shall have been tested and qualified in accordance with ICC-ES AC106 or ICC-ES AC58 as appropriate. All anchors shall be installed per the anchor manufacturer's written instructions with appropriate screen tubes used for adhesives.
7. Foundations
A. Structural foundations consist of a network of straight shaft drilled piers (caissons established on highly weathered limestone capable of safely supporting 10 ksf end bearing.
B. Contractor shall provide for dewatering at excavations from either surface water or seepage.
C. All foundation excavations shall be inspected by a qualified soil engineer, approved by the architect and/or structural engineer, prior to placement of steel or concrete. This inspection shall be at the owner's expense.
D. All concrete in the structural portion retaining the backfill shall have attained its design strength prior to being backfilled.
E. Moisture content in soils beneath building locations should not be allowed to change after footing excavations and after grading for slabs on grade are completed. If subgrade materials become desiccated or softened by water or other conditions, recompact materials to the density and water content specified for engineered fill. Do not place concrete on frozen ground.
8. Shop Drawings and Deferred Submittals
A. Bob D. Campbell and Company, Inc. will review the General Contractor’s (GC) shop drawings and related submittals (as indicated below) with respect to the ability of the detailed work, when complete, to be a properly functioning integral element of the overall structural system designed by Bob D. Campbell and Company, Inc.
B. Deferred submittals shall be submitted to the architect of record for review who shall forward to the building official for review and approval. Design calculations for deferred sub mittals shall be submitted at the same time as the shop drawings for review. Design calculations shall be prepared and sealed by a Professional Engineer licensed in the state of the project. The deferred submittal items shall not be installed until the deferred submittal documents have been approved by the building official.
C. Prior to submittal of a shop drawing or any related material to Bob D. Campbell and Company, Inc., the GC shall:
1. Review each submission for conformance with the means, methods, techniques, sequences and operations of construction and safety precautions and programs incidental thereto, all of which are the sole responsibility of the GC.
2. Review and approve each submission.
3. Stamp each submission as approved.
D. Bob D. Campbell and Company, Inc. shall assume that no submission comprises a variation unless the GC advises Bob D. Campbell and Company, Inc. with written documentation.
E. Bob D. Campbell and Company, Inc. shall review shop drawings and related materials with comments provided that each submission has met the above requirements. Bob D. Campbell and Company, Inc. shall return without comment unrequired material or submissions without GC approval stamp.
F. Required shop drawings and related material (if any) are indicated below.
Should Bob D. Campbell and Company, Inc. require more than ten (10) working days to perform the review, Bob D. Campbell and Company, Inc. shall so notify the GC.
1. Concrete mix designs and material certificates including admixtures and compounds applied to the concrete after placement.
2. Reinforcing steel shop drawings including erection drawings and bending details.Bar list will not be reviewed for correct quantities.
3. Structural steel shop drawings including erection drawings and piece details.
Include decking and connector submittals. Include miscellaneous framing specified on the structural drawings, but do not submit framing specified on non-structural drawings for Bob D. Campbell and Company, Inc. review.
10. Statement of Structural Special Inspections
A. The structural design for this project is based on completion of special inspections during construction in accordance with section 1704 of the International Building Code. The owner shall employ one or more qualified special inspectors to provide the required special inspections.
B. The special inspector shall furnish inspection reports to the building official, owner, architect and structural engineer, and any other designated person.
C. All discrepancies shall be brought to the immediate attention of the contractor for correction, then, if uncorrected, to the proper design authority, building official and structural engineer.
D. The special inspector shall submit a final signed report stating that the work requiring special inspection was, to the best of the inspector's knowledge, in conformance with the approved plans and specifications and the applicable workmanship provisions of the building code.
E. The following inspections and tests are required with the frequency (continuous or periodic) as defined within the referenced section or standard listed below. The General Contractor shall provide notification to the inspector when items requiring inspection are ready to be inspected and provide access for those inspections.
1. Shop Fabrication – structural steel and steel bar joist per Section 1704.2.5 unless AISC certified shop
2. Steel Construction per Section 1705.2 and the quality assurance requirements of AISC 341 Chapter J (as referenced by AISC 360)
3. Concrete Construction per Section 1705.3 and Table 1705.3
a. Reinforcing Steel Placement
b. Cast in Place Anchors
c. Design Mix Verification
d. Concrete Sampling and Testing
e. Concrete Placement
f. Concrete Curing
4. Verification of Soils per Table 1705.6
5. Inspections and Tests of Cast-In-Place Deep Foundation per Table 1705.8
11. Copyright and Disclaimer
A. All drawings in the structural set (S-series drawings) are the copyrighted work of Bob D. Campbell and company, Inc. These drawings may not be photographed, traced, or copies in any manner without the written permission of Bob D. Campbell and Company, Inc. Exception: Original drawings may be printed for distribution to the owner, architect, and general contractor for coordination, bidding, and construction. Subcontractors may not reproduce these drawings for any purpose or in any manner.
B. I, Wayne E. Davis, P.E., registered engineer and a representative of Bob D.
Campbell and Company, Inc., do hereby accept professional responsibility as required by the professional registration laws of this state for the structural design drawings consisting of S-series drawings. I hereby disclaim responsibility for all other drawings in the construction document package, they being the responsibility of other design professionals whose seals and signed statements may appear elsewhere in the construction document package.
A. Roof Live = 20 psf; Roof Dead = 15 psf B. Snow: Pg = 20psf, Pf =17psf, Is = 1.0, Ce = 1.0, Ct = 1.2, Drift per ASCE/SEI 7 C. Lateral Loads:
1. Wind:
• V = 108 mph, Exposure B
• Occupancy [Risk] Category II, Iw=1.0 GCpi=+/-0.18
• Design wind pressures to be used for the design of exterior component and cladding materials on the designated zones of wall and roof surfaces shall be per section 30.7 and Table 30.7-2 of ASCE/SEI 7. Tabulated pressures shall be multiplied by effective area reduction factors, exposure adjustment factors, and topographic factors where applicable
2. Seismic:
• Ss = 0.438, S1 = 0.157
• Occupancy [Risk] Category II, Ie=1.0,
• Site Classification D; Sds = 0.423; Sd1 = 0.239
• Seismic Design Category D
LEGEND:
RD-1
SPAN DIRECTION OF DECK
. . . . . . 1½", 22ga GALVANIZED WIDE RIB ROOF
DECK (3 SPAN CONTINUOUS) ATTACH
TO STRUCTURE TO DEVELOP 325plf
DIAPHRAGM SHEAR (ASD LOAD).
@ AT
& AND
Ø ROUND, DIAMETER
ADTL ADDITIONAL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ARCH ARCHITECTURAL
BLDG BUILDING
B/ BOTTOM OF
BM BEAM
BOTT BOTTOM
BRG BEARING
C CAMBER
CD-# CONCRETE DECK TYPE
CJ CONSTRUCTION/CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
COORD COORDINATE
COV, CVR COVER
DBL DOUBLE
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DL DEAD LOAD
DWG DRAWING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
EMBED EMBEDMENT, EMBEDDED
ENGR ENGINEER
EOD EDGE OF DECK
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EXP EXPANSION
EXT EXTERIOR
EXTG, EXIST EXISTING
FD-# FLOOR DECK TYPE
FDN FOUNDATION
FF FAR FACE
FIN FINISH
FLR FLOOR
FS FAR SIDE
FTG FOOTING
FV FIELD VERIFY
STRUCTURAL ABBREVIATIONS
GA GAGE
GALV GALVANIZE(D)
GEN GENERAL
GR GRADE
HORIZ HORIZONTAL
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INFO INFORMATION
INT INTERIOR
JST JOIST
JT JOINT
K KIPS (1000 LBS)
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LBS, # POUNDS
Ld DEVELOPMENT LENGTH
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LSLT LONG-SLOTTED HOLE TRANSVERSE
LTWT LIGHTWEIGHT
M MOMENT FORCE
MAX MAXIMUM
MECH MECHANICAL
MFGR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MSRY MASONRY
MTL METAL
NF NEAR FACE
NS NEAR SIDE
NTS NOT TO SCALE
NW NORMAL WEIGHT
OC ON CENTER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OVS OVERSIZED HOLE
P AXIAL FORCE
PAF POWDER ACTUATED FASTENER
PC PRECAST
PCF POUNDS PER CUBIC FOOT
PEMB PRE-ENGINEERED METAL BUILDING
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PJP PARTIAL JOINT PENETRATION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RAD RADIUS
RD-# ROOF DECK TYPE
REF REFERENCE
REINF REINFORCEMENT
REQD REQUIRED
REV REVISION
RLL ROOF LIVE LOAD
RTU ROOF TOP UNIT
SC SLIP CRITICAL
SCHED SCHEDULE(D)
SECT SECTION
SHT SHEET
SIM SIMILAR
SJ SAW JOINT
SL SNOW LOAD
SOG SLAB-ON-GRADE
SOG-# SLAB-ON-GRADE TYPE
SPCG SPACING
SPEC SPECIFICATION
SPRT SUPPORT
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT-SLOTTED HOLE TRANSVERSE
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STRUCT STRUCTURE, STRUCTURAL
T/ TOP OF
THRU THROUGH
TOS TOP OF STEEL, TOP OF SLAB
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V SHEAR FORCE
VERT VERTICAL
W/ WITH
W/0 WITHOUT
WF WIDE FLANGE
WL WIND LOAD
WP WORK POINT
WWF WELDED WIRE FABRIC
PRELIMINARY
DRAWINGS FOR
REVIEW
PURPOSES ONLY,
NOT FOR
CONSTRUCTION
OR
IMPLEMENTATION
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
TAJ
TAJ
07/02/2024
J E
F F
E R
S O
N B
A R
R A
C K
S
S001
GENERAL NOTES
100% CD
WED
C O
V E
R E
D P
A R
K
IN
G
B U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
Description Date
Seal:
7-2-24
B
C
D
E
F
G
A A
2 3 4 5 6 8
S101
6'-0 1/8" 23'-0" 23'-0" 23'-0" 23'-0" 23'-0"
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
H
SS20X12X1/2
S101
TYP
T/CONCRETE PIER
EL. 453'-3"
TYP. ON GRID A
TYP
T/CONCRETE PIER
EL. 453'-3"
TYP. ON GRID 1
PRELIMINARY
DRAWINGS FOR
REVIEW
PURPOSES ONLY,
NOT FOR
CONSTRUCTION
OR
IMPLEMENTATION
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
TAJ
TAJ
07/02/2024
J E
F F
E R
S O
N B
A R
R A
C K
S
S100
FOUNDATION PLAN
100% CD
WED
C O
V E
R E
D P
A R
K
IN
G
B U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
1/8" = 1'-0"1 FOUNDATION PLAN
Description Date
B B
C
D
E
F
G
A A
2 3 4 5 6 8
S101
6'-0 1/8" 23'-0" 23'-0" 23'-0" 23'-0" 23'-0"
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
H S
S X
X
/8
H S
S X
X
/8
H S
S X
X
/8
H S
S X
X
/8
H S
S X
X
/8
H S
S X
X
/8
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
HSS12X12X5/8
HSS12X12X5/8
HSS12X12X5/8
HSS12X12X5/8
HSS12X12X5/8
HSS12X12X5/8
/4
/4
1'-11 1/4"
1'-11 1/4"
R D
-1
RD-1
S101
TYP
S300
L X
X
/4
TYP
S300
L X
X
/4
OPP
HAND
TYP
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
HSS10X6X5/16
S300
TYP
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
L2X2X1/4
L2X2X1/4
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
H S
S X
X
/1
S300
TYP
S300
TYP
S300
TYP
SIM
SIM
23'-6"
14'-1 9/16"
9'-4 7/16"
S300
S300
S300
S300
3'-11"
3'-11"
3'-11"
3'-11"
3'-11"
3'-11"
T/PIER
EL. 453'-3"
PAVEMENT PER CIVIL
T/COLUMN
EL. 465'-9"
2 1/8
PRELIMINARY
DRAWINGS FOR
REVIEW
PURPOSES ONLY,
NOT FOR
CONSTRUCTION
OR
IMPLEMENTATION
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
TAJ
TAJ
07/02/2024
J E
F F
E R
S O
N B
A R
R A
C K
S
S101
ROOF FRAMING PLAN
100% CD
WED
C O
V E
R E
D P
A R
K
IN
G
B U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
1/8" = 1'-0"1 ROOF FRAMING PLAN
3/8" = 1'-0"2 SECTION
Description Date
NOTES:
1. REFER TO GENERAL NOTES AND LEGEND ON SHEET S001.
2. ALL STEEL AND CONNECTION COMPONENTS TO BE HOT DIPPED GALVANIZED.
ROOF DECK PER PLAN
R
AD
IU
S =
'-2
/4
1/2" COVER PLATE
HSS10X6X5/16
TYP
GRIND
FLUSH
HSS12X12X5/8
ROOF DECK PER PLAN
1/2" COVER PLATE
HSS10X6X5/16
HSS12X12X5/8
1/2"
1/2"
TYP.
GRID
PER
PLAN
1/2"
TYP
GRIND
FLUSH
ROOF DECK PER PLAN
1/2" COVER PLATE
1/2"⌀ WEEP HOLE
HSS10X6X5/16
HSS12X12X5/8
'-2
/4
GRID
PER
PLAN
1/2" ISOLATION JOINT.
FILL w/ COMPRESSIBLE
MATERIAL & SEALANT
AT TOP.
SLAB PER PLAN
"o c
T
IE
S
(8) #6 VERTS
#3 CIRCULAR TIES
@ 12"o.c. (TYP) W/
18" MIN. LAP
GRID
PER
PLAN
GRID
PER
PLAN
(16) #8 VERTICALS#3 TIES
COVER
3" CLEAR
3'-0" DIAMETER
TYPICAL PIER REINFORCING DETAIL
2" 1'-0" 1'-0" 2"
2'-4"
18" M
IN. TIE LAP
3'-0" DIAMETER
1½" GROUT
(8) 1"⌀ ANCHOR BOLTS
W/ 18" EMBEDMENT
3/4" CHAMFER
ALL AROUND
BASE PLATE
1½"X20"X28"
HSS20X12X1/2
TYPICAL COLUMN BASEPLATE
ACI STD. HOOK TYP.
T/PIER
EL. 453'-3"
/2
G A
P
1/2"⌀ WEEP HOLE ON
BOTTOM OF TUBE
1/4" END PLATE,
SEAL WELD TYP.
HSS10X6X5/16
HSS12X12X5/8
3/4"⌀ THREADED STUD
3/16"
3/16"
TYP
L4X4X1/4 W/ 13/16"X1¾" SLOT
1'-11 1/4"
GRID
PER
PLAN
1/2"⌀ WEEP HOLE ON
BOTTOM OF TUBE
2 1/2"
1/4" END PLATE,
SEAL WELD TYP.
L2X2X1/4 EDGE
ANGLE
HSS10X6X5/16
HSS12X12X5/8
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
PRELIMINARY
DRAWINGS FOR
REVIEW
PURPOSES ONLY,
NOT FOR
CONSTRUCTION
OR
IMPLEMENTATION
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
P R
O J E
C T
N A
M E
1218003
Seal:
TAJ
TAJ
07/02/2024
J E
F F
E R
S O
N B
A R
R A
C K
S
S300
FRAMING DETAILS
100% CD
WED
C O
V E
R E
D P
A R
K
IN
G
B U
IL
D
IN
G
M
A Y
R O
A D
S T
L
O U
IS
M O
1 1/2" = 1'-0"1 SECTION
1 1/2" = 1'-0"2 SECTION
1 1/2" = 1'-0"3 SECTION
3/4" = 1'-0"4 SECTION
Description Date
1 1/2" = 1'-0"5 SECTION
1 1/2" = 1'-0"6 SECTION
GRID INTERACTIVE PHOTOVOLTAIC (PV) SYSTEM SUMMARY
SYSTEM SIZE 122.4 KW (DC) (+/- 8%)
INVERTER RATIO (DC:AC) 1.2 (+/- 5%)
MINIMUM ANNUAL ENERGY 170 MWHR (YEAR 1)
PV MODULE MONOCRYSTALLINE OR THIN FILM SOLAR CELLS, BOD: FIRST SOLAR, FS-6450A
INVERTER CPS, SCA 25 KTL-DO/US-208
ORIENTATION 10 DEGREE TILT
RACKING ATTACH TO COVERED PARKING STRUCTURE
POINT OF CONNECTION BUILDING 41 SERVICE ENTRANCE PANEL
INTERCONNECTION VOLTAGE 208V - 3 PHASE
DESIGN WIND LOAD 90 MPH
NATIONAL ELECTRIC CODE 2023 EDITION
www.branchpattern.com
BETTER BUILT ENVIRONMENTS
Phone: 800-200-9160
These drawing and the designs here Illustrated are the sole property of BranchPattern, Inc. and may not be reproduced in whole or in part without express written permission.
Designed By:
Drawn By:
Reviewed By:
Project No:
Date:
Submittal Level:
Sheet Title:
Sheet No.:
P R
O J E
C T
N A
M E
1218003
Seal:
Civil Engineering | Surveying | Utilities | Construction Services 7101 College Blvd., Ste. 400 Overland Park, KS 66210 o: (913) 663-1900
AP
BP
07/02/2024
J E
F F
E R
S O
N B
A R
R A
C K
S
E001
ELECTRICAL SYMBOL
LEGEND
100% CD
BP
C O
V E
R E
D P
A R
K
IN
G
B U
IL
D
IN
G
M
A Y
R D
S
T
L O
U
IS
M
O
M
G
G
THIS IS A MASTER SYMBOLS LIST. ALL SYMBOLS, ABBREVIATIONS, ETC. MAY NOT NECESSARILY BE USED ON ALL DRAWINGS
20 AMP, 125V, NEMA 5-20R DUPLEX RECEPTACLE
PANELBOARD, ELECTRICAL DISTRIBUTION PANEL, OR LOAD CENTER
SURFACE MOUNTED
PANELBOARD, ELECTRICAL DISTRIBUTION PANEL, OR LOAD CENTER
RECESS MOUNTED
A AMPS, AIR (COMPRESSED)
AC ABOVE COUNTER
AF FUSE RATING
AFC ABOVE FINISHED CEILING
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFEA AREA FOR EVACUATION ASSISTANCE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CURRENT
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
AV AUDIO VISUAL
BFF BELOW FINISHED FLOOR
BKR BREAKER
BOS BOTTOM OF STRUCTURE
BTU BRITISH THERMAL UNIT
C CONDUIT
CATV CABLE TELEVISION SYSTEM
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CM COFFEE MAKER
CT CURRENT TRANSFORMER
CU COPPER, CONDENSING UNIT
CW CLOTHES WASHER
(D) DEMOLISHED
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DW DISHWASHER
(E) EXISTING
ECD ELECTRIC CLOTHES DRYER
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
FBO FURNISHED BY OTHERS
FF FINISHED FLOOR
FHC FIRE HOSE CABINET
FLA FULL LOAD AMPS
FLR FLOOR
FRZR FREEZER
FVNR FULL VOLTAGE, NON REVERSING
GD GARBAGE DISPOSAL
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT CIRCUIT INTERRUPTER
(PERSONAL PROTECTION ON DEVICE)
GFP GROUND FAULT PROTECTED FROM UPSTREAM
GFR GROUND FAULT RELAY
GND GROUND
HOA HAND OFF AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTG HEATING
HTR HEATER
ISCA AVAILABLE SHORT-CIRCUIT CURRENT (AMPS)
IG ISOLATED GROUND
KCMIL 1000 CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPS
KVAR KILOVOLT AMPS REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LRA LOCKED ROTOR AMPS
MATV MASTER ANTENNA TELEVISION SYSTEM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MDP MAIN DISTRIBUTION PANEL
MFP MULTI-FUNCTION PRINTER
MFR MANUFACTURER
MGB MAIN GROUND BAR
MH MANHOLE
MSB MAIN SWITCHBOARD
MTD MOUNTED
MW MICROWAVE
(N) NEW
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
N/O,N/C NORMALLY OPEN, NORMALLY CLOSED
N/L NIGHT LIGHT
OC ON CENTER
OV OVEN
PBB PRIMARY BONDING BAR
PDU POWER DISTRIBUTION UNIT
PH,ø PHASE
PJ PROJECTOR
PLOT PLOTTER
PNL PANEL
PRINT PRINTER (SMALL)
PT POTENTIAL TRANSFORMER
PV PHOTOVOLTAIC
QTY QUANTITY
(R) RELOCATED
RA RETURN AIR
RANGE RANGE\STOVE
RCP REFLECTED CEILING PLAN
REF REFRIGERATOR
REV REVISION
RH RELATIVE HUMIDITY
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SBB SECONDARY BONDING BAR
SD SMOKE DETECTOR
SF SQUARE FEET
SPDT SINGLE POLE, DOUBLE THROW
SPST SINGLE POLE, SINGLE THROW
SP STATIC PRESSURE
SWBD SWITCHBOARD
TL TWISTLOCK
TV TELEVISION
TYP TYPICAL
U/F UNDERFLOOR
U/G UNDERGROUND
U/S UNDER SLAB
UL UNDERWRITERS LABORATORIES, INC.
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
USB RECEPTACLE W/ INTEGRATED USB PORT
V VOLTAGE
VAC VOLTS ALTERNATING CURRENT, VACUUM
VM VENDING MACHINE
W WATTS
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WT WATERTIGHT, WEIGHT
XFMR TRANSFORMER
XP EXPLOSION PROOF
ELECTRICAL LEGEND
ELECTRICAL
ABBREVIATIONS
JUNCTION BOX, FLOOR MOUNTED
JUNCTION BOX, WALL MOUNTED
SPECIAL RECEPTACLE, FLOOR MOUNTED, CONFIGURATION AS NOTED ON PLAN
SPECIAL RECEPTACLE, WALL MOUNTED, CONFIGURATION AS NOTED ON PLAN
COMBINATION DISCONNECT, WITH RECEPTACLE, REFER TO DRAWING FOR
SIZE
HEAVY DUTY SAFETY SWITCH, NON-FUSED
COMBINATION STARTER/DISCONNECT (SIZE AS INDICATED)
HEAVY DUTY FUSED DISCONNECT
J
J
JUNCTION BOX, CEILING MOUNTEDJ
SPECIAL RECEPTACLE, CEILING MOUNTED, CONFIGURATION AS NOTED ON PLAN
TYPICAL MOUNTING HEIGHTS UNO
POWER (SERVICE) POLEPP
SUBSCRIPTS ADJACENT DEVICES INDICATE THE FOLLOWING:
G = GFCI
T = TAMPER RESISTANT
AC = MOUNT 6" ABOVE COUNTER OR BACKSPLASH
USB = DEVICE WITH USB CHARGING PORT
ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS
INDICATED ON ELECTRICAL DRAWINGS. DIMENSION TO CENTERLINE UNO.
WP = WEATHER PROOF
H = HOSPITAL GRADE
UC = MOUNT 12" UNDER COUNTER
RECEPTACLES 18"
RECEPTACLES IN EQUIPMENT ROOMS 46"
RECEPTACLES (EXTERIOR) 24"
RECEPTACLES (GARAGES) 24"
ALARMS, SWITCHES AND CONTROLS 46"
SAFETY SWITCHES 46"
STARTERS 48"
PANELS (TOP) 72"
FIRE ALARM PULL STATIONS (HANDLE) 44"
STROBES 96" OR 6" BELOW CEILING, WHICHEVER IS LOWER
FIRE ALARM BELLS (EXTERIOR) 12'-0"
FIRE ALARM CONTROL PANELS (TOP) 66"
ANNUNCIATION PANELS 48"
REMOTE INDICATING LIGHTS (EQUIPMENT ROOMS) 48"
REMOTE INDICATING LIGHTS (FINISHED AREAS) CEILING
EXIT SIGNS (WALL MOUNTED BOTTOM) 6" ABOVE DOOR
MAXIMUM HEIGHT OF OPERABLE COMPONENTS 48" TO TOP
PHOTOCELLS 12'-0"
ADA DOOR OPENER 46"
NOTE: UPPER CASE LETTER DENOTES LUMINAIRES TYPE. LOWER CASE LETTER
ADJACENT TO LUMINAIRE INDICATES SWITCH THAT CONTROLS LUMINAIRES.
MOUNTING IS NOTED ON LUMINAIRE SCHEDULE
NORMAL POWER
SPD
GROUND ROD
GROUND CONNECTION WITH TEST WELL
CURRENT TRANSFORMER, RATED AS SPECIFIED OR REQUIRED
SURGE PROTECTIVE DEVICE
GROUND CONNECTION
SWITCH, RATING AS SHOWN
FUSE, FUSE AMPACITY AND TYPE AS SHOWN
UTILITY METER (AS REQUIRED BY UTILITY)
CIRCUIT BREAKER, RATING AS SHOWN. LSIG DENOTES ELECTRONIC TRIP
UNIT WITH ADJUSTABLE SETTINGS FOR: L= LONG TIME TRIP DELAY, S=
SHORT TIME TRIP DELAY, I= INSTANTANEOUS, G= GROUND FAULT
PANEL
TRANSFORMER NAME, SIZE, TYPE, AND RATING AS SHOWN
CONDUIT CONNECTION
CIRCUIT BREAKER WITH GROUND FAULT PROTECTION
FUSE WITH GROUND FAULT PROTECTION
POLE MOUNTED UTILITY TRANSFORMER
LSIG
400A
FRN
800A3P
PANEL
XXX
SHORT CIRCUIT TAG DESIGNATION
FEEDER TAG DESIGNATIONXXXX
X
SHUNT TRIPST
T
PHOTOVOLTAIC MODULE
DC-AC INVERTER
KEY NOTE DESIGNATION
NEW TO EXISTING CONNECTION
REVISION NUMBER DESIGNATION
MISCELLANEOUS
X
X
DEMOLITION KEY NOTE DESIGNATIONX
DEMO TO EXISTING CONNECTION
XX SPECIALTY EQUIPMENT (BY OTHERS)
PANEL NAME - CIRCUIT NUMBER
BRANCH CIRCUITS HOMERUN USE NUMBER 12 AWG WIRE, UNLESS
OTHERWISE NOTED. ALL CIRCUITS SHALL CONTAIN A GROUND AND
NEUTRAL CONDUCTOR, UNLESS NOTED OTHERWISE. CONTRACTOR
SHALL PROVIDE MULTI-WIRE CIRCUIT HANDLE TIES AS FINAL FIELD
INSTALLED WIRING REQUIRES.
CONDUIT AND WIRE CONCEALED, 3/4" UNLESS OTHERWISE NOTED,
CONDUIT USED FOR SWITCH LEGS, AND CONDUIT USED FOR CONTROL
WIRING
CONDUIT AND WIRE EMBEDDED IN CONCRETE OR BELOW GRADE
CONDUIT TURNING DOWN
CONDUIT TURNING UP
CONDUIT DESIGNATIONS
XX-XXX
CONDUIT CONTINUATION
PANEL NAME - CIRCUIT NUMBER
HOME RUNS SHALL USE #12 AWG WIRE UNO.
XX-#
CONDUIT CAPPED FOR FUTURE USE
1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL
DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK.
2. REVIEW ARCHITECTURAL, STRUCTURAL, AND OTHER DRAWINGS FOR
ADDITIONAL SCOPE REQUIREMENTS PRIOR TO BID.
3. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE
SATISFACTION OF THE…