P.O. BOX 10608, NEW ORLEANS, LA 70181

(504) 733-1330 FAX (504) 736-9348

FIRE PUMP TEST

PER

NFPA 20

Property V.A. HOSPITAL Address 2418 CANAL STREET Date 7-28-2015 NEW ORLEANS, LA. 70119 Contractor NORTHSTAR FIRE PROTECTION

Pump Manufacturer AURORA Capacity 1000 GPM 145 PSI Model 12CFM-4 STAGE 150% 1500 GPM 100.5 PSI Serial # 2360595-1 S.O. 0 GPM 180.5 PSI Imp. Dia. 4 @ 9.61" Size 6" �³�; �³