VA PUMP 1 field test report.pdf
PDF 204 KB Posted
- Attached to
- C1NZ--Design Build Project: 629-20-118 CFM - Redesign and Repair Fire and Jockey Pump Systems
- Solicitation number
- 36C25621R0026
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sprinkler - CEP - 3 Standpipes.pdf | ||
| CEP_L01_ALL_FP_NS_FAB.pdf | ||
| CEP_L02_ALL_FP_NS_FAB.pdf | ||
| Section 01 33 23.docx | DOCX document | |
| CEP_L03_ALL_FP_NS_FAB.pdf | ||
| CEP_L02_ALL_FP_NS_FAB.pdf | ||
| CEP_ 3 Standpipes_Sprinkler.pdf | ||
| VA PUMP 2 FIELD TEST REPORT.pdf | ||
| CEP_L04-5_ALL_FP_NS_FAB.pdf | ||
| Section 01 00 00.docx | DOCX document | |
| Section 01 35 26.docx | DOCX document | |
| CEP_L04_ALL_FP_NS_FAB.pdf | ||
| CEP_L01_ALL_FP_NS_FAB.pdf | ||
| 4. VA Master Specs Table of Contents.docx | DOCX document | |
| CEP_L03-5_ALL_FP_NS_FAB.pdf | ||
| Section 01 32 16_15.docx | DOCX document | |
| CEP_Fire_Pump_Test_Method Of Procedure 06-02-16.pdf | ||
| 015-7FX301.pdf | ||
| 016-7FX302.pdf | ||
| 36C25621R0026_1.docx | DOCX document | |
| Section 00 11 21.docx | DOCX document | |
| General Decision LA 20200041 10-09-2020.pdf | ||
| EXHIBIT A CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY.pdf | ||
| 017-7FX501.pdf |
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P.O. BOX 10608, NEW ORLEANS, LA 70181
(504) 733-1330 FAX (504) 736-9348
FIRE PUMP TEST
PER
NFPA 20
Property V.A. HOSPITAL Address 2418 CANAL STREET
Date 7-28-2015 NEW ORLEANS, LA. 70119
Contractor NORTHSTAR FIRE PROTECTION
Pump Manufacturer AURORA Capacity 1000 GPM 145 PSI
Model 12CFM-4 STAGE 150% 1500 GPM 99.7 PSI
Serial # 2360595-0 S.O. 0 GPM 179.0 PSI
Imp. Dia. 4 @ 9.61" Size 6" “X “
RPM __1770_________________________
Controller
Manufacturer METRON Serial # 23120674
Model MP300-125-46--
MTS
H.P. 125 Voltage 460
Phase 3 Cycles 60
Interrupting Capacity 100,000
Electric Motor
Manufacturer U.S. Serial # U10-469831-0001-GT-01
H.P. 125 Voltage 460 AMP 147.0
RPM 1780 Phase 3 Cycles 60 Enclosure WP1
Conductors # Size (To Controller)
Conductors # Size (To Motor))
Transformer
Piping
Sensing Lines Per NFPA 20 Yes No
Check Valves Suction ----- Discharge 6" Bypass ---
OS&Y Valves Suction ---- Discharge 6" Bypass -----
TEST Header 6" with 4 2-1/2 Hose Valves
Roof Manifold
Pump Casing Relief Valve ------- Auto Air Release -------
Gauges: Suction ------ Discharge 3-1/2" System 3-1/2"
Jockey Pump Cut in Pressure: 150 Cut out Pressure: 160
Fire Pump Cut in Pressure: 140 Cut out Pressure: 145
Manual Stop: Auto Stop: XX Time 10 Min. 10 Manual Starts 10 Auto Starts
Remarks: Personnel At Test:
TRANSFER SWITCH TEST NOT COMPLETED AT THIS JESSE KLUPS - NORTHSTAR FIRE PROTECTION
TIME CHUCK RHODES - NORTHSTAR FIRE PROTECTION
JASON CHRISTOPHERSON - NORTHSTAR FIRE PROTEC.
CHRIS FAVA - CMHP
TOM EPPY - CMHP
GERALD FAULKNER - VA HOSPITAL
STEVE ECUYER -AURORA -FLUID PROCESS PUMPS
(504) 733-1330 FAX (504) 736-9348
Property Name: V.A. HOSPITAL PUMP #1
Date: 7-28-2015
Time Electric Motor Pump Pressures Flow Nozzel / Pitot / GPM Total
Volts Amps RPM Suct Disc Net # 1 2 3 4 GPM
487 79 -30' 162 175
10:31 490 79 1783
490 83 1 0
486 124 -30 130 143 1-3/4" 1-3/4"
10:36 488 126 1776 30 35
488 130 2 501 540 1041
485 135 -30 88 101 FLOW Meter
10:44 488 135 1772
488 139 3 1500
Stand Pipe Test Test Conducted By
Static Pressure PSI STEVE ECUYER
Pitot Pressure
GPM Flowing GPM
Flowing Pressure PSI