View the file

Other files

File Type Posted
Sprinkler - CEP - 3 Standpipes.pdf PDF
CEP_L01_ALL_FP_NS_FAB.pdf PDF
CEP_L02_ALL_FP_NS_FAB.pdf PDF
Section 01 33 23.docx DOCX document
CEP_L03_ALL_FP_NS_FAB.pdf PDF
CEP_L02_ALL_FP_NS_FAB.pdf PDF
CEP_ 3 Standpipes_Sprinkler.pdf PDF
VA PUMP 2 FIELD TEST REPORT.pdf PDF
CEP_L04-5_ALL_FP_NS_FAB.pdf PDF
Section 01 00 00.docx DOCX document
Section 01 35 26.docx DOCX document
CEP_L04_ALL_FP_NS_FAB.pdf PDF
CEP_L01_ALL_FP_NS_FAB.pdf PDF
4. VA Master Specs Table of Contents.docx DOCX document
CEP_L03-5_ALL_FP_NS_FAB.pdf PDF
Section 01 32 16_15.docx DOCX document
CEP_Fire_Pump_Test_Method Of Procedure 06-02-16.pdf PDF
015-7FX301.pdf PDF
016-7FX302.pdf PDF
36C25621R0026_1.docx DOCX document
Section 00 11 21.docx DOCX document
General Decision LA 20200041 10-09-2020.pdf PDF
EXHIBIT A CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY.pdf PDF
017-7FX501.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P.O. BOX 10608, NEW ORLEANS, LA 70181

(504) 733-1330 FAX (504) 736-9348

FIRE PUMP TEST

PER

NFPA 20

Property V.A. HOSPITAL Address 2418 CANAL STREET

Date 7-28-2015 NEW ORLEANS, LA. 70119

Contractor NORTHSTAR FIRE PROTECTION

Pump Manufacturer AURORA Capacity 1000 GPM 145 PSI

Model 12CFM-4 STAGE 150% 1500 GPM 99.7 PSI

Serial # 2360595-0 S.O. 0 GPM 179.0 PSI

Imp. Dia. 4 @ 9.61" Size 6" “X “

RPM __1770_________________________

Controller

Manufacturer METRON Serial # 23120674

Model MP300-125-46--

MTS

H.P. 125 Voltage 460

Phase 3 Cycles 60

Interrupting Capacity 100,000

Electric Motor

Manufacturer U.S. Serial # U10-469831-0001-GT-01

H.P. 125 Voltage 460 AMP 147.0

RPM 1780 Phase 3 Cycles 60 Enclosure WP1

Conductors # Size (To Controller)

Conductors # Size (To Motor))

Transformer

Piping

Sensing Lines Per NFPA 20 Yes No

Check Valves Suction ----- Discharge 6" Bypass ---

OS&Y Valves Suction ---- Discharge 6" Bypass -----

TEST Header 6" with 4 2-1/2 Hose Valves

Roof Manifold

Pump Casing Relief Valve ------- Auto Air Release -------

Gauges: Suction ------ Discharge 3-1/2" System 3-1/2"

Jockey Pump Cut in Pressure: 150 Cut out Pressure: 160

Fire Pump Cut in Pressure: 140 Cut out Pressure: 145

Manual Stop: Auto Stop: XX Time 10 Min. 10 Manual Starts 10 Auto Starts

Remarks: Personnel At Test:

TRANSFER SWITCH TEST NOT COMPLETED AT THIS JESSE KLUPS - NORTHSTAR FIRE PROTECTION

TIME CHUCK RHODES - NORTHSTAR FIRE PROTECTION

JASON CHRISTOPHERSON - NORTHSTAR FIRE PROTEC.

CHRIS FAVA - CMHP

TOM EPPY - CMHP

GERALD FAULKNER - VA HOSPITAL

STEVE ECUYER -AURORA -FLUID PROCESS PUMPS

(504) 733-1330 FAX (504) 736-9348

Property Name: V.A. HOSPITAL PUMP #1

Date: 7-28-2015

Time Electric Motor Pump Pressures Flow Nozzel / Pitot / GPM Total

Volts Amps RPM Suct Disc Net # 1 2 3 4 GPM

487 79 -30' 162 175

10:31 490 79 1783

490 83 1 0

486 124 -30 130 143 1-3/4" 1-3/4"

10:36 488 126 1776 30 35

488 130 2 501 540 1041

485 135 -30 88 101 FLOW Meter

10:44 488 135 1772

488 139 3 1500

Stand Pipe Test Test Conducted By

Static Pressure PSI STEVE ECUYER

Pitot Pressure

GPM Flowing GPM

Flowing Pressure PSI