U. nLight System - Wallpod Scene Control (Basis of Design).pdf

PDF 823 KB Posted

Attached to
C3 Interior LED Lighting
Solicitation number
15F06723Q0000316
Issued by

About this file

This document provides product specifications for nLight Wallpod Scene Control devices. The nPODM xS Series WallPods are single gang, nLight-enabled devices that provide one, two, or four scene control options. They allow selection of custom lighting scenes or activation of global profile scenes. Models include options for the number of scenes and buttons, as well as finishes. Features include communication over the nLight network, remote configuration/upgrading, running local or global scenes, and programming of different scene types. Default settings and example scene configurations are outlined. Installation involves mounting and interconnecting units via CAT5e cabling. Specifications cover electrical ratings, dimensions, environmental tolerances, standards compliance, and warranties.

The related federal contract opportunity is a solicitation from the Department of Justice Federal Bureau of Investigation Headquarters Division for C3 Interior LED Lighting with solicitation number 15F06723Q0000316.

View the file

Other files

File Type Posted
Questions - Answers.xlsx XLSX spreadsheet
Amendment One SF30.pdf PDF
K. RELOC OnePass Cables - Fixture Cable - OFC Series (Basic of Design).pdf PDF
A. BLTR -1x4 Relight LED Light Fixture (Basis of Design).pdf PDF
S. nLight System - Occupancy Sensor (Basis of Design).pdf PDF
D. CJIS Existing Supporting Rooms Light Fixture – F3.pdf PDF
23-0801_Brand Name or Equal for Solicitation.pdf PDF
N. RELOC External Connector - RCAT5.pdf PDF
J. RELOC OnePass Cables - Cable - OC1 Series (Basic of Design).pdf PDF
T. nLight System - Wallpod On & Off Control (Basis of Design).pdf PDF
C. Photometric Analysis with 2BLT2 Light Fixture (Basis of Design).pdf PDF
G. Support Rooms Light Fixture Drawing PDF - Please Request DWG File.pdf PDF
23-0830 C3 LED LGT Control Materials List.xlsx XLSX spreadsheet
M. RELOC OnePass System Drops - Drop Cable (Basis of Design).pdf PDF
O. RELOC Distribution Box Primary (Basis of Design).pdf PDF
E. New Support RM 48-inch LED Strip Light Fixture (Basis of Design).pdf PDF
Q. nLight System - Eclypse Controller (Basis of Design).pdf PDF
15F06723Q0000316 - RFQ.pdf PDF
B. BLT -2x2 LED Light Fixture (Basis of Design).pdf PDF
V. nLight System - Unitouch Touch Screen Wall Switch (Basis of Design).pdf PDF
R. nLight System - 8-Port Bridge (Basis of Design).pdf PDF
L. RELOC OnePass Splitter Splice - OSS Series (Basis of Design).pdf PDF
I. RELOC OnePass Convertor - OC Series (Basis of Design).pdf PDF
F. Photometric Analysis of Support Rooms with Basis of Design Light Fixture.pdf PDF
P. RELOC Rectangular Floor Module.pdf PDF
H. RELOC RRL Universal Fixture Connector for Basis of Design.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight © 2014-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/24/20 nPODM-xS nPODM Example: nPODM 1SB WH

Series # of Scenes Dimming Control Dynamic Color Temp/Humidity nPODM 1SB 1 Scene control (2 buttons) 2S 2 Scene control (2 buttons) 2SB 2 Scene control (4 buttons) 4S 4 Scene control (4 buttons) 4SB 4 Scene control (8 buttons)

[blank] Standard DX1 On/off + raise/ lower control

[blank] Standard EDUTW2 Tunable White GRSC3 Grayscale COLOR3 Color control

WH White IV Ivory GY Gray AL Almond BK Black RD Red

[blank] Standard LT Low temp

OVERVIEW

The nPODM xS Series WallPods are single gang nLight-enabled devices that provide one, two, and four scene control. These units provide a convenient method of selecting a custom lighting control scene for the room in which it is installed, or requesting a global profile scene be run across several remote zones.

By default, however, the buttons of an nPODM xS are configured as on/off toggle switches. Scenes are programmed to these units utilizing available SensorView software.

The nPODM xS has soft-click push-buttons with a green LED indicator for each button. These button are field replaceable and can be custom engraved. Two RJ-45 connectors allow the nPODM xS to be daisy-chain wired with CAT-5e cabling to other nLight network devices.

The nPODM xSB offers individual on/off buttons for each scene. Pressing the “on” button will reset the expiration time of a scene back to the original programmed time.* *In order to utilize a blink warning, system gateway and additional programming is required.

nPODM xSB WallPods are not recommended for use with “preset” style scenes.

FEATURES

• Communicates w/ nLight network

• Remotely configurable/upgradable

• Runs locally stored scenes or global scenes (stored on gateway)

• Capable of Programming 4 Different Scene Types

• Local “Profile” Scene — Modifies the operational configuration of up to 80 devices in the local zone.

Stopping scene will revert devices to default settings.

• Local “Preset” Scene — Modifies on/off/dim levels for up to 16 local switch groups.

Exit scene through additional “preset” scene or WallPod control.

• Global “Profile” Scene — Modifies the operational configuration of any devices on the system.

Stopping scene will revert devices to default settings. Scene is stored on the system Gateway, model nGWY2 KIT.

• Global “Preset” Scene — Modifies on/off/dim levels for up to 128 global switch groups.

Exit scene through additional “preset” scene or WallPod control.

• Expiration timer programmable to each scene

• Programmable to initiate occ. sensor time delay sweep

• "Dynamic" options for custom button names when pairing with Acuity Brands nTUNE fixtures

ORDERING INFORMATION

Catalog Number: Date: Project:

nPODM 1SB nPODM 2S(B) nPODM 4S(B)

Notes

1. Available with 2S and 4S versions

2. Available with 4S and 4S DX versions

3. Available with 4S DX version only

Warranty Five-year limited warranty. Complete warranty terms located at:

www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

http://www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nPODM-xS

OVERVIEW

DEFAULT SETTINGS (example) All lights on, dimming photocell enabled Sensors at 10 minute time delay & in AUTO ON/AUTO OFF mode

1 MOVIE MODE

Button in Local Scene mode

Front rows off, middle rows 75% dim, rear rows 50% dim Sensor at 20 minute time delay Sensor LEDs off Photocell Disabled

2 PRESENTER MODE

Button in Local Scene mode

Podium lights on All other rows 60% dim Photocell Disabled

3 ACCENT LIGHTS CONTROL

Button in WallPod

Press to toggle on/off

4 PARKING LOT

Button in Remote Scene mode

Runs profile stored on Gateway to turn on parking lot lights

Below is an outline of example scene configurations for the nPODM 4S. When no local scene is selected, the user configurable device default settings are active.

GRAY

SCALE

FAST

ON

OFF

WHITE

SLOW

nPODM 4S DX GRSC

Custom engraved lettering for WH, IV, AL, and GY units can be specified and ordered at:

http://www.acuitybrands.com/-/media/Files/Acuity/Products/Controls/nLight/NGRAVE%20110%20pdf.pdf?la=en

WHITE COLOR

COLOR

COLOR

ON

OFF

nPODM 4S DX COLORnPODM 4S EDUTW

GENERAL

READING

TESTING

ENERGY

nPODM 4S DX

EDUTW

ON

OFF

GENL READ

TEST ENRGY

Dynamic wallpods below are paired with Acuity Brands nTUNE fixtures for out-of-box operation.

Reference fixture cut sheets for additional details.

nPODM 4SnPODM 2S nPODM 4S DX nPODM 4L DX

SCENE

SCENE

SCENE

SCENE

ON

OFF

LEVEL

LEVEL

LEVEL

LEVEL

ON

OFF

nPODM 4S DXnPODM 4SBnPODM 1SB nPODM 2SB nPODM 2S DX

INSTALLATION

• Mount WallPod using holes that align with standard single gang switch box or low voltage ring

• Access RJ-45 ports by sliding plastic guard up

• Insert CAT-5e cable(s), T568B wiring convention recommended

• Slide guard back onto metal strap

• Interconnect unit with other nLight devices in lighting zone using CAT-5e cables

• Once power is received via CAT-5e connection, all devices in zone will automatically begin functioning together according to respective device’s defaults

SLID

E

TO RJ-45 PORT

TO RJ-45 PORT

CAT-5

CAT-5

Attention! Only use non-booted CAT5e cables.

http://www.acuitybrands.com/-/media/Files/Acuity/Products/Controls/nLight/NGRAVE%20110%20pdf.pdf?la=en

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nPODM-xS

Electrical Input Ratings 15-24VDC, 5mA, Class 2 (nLight network power)

Mechanical Dimensions 2.74”H x 1.68”W x 1.63”D (70mm x 43mm x 41mm) - does not include ground strap

Mounting Single-Gang Box or Low Voltage Ring Connection Type RJ-45 nLight Network Ports (2)

Environmental Warrantied Operating Temperature 32°F to 140°F (0°C to 60°C)

Relative Humidity Up to 90%, Non-Condensing Standards/ Ratings Energy Management Equipment, UL916 (E167435)

RoHS

Security Complies with California Civil Code Title 1.81.26, Security of Connected Devices, approved under Senate Bill No. 327 (2018)

SPECIFICATIONS

Text Field 1:
Text Field 2:
Text Field 3:
Text Field 4:
Text Field 5:
Text Field 6:
Text Field 7:
Text Field 8:
Text Field 9: