F. Photometric Analysis of Support Rooms with Basis of Design Light Fixture.pdf

PDF 55 KB Posted

Attached to
C3 Interior LED Lighting
Solicitation number
15F06723Q0000316
Issued by

About this file

This photometric analysis report provides lighting calculations for two mechanical rooms in an FBI building. It details the existing and proposed lighting layouts and fixtures for Room 1 and Room 2, including luminaire schedules, light level measurements at workplane and ceiling heights, and calculation summaries. For Room 1, the report models replacing the existing fixtures with seven Lithonia ZL1D 5000K LED downlights outputting 5457 lumens each. For Room 2, it analyzes installing 20.8 footcandles of average illumination at the workplane using an unspecified number and type of new fixtures. The related federal contract opportunity is a solicitation from the Department of Justice FBI Headquarters Division for interior LED lighting under number 15F06723Q0000316.

View the file

Other files

File Type Posted
Questions - Answers.xlsx XLSX spreadsheet
Amendment One SF30.pdf PDF
K. RELOC OnePass Cables - Fixture Cable - OFC Series (Basic of Design).pdf PDF
A. BLTR -1x4 Relight LED Light Fixture (Basis of Design).pdf PDF
S. nLight System - Occupancy Sensor (Basis of Design).pdf PDF
D. CJIS Existing Supporting Rooms Light Fixture – F3.pdf PDF
23-0801_Brand Name or Equal for Solicitation.pdf PDF
N. RELOC External Connector - RCAT5.pdf PDF
J. RELOC OnePass Cables - Cable - OC1 Series (Basic of Design).pdf PDF
T. nLight System - Wallpod On & Off Control (Basis of Design).pdf PDF
C. Photometric Analysis with 2BLT2 Light Fixture (Basis of Design).pdf PDF
U. nLight System - Wallpod Scene Control (Basis of Design).pdf PDF
G. Support Rooms Light Fixture Drawing PDF - Please Request DWG File.pdf PDF
23-0830 C3 LED LGT Control Materials List.xlsx XLSX spreadsheet
M. RELOC OnePass System Drops - Drop Cable (Basis of Design).pdf PDF
O. RELOC Distribution Box Primary (Basis of Design).pdf PDF
E. New Support RM 48-inch LED Strip Light Fixture (Basis of Design).pdf PDF
Q. nLight System - Eclypse Controller (Basis of Design).pdf PDF
15F06723Q0000316 - RFQ.pdf PDF
B. BLT -2x2 LED Light Fixture (Basis of Design).pdf PDF
V. nLight System - Unitouch Touch Screen Wall Switch (Basis of Design).pdf PDF
R. nLight System - 8-Port Bridge (Basis of Design).pdf PDF
L. RELOC OnePass Splitter Splice - OSS Series (Basis of Design).pdf PDF
I. RELOC OnePass Convertor - OC Series (Basis of Design).pdf PDF
P. RELOC Rectangular Floor Module.pdf PDF
H. RELOC RRL Universal Fixture Connector for Basis of Design.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D a te :7

/2

/2

P a g e

L a F a ce

M cG o ve rn A ss o c.

I n c

Z a n e L e e p e r

T e ch

S u p p o rt

A p p lic a ti o n s

E n te rp ri se B lv d

B e th e l P a rk

P a

-8

-3

E -m a il zl e e p e r@ la fa ce -m cg o ve rn .c o m

P ro je ct

F

B I B

U

IL

D

IN

G

M

E C

H R

O O

M S

"F3"

S

ROOM 1

15'-5"

12'-0"

23 27 28 28 28 27 23

29 34 35 35 35 34 29

32 37 38 39 38 37 32

32 37 39 39 39 37 32

32 37 39 40 39 37 32

32 36 39 39 38 36 32

29 33 35 35 35 33 29

23 27 28 28 28 26 23

"F3"

S

ROOM 2

9'-0"

20'-8"

16 20 23 25 26 26 25 24 22

20 26 29 31 32 33 32 30 28

22 28 32 34 35 36 35 33 30 25

21 27 30 32 34 34 33 31 29 24

17 22 25 26 28 28 27 26 23 19

NOTES:

1. All light levels are at workplane as indicated

2. Lumen output is based on anticipated lumen output at 1/2 the life of the LEDs

3. Light levels are calculated based reflectance values of 40 / 30 / 10

4. All lumen output is based on IES mandated of 25C, unless otherwise noted

5. Results are based on information provided to L& M. Changes to location, fixture, wattage will affect final results

Luminaire Schedule

Label Symbol Qty LLD [MANUFAC] Description Lum. Watts Lum. Lumens

F3 7 0.850 Lithonia Lighting ZL1D L48 5000LM FST MVOLT 35K 80 CRI 40.56 5457

Calculation Summary

Label Avg Max Min Avg/Min Max/Min

5.6 7 3 1.9 2.3

ROOM 1_Workplane 32.9 40 23 1.4 1.7

ROOM 2_Ceiling 4.3 5 3 1.4 1.7

ROOM 2_Workplane 27.4

ROOM 1_Ceiling

36 16 1.7 2.3