This file provides product specifications for nLight networked ceiling occupancy sensors. The S. nLight System - Occupancy Sensor (Basis of Design) document outlines technical details for the nCM xx RJB family of ceiling/surface mount occupancy sensors. Key details include 100% digital PIR detection with optional dimming photocell and auxiliary low voltage relay features. The sensors utilize adjustable settings that can be controlled via push-button or software application. Coverage patterns and mounting options are specified for small, large, and high motion detection applications. Installation instructions and wiring diagrams are provided for connecting the sensors to nLight dimming packs, relay packs, and enabled luminaires. Environmental ratings and agency standards compliance are noted.

The related federal contract opportunity is a solicitation from the Department of Justice Federal Bureau of Investigation Headquarters Division for C3 Interior LED Lighting. No further specifics on required products, response dates, or award details are provided in the opportunity description.

View the file

Other files

File Type Posted
Questions - Answers.xlsx XLSX spreadsheet
Amendment One SF30.pdf PDF
K. RELOC OnePass Cables - Fixture Cable - OFC Series (Basic of Design).pdf PDF
A. BLTR -1x4 Relight LED Light Fixture (Basis of Design).pdf PDF
D. CJIS Existing Supporting Rooms Light Fixture – F3.pdf PDF
23-0801_Brand Name or Equal for Solicitation.pdf PDF
N. RELOC External Connector - RCAT5.pdf PDF
J. RELOC OnePass Cables - Cable - OC1 Series (Basic of Design).pdf PDF
T. nLight System - Wallpod On & Off Control (Basis of Design).pdf PDF
C. Photometric Analysis with 2BLT2 Light Fixture (Basis of Design).pdf PDF
U. nLight System - Wallpod Scene Control (Basis of Design).pdf PDF
G. Support Rooms Light Fixture Drawing PDF - Please Request DWG File.pdf PDF
23-0830 C3 LED LGT Control Materials List.xlsx XLSX spreadsheet
M. RELOC OnePass System Drops - Drop Cable (Basis of Design).pdf PDF
O. RELOC Distribution Box Primary (Basis of Design).pdf PDF
E. New Support RM 48-inch LED Strip Light Fixture (Basis of Design).pdf PDF
Q. nLight System - Eclypse Controller (Basis of Design).pdf PDF
15F06723Q0000316 - RFQ.pdf PDF
B. BLT -2x2 LED Light Fixture (Basis of Design).pdf PDF
V. nLight System - Unitouch Touch Screen Wall Switch (Basis of Design).pdf PDF
R. nLight System - 8-Port Bridge (Basis of Design).pdf PDF
L. RELOC OnePass Splitter Splice - OSS Series (Basis of Design).pdf PDF
I. RELOC OnePass Convertor - OC Series (Basis of Design).pdf PDF
F. Photometric Analysis of Support Rooms with Basis of Design Light Fixture.pdf PDF
P. RELOC Rectangular Floor Module.pdf PDF
H. RELOC RRL Universal Fixture Connector for Basis of Design.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight © 2014-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/26/23 nCM xx RJB — TN-139-001

OVERVIEW

The nCM xx RJB family of nLight ceiling/surface mount occupancy sensors provide a range of networked sensor solutions for applications with finished ceilings (e.g. ceiling tiles, sheetrock, plaster). nCM xx RJB family sensors utilize 100% digital Passive Infrared (PIR) detection and are available with several lens options, providing flexibility for multiple mounting height and coverage pattern requirements. Dual technology occupancy detection can also be added as an option for applications where occupants are stationary for long periods of time. nCM xx RJB family sensors are also available with an optional auxiliary low voltage relay for simple integration with a BMS system or other building system.

nCM xx RJB family sensors are powered via the nLight network bus and typically communicate with one or more nLight enabled luminaires (e.g. Lithonia VTLED Series) or nLight relay/dimming packs to enable control of fixtures individually or in groups. These configurations work standalone and do not require a connection to a larger nLight network.

FEATURES

• 100% digital PIR detection

• Optional dimming photocell (ADCX option)

• Optional auxiliary low voltage relay (AR option) for dry contact output – relay only tracks occupancy by default, ignoring switch and photocell commands

• LED status indicator

• Adjustable settings (e.g. occupancy time delays, photocell set-points) via push-button or SensorView software application

• Broadcasts occupancy and photocell information over a local nLight channel

• Remotely upgradeable firmware

Catalog Number: Date: Project:

nCM xx RJB nCM PDT xx RJB nCM 9 RJB nCM PDT 9 RJB nCM 10 RJB nCM PDT 10 RJB nCM 6 RJB

Buy American Act Product with the BAA option is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations.

Please refer to www.acuitybrands.com/buy-american for additional information.

Warranty Five-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions

Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

Items marked by a shaded background qualify for the Design Select program and ship in 15 days or less. To learn more about Design Select, visit www.acuitybrands.com/designselect.

*See ordering tree for details

Capable This item is an A+ capable component, which has been designed and tested to provide out-of-the-box luminaire compatibility with simple commissioning, when included as part of an A+ Certified™ Solution.

To learn more about A+, visit www.acuitybrands.com/aplus.

https://www.acuitybrands.com/buy-american https://www.acuitybrands.com/support/warranty/terms-and-conditions https://www.acuitybrands.com/designselect nCM xx RJB — TN-139-001 nCM xx RJB Example: nCM PDT 9 ADCX RJB

Series / Detection Coverage Type Options (See Below) RJ45 Port Location Buy America(n)2 nCM PIR Detection nCM PDT Dual Tech

(PIR/ Microphonics)

9 Small Motion 360° 10 Large Motion 360 ° 6 High Mount 360 ° (not available with PDT version)

RJB Rear RJ45 (CAT5e patch cable & RJ45 splitter included) blank Standard BAA Buy America(n) Act

Compliant

ORDERING INFORMATION

nCM xx RJB Options

Photocell Auxiliary Relay Preset Type 1 Time Delay Temp/ Humidity

[blank] Standard (No photocell) ADCX Automatic Dimming Control

(of remote dimming output)

[blank] None AR Low Voltage Aux. Relay

[blank] Single Time Delay 2P Dual Time Delay

[blank] Standard 15M 15 Minutes 20M 20 Minutes 30M 30 Minutes

[blank] Standard LT Low Temp / High

Humidity

NOTES:

1. Not available with AR or ADCX options.

2. Not available with AR, 2P, Time Delay, or LT options

COVERAGE PATTERNS*

HIGH MOUNT 360º (Model # nCM 6)

• Best choice for 15 to 45 ft (4.57 to 13.72 m) mounting heights

• 15 to 20 ft (4.57 to 6.10 m) radial coverage overlaps area lit by a typical high bay fixture

• Excellent detection of large motion (e.g.

walking) up to 35 ft (10.76 m)

• Excellent detection of extra large motion (e.g.

forklifts) up to a 45 ft (13.72 m)

30 20 10 0 ft 10 20 30

9.1 6 3 0 m 3 6 9.1

0 ft

0 m

4.6

9.1

13.7

LOW VIEW HIGH VIEW

0 ft

0 m

4.6

20 10 0 ft 10 20

6 3 0 m 3 6

30 20 10 0 ft 10 20 30

9.1 6 3 0 m 3 6 9.1

0 ft

0 m

4.6

9.1

13.7

LOW VIEW HIGH VIEW

0 ft

0 m

4.6

20 10 0 ft 10 20

6 3 0 m 3 6

• Best choice for large motion detection (e.g.

walking)

• 360º conical shaped pattern

• Provides ~24 ft (7.32 m) radial coverage

(~2000 ft2) when mounted at 9 ft (2.74 m)

• 7 to 15 ft (2.13 to 4.57 m) mounting heights provide 16 to 36 ft (4.88 to 10.97 m) radial coverage

• Detection range improves when walking across beams compared to into beams

LARGE MOTION 360º (Model # nCM 10/nCM PDT 101)

0 ft

0 m

2.7

28 21 14 7 0 ft 7 14 21 28

8.5 6.4 4.3 2.1 0 m 2.1 4.3 6.4 8.5

SIDE VIEW TOP VIEW

0 ft

8.5

4.3

0 m

4.3

8.5

1 Sensors with Microphonics™ provides overlapping detection of human activity over the complete PIR coverage area. Advanced filtering is also utilized to prevent non-occupant noises from keeping the lights on.

• Best choice for small motion (e.g. hand movements) detection

• 360º conical shaped pattern

• Provides 12 ft (3.66 m) radial coverage (~500 ft2) when mounted to standard 9 ft (2.74 m) ceiling

• 8 to 15 ft (2.44 to 4.57 m) mounting heights provide 10 to 20 ft (3.05 to 6.10 m) radial coverage

SMALL MOTION 360º (Model # nCM 9/nCM PDT 91)

12 6 0 ft 6 12

3.7 1.8 0 m 1.8 3.7

SIDE VIEW

0 ft

0 m

2.7

TOP VIEW

0 ft

3.7

1.8

0 m

1.8

3.7

1 Sensors with Microphonics™ provides overlapping detection of human activity over the complete PIR coverage area. Advanced filtering is also utilized to prevent non-occupant noises from keeping the lights on.

* Coverage pattern shown is derived from NEMA WD7 testing

Design Select options indicated by this color background.

nCM xx RJB — TN-139-001

Wiring an nCM xx ADCX RJB to an nLight Dimming Pack

Wiring to an nLight Enabled Luminaire

Wiring to an nLight Relay Pack

TYPICAL APPLICATIONS

The following instructions are for mounting sensor directly to a ceiling tile or sheetrock surface.1 Sensor’s mounting holes also align with standard round fixture or single gang handy box (screws not provided).

1. Using template included with unit, mark spots on ceiling tile/sheetrock for cable hole and mounting anchors/screws

2. Drill 1/2” hole through ceiling surface at location indicated on template

3. Insert provided anchors into ceiling surface at locations indicated on template

4. Remove provided RJ-45 splitter from sensor’s attached CAT5e cable and then thread cable (and low voltage wires if -AR option included) through hole from underside

5. Mount sensor to anchors using two screws provided

6. Attach provided RJ45 splitter device (model CAT5 Y) above ceiling to cable from sensor

(see diagram on right)

7. Interconnect CAT-5e cables to/from rest of nLight zone to RJ45 splitter 2

8. Once power is received via CAT-5e connection, all devices in zone will automatically begin functioning together according to each device’s defaults

9. Install decorative sensor lid by rotating clockwise

10. Refer to included instruction card for default settings and directions on push-button programming.

CAT-5e

BRN

BRN

CAT-5e Splitter

CAT-5e CAT-5e

- AR option (contact closure) to/from nLight Zone

TYPICAL APPLICATIONS

nPP16

WHT (neutral)

BLU (line in)

BLU (line out)

CAT-5e

120 VAC

OR

277 VAC1

BLK1 (line in)

ORN1 (line in)

LOAD

To other nLight devices (optional)

CAT-5e CAT-5e Splitter

(included)

CAT-5e CAT-5e

To other nLight devices (optional) nCM xx RJB

WHT(neutral)

BLU (line in)

BLU (line out)

VIO (low voltage dim out)

GRY (low voltage common)

GRN

CAT-5e nPP16 D or nPP16 DS

0-10 VDC

Ballast or

LED Driver

120 VAC

OR

277 VAC1 ORN1 (line in)

BLK1 (line in)

To other nLight devices (optional)

CAT-5e Splitter (included)

CAT-5e CAT-5e

To other nLight devices (optional) nCM xx ADCX RJB

CAT-5e To other nLight devices (optional) nLight Enabled Luminaire

CAT-5e Splitter (included)

CAT-5e CAT-5e To other nLight devices (optional) nCM xx RJB or nCM xx ADCX RJB

Note:

1. Recommended mounting 4’ or more away from HVAC vents.

2. T568B pin/pair assignment is recommended for all CAT-5e cables. Sensor power is provided via a CAT-5e connection to an nLight power pack/supply, nLight enabled digital luminaire, or nLight Bridge.

nCM xx RJB — TN-139-001

Electrical Input Ratings 15-24VDC, 3mA, Class 2 (nLight network power)

Output Ratings 24 VAC/VDC, 1A - Resistive (AR option)

Relay Type Latching (AR option)

Standards/ Ratings Energy Management Equipment, UL916 (E167435)

Mechanical Dimensions 4.55”W x 1.55”D (116mm x 40mm)

Mounting Single-Gang or Octagonal Box, Surface Mount

Color White

Finish Matte Connection Type RJ-45 nLight Network Ports (2 ports via included RJ-45 splitter)

Low-Voltage Leads (AR option)

Environmental Warrantied Operating Temperature Standard: 14°F to 185°F (-10°C to 85°C) PDT option: 14°F to 140°F (-10°C to 60°C) LT option: -4°F to 185°F (-20°C to 85°C) PDT LT options: -4°F to 140°F (-20°C to 60°C)

Relative Humidity Up to 90%, Non-Condensing Standards/ Ratings RoHS

General Standards/ Ratings System Component to aid in compliance with Title 24, ASHRAE 90.1, IECC

SPECIFICATIONS

Catalog Number 2:
Date 2:
Project 2:
Text Field 1:
Text Field 2:
Text Field 3:
Text Field 4:
Text Field 6:
Text Field 7:
Text Field 8:
Text Field 9:
Text Field 10:
Text Field 11:

File details come from the government source that posted it. Updated .