J. RELOC OnePass Cables - Cable - OC1 Series (Basic of Design).pdf
PDF 650 KB Posted
- Attached to
- C3 Interior LED Lighting
- Solicitation number
- 15F06723Q0000316
About this file
This document provides product specifications for one-pass cables used in relocatable wiring systems. The cables include OFC fixture cables, OC1 cable 1-port, OC2 cable 2-port, and OC3 cable 3-port. The specifications cover intended use, electrical ratings, listing information, dimensions, ordering instructions, and accessories. Voltages range from 120V to 480V, and conductor sizes are from 10AWG to 18AWG. Lengths are available from 1 foot to 50 feet. Options include extreme temperature ratings, healthcare facility requirements, converter cables, modular plugs, and pre-terminated CAT5 cables.
The related federal contract opportunity is a solicitation from the Department of Justice Federal Bureau of Investigation Headquarters Division for interior LED lighting. The solicitation number is 15F06723Q0000316 and the opportunity type is listed as a solicitation. No further details are provided on the products or services required, response dates, or other salient information.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OFC_OC1_OC2_OC3
Catalog Number
Notes Type
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 1996-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/19/23
FEATURES & SPECIFICATIONS
INTENDED USE
The OnePass Fixture Cable (OFC), Cable 1 port (OC1), Cable 2 port (OC2), and Cable 3 Port (OC3) are male/female cables that provides additional length throughout the RELOC system.
Cables can also provide power to miscellaneous devices such as exits, emergency units, convenience power and access floor systems. The OFC attaches directly into the access plate or through any 1/2” trade-size knockout. The OC2 is a splitter and cable extender in one easy-to-use component. The OC2 All Metal Housings (AMH) provides installers options for how to configure the system based on specification requirements. The OC3 is a splitter and cable extender in one component.
ELECTRICAL
• Rated for use on 20-amp branch circuits.
• Safety-keying prevents accidental mating of components with different voltages.
• C12S option includes three 12 AWG conductors and 18 AWG shielded pair for controls wiring. (-20°C to +90°C).
• The OC2 conductors are 10 AWG or 12 AWG copper conductors with -20°C to +90°C thermoplastic insulation rated 600V. It includes a fully rated No. 12 AWG & 10 AWG grounding conductor.
• The OC1, OC2 with AMH option, and OC3 are 12 AWG copper with -20°C to +90°C thermoplastic insulation rated 600V. It includes a fully rated No. 12 AWG grounding conductor.
• The OFC Fixture leads are No. 18 AWG solid copper with pre-stripped , solid-color leads for easy installation into side, back or push-in-type terminals.
SYSTEM FEATURES
• Pin and socket contacts.
• Color-coded labels for quick voltage identification.
• Available in varying lengths to suit most common fixture spacing requirements.
• Auto-latching springs prevent accidental disengagement.
• Available with green armor standard for easy identification in healthcare facilities (HCF option).
• Dust Cover available for unused ports: RDC3 METAL DUST COVER CSA/UL J50 (available job pack of 50 only)
• The OC1, OC2, and OC3 EXT option enables them to be installed in hot and cold applications
(-40° to +90°C).
• Type of insulation for EXT option is based on NEC Table 310.104(A).
• Non-plenum rated OC2 plastic housing.
• Plenum rated low voltage cable (LVC option)
• The OC1 QFOP and 820OP cable options provide a conversion between legacy RELOC wiring systems. The male end will be the legacy system and the female end will be the One Pass OC1.
LISTINGS
• C-UL-US listed for indoor, dry, and accessible locations
• Meets or exceed all the requirements of UL183 and NEC (NFPA70) Article 604 for manufactured wiring systems
• C12S option meets NEC requirements for separation of Class 2 and Class 3 circuits from Class 1 circuits by a barrier as defined by Article 725.136(B).
• Meets NEC requirements for redundant ground paths for patient care areas in healthcare facilities (HCF option).
• Canadian Patent No. 2,845,603 (Class l, Class ll)
BUY AMERICAN ACT
This product is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations.
Please refer to www.acuitybrands.com/resources/buy-american for additional information.
WARRANTY
• 5-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at:
www.acuitybrands.com/support/warranty/terms-and-conditions
Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.
OnePass® Cables
OFC, OC1, OC2, OC3
OC1
Cable 1 Port
OC2
Cable 2 Port
OC3
Cable 3 Port
OFC
Fixture Cable mailto:techsupportreloc%40acuitybrands.com?subject= https://reloc.acuitybrands.com/ https://www.acuitybrands.com/resources/buy-american http://www.acuitybrands.com/support/warranty/terms-and-conditions
OnePass® Cables
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 1996-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/19/23
Series Voltage Conductors Length Controls Wiring Color Options
OC2 120 120V
208 208V 240 240V 277 277V 347 347V 480 480V
10/2G Three 10 AWG conductors, including one 10 AWG ground
10/3G Four 10 AWG conductors, including one 10 AWG ground
10/4G Five 10 AWG conductors, including one 10 AWG ground
12/2G Three 12 AWG conductors, including one 12 AWG ground
12/3G Four 12 AWG conductors, including one 12 AWG ground
12/4G Five 12 AWG conductors, including one 12 AWG ground
01 ft up to 75 ft
(blank) Not required
C12S Integrated CI,CII rated line voltage and signal wires ‡
(blank) Not required
RD Red ‡
(blank) Not required
2N Two circuit, two neutral ‡
AMH All metal housings ‡
EXT Extreme temperature rating conductors ‡
ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC2 277 12/4G 25
‡ Option Value Ordering Restrictions
Option value Restriction 2N 2N option available only in 120V, 277V and 347V, Available with 12/4G conductors only.
820OP Converter cables used to convert 820 legacy system to OnePass. Only available in 1ft lengths, 120 or 277 volt. 820OP must be ordered with 12/4G.
C12S C12S must use 12/2G conductors.
CAT5_ Must specify length. Example: CAT510. See spec sheet RCAT5 for details. CAT5 length must be 2FT longer than OC1. When used with OCS, OCU or OD fixture drop, CAT5 length must include the length of the OC1 and the length of drop for the fixture plus 2FT.
HCF HCF available with 12/4G conductors only. HCF not available with controls wiring options C12S or CAT5.
QFOP Converter cables used to convert QF legacy system to OnePass. Only available in 1ft lengths, 120 or 277 volt. QFOP must be ordered with 12/3G.
RD Non-plenum rated color cable available up to 35ft only.
X Available with 12/3G conductors only. Hot conductors 1 and 2 alternate internally to the cable.
‡ Option Value Ordering Restrictions
Option value Restriction 2N 2N option available only in 120V, 277V and 347V, Available with 12/4G conductors only.
AMH Available with 12/2G, 12/3G, 12/4G conductors.
C12S C12S must use 12/2G conductors.
EXT Required for EXTREME hot and cold temperature applications (-40° to 90°C). Available with 10/2G, 10/3G, 12/2G, and 12/3G conductors.
RD Non-plenum rated color cable available up to 35ft only.
Series Voltage Conductors Length Conversion Connector Controls Wiring
OC1 120 120V
208 208V 240 240V 277 277V 347 347V 480 480V
12/2G Three 12 AWG conductors, including one 12 AWG ground
12/3G Four 12 AWG conductors, including one 12 AWG ground
12/4G Five 12 AWG conductors, including one 12 AWG ground
01 ft up to 50 ft 820OP 820 system to OnePass system converter cable ‡
QFOP QuickFlex system to OnePass system converter cable ‡
(blank) Not required
C12S Integrated CI,CII rated line voltage and signal wires ‡
ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC1 277 12/3G 09
Color Options CAT5 Cable
(blank) Not required
RD Red ‡
(blank) Not required
2N Two circuit, two neutral ‡
HCF Meets healthcare facility requirements ‡
X Cross Over Cable ‡
(blank) Not required
CAT5_ Pre-terminated and tested CAT5 cable attached ‡ mailto:techsupportreloc%40acuitybrands.com?subject= https://reloc.acuitybrands.com/ https://img.acuitybrands.com/public-assets/catalog/148375/rcat5.pdf
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 1996-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/19/23
Series Voltage Conductors Length Modular Plug Controls Wiring Options CAT5 Cable
OFC 120 120V
208 208V 240 240V 277 277V 347 347V 480 480V
12/2G Three 12 AWG conductors, including one 12 AWG ground
12/3G Four 12 AWG conductors, including one 12 AWG ground
12/4G Five 12 AWG conductors, including one 12 AWG ground
01 ft up to 50 ft
(blank) Not required
RRL RELOC® - Ready Luminaire Universal Fixture Connector ‡
(blank) Not required
C12S Integrated CI,CII rated line voltage and signal wires ‡
(blank) Not required
2N Two circuit, two neutral ‡
G Ground wire ‡
HCF Meets healthcare facility requirements ‡
X Cross Over Cable ‡
(blank) Not required
CAT5_ Pre-terminated and tested CAT5 cable attached ‡
ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OFC 277 12/3G 11
‡ Option Value Ordering Restrictions
Option value Restriction 2N 2N option available only in 120V, 277V and 347V, Available with 12/4G conductors only.
C12S C12S must use 12/2G conductors. G option required with C12S.
CAT5_ Must specify length. Example: CAT510. See spec sheet RCAT5 for details. CAT5 length must be 2FT longer than OC1. When used with OCS, OCU or OD fixture drop, CAT5 length must include the length of the OC1 and the length of drop for the fixture plus 2FT.
G Required for use in Canada. Required for C12S, HCF and RRL option.
HCF Available with 12/4G conductors only. HCF not available with controls wiring options C12S or CAT5. G option required with HCF.
RRL If RRL selected, fixture must have RRL and wiring instruction. See fixture spec sheet for details. See RRL spec sheet for connector details. G option required with RRL.
X Available with 12/3G conductors only. Hot conductors 1 and 2 alternate internally to the cable.
Series Voltage Conductors Length Color Options
OC3 120 120V
208 208V 240 240V 277 277V 347 347V 480 480V
12/2G Three 12 AWG conductors, including one 12 AWG ground
12/3G Four 12 AWG conductors, including one 12 AWG ground
12/4G Five 12 AWG conductors, including one 12 AWG ground
01 ft up to 50 ft (blank) Not required
RD Red ‡
(blank) Not required
2N Two circuit, two neutral ‡
EXT Extreme temperature rating conductors ‡
ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC3 277 12/3G 15
‡ Option Value Ordering Restrictions
Option value Restriction 2N 2N option available only in 120V, 277V and 347V. Available with 12/4G conductors only.
EXT Required for EXTREME hot and cold temperature applications (-40° to 90°C). Available with 10/2G, 10/3G, 12/2G, and 12/3G conductors.
RD Non-plenum rated color cable available up to 35ft only.
mailto:techsupportreloc%40acuitybrands.com?subject= https://reloc.acuitybrands.com/ https://img.acuitybrands.com/public-assets/catalog/148375/rcat5.pdf https://img.acuitybrands.com/public-assets/catalog/248102/rrl.pdf
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 1996-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/19/23
DIMENSIONS
Dimensions are shown in inches (millimeters)
A – Die-cast zinc with zinc-plated CRS cover B – UL recognized connector body C – Tin-plated brass contacts D – MC Cable standard. HCF MC, C12S MC optional, Isolated ground wire standard with flexible metal conduit.
E – 18-gauge galvanized steel cover, zinc alloy casting
OC1 – Cable 1 Port
OC1 – Converter Cable: Option (820OP)
OC1 – Converter Cable: Option (QFOP)
2-1/4 (58)
2-3/16 (55.6)
AB
D C
9/16 (14.3)
7/16 (11.1)
3-1/4 (82.6)
3-3/8 (87.5)
2-1/4 (58)
2-3/16 (55.6)
AB
D C
9/16 (14.3)
7/16 (11.1)
3-1/4 (82.6)
3-3/8 (87.5)
3-1/2 (89)
5/8 (16)
2-1/8 (54)
E
2-3/16 (55.6)
AB
D C
9/16 (14.3)
3-3/8 (87.5) mailto:techsupportreloc%40acuitybrands.com?subject=
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 1996-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/19/23
DIMENSIONS
Dimensions are shown in inches (millimeters)
3-1/4 (82.6)
4-1/2 (114.3)
1-1/8 (28.6)A
B 7/16 (11.2)
2-1/4 (57.2)
2-1/4 (57.2)
D
C
A – Injection-molded, high-impact polymeric compound enclosure B – Tin-plated, brass contacts C – MC Cable standard. C12S MC optional, Isolated ground wire standard with flexible metal conduit.
D – 18-gauge galvanized steel cover, zinc alloyed casting
OC2 – Cable 2 Port
2-1/4 (58)
7/16" (11.1)
5/8" (16)
2 1/4 (58)
3 3/8" (87.5)
4 9/16" (116)
A B
C
D
A – Die-cast zinc with zinc-plated CRS cover B – UL recognized connector body C – Tin-plated brass contacts D – MC Cable standard. HCF MC, C12S MC optional, Isolated ground wire standard with flexible metal conduit.
OC3 – Cable 3 Port mailto:techsupportreloc%40acuitybrands.com?subject=
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 1996-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/19/23
A – UL-recognized connector body B – Die-cast zinc with zinc-plated CRS cover C – Tin-plated, brass contacts D – Cast snap-in fitting fits 1.2” trade-size K.O. and provides grounding E – No. 18 AWG solid copper wires rated at 600V, 90°C thermoplastic insulation with stripped leads F – MC cable standard. HCF MC, C12S MC optional.
NOTES
• One, two or three hot conductors in 120V and 277V as required.
• Rated for 20-amp capacity.
• Prefabricated standard selector cable carrying No. 12 AWG copper conductors. 600V, 90°C thermoplastic insulation and fully rated bare grounding conductor.
• Standard selector cable provides auto-grounding to fixture unless specified otherwise.
B
F
C D
A
2-1/4 (58)
2-3/16 (55.6)
7/16 (11.1)
9/16 (14.3)
1-1/4 (31.8)
3-3/8 (87.5)
3-1/4 (82.6)
E
E
DIMENSIONS
Dimensions are shown in inches (millimeters)
OFC - Fixture Cable
SYSTEM VIEW
System View designs are for illustrative purposes only.
OC1
OFC
OFC
OC
OST
OnePass OFC Wire Color Chart 120V, 277V, 347V Standard Wire Colors
Position 1 2 3 4 5 Conductor Ground Hot #1 Hot #2 Hot #3 Neutral #1
120V & 347V Bare or Green Black Red Blue White 277V Bare or Green Brown Orange Yellow Gray
208V, 240V, 480V Standard Wire Colors Position 1 2 3 4 5 Conductor Ground Hot #1 Hot #2 Hot #3 Hot #4
208V & 240V Bare or Green Black Red Blue Violet 480V Bare or Green Brown Orange Yellow Violet
120V, 277V, 347V Two Circuit, Two Neutral (2N option) Position 1 2 3 4 5 Conductor Ground Hot #1 Hot #2 Neutral #2 Neutral #1
120V & 347V Bare or Green Black Red Gray White 277V Bare or Green Brown Orange White Gray
120V, 277V, 347V Class I, Class II (C12S option) Position 1 2 3 4 5 Conductor Hot #1 Neutral #1 Ground Data #1 Data #2
120V & 347V Black White Bare or Green Violet Pink (or Gray) 277V Brown Gray Bare or Green Violet Pink (or Gray)
208V & 240V Brown Orange Bare or Green Violet Pink (or Gray) 480V Brown Orange Bare or Green Violet Pink (or Gray)
Note: Wire colors are specific for cables with exposed wireleads.
mailto:techsupportreloc%40acuitybrands.com?subject= https://reloc.acuitybrands.com/
| Catalog Number 5: |
| Page 1: |
| Notes 5: |
| Page 1: |
| Type 5: |
| Page 1: |
| Text Field 38: |
| Text Field 39: |
| Text Field 40: |
| Text Field 41: |
| Text Field 42: |
| Text Field 43: |
| Text Field 44: |
| Text Field 52: |
| Text Field 53: |
| Text Field 54: |
| Text Field 55: |
| Text Field 56: |
| Text Field 57: |
| Text Field 58: |
| Text Field 66: |
| Text Field 67: |
| Text Field 59: |
| Text Field 60: |
| Text Field 61: |
| Text Field 62: |
| Text Field 63: |
| Text Field 64: |
| Text Field 65: |
| Text Field 45: |
| Text Field 46: |
| Text Field 47: |
| Text Field 48: |
| Text Field 49: |
| Text Field 51: |
| Text Field 68: |
File details come from the government source that posted it. Updated .