I. RELOC OnePass Convertor - OC Series (Basis of Design).pdf
PDF 738 KB Posted
- Attached to
- C3 Interior LED Lighting
- Solicitation number
- 15F06723Q0000316
About this file
This document provides product specifications for OnePass converters, starter fixture cables, and starter cable 2 port products used in modular wiring systems. The components include connectors, cables, and housing units available in various voltage ratings and conductor configurations. Key features include auto-latching springs, color-coded labels, integrated low voltage control options, extreme temperature ratings, and healthcare facility requirements. Dimensions, construction details, and wiring diagrams are provided.
The related federal contract opportunity is a solicitation from the Department of Justice Federal Bureau of Investigation Headquarters Division seeking interior LED lighting under solicitation number 15F06723Q0000316. The opportunity type is listed as a solicitation but no further product or service details, response dates, or award information is included.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OC_OSFC_OSC2
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 2017-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22
Catalog Number
Notes Type
FEATURES & SPECIFICATIONS
INTENDED USE
The OnePass converters (OC), starter fixture cable (OSFC), and starter cable 2 port (OSC2) provides the interface between hardwiring and RELOC at the homerun location. The OC is a single female port available with 6 inch wire leads standard or with armored cable. The OSFC attaches directly into the access plate or through any 1/2" trade-size knockout. The OSC2 is a splitter and starter extender cable in one easy to-use component.
ELECTRICAL
• Fits a standard 1/2" trade size knockout.
• 6" leads prestripped 5/8" for ease of wiring.
• Available in varying lengths to suit most common fixture spacing requirements.
• Auto-latching springs prevent accidental disengagement.
• The OC with cable length and OSFC available with green armor standard for easy identification in healthcare facilities (HCF option).
• Non-plenum rated OC2 plastic housing.
• The OC, OSS and OSC2 with EXT opiton enables them to be installed in hot and cold applications (-40° to +90°C).
• Type of insulation for EXT option is based on NEC Table 310.104(A)
SYSTEM FEATURES
• Pin and socket contacts.
• Color-coded labels for quick voltage identification.
• Dust Cover available for unused ports: RDC3 METAL DUST COVER CSA/UL J50 (available job pack of 50 only)
CONTROLS-ENABLED WIRING OPTIONS
• 0-24V integrated single-circuit or 0-10V low voltage controls applications: select C12S option.
• Sensor Switch®, nLight®, LC&D XPoint™ fixture level controls applications: select CAT5_
(length) option.
LISTINGS
• C-UL-US listed for indoor, dry, and accessible locations.
• Meets or exceed all the requirements of UL183 and NEC (NFPA70) Article 604 for manufactured wiring systems.
• C12S option meets NEC requirements for separation of Class 2 and Class 3 circuits from Class
1 circuits by a barrier as defined by Article 725.136(B).
• Meets NEC requirements for redundant ground paths for patient care areas in healthcare facilities (HCF option).
• Canadian Patent No. 2,845,603 (Class l, Class ll)
BUY AMERICAN ACT
This product is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations.
Please refer to www.acuitybrands.com/resources/buy-american for additional information.
WARRANTY
5-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/ warranty/terms-and-conditions Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.
OnePass® Converter/Starter Cables
OC, OSFC, OSC2
OC
Converter
OSFC
Starter Fixture Cable
OSC2
Starter Cable 2 Port mailto:techsupportreloc%40acuitybrands.com?subject= http://www.relocwiring.com https://www.acuitybrands.com/resources/buy-american http://www.acuitybrands.com/support/warranty/terms-and-conditions http://www.acuitybrands.com/support/warranty/terms-and-conditions
OnePass® Converter/Starter Cables
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 2017-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22
Series Voltage Conductors Length Controls Wiring Finish Options
OSC2 120 120V
208 208V 240 240V 277 277V 347 347V 480 480V
10/2G Three 10 AWG conductors, including one 10 AWG ground
10/3G Four 10 AWG conduc-tors, including one 10 AWG ground
10/4G Five 10 AWG conduc-tors, including one 10 AWG ground
12/2G Three 12 AWG conductors, including one 12 AWG ground
12/3G Four 12 AWG conduc-tors, including one 12 AWG ground
12/4G Five 12 AWG conduc-tors, including one 12 AWG ground
01 ft up to 50 ft (blank) Not required C12S Integrated CI,CII rated line voltage and signal wires ‡
CAT5_ Preterminated and tested CAT5 cable attached, specify length ‡
(blank) Not required RD Red ‡
(blank) Not required 2N Two circuit, two neutral ‡ EXT Extreme temperature rating conductors ‡
ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OSC2 277 10/4G 01
Series Voltage Conductors Length Controls Wiring Finish Options
OC 120 120V
208 208V 240 240V 277 277V 347 347V 480 480V
12/2G Three 12 AWG conductors, including one 12 AWG ground
12/3G Four 12AWG conductors, including one 12 AWG ground
12/4G Five 12 AWG conductors, including one 12 AWG ground
(blank) 6" wire leads 01 ft up to 50 ft
(blank) Not required C12S Integrated CI,CII rated line voltage and signal wires ‡
(blank) Not required RD Red ‡
(blank) Not required 2N Two circuit, two neutral ‡ EXT Extreme temperature rating conductors ‡ HCF Meets healthcare facility requirements ‡
ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC 277 12/4G 01 RD
‡ Option Value Ordering Restrictions & Notes
Option value Restriction 2N Available with 12/4G and 120 or 277 or 347 only.
C12S Available with 12/2G only.
EXT Available with 12/2G and 12/3G only. Required for EXTREME hot and cold temperature applications (-40° to 90°C).
HCF Available with 12/4G only. Not available with C12S or 6" wire leads.
RD Available in lengths up to 35 foot only. Not available with 6" wire leads.
‡ Option Value Ordering Restrictions & Notes
Option value Restriction 2N Available with 10/4G or 12/4G and 120 or 277 or 347 only.
C12S Available with 12/2G only.
CAT5_ See spec sheet RCAT5 for details. When used with OCS, OCU or OD fixture drop, CAT5 length must include the length of the OSC2 and the length of drop for the fixture plus 2FT.
EXT Available with 10/2G or 10/3G or 12/2G or 12/3G only. Required for EXTREME hot and cold temperature applications.(-40° to 90°C).
RD Available in lengths up to 35 foot only.
mailto:techsupportreloc%40acuitybrands.com?subject= http://www.relocwiring.com https://www.acuitybrands.com/products/detail/148375/reloc/rcat5-modular-wiring/onepassr-rcat5-modular-wiring
OnePass® Converter/Starter Cables
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 2017-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22
Series Voltage Conductors Length Connector Type Controls Wiring Options CAT5 Cable
OSFC 120 120V
208 208V 240 240V 277 277V 347 347V 480 480V
12/2G Three 12 AWG conductors, including one 12 AWG ground
12/3G Four 12AWG conductors, including one 12 AWG ground
12/4G Five 12 AWG conductors, including one 12 AWG ground
01 ft up to 50 ft (blank) Not required RRL RELOC®-ready luminaires ‡
(blank) Not required C12S Integrated
CI,CII rated line voltage and signal wires ‡
(blank) Not required G Ground wire ‡ 2N Two circuit, two neutral ‡ HCF Meets healthcare facility requirements ‡
(blank) Not required CAT5_ Preterminated and tested CAT5 cable attached, specify length ‡
ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OSFC 277 12/2G 05
‡ Option Value Ordering Restrictions & Notes
Option value Restriction 2N Available with 12/4G and 120 or 277 or 347 only.
C12S Available with 12/2G only.
CAT5_ See spec sheet RCAT5 for details. CAT5 length must be 2 foot longer than OSFC length.
G G option required for use in Canada. Required for C12S, HCF, and RRL Option.
HCF Available with 12/4G only. Not available with C12S or CAT5_.
RRL For use with fixtures. Fixture must have RRL and wiring instruction installed to use this option. See fixture spec sheet for details and availability. See RRL spec sheet sheet for connector details.
mailto:techsupportreloc%40acuitybrands.com?subject= http://www.relocwiring.com https://www.acuitybrands.com/products/detail/148375/reloc/rcat5-modular-wiring/onepassr-rcat5-modular-wiring https://www.acuitybrands.com/products/detail/248102/reloc/rrl/reloc-ready-connector
OnePass® Converter/Starter Cables
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 2017-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22
DIMENSIONS
Dimensions are shown in inches (millimeters)
OC – Converter
A – 18-gauge, zinc-plated, CRS cover B – UL-recognized connector body C – Tin-plated, brass contacts D – 6" leads prestripped 5/8" E – Threaded nipple with locknut for easy installation in 1/2" trade-size K.O.
A – Die-cast zinc with zinc-plated CRS cover B – UL recognized connector body C – Tin-plated brass contacts D – Length option required. MC Cable standard. HCF MC, C12S MC optional. IGW option standard with FMC.
NOTES
• One, two or three hot conductors in 120V and 277V as required.
• Rated for 20-amp capacity.
• Prefabricated circuit distributor carrying No. 12 AWG copper conductors rated at 600V, 90°C thermoplastic insulation and fully rated solid bare grounding conductor.
Standard Construction Armored Cable Construction
2-3/16 (55.6)
2-3/8 (60.3)
9/16 (14.3)
BA
CD
E
2-3/16 (55.6)
9/16 (14.3)
3-3/8 (87.5)
B A
C D
OC2OC
OC2OCS/OCU
OCS/OCU
SYSTEM VIEW
System View designs are for illustrative purposes only.
mailto:techsupportreloc%40acuitybrands.com?subject=
OnePass® Converter/Starter Cables
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 2017-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22
A – Injection-molded, high-impact polymeric compound enclosure
B – Tin-plated, brass contacts C – MC Cable standard. C12S MC optional.
DIMENSIONS
Dimensions are shown in inches (millimeters)
4-1/2 (114.3)
1-1/8 (28.7)
2-1/4 (57.2)
B
A
C
SYSTEM VIEW
System View designs are for illustrative purposes only.
OSC2
OC2OCS/OCU
OCS/OCU
OSC2 – Starter Cable 2 Port
OnePass® Converter/Starter Cables
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 2017-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22
OSFC – Starter Fixture Cable
DIMENSIONS
Dimensions are shown in inches (millimeters)
A – UL-recognized connector body B – Die-cast zinc with zinc-plated CRS cover C – Tin-plated, brass contacts D – Cast snap-in fitting fits 1.2" trade-size K.O. and provides grounding E – No. 18 AWG solid copper wires rated at 600V, 90°C thermoplastic insulation with stripped leads F – MC Cable standard. FMC, HCF MC, C12S MC optional
NOTES
• One, two or three hot conductors in 120V and 277V as required.
• Rated for 20-amp capacity.
• Prefabricated standard selector cable carrying No. 12 AWG copper conductors. 600V, 90°C thermoplastic insulation and fully rated bare grounding conductor.
• Standard selector cable provides auto-grounding to fixture unless specified otherwise.
B
F
C D
A
2-1/4 (58)
2-3/16 (55.6)
7/16 (11.1)
9/16 (14.3)
1-1/4 (31.8)
3-3/8 (87.5)
3-1/4 (82.6)
E
E
SYSTEM VIEW
System View designs are for illustrative purposes only.
Connection above the wall
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
Connection inside the wall
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
OFSC
OFSCOFSC
OFSC
OFC
OFC
OFC
OFC
OnePass® Converter/Starter Cables
One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com © 2017-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22
ONEPASS® CONVERTER/STARTER CABLES WIRE COLOR CHART
120V, 277V, 347V Standard Wire Colors
Position 1 2 3 4 5 Conductor Ground Hot# 1 Hot# 2 Hot# 3 Neutral #1
120V & 347V Bare or Green Black Red Blue White 277V Bare or Green Brown Orange Yellow Gray
208V, 240V, 480V Standard Wire Colors Position 1 2 3 4 5 Conductor Ground Hot# 1 Hot# 2 Hot# 3 Hot #4
208V & 240V Bare or Green Black Red Blue Violet 480V Bare or Green Brown Orange Yellow Violet
120V, 277V, 347V Two Circuit, Two Neutral (2N option) Position 1 2 3 4 5 Conductor Ground Hot# 1 Hot# 2 Neutral #2 Neutral #1
120V & 347V Bare or Green Black Red Gray White 277V Bare or Green Brown Orange White Gray
120V, 277V, 347V Class I, Class II (C12S option) Position 1 2 3 4 5 Conductor Hot #1 Neutral #1 Ground Data #1 Data #2
120V & 347V Black White Bare or Green Violet Pink (or Gray) 277V Brown Gray Bare or Green Violet Pink (or Gray)
208V & 240V Brown Orange Bare or Green Violet Pink (or Gray) 480V Brown Orange Bare or Green Violet Pink (or Gray)
120V Isolated Ground Wire (IGW option) Position 1 2 3 4 5 Conductor Ground Hot# 1 Hot# 2 IGW Neutral #1
120V Bare or Green Black Red Green w/Yellow stripe White mailto:techsupportreloc%40acuitybrands.com?subject= http://www.relocwiring.com
| Catalog Number 3: |
| Page 1: |
| Notes 3: |
| Page 1: |
| Type 3: |
| Page 1: |
| Type 5: |
| Type 6: |
| Type 7: |
| Type 8: |
| Type 9: |
| Type 10: |
| Type 26: |
| Type 11: |
| Type 12: |
| Type 13: |
| Type 14: |
| Type 15: |
| Type 16: |
| Type 17: |
| Type 19: |
| Type 20: |
| Type 21: |
| Type 22: |
| Type 23: |
| Type 24: |
| Type 25: |
| Type 27: |
File details come from the government source that posted it. Updated .