SOK-D-NXRAD-E023.pdf
PDF 241 KB Posted
- Solicitation number
- 6973GH-20-R-00139
About this file
This document provides details for a federal solicitation seeking construction services. The Federal Aviation Administration is soliciting proposals to replace an existing 9' x 25' engine generator shelter with a 13' x 25' concrete masonry unit shelter at its NEXRAD weather radar facility in Loleau, Kauai, Hawaii. Offerors must be registered in the System for Award Management by August 31, 2020 to be eligible. Proposals are due by 5:00pm Central Standard Time on August 31, 2020 and shall be submitted electronically to the contract specialist's email. The work will be awarded as a firm-fixed-price construction contract and the contractor will be responsible for furnishing all labor, materials, equipment, insurance, and supervision to complete the project. Site visits are not recommended due to COVID-19 restrictions and all questions must be submitted in writing by August 24th.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
04’ 4’ 8’
SCALE: 1/4" = 1’-0"
4’-0"
5’-8�"
4’
CHARGER
BATT
120/208V, 3PH, 4W
125KW EG
ATS
MSD
STORAGE SHELTER
UPS BLDG
MDPE
RMM
SEE NOTE 3
TVSS
TANK
DAY
PANEL
CTRL
ENV
SEE NOTE 19
SEE NOTE 16
SEE NOTE 2
SEE NOTE 15
PANEL
HOUSE
EG TVSS
SEE NOTE 17
EG ROOM DS
DISC
TVSS
SEE NOTE 14
"8 74’-3 "8
713’-8
8’-10�"
"8 715’-11
’-6
E D
M
IS
S
U E
D F
O R
HI
WY
JKB
ES 08/29/2018 1704153
SOK-D-NXRAD-E023
C O
N S
T R
U C
T
IO
N
ENGINEERING SERVICES
INFRASTRUCTURE
NEXRAD
UNDERGROUND CONDUIT
ELECTRICAL SITE PLAN AND
KAUAIIOLEAU
PROJECT ENGINEER MGR: ENGINEERING - LA
s o k -d -n x ra d -e
.d g n
DRAWING PRODUCED ON WSA MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
NOTES FOR UNDERGROUND CONDUIT LAYOUT
19.
18.
17.
16.
15.
14.
13.
12.
11.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
N
N
N
MDPE TO EG PANEL
TO USE FROM
EXISTING SPARE
ATS TO MDPE
CONDUIT FROM
UNDERGROUND
EXISTING 3"
RMM TO PB#2
CONDUIT FROM
UNDERGROUND
EXISTING 3"
POWER
2-3" PVC
EXISTING
COMM
2-2" PVC
EXISTING
REPLACEMENT SHELTER FOR EG
PB #1
EXISTING
PULLBOX #3
NEW 4’X4’
INSTALL
(FUTURE)
4, 12 & 13
SEE NOTE
1, 12 & 13
SEE NOTE
PB
#24’
X4
’NEWIN
STALL
POWER CONDUCTORS. Ref. FAA-C-1391e, Section 5.5.10e.
OUTSIDE WALL TO OUTSIDE WALL FROM CONDUIT WHICH CONTAIN
SYSTEM. CONDUIT FOR CONTROL CABLES NEED A MINIMUM OF 3"
2" PVC COATED RGS FROM PULLBOX #2 TO EG ROOM FOR RMM
FROM: ATS
TO: MDPE
FROM: MDPE
TO: EG HOUSE PNL
FROM: MAIN SERV DISC SW
TO: EG ROOM DISC SW
CONDUIT.
BRASS TAGS THAT IDENTIFY CABLES BEING INSTALLED FOR EACH
CONDUIT/COUPLING FLUSH WITH THE FINISHED FLOOR.
SWITCH TO LOADBANK CONTROLS UNIT. STUB UP THE
3" PVC COATED RGS FROM 125KW EG LOADBANK DISCONNECT
DISCONNECT SWITCH.
3" PVC COATED RGS FROM NEW PULLBOX #3 TO EG ROOM
2" PVC COATED RGS FROM PULLBOX #2 TO EG HOUSE PANEL.
CONDUIT ENTRY AREA.
3" PVC COATED RGS FROM ATS TO EG. REF DRAWING E021 FOR
ASSEMBLY ON THE INTERIOR OF THE CONCRETE PULLBOX.
A 26"X4"X1/4" COPPER GROUND PLATE WITH COVER AND MOUNTING
THE CONTRACTOR TO GROUND THE INTERIOR CONDUITS.
THE INTERIOR OF THE PULLBOX. THIS GROUND PLATE WILL ALLOW
FROM THE EES TO THE GROUND PLATE WHICH WILL BE INSTALLED ON
A 2" PVC SCH SLEEVE FOR A BARE #4/0 COPPER CONDUCTOR
LINE".
DETECTABLE UNDERGROUND TAPE. "CAUTION: BURIED ELECTRICAL
GRADE SHALL BE 3" PER 100 FEET.
ALL CONDUIT SHALL BE LAID TO SLOPE TOWARDS THE MANHOLE.
MINIMUM CONDUIT DEPTH 24" BELOW GRADE.
MINIMUM OF 3" (OUTSIDE WALL TO OUTSIDE WALL).
MINIMUM SEPARATION BETWEEN CONTROL AND POWER SHALL BE A
DIRECTION.
6" APART (OUTSIDE WALL TO OUTSIDE WALL) IN A VERTICAL
TO OUTSIDE WALL) IN A HORIZONTAL DIRECTION OR NOT LESS THAN
THEY SHALL BE SPACED NOT LESS THAN 2" APART. (OUTSIDE WALL
WHEN TWO OR MORE DUCTS ARE INSTALLED IN THE SAME TRENCH,
2234 TAPE PRIOR TO BURIAL.
THE DAMAGED AREAS OF THE 40 MIL PVC COATING WITH SCOTCH
AFTER THE CONDUIT AND COUPLING HAVE BEEN INSTALLED REPAIR
COATED HOT DIPPED RIGID GALVANIZED STEEL CONDUIT.
ALL UNDERGROUND CONDUIT AND FITTINGS SHALL BE 40 MIL PVC
RATED. MINIMUM LID OPENING TO BE 36"X 36".
NEW 4’X4’ PULLBOX WITH GALVANIZED STEEL LID H-20 TRAFFIC
PULLBOX #2.
(2) - 3" PVC COATED RGS CONDUIT FROM ATS TO EXISTING
DISCONNECT TO NEW PULLBOX #3.
(2) - 3" PVC COATED RGS CONDUIT FROM MAIN SERVICE
RATED. MINIMUM LID OPENING TO BE 36"X 36".
NEW 4’X4’ PULLBOX WITH A GALVANIZED STEEL LID H-20 TRAFFIC INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
s o k -d -n x ra d -e
.d g n
/6 /2
:3
:2
A
M Is a b e ll e C
T R I n a
A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
A
| 2020-05-06T15:18:52-0700 | |
| ELYZZA E SESON |
| 2020-05-06T16:19:16-0700 | |
| HARRY MOREAU |