This solicitation is for a firm-fixed-price construction contract to replace an existing 9' x 25' Engine Generator shelter with a 13' x 25' CMU shelter at the NEXRAD SOK facility in Loleau, Kauai, Hawaii. The Federal Aviation Administration requires contractors to furnish all materials, equipment, labor, insurance, and supervision to perform the work described in the attached specifications, drawings, and documents. Contractors must be registered in the System for Award Management and complete all required forms by August 31, 2020 to submit proposals. The solicitation number is 6973GH-20-R-00139. Questions regarding the project scope, drawings, or documents are due by August 24, 2020. Proposals must be received by August 31, 2020; late submissions may be determined ineligible. The contract will be awarded according to the Federal Aviation Administration's Acquisition Management System.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4’-6"
2’-1 1/4"
10 3/8"
6 3/4"
2’-8 7/16"
11 13/16"
2’-1 11/16"
5’-8 9/16"
8 1/2"
3’-7 15/16" 5 1/16"
8 7/8 "
7"
1 1/2"
10�"
4’-6 1/8"
3’-10 5/8"
2’-7 3/4"
01’ 1’ 3’2’
SCALE: 3/4" = 1’-0"
SEE NOTE 19
SEE NOTE 20
SEE NOTE 4
SEE NOTE 1
SEE NOTE 18
SEE NOTE 2
SEE NOTE 3
TVSS
DISC
TVSS
ATS
34"W X 28"D
X 85.13"H
SEE NOTE 14
60.1" HX44.4" WX106.3" D
120/208V, 3PH, 4W
125KW EG
6"DIA.
SEE NOTE 11
34.5"H X 13"D
46.4"W X
LOAD BANK
INTAKE LOUVER
5’X5’
X 20"H
20"L X 5.75"D
EG PANEL
EXHAUST FAN
EG ROOM
DS
SEE NOTE 7
S
T
S T
U
BOTTOM
CONDUIT
ENTRY AREA
15.7"W X 3.9"H
RADIATOR
OPENING
26.4"WX30.5"H
36.62" Wx17.75" D
X 69.13" H
8 & 9
SEE NOTES
EXHAUST
LOUVER
48"X48"
SEE NOTE 13
SEE NOTE 6
LOAD BANK
CNTRL UNIT
24"Wx12"H x 7.34"D
SEE NOTE 16
SEE NOTE 23
SEE NOTE 22
EG PANEL
TVSS
BATTERY CHARGER
10.5"Lx16.5"Hx6"D
ENVIR.CONTRL
PANEL
SEE NOTE 5
SEE NOTE 12
36"Wx22"D
50.7"H x
DAYTANK
NOTES:
SEE
NOTE 15
9.
8.
7.
6.
5.
4.
3.
2.
1.
18.
17.
16.
15.
14.
13.
12.
11.
10.
24.
23.
22.
21.
20.
19.INSTALL
(FUTURE)
(FUTURE)
(FUTURE)
INSTALL
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
INSTALL
(FUTURE)
(FUTURE)
(FUTURE)
INSTALL
SEE NOTE 10
SEE NOTE 24
GENERAL NOTES:
3.
2.
1.
6’-0"
6’-10�"
INSTALL
(FUTURE)
(FUTURE)
INSTALL
INSTALL
INSTALL
INSTALL
INSTALL
E D
M
IS
S
U E
D F
O R
HI
WY
JKB
ES 08/29/2018 1704153
SOK-D-NXRAD-E021
C O
N S
T R
U C
T
IO
N
ENGINEERING SERVICES
INFRASTRUCTURE
NEXRAD
EG ROOM FLOOR PLAN
KAUAIIOLEAU
PROJECT ENGINEER MGR: ENGINEERING - LA
s o k -d -n x ra d -e
.d g n
DRAWING PRODUCED ON WSA MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SENSOR
TEMP.
3"
4�"
STOP
EMERGENCY
REPLACEMENT SHELTER FOR EG
3’-0"
(FUTURE)
(FUTURE)(FUTURE)
(FUTURE)
INSTALL
INSTALL
CODE CONDUCTOR LONG BARREL, STUD HOLE SIZE 3/8" MIN.
SHALL BE MADE WITH A BURNDY COMPRESSION TWO HOLE LUG
COPPER CONDUCTOR. CONNECTIONS TO THE HOOD AND LOUVER
HOOD AND THE DAMPER TO THE COUNTERPOISE WITH A 4/0 BARE
STAINLESS STEEL 90° HOOD SIZE TO FIT. GROUND BOTH THE
DAYTON 16" BACKDRAFT DAMPER/WALL SHUTTER. INSTALL A 316
THERMOSTAT AND A VARIABLE FAN SPEED CONTROL DEVICE.
MODEL #21A089, 120V. INSTALL/PROVIDE A COMPATIBLE
SAW CUT OPENING AND INSTALL A 16" EXHAUST FAN, GRAINGER
TOWARD DIRECTION OF DISCHARGE. REFERENCE DRAWING M005.
STAINLESS STEEL (#304) EXHAUST PIPE, SLOPE 1/8" PER FOOT
DRAWING M005.
RESIDENTIAL MUFFLER (GFE). 61.4"LX14.1"O.D. REFERENCE
DOOR-IN-DOOR TRIM WITH THE PIANO HINGE DOWN ON SIDE.
DIRECTORY, CIRCUIT BREAKER I.D. NUMBER STRIP AND
COPPER BUS BAR, GROUNF BUS, NEUTRAL BUS, METAL FRAME
120/208V, 3 PH, 4W, 100A MCB. WITH THE FOLLOWING OPTIONS:
E/G HOUSE PANEL, MANUFACTURED BY SQ-D, NQ PANELBOARD,
ATS, 600A, 3PH, 4W, 120/208V, KOHLER CLIN 3015D (GFE).
120-3Y-A1-4-06-A.
TVSS FOR EG ROOM DISC SWITCH - RAYCAP MODEL,
AND NEUTRAL BUS THAT WILL ACCOMMODATE 4/0 CONDUCTORS.
SQ-D CIRCUIT BREAKER ENCLOSURE #J250S. PROVIDE A GROUND
TVSS DISCONNECT SQ-D 225A CIRCUIT BREAKER, #JGL36225 IN A
SWITCH, 600V, SINGLE THROW, SQ-D PART #H367N.
EG ROOM DISCONNECT SWITCH, 800A FUSIBLE HEAVY DUTY SAFETY
FLUSH WITH THE FINISHED FLOOR.
2- 3" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING
AREA IS 16"Dx4.5"W
FLUSH WITH THE FINISHED FLOOR. ATS BOTTOM CONDUIT ENTRY
4-3" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING
SIZE TO FIT.
THE OPEN POSITION. INSTALL A 16 GA. STAINLESS STEEL 90°HOOD
CLOSE DAMPERS WHEN EG NOT IN OPERATION, DAMPERS TO FAIL IN
RELAY TO SPRING OPEN DAMPERS UPON EG START AND MOTOR
APPROVED EQUAL. 120V(SIDE MOUNT), INTERLOCK WITH ENGINE RUN
FILTER BANK. ACTUATORS SHALL BE BELIMO AF SERIES TYPE OR
OPTIONS: STAINLESS STEEL FRAME AND BLADE, INSECT SCREEN, AND
60"X60"AIR INTAKE GREENHECK FAD-402. WITH THE FOLLOWING
AVTRON LOADBANK CONTROL UNIT (GFE).
125 KW EG, 3 PH, 4W, 208/120V, KOHLER CLIN 3002GA (GFE).
STAINLESS STEEL 90° HOOD SIZE TO FIT.
FRAME), AND 87 (STAINLESS STEEL 316). INSTALL A 16 GA.
06 (BLADE EDGE SEAL), 31 (FLANGE, 1 1/2" FASTENED TO DAMPER
BACKDRAFT DAMPER, MODEL 3102 WITH THE FOLLOWING OPTIONS:
48"X48" EXHAUST LOUVER, VENT PRODUCT COUNTER-BALANCED
50 GAL DAYTANK, CLIN 3030I-S (GFE).
(GFE). SEE DRAWING SOK-D-NXRAD -E027.
#K711208-30-28-4E-ABNT, INLINE MTD, CLIN GM88033-C1002G
EG LOADBANK 3PH, 3W, 208/120V, AVTRON, PART
LOADBANK IS BOTTOM ENTRY.
WITH THE FINISHED FLOOR. THE CONDUIT ENTRANCE POINT FOR THE
3" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING FLUSH
CONDUIT.
FLUSH WITH THE FINISHED FLOOR. 1.5" SPACING BETWEEN EACH
3-3" PVC COATED RGS CONDUIT STUB UP CONDUIT/COUPLING
FLUSH WITH THE FINISHED FLOOR.
2" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING
FLUSH WITH THE FINISHED FLOOR.
2" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING
A 3/4"C FROM THE ATS TO THE EG LOADBANK CONTROLLER.
F. DOOR SENSOR
E. SMOKE DETECTOR
D. HEAT DETECTOR
C. TEMPERATURE SENSOR
B. EG
A. ATS
VARIOUS DEVICES.
FUNCTIONS. INSTALL CONDUIT FROM THE 6"X6" PULLBOX TO THE
SERVE AS THE DISTRIBUTION POINT FOR THE EG RMM CONTROL
A 6"X6" PULLBOX W/ SCREW TYPE COVER, THIS BOX WILL
CHARGER, EG EMERGENCY STOP, ATS, AND DAYTANK.
DEVICES, REFERENCE DRAWING E026, BATTERY
INSTALL CONDUIT FROM 6"X6"PULLBOX TO THE VARIOUS
AS THE DISTRIBUTION POINT FOR THE E/G CONTROL FUNCTIONS.
A 6"X6"PULLBOX W/ SCREW TYPE COVER. THIS BOX WILL SERVE
THE UPS BUILDING TO THE NEW EG BUILDING.
THE RMM SYSTEM WILL BE INSTALLED BY FAA AND RE FROM
PAIR #22 AWG SOLID COPPER CONDUCTOR WITH A SHIELD.
CONTRACTOR SHALL POWER (1000’) SINGLE TWISTED
MODEL: 5602
TYPE: MECHANICAL DETECTOR
MANUFACTURER: SYSTEM SENSOR
MECHANICAL HEAT DETECTOR.
DOOR SENSORS THAT WILL BE PROVIDED BY THE SSC.
SEE NOTE 17
BETWEEN EACH CONDUIT
4-3"C, 1 1/4" SPACE
U
4’-0"
5’-0" s o k -d -n x ra d -e
.d g n
/6 /2
:3
:0
A
M Is a b e ll e C
T R I n a
A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
A
| 2020-05-06T15:15:29-0700 | |
| ELYZZA E SESON |
| 2020-05-06T16:18:21-0700 | |
| HARRY MOREAU |
File details come from the government source that posted it. Updated .