About this file

This solicitation is for a firm-fixed-price construction contract to replace an existing 9' x 25' Engine Generator shelter with a 13' x 25' CMU shelter at the NEXRAD SOK facility in Loleau, Kauai, Hawaii. The Federal Aviation Administration requires contractors to furnish all materials, equipment, labor, insurance, and supervision to perform the work described in the attached specifications, drawings, and documents. Contractors must be registered in the System for Award Management and complete all required forms by August 31, 2020 to submit proposals. The solicitation number is 6973GH-20-R-00139. Questions regarding the project scope, drawings, or documents are due by August 24, 2020. Proposals must be received by August 31, 2020; late submissions may be determined ineligible. The contract will be awarded according to the Federal Aviation Administration's Acquisition Management System.

View the file

Other files

File Type Posted
Questions and Answers on SIR 6973GH-20-R-00139.pdf PDF
wp-d-645-40931-s06 (EG Bldg Foundation).pdf PDF
sok-d-nxrad-c003 markup.pdf PDF
6973GH-20-R-00139 Amendment 0002.pdf PDF
6973GH-20-R-00139 Amendment 0001.pdf PDF
6973GH-20-R-00139 Photos of Site.pdf PDF
SOK-D-NXRAD-E024.pdf PDF
Scope of Work for the Kauai (SOK) NEXRAD Facility 120-208V 3 Phase System.doc DOC document
Contractors Release Form DOT F 4220.4.pdf PDF
SOK-D-NXRAD-E038.pdf PDF
SOK-D-NXRAD-E016.pdf PDF
SOK-D-NXRAD-D007.pdf PDF
Experience Information Form.doc DOC document
FAA-C-1391e Installation Termination Splicing and Transient-Surge Protection.....pdf PDF
SOK-D-NXRAD-E025.pdf PDF
SOK-D-NXRAD-E039.pdf PDF
SOK-D-NXRAD-C003.pdf PDF
Performance Bond.pdf PDF
SOK-D-NXRAD-D008.pdf PDF
SOK-D-NXRAD-C004.pdf PDF
Payment Bonds.doc DOC document
SOK-D-NXRAD-G005.pdf PDF
SOK-D-NXRAD-G006.pdf PDF
SOK-D-NXRAD-C005.pdf PDF
WP-D-645-40931-E18.pdf PDF
FAA-STD-019f Lightning and Surge Protection Grounding Bonding and Shielding...pdf PDF
SOK-D-NXRAD-E023.pdf PDF
FAA-C-1217G Electrical Work Interior.pdf PDF
SOK-D-NXRAD-D006.pdf PDF
Solicitation (SIR) 6973GH-20-R-00139.pdf PDF
Wage Determination HI20200001 as of 7-24-2020.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4’-6"

2’-1 1/4"

10 3/8"

6 3/4"

2’-8 7/16"

11 13/16"

2’-1 11/16"

5’-8 9/16"

8 1/2"

3’-7 15/16" 5 1/16"

8 7/8 "

7"

1 1/2"

10�"

4’-6 1/8"

3’-10 5/8"

2’-7 3/4"

01’ 1’ 3’2’

SCALE: 3/4" = 1’-0"

SEE NOTE 19

SEE NOTE 20

SEE NOTE 4

SEE NOTE 1

SEE NOTE 18

SEE NOTE 2

SEE NOTE 3

TVSS

DISC

TVSS

ATS

34"W X 28"D

X 85.13"H

SEE NOTE 14

60.1" HX44.4" WX106.3" D

120/208V, 3PH, 4W

125KW EG

6"DIA.

SEE NOTE 11

34.5"H X 13"D

46.4"W X

LOAD BANK

INTAKE LOUVER

5’X5’

X 20"H

20"L X 5.75"D

EG PANEL

EXHAUST FAN

EG ROOM

DS

SEE NOTE 7

S

T

S T

U

BOTTOM

CONDUIT

ENTRY AREA

15.7"W X 3.9"H

RADIATOR

OPENING

26.4"WX30.5"H

36.62" Wx17.75" D

X 69.13" H

8 & 9

SEE NOTES

EXHAUST

LOUVER

48"X48"

SEE NOTE 13

SEE NOTE 6

LOAD BANK

CNTRL UNIT

24"Wx12"H x 7.34"D

SEE NOTE 16

SEE NOTE 23

SEE NOTE 22

EG PANEL

TVSS

BATTERY CHARGER

10.5"Lx16.5"Hx6"D

ENVIR.CONTRL

PANEL

SEE NOTE 5

SEE NOTE 12

36"Wx22"D

50.7"H x

DAYTANK

NOTES:

SEE

NOTE 15

9.

8.

7.

6.

5.

4.

3.

2.

1.

18.

17.

16.

15.

14.

13.

12.

11.

10.

24.

23.

22.

21.

20.

19.INSTALL

(FUTURE)

(FUTURE)

(FUTURE)

INSTALL

(FUTURE)

(FUTURE)

(FUTURE)

(FUTURE)

INSTALL

(FUTURE)

(FUTURE)

(FUTURE)

INSTALL

SEE NOTE 10

SEE NOTE 24

GENERAL NOTES:

3.

2.

1.

6’-0"

6’-10�"

INSTALL

(FUTURE)

(FUTURE)

INSTALL

INSTALL

INSTALL

INSTALL

INSTALL

E D

M

IS

S

U E

D F

O R

HI

WY

JKB

ES 08/29/2018 1704153

SOK-D-NXRAD-E021

C O

N S

T R

U C

T

IO

N

ENGINEERING SERVICES

INFRASTRUCTURE

NEXRAD

EG ROOM FLOOR PLAN

KAUAIIOLEAU

PROJECT ENGINEER MGR: ENGINEERING - LA

s o k -d -n x ra d -e

.d g n

DRAWING PRODUCED ON WSA MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

SENSOR

TEMP.

3"

4�"

STOP

EMERGENCY

REPLACEMENT SHELTER FOR EG

3’-0"

(FUTURE)

(FUTURE)(FUTURE)

(FUTURE)

INSTALL

INSTALL

CODE CONDUCTOR LONG BARREL, STUD HOLE SIZE 3/8" MIN.

SHALL BE MADE WITH A BURNDY COMPRESSION TWO HOLE LUG

COPPER CONDUCTOR. CONNECTIONS TO THE HOOD AND LOUVER

HOOD AND THE DAMPER TO THE COUNTERPOISE WITH A 4/0 BARE

STAINLESS STEEL 90° HOOD SIZE TO FIT. GROUND BOTH THE

DAYTON 16" BACKDRAFT DAMPER/WALL SHUTTER. INSTALL A 316

THERMOSTAT AND A VARIABLE FAN SPEED CONTROL DEVICE.

MODEL #21A089, 120V. INSTALL/PROVIDE A COMPATIBLE

SAW CUT OPENING AND INSTALL A 16" EXHAUST FAN, GRAINGER

TOWARD DIRECTION OF DISCHARGE. REFERENCE DRAWING M005.

STAINLESS STEEL (#304) EXHAUST PIPE, SLOPE 1/8" PER FOOT

DRAWING M005.

RESIDENTIAL MUFFLER (GFE). 61.4"LX14.1"O.D. REFERENCE

DOOR-IN-DOOR TRIM WITH THE PIANO HINGE DOWN ON SIDE.

DIRECTORY, CIRCUIT BREAKER I.D. NUMBER STRIP AND

COPPER BUS BAR, GROUNF BUS, NEUTRAL BUS, METAL FRAME

120/208V, 3 PH, 4W, 100A MCB. WITH THE FOLLOWING OPTIONS:

E/G HOUSE PANEL, MANUFACTURED BY SQ-D, NQ PANELBOARD,

ATS, 600A, 3PH, 4W, 120/208V, KOHLER CLIN 3015D (GFE).

120-3Y-A1-4-06-A.

TVSS FOR EG ROOM DISC SWITCH - RAYCAP MODEL,

AND NEUTRAL BUS THAT WILL ACCOMMODATE 4/0 CONDUCTORS.

SQ-D CIRCUIT BREAKER ENCLOSURE #J250S. PROVIDE A GROUND

TVSS DISCONNECT SQ-D 225A CIRCUIT BREAKER, #JGL36225 IN A

SWITCH, 600V, SINGLE THROW, SQ-D PART #H367N.

EG ROOM DISCONNECT SWITCH, 800A FUSIBLE HEAVY DUTY SAFETY

FLUSH WITH THE FINISHED FLOOR.

2- 3" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING

AREA IS 16"Dx4.5"W

FLUSH WITH THE FINISHED FLOOR. ATS BOTTOM CONDUIT ENTRY

4-3" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING

SIZE TO FIT.

THE OPEN POSITION. INSTALL A 16 GA. STAINLESS STEEL 90°HOOD

CLOSE DAMPERS WHEN EG NOT IN OPERATION, DAMPERS TO FAIL IN

RELAY TO SPRING OPEN DAMPERS UPON EG START AND MOTOR

APPROVED EQUAL. 120V(SIDE MOUNT), INTERLOCK WITH ENGINE RUN

FILTER BANK. ACTUATORS SHALL BE BELIMO AF SERIES TYPE OR

OPTIONS: STAINLESS STEEL FRAME AND BLADE, INSECT SCREEN, AND

60"X60"AIR INTAKE GREENHECK FAD-402. WITH THE FOLLOWING

AVTRON LOADBANK CONTROL UNIT (GFE).

125 KW EG, 3 PH, 4W, 208/120V, KOHLER CLIN 3002GA (GFE).

STAINLESS STEEL 90° HOOD SIZE TO FIT.

FRAME), AND 87 (STAINLESS STEEL 316). INSTALL A 16 GA.

06 (BLADE EDGE SEAL), 31 (FLANGE, 1 1/2" FASTENED TO DAMPER

BACKDRAFT DAMPER, MODEL 3102 WITH THE FOLLOWING OPTIONS:

48"X48" EXHAUST LOUVER, VENT PRODUCT COUNTER-BALANCED

50 GAL DAYTANK, CLIN 3030I-S (GFE).

(GFE). SEE DRAWING SOK-D-NXRAD -E027.

#K711208-30-28-4E-ABNT, INLINE MTD, CLIN GM88033-C1002G

EG LOADBANK 3PH, 3W, 208/120V, AVTRON, PART

LOADBANK IS BOTTOM ENTRY.

WITH THE FINISHED FLOOR. THE CONDUIT ENTRANCE POINT FOR THE

3" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING FLUSH

CONDUIT.

FLUSH WITH THE FINISHED FLOOR. 1.5" SPACING BETWEEN EACH

3-3" PVC COATED RGS CONDUIT STUB UP CONDUIT/COUPLING

FLUSH WITH THE FINISHED FLOOR.

2" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING

FLUSH WITH THE FINISHED FLOOR.

2" PVC COATED RGS CONDUIT. STUB UP CONDUIT/COUPLING

A 3/4"C FROM THE ATS TO THE EG LOADBANK CONTROLLER.

F. DOOR SENSOR

E. SMOKE DETECTOR

D. HEAT DETECTOR

C. TEMPERATURE SENSOR

B. EG

A. ATS

VARIOUS DEVICES.

FUNCTIONS. INSTALL CONDUIT FROM THE 6"X6" PULLBOX TO THE

SERVE AS THE DISTRIBUTION POINT FOR THE EG RMM CONTROL

A 6"X6" PULLBOX W/ SCREW TYPE COVER, THIS BOX WILL

CHARGER, EG EMERGENCY STOP, ATS, AND DAYTANK.

DEVICES, REFERENCE DRAWING E026, BATTERY

INSTALL CONDUIT FROM 6"X6"PULLBOX TO THE VARIOUS

AS THE DISTRIBUTION POINT FOR THE E/G CONTROL FUNCTIONS.

A 6"X6"PULLBOX W/ SCREW TYPE COVER. THIS BOX WILL SERVE

THE UPS BUILDING TO THE NEW EG BUILDING.

THE RMM SYSTEM WILL BE INSTALLED BY FAA AND RE FROM

PAIR #22 AWG SOLID COPPER CONDUCTOR WITH A SHIELD.

CONTRACTOR SHALL POWER (1000’) SINGLE TWISTED

MODEL: 5602

TYPE: MECHANICAL DETECTOR

MANUFACTURER: SYSTEM SENSOR

MECHANICAL HEAT DETECTOR.

DOOR SENSORS THAT WILL BE PROVIDED BY THE SSC.

SEE NOTE 17

BETWEEN EACH CONDUIT

4-3"C, 1 1/4" SPACE

U

4’-0"

5’-0" s o k -d -n x ra d -e

.d g n

/6 /2

:3

:0

A

M Is a b e ll e C

T R I n a

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

2020-05-06T15:15:29-0700
ELYZZA E SESON
2020-05-06T16:18:21-0700
HARRY MOREAU

File details come from the government source that posted it. Updated .