Security_RTU_HVAC_Stamped_DWGS.pdf

PDF 9 MB Posted

Attached to
HVAC Replacements at Elati, Mariposa, and Security Command Center Locations (15% SBE Goal)
Solicitation number
IFB 325DH003
Issued by
Denver County, Colorado

About this file

This document is a comprehensive set of mechanical and electrical engineering design drawings for the Regional Transportation District (RTD) Mechanical Upgrades project at the Security Command Center located in Denver, Colorado. The project involves mechanical and electrical system upgrades, specifically focusing on replacing two existing rooftop heating and cooling units (RTU-1 and RTU-2) with new units. The drawings, prepared by HDR Engineering and dated November 25, 2024, include detailed plans for HVAC demolition, new HVAC installation, electrical power plans, one-line electrical diagrams, and various technical specifications and notes.

The electrical upgrades include replacing the existing rooftop units with new units that have different electrical load requirements. The service load justification indicates a net load change of 12,470 VA added to the existing 250A service, bringing the total service load to 76,532 VA or 92 amps at 480V, three-phase. The project involves modifying existing electrical circuits, with the existing 30A3P circuit breaker for RTU-2 potentially being reused and the circuit breaker for RTU-1 being replaced with a new 40A3P circuit breaker. The drawings also show the existing electrical infrastructure, including a 100 KVA generator, utility transformer, and various electrical panels, with careful attention to maintaining the existing electrical system's integrity while implementing the necessary upgrades.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/

2" 1"

2"

SHEET REFERENCE

NUMBER:

4' 8' 16'

FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

/2

/2

3:

:5

P

M \\d en -s rv 1\

N ew fo rm a\

4\

\1

9\ 6.

0_ C

A D

_B

IM

\6 .2

_W

IP

\R T

D _M ec h

U pg ra de s.

rv t

G0001

RTD MECHANICAL UPGRADES - SECURITY

COMMAND CENTER

COVER SHEET

THE REGIONAL TRANSPORTATION DISTRICT

SECURITY COMMAND CENTER

1205 W 7th Ave, DENVER, CO 80204

100% CONSTRUCTION DOCUMENTATION

RTD MECHANICAL UPGRADES

HDR Engineering Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

MARK REVISIONS BY DATE

1 50% DESIGN DEVELOPMENT 1/12/2024

2 75% CONSTRUCTION DOCUMENTS 3/13/2024

3 100% CONSTRUCTION DOCUMENTS 11/25/2024

HD

R-

A So rt Co de

RTD MECHANICAL UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

1/2

1"

2" 6/2

0/2

6 2 :12

:55 P

M Fil e P ath FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

50% DESIGN DEVELOPMENT1 EAB 01/12/2024

The Ballard Group, Inc.

Mechanical Consulting Engineers

(303) 988-4514

75% CONSTRUCTION DOCUMENTS2 EAB 03/12/2024

100% CONSTRUCTION DOCUMENTS3 EAB 11/25/2024

M-001

MECHANICAL COVER SHEET

11-25-20

VESTIBULE

CORRIDOR

WORK

AREA

OFFICE

STORAGE

ADMIN.

OFFICE

ADMIN.

OFFICE

WOMEN'S

RESTROOM

ADMIN.

OFFICE

VIEWING

ROOM

MEN'S

RESTROOM

CORRIDOR

KITCHEN

STORAGE

ROOM

COMM./TELE.

ROOM

JAN.

ELEC.

ROOM

CORRIDOR

OFFICE

CONFERENCE

ROOM

OFFICE

VESTIBULE

CORRIDOR

WORK

AREA

OFFICE

STORAGE

ADMIN.

OFFICE

ADMIN.

OFFICE

WOMEN'S

RESTROOM

ADMIN.

OFFICE

VIEWING

ROOM

MEN'S

RESTROOM

CORRIDOR

KITCHEN

STORAGE

ROOM

COMM./TELE.

ROOM

JAN.

ELEC.

ROOM

CORRIDOR

OFFICE

CONFERENCE

ROOM

OFFICE

HD

R-

A So rt Co de

RTD MECHANICAL UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

1/2

1"

2" 6/2

0/2

6 2 :12

:55 P

M Fil e P ath FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

50% DESIGN DEVELOPMENT1 EAB 01/12/2024

The Ballard Group, Inc.

Mechanical Consulting Engineers

(303) 988-4514

75% CONSTRUCTION DOCUMENTS2 EAB 03/12/2024

100% CONSTRUCTION DOCUMENTS3 EAB 11/25/2024

HVAC ROOF DEMOLITION PLAN

HVAC ROOF PLAN

HVAC DEMOLITION FLOOR PLAN

HVAC FLOOR PLAN

M-101

HVAC FLOOR PLANS

Scale

1/8" = 1'-0"

0 4' 8' 16'

HD

R-

A So rt Co de

RTD MECHANICAL UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

1/2

1"

2" 6/2

0/2

6 2 :12

:55 P

M Fil e P ath FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

50% DESIGN DEVELOPMENT1 EAB 01/12/2024

The Ballard Group, Inc.

Mechanical Consulting Engineers

(303) 988-4514

75% CONSTRUCTION DOCUMENTS2 EAB 03/12/2024

100% CONSTRUCTION DOCUMENTS3 EAB 11/25/2024

SCALE: NONE

ROOFTOP UNIT CONTROL DIAGRAM

RTU-1 & 2

BAS NETWORK DIAGRAM

SCALE: NONE

M-301

HVAC SCHEDULES, DETAILS, AND CONTROL DRAWINGS

E-001

SYMBOLS, LEGEND & GENERAL NOTES

DRAWOUT CIRCUIT BREAKER

CIRCUIT BREAKER

INTERRUPTER SWITCH

METERING DEVICE

JUNCTION BOX (SIZE AS REQUIRED UNO)

SHADING INDICATES EGRESS FIXTURE

SHEET NOTE DESIGNATION

EMERGENCY LIGHTING UNIT

DOWNLIGHT

STRIP FIXTURE

SHUNT TRIP DEVICE

GROUND FAULT INTERRUPTER DEVICE

SURFACE MOUNT TROFFER

SPEAKER

TELEVISION OUTLET: 18" AFF (UNO)

TELEPHONE TERMINAL BOARD (TTB)

DATA / VOICE OUTLET: FLOOR MOUNTED

MULTI-OUTLET ASSEMBLY: SPACING PER DWGS

FIXTURE DESIGNATION: F1=TYPE (SEE FIXTURE SCH.)

REVISION DELTA: NUMBER REPRESENTS REVISION

EQUIPMENT CONNECTION

TELEPHONE OUTLET: 18" AFF

NEUTRAL CONDUCTOR

PHASE CONDUCTOR(S)

ISOLATED GROUNDING CONDUCTOR

HOMERUN TO PANELBOARD OR DEVICE

NEUTRAL CONDUCTOR (N=1, 2N=2 NEUTRALS,

PHASE CONDUCTOR(S)

GROUNDING CONDUCTOR

HOMERUN CIRCUIT DESIGNATION

PANELBOARD DESIGNATION

HOMERUN CIRCUIT DESIGNATION

(3 PHASE CIRCUIT SHOWN)

* FIXTURE SCHEDULE HAS PRECEDENCE *

VOLUMETRIC TROFFER

FLANGED TROFFER

WALL PACK

POLE MOUNT

EXIT SIGN FIXTURE - SHADED AREA DENOTES LIGHTED

FACE - ARROWS INDICATE DIRECTION

DATA / VOICE OUTLET: 18" AFF - 1 VOICE, 1 DATA JACK,

TRANSFORMER

MOTOR - # INDICATES HP

FUSE

VOLUME CONTROL

PHASE CONDUCTOR(S)

GROUNDING CONDUCTOR

PANELBOARD DESIGNATION

NORMALLY OPEN (NO) CONTACT

NORMALLY CLOSED (NC) CONTACT

GROUNDING BAR

TICS = NO. OF #12 WIRES (UNO) IF MORE THAN

TWO WITHIN RACEWAY. GROUNDING CONDUCTOR

(NOT SHOWN) ALWAYS REQUIRED.

CURRENT TRANSFORMER

REMOTE METER

GENERATOR

GROUND FAULT RELAY W/ CT OR SENSOR

3N=3 NEUTRALS)

TRANSFER SWITCH (A=AUTOMATIC, M=MANUAL)

# FOR POLES 2, 3 OR 4

THERMOSTAT (PROVIDED BY MECH. CONTRACTOR UNO)

COIL - VOLTAGE PER CONTROL DIAGRAMS

PILOT LIGHT (LED) NON PUSH-TO-TEST

THERMAL OVERLOAD

MAGNETIC OVERLOAD

PUSH BUTTON NORMALLY OPEN (NO)

HAND-OFF-AUTO (HOA) SELECTOR SWITCH

LIMIT SWITCH NORMALLY OPEN (NO)

PUSH BUTTON ILLUMINATED (LED)

PILOT LIGHT (LED) PUSH-TO-TEST. LETTER INDICATES

COLOR (R=RED, G=GREEN, A=AMBER, Y=YELLOW)

PUSH BUTTON NORMALLY CLOSED (NC)

LIMIT SWITCH NORMALLY CLOSED (NC)

A

ADA

AFC

AFCI

AFF

AFG

AHJ

AIC

AL

ATS

AWG

BC

BKR

C

CEC

CKT

CLG

CO

CT

CU

DB

DDC

DPDT

DPST

DWG

(E)

ELEC

EM

EMT

(F)

FLA

FMC

FPEN

GFI

GFR

GND

HID

HOA

HP

HSKP

IMC

J-BOX

K

KVA

KW

LTG

IG

MCB

MCM

MFG

MLO

MS

MSB

MTS

NC

NEC

NEMA

NIC

NL

NO

NTS

NVE

P

PH/Ø

PV

PNL

PTC

PWR

(R)

RAC

RFC

RSC

SE

SPDT

SPST

STC

SW

TE

TTB

TYP

UL

UNO

UNSW

UPS

V

VA

VFD

W

WP

(X)

XFMR OR XF

AMPS

AMERICANS WITH DISABILITIES ACT

ABOVE FINISHED CEILING

ARC-FAULT CIRCUIT INTERRUPTER

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTHORITY HAVING JURISDICTION

AMP INTERRUPTING CAPACITY

ALUMINUM

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BARE COPPER

BREAKER

CONDUIT/RACEWAY

CALIFORNIA ENERGY COMMISSION

CIRCUIT

CEILING

CONDUIT/RACEWAY ONLY

CURRENT TRANSFORMER

COPPER

DISTRIBUTION BOARD

DIRECT DIGITAL CONTROLLER

DOUBLE-POLE, DOUBLE-THROW

DOUBLE-POLE, SINGLE-THROW

DRAWING

EXISTING TO REMAIN

ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

FUTURE

FULL LOAD AMPS

FLEXIBLE METAL CONDUIT (STEEL)

FUSE PER EQUIP. NAMEPLATE

GROUND FAULT INTERRUPT

GROUND FAULT RELAY

GROUND

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTO SWITCH

HORSEPOWER

HOUSEKEEPING

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

kcmil (300K = 300 kcmil)

KILOVOLT AMPS

KILOWATT

LIGHTING

ISOLATED GROUND

MAIN CIRCUIT BREAKER

THOUSAND CIRCULAR MILS

MANUFACTURER

MAIN LUGS ONLY

MOTOR STARTER

MAIN SWITCHBOARD

MANUAL TRANSFER SWITCH

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NOT IN CONTRACT

NIGHTLIGHT

NORMALLY OPEN

NOT TO SCALE

NV ENERGY

POLE

PHASE

PHOTOVOLTAIC

PANEL

PV USA TEST CONDITIONS

POWER

RELOCATE/RELOCATED

RIGID ALUMINUM CONDUIT

RIGID FIBERGLASS CONDUIT

RIGID STEEL CONDUIT

SERVICE ENTRANCE

SINGLE-POLE, DOUBLE-THROW

SINGLE-POLE, SINGLE-THROW

STANDARD TEST CONDITIONS

SWITCH

TELECOM

TELEPHONE TERMINATION BOARD

TYPICAL

UNDERWRITER'S LABORATORY

UNLESS NOTED OTHERWISE

UNSWITCHED

UNINTERRUPTED POWER SUPPLY

VOLTS

VOLT AMPS

VARIABLE FREQUENCY DRIVE

WATTS

WEATHER PROOF

EXISTING TO BE REMOVED

TRANSFORMER

FEEDER DESIGNATION

DATA OUTLET: 18" AFF

SURGE PROTECTION DEVICE

SPD SURGE PROTECTION DEVICE

ELECTRICAL LEGEND

DEVICE MOUNTED AT NON-STANDARD HEIGHT. IF NO HEIGHT

SHOWN VERIFY HEIGHT WITH ARCHITECT

QUAD RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

DUPLEX RECEPTACLE: FLOOR MOUNTED

DUPLEX RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

SINGLE RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

DUPLEX RECEPTACLE: HALF SWITCHED, +18" AFF

ISOLATED GROUND TYPE RECEPTACLE (ORANGE TRIANGLE),

20A, 125V, NEMA 5-20IG, +18" AFF

DUPLEX RECEPTACLE GFI TYPE - 20A, 125V, NEMA 5-20 GFI

SPECIAL PURPOSE RECEPTACLE: SEE DWGS FOR NEMA

DUPLEX RECEPTACLE: CEILING MOUNTED

MULTI-OUTLET ASSEMBLY: SPACING PER DWGS

QUAD RECEPTACLE: FLOOR MOUNTED

BLANK GFCI PROTECTIVE DEVICE IN READILY ACCESSIBLE

LOCATION (LABEL PROTECTED DEVICES)

PHOTOELECTRIC CELL (ON ROOF FACING NORTH UNO)

OCCUPANCY SENSOR - WALL MOUNTED 48" AFF

CONTROL STATION

TIME WALL SWITCH EQUAL TO HUBBELL DT2000W

SWITCH WITH PILOT LIGHT 48" AFF

DIMMER OPERATED SWITCH 48" AFF

KEY OPERATED SWITCH 48"

SINGLE POLE SWITCH 48" AFF

THREE WAY SWITCH 48" AFF

FOUR WAY SWITCH 48" AFF

MANUAL MOTOR STARTER

COMMUNICATIONS OR SIGNAL

PRIMARY

SECONDARY

OVERHEAD SERVICE

CONDUIT/RACEWAY BELOW GRADE OR BELOW FLOOR

CONDUIT/RACEWAY IN WALL OR ABOVE CEILING

LOW VOLTAGE AND/OR CONTROL WIRING

CONDUIT/RACEWAY STUB OUT: MARK AND CAP (SITE)

TELEPHONE

TIMECLOCK

BREAK OR RUN CONTINUES

CONDUIT/RACEWAY SLEEVE

EMERGENCY CIRCUIT

CONTACTOR OR RELAY

OCCUPANCY SENSOR - CEILING MOUNTED. PROVIDE

WITH POWER PACK PER MFG REQUIREMENTS.

SWITCH WITH LIGHTED HANDLE

TELEVISION

0-10V DIMMING OCCUPANCY SENSOR - WALL MOUNTED

48" AFF - EQUAL TO SENSOR SWITCH WSX-D

OCCUPANCY SENSOR - CORNER MOUNTED. PROVIDE

WITH POWER PACK PER MFG REQUIREMENTS.

DUPLEX "CLOCK" RECEPTACLE: 125V, NEMA 5-20R, +60" AFF

QUAD RECEPTACLE: CEILING MOUNTED

LENSED TROFFER

DEVICE MOUNTED AT NON-STANDARD HEIGHT. IF NO HEIGHT

SHOWN VERIFY HEIGHT WITH ARCHITECT

(RR) REMOVE AND REPLACE

HA-[1,3,5,3N]G

HA-(1.3.5)G

XF

PC

TC

GFI

M

ST

S

TV

VC

A

M

G

GFI

X"

T

J

F1

48" AFF

+18" AFF

COMBO DUAL USB CHARGER / DUPLEX RECEPTACLE, 5.1A, (1)

TYPE A & (1) TYPE C USB (3.1, 3.0, 2.0 AND 1.1 COMPATIBLE),

20A, 125V, NEMA 5-20R, +18AFF

QUAD USB CHARGER, 5.1A, (2) TYPE A & (2) TYPE C USB (3.1,

3.0, 2.0 AND 1.1 COMPATIBLE), +18AFF

CONFIGURATION

2 BLANKS

BRANCH CIRCUIT (WHEN TIC MARKS ARE NOT

SHOWN) = (1) PHASE, (1) NEUTRAL AND (1)

GROUNDING CONDUCTOR

L R

E M M1

K H

= LIGHTING

= RECEPTACLES

= EQUIPMENT = MOTOR

= LARGEST MOTOR

= KITCHEN EQUIP

= ELECTRIC HEAT

PANELBOARD: SURFACE MOUNTED

PANELBOARD: FLUSH MOUNTED

SWITCHBOARD OR DISTRIBUTION PANEL

TRANSFORMER

PULLBOX / VAULT

MOTOR STARTER

COMBINATION MOTOR STARTER

COMBINATION MOTOR STARTER PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

DISCONNECT SWITCH - FUSIBLE (FUSED PER EQUIP.

NAMEPLATE)

DISCONNECT SWITCH - NON-FUSIBLE

DISCONNECT SWITCH PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

VARIABLE FREQUENCY DRIVE

VARIABLE FREQUENCY DRIVE PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

ENCLOSED CIRCUIT BREAKER

GROUND ROD

SHUNT TRIP STATION OR EMERGENCY PUSHBUTTON

REMOTE METER

NOTE: THIS IS A MASTER SYMBOL LIST. IT MAY BE THAT NOT ALL SYMBOLS SHOWN ARE USED WITHIN THIS SET OF PLANS. HEIGHTS GIVEN ARE TO TOP OF BOX.

BREAKERS: 20 = SINGLE POLE CIRCUIT BREAKER 20/2 = TWO POLE CIRCUIT BREAKER 20/3 = THREE POLE CIRCUIT BREAKER 20A = ARC FAULT CIRCUIT BREAKER 20C = CONTROLLABLE CIRCUIT BREAKER 20G = GFI CIRCUIT BREAKER

DRAWING SCHEDULE

SHEET DESCRIPTION

E-001 ELECTRICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES

E-101 POWER PLAN - LEVEL 01

E-201 POWER PLANS - ROOF LEVEL

E-301 ONE-LINE DIAGRAM

TOTAL SHEETS IN ISSUE:

C O

N

ST

R U

C

TI

O N

D R

AW

IN

G S

/1

3/

SCOPE OF WORK

PROVIDE NEW ELECTRICAL CONNECTIONS FOR REPLACEMENT OF ROOF MOUNTED HVAC EQUIPMENT.

GENERAL NOTES

1. INSTALLATION SHALL COMPLY WITH CURRENTLY ADOPTED 2023 NEC AND LOCAL CODES. ALL WORK

PRACTICESSHALL COMPLY WITH NFPA 70E. ENERGIZED WORK IS PROHIBITED UNLESS PERFORMED UNDER AN APPROVED ENERGIZED WORK PERMIT WITH AN IEE 1584 COMPLIANT ARC FLASH ASSESSMENT

2. DATA PRESENTED ON THESE DRAWINGS ARE REPRESENTS DESIGN INTENT BASED ON AVAILABLE INFORMATION, BUT FIELD VERIFICATION OF ALL DIMENSIONS, LOCATIONS, LEVELS, ETC. TO SUIT FIELD CONDITIONS IS REQUIRED. REVIEW ALL CIVIL DETAILS AND ADJUST WORK TO MEET THE REQUIREMENTS OF

CONDITIONS SHOWN. DISCREPANCIES BETWEEN DIFFERENT PLANS OR BETWEEN DRAWINGS AND

SPECIFICATIONS, OR REGULATIONS AND CODES GOVERNING THE INSTALLATION SHALL BE BROUGHT TO THE

ATTENTION OF THE ENGINEER IN WRITING.

3. ALL WORK SHALL BE COMPLETED IN A NEAT AND WORKMANLIKE MANNER AND IN ACCORDANCE WITH NECA STANDARDS, INCLUDING NECA 1 STANDARDS FOR GOOD WORKMANSHIP IN ELECTRICAL CONSTRUCTION.

4. ALL WORK SHALL BE SUBJECT TO INSPECTION AND POSSIBLE REJECTION IF NOT IN ACCORDANCE WITH THE

DRAWINGS AND SPECIFICATIONS AND INSTALLED IN A NEAT AND WORKMANLIKE MANNER.

5. WORK REJECTED DUE TO CONTRACT, COD, SPECIFICATION, DRAWINGS, OR COORDINATIONDEFICIENCIES

WORK SHALL BE REPLACED AT NO ADDITIONAL COST TO THE OWNER.

6. PROVIDE REPRODUCIBLE RECORD DRAWINGS OF ALL COMPLETED WORK. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS

7. THE CONTRACTOR SHALL REMOVE FROM THE JOB SITE ALL DISCARD AND ABANDONED MATERIALS FROM DEMOLITION AND INSTALLATION. THIS INCLUDES BUT IS NOT LIMITED TO CONDUIT, FASTENERS, BOXES, & ETC. MATERIALS EMBEDDED IN GRADE AND / OR CONCRETE MAY BE ABANDONED IN PLACE. ALL ABANDONED

CONDUIT SHALL BE CAPPED. ALL DEMOLISHED CONDUCTORS SHALL BE REMOVED.

8. DO NOT SPLICE FEEDER CONDUCTORS UNLESS WRITTEN PRIOR APPROVAL HAS BEEN OBTAINED FROM THE

ENGINEER. APPROVING SPECIFIC CONTRACTOR PROPOSED LOCATION AND SPLICING METHOD.

9. THE MAXIMUM NUMBER OF CONDUIT BENDS SHALL NOT BE GREATER THAN 270 DEGREES BETWEEN PULLING

STRUCTURES. THIS INCLUDES THE AGGREGATE OF ALL HORIZONTAL AND VERTICAL CHANGES.

10. ALL CONDUIT, PULLBOXES AND VAULTS SHALL BE LABELED PER THE SPECIFICATIONS.

11. EACH CONDUIT SHALL BE PROVIDED WITH A 1250 LBS. PULL ROPE AND TO/FROM IDENTIFICATION TAGS

NOTE: "(E)" IN HOMERUN INDICATES NEW HOMERUN

TO EXISTING PANEL

D

ES

IG

N

D

EV

EL

O

PM

EN

T

/1 2/

N/A N/A

RTD MECHANICAL UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-12

ELECTRICAL

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

100% CONSTRUCTION DOCUMENTS3 JM 2024-11-25

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

0%

C O

N

ST

R U

C

TI

O N

D R

AW

IN

G S

/2

5/

11/25/2024

M

C T

T A

XF

XF

XF

F

CONFERENCE

ROOM

OFFICE

CORRIDOR

ELEC.

ROOM

JAN.

COMM./TELE.

ROOM

STORAGE

ROOM

KITCHEN

CORRIDOR

MEN'S

RESTROOM

VIEWING

ROOM

ADMIN.

OFFICE

WOMEN'S

RESTROOM

ADMIN.

OFFICE

ADMIN.

OFFICE

STORAGE

OFFICE

WORK

AREA

OFFICE

CORRIDOR

CORRIDOR

VESTIBULE

E-101

POWER PLAN - LEVEL 01

SCALE:

POWER PLAN - LEVEL 011

E-101 1/8" = 1'-0"

GENERAL NOTES - NEW WORK

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW

EQUIPMENT UNLESS NOTED OTHERWISE.

2. TERMINAL UNITS SHOWN FOR REFERENCE ONLY. CONTROL WIRING TO EACH UNIT (NOT SHOWN) BY

TEMPERATURE CONTROLS CONTRACTOR. REFER TO TEMPERATURE CONTROL DRAWINGS FOR MORE

INFORMATION.

3. THE CONTRACTOR SHALL OBTAIN ALL WIRING DIAGRAMS ASSOCIATED WITH MECHANICAL EQUIPMENT CONTROLS FROM MECHANICAL/CONTROLS CONTRACTOR. CONTROL WIRING SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR. ANY CONDUIT REQUIRED FOR CONTROL WIRING SHALL BE

PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR AND SHALL BE COMPLETED UNDER THE

SUPERVISION OF MECHANICAL/CONTROLS CONTRACTOR.

4. LOCATE ALL DISCONNECTS, STARTERS AND DRIVES WHERE ACCESSIBLE. PROVIDE ACCESS AND CLEARANCE AS REQUIRED PER NEC. PROVIDE ACCESS HATCH IF LOCATED ABOVE HARD LID CEILING.

5. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR MECHANICAL UNIT MODEL NUMBERS AND

SPECIFIC ELECTRICAL REQUIREMENTS, OPTIONS AND ACCESSORIES.

6. INFORMATION ON MECHANICAL DRAWINGS SUPERSEDE INFORMATION SHOWN ON ELECTRICAL

DRAWINGS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS PRIOR TO

ROUGH-IN.

7. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL REQUIREMENTS FOR FINAL

MECHANICAL EQUIPMENT INSTALLED. SHOULD THERE BE ANY DISCREPANCY BETWEEN ACTUAL

EQUIPMENT INSTALLED AND ELECTRICAL OR MECHANICAL DRAWINGS, CONTRACTOR SHALL NOTIFY

ENGINEER IMMEDIATELY FOR CLARIFICATION AND FURTHER DIRECTION.

Scale

1/8" = 1'-0"

0 4' 8' 16'

1/8" = 1'-0" N/A

RTD MECHANICAL UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-12

ELECTRICAL

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

100% CONSTRUCTION DOCUMENTS3 JM 2024-11-25

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

(E) 45KVA

"TRANSFORMER #2"

(E) "LP2"

(E) "LP1"

(E) 400A ATS

(E) (E)

(E) 400A3P

SERVICE DISCONNECT

(E) 75 KVA UTILITY

TRANSFORMER

(E) 100KVA

GENERATOR

(E) TTBAREA OF WORK

(E) 45KVA

"TRANSFORMER #1"

(E) MDP

RTU - 2: REFER TO

ROOF PLAN

RTU - 1: REFER TO

ROOF PLAN

FOR REFERENCE ONLY

F

F

E-201

POWER PLANS - ROOF LEVEL

SCALE:

POWER PLAN - ROOF LEVEL1

E-201 1/8" = 1'-0"

DEMOLITION -

SCALE:

POWER PLAN - ROOF LEVEL2

E-201 1/8" = 1'-0"

NEW CONSTRUCTION

GENERAL NOTES - DEMOLITION

1. THIS DRAWING REPRESENTS THE EXISTING POWER SYSTEMS WITHIN THE EXISTING BUILDING (AREA TO

BE REMODELED). THE CONTRACTOR IS RESPONSIBLE FOR REMOVING, RELOCATING AND REWIRING ALL EQUIPMENT AS INDICATED ON THE DRAWINGS, INCLUDING EQUIPMENT THAT LIES WITHIN WALLS AND

CEILINGS TO BE DEMOLISHED OR REMODELED.

2. (X) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE REMOVED, (R) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE RELOCATED, (E) AND/OR HALFTONE LINES INDICATE EXISTING

EQUIPMENT TO REMAIN UNLESS NOTED OTHERWISE.

3. SALVAGEABLE ITEMS REMOVED DURING DEMOLITION SHALL BE OFFERED TO OWNER PRIOR TO

DISPOSAL OR REMOVAL FROM SITE.

4. EXISTING CIRCUITS AS INDICATED ARE BASED ON LIMITED FIELD OBSERVATION AND INFORMATION PER RECORD DRAWINGS AND SHALL BE FIELD VERIFIED BY ELECTRICAL CONTRACTOR PRIOR TO START OF

DEMOLITION WORK.

5. THE CONTRACTOR SHALL SALVAGE AND REUSE EXISTING BOXES AND CONDUIT WHERE POSSIBLE.

DAMAGED CONDUIT, FITTINGS BOXES, ETC. MAY NOT BE RE-USED. NEW CIRCUITING AS INDICATED ON THE DRAWINGS IS SHOWN FOR INTENT ONLY AND MAY VARY BASED ON ACTUAL FIELD CONDITIONS

(NEW CIRCUITING SHALL MATCH EXISTING WHERE POSSIBLE TO UTILIZE EXISTING HOME-RUN

CONDUITS, ETC.). KEEP AS-BUILT DRAWINGS CURRENT WITH ANY DEVIATION IN CIRCUITING FROM WHAT

IS INDICATED WITHIN THESE PLANS.

6. THE CONTRACTOR SHALL REMOVE FROM THE JOB SITE ALL DISCARDED AND ABANDONED MATERIALS LEFT OVER FROM DEMOLITION AND INSTALLATION. THIS INCLUDES, BUT IS NOT LIMITED TO, CONDUIT, FASTENERS AND BOXES. MATERIALS EMBEDDED IN GRADE AND / OR CONCRETE MAY BE ABANDONED IN

PLACE. ALL ABANDONED CONDUIT SHALL BE CAPPED.

SHEET NOTES

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED. DE-ENERGIZE AND REMOVE CONDUCTORS,

CONDUIT, AND EXISTING DISCONNECT. REMOVE CONDUCTORS BACK TO SOURCE . CONDUIT MAY BE REUSED FOR CONNECTION TO NEW EQUIPMENT. DISCONNECT EXISTING DUCT SMOKE DETECTOR AND

SAFE OFF FIRE ALARM CONNECTION TO NEW EQUIPMENT. COORDINATE DEMOLITION OF HVAC

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO THE START OF WORK.

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED. DE-ENERGIZE AND REMOVE CONDUCTORS AND CONDUIT BACK TO EXISTING DISCONNECT. SAFE OFF CONDUCTORS FOR RE-CONNECTION TO NEW

EQUIPMENT . EXISTING CONDUCTORS AND CONDUIT MAY BE REUSED FOR CONNECTION TO NEW

EQUIPMENT. DISCONNECT EXISTING DUCT SMOKE DETECTOR AND SAFE OFF FIRE ALARM CONNECTION TO NEW EQUIPMENT. COORDINATE DEMOLITION OF HVAC EQUIPMENT WITH MECHANICAL CONTRACTOR

PRIOR TO THE START OF WORK.

RECONNECT NEW DUCT SMOKE DETECTOR TO NEW HVAC EQUIPMENT. COORDINATION CONNECTION

WITH TEMPERATURE CONTROLS AND MECHANICAL CONTRACTOR PRIOR TO THE START OF WORK.

EXISTING HVAC MOUNTED RECEPTACLE SHALL BE DEMOLISHED. DE-ENERGIZE RECEPTACLE AND

REMOVE CONDUCTORS AND CONDUIT BACK TO SOURCE OR NEAREST JUNCTION BOX TO REMAIN.

EXISTING BRANCH CIRCUIT SHALL BE REUSED TO SERVE NEW INTEGRAL RTU RECEPTACLE

EXTEND EXISTING BRANCH CIRCUIT AND CONDUIT PREVIOUSLY SERVING DEMOLISHED RECEPTACLE FOR CONNECTION TO RECEPTACLE INTEGRAL TO NEW RTU UNIT. COORDINATE CONNECTION WITH

MECHANICAL CONTRACTOR PRIOR TO START OF WORK.

GENERAL NOTES - NEW WORK

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW

EQUIPMENT UNLESS NOTED OTHERWISE.

2. TERMINAL UNITS SHOWN FOR REFERENCE ONLY. CONTROL WIRING TO EACH UNIT (NOT SHOWN) BY

TEMPERATURE CONTROLS CONTRACTOR. REFER TO TEMPERATURE CONTROL DRAWINGS FOR MORE

INFORMATION.

3. THE CONTRACTOR SHALL OBTAIN ALL WIRING DIAGRAMS ASSOCIATED WITH MECHANICAL EQUIPMENT CONTROLS FROM MECHANICAL/CONTROLS CONTRACTOR. CONTROL WIRING SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR. ANY CONDUIT REQUIRED FOR CONTROL WIRING SHALL BE

PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR AND SHALL BE COMPLETED UNDER THE

SUPERVISION OF MECHANICAL/CONTROLS CONTRACTOR.

4. LOCATE ALL DISCONNECTS, STARTERS AND DRIVES WHERE ACCESSIBLE. PROVIDE ACCESS AND CLEARANCE AS REQUIRED PER NEC. PROVIDE ACCESS HATCH IF LOCATED ABOVE HARD LID CEILING.

5. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR MECHANICAL UNIT MODEL NUMBERS AND

SPECIFIC ELECTRICAL REQUIREMENTS, OPTIONS AND ACCESSORIES.

6. INFORMATION ON MECHANICAL DRAWINGS SUPERSEDE INFORMATION SHOWN ON ELECTRICAL

DRAWINGS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS PRIOR TO

ROUGH-IN.

7. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL REQUIREMENTS FOR FINAL

MECHANICAL EQUIPMENT INSTALLED. SHOULD THERE BE ANY DISCREPANCY BETWEEN ACTUAL

EQUIPMENT INSTALLED AND ELECTRICAL OR MECHANICAL DRAWINGS, CONTRACTOR SHALL NOTIFY

ENGINEER IMMEDIATELY FOR CLARIFICATION AND FURTHER DIRECTION.

Scale

1/8" = 1'-0"

0 4' 8' 16'

1/8" = 1'-0" N/A

RTD MECHANICAL UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-12

ELECTRICAL

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

100% CONSTRUCTION DOCUMENTS3 JM 2024-11-25

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

1 (X) RTU-1

2 (X) RTU-2

(X)

MDP-(7.9.11)G

MDP-(1.3.5)G

(N) RTU

(N) RTU

CONTROLLER

G

GND NEUT

(E) 100 KVA GENERATOR

277/480V, 3PH, 4W

(E) 150A CB

(E) PAD MOUNTED 75 KVA 277/480V,

3PH, 4W UTILITY TRANSFORMER

(E) GROUND ROD

C T

M

400/3

250A

FRS-R

(E) UTILITY

METER

(E) HEAVY DUTY

NEMA 3R (SERVICE

RATED/LOCKABLE)

(E) 400 A AUTOMATIC

TRANSFER SWITCH

NEMA 3R

250/3

MCB

70/3

(E)

PANEL

"MDP"

70/3

2XF

150/3

(E)

PANEL

"LP2"

XF

150/3

(E)

PANEL

"LP1"

(E) CWP, BLDG STEEL

(E) CWP, BLDG

STEEL

(E) 45 KVA TRANSFORMER

480-120/208 3PH, 4W

FLOOR MOUNTED

(E) 45 KVA TRANSFORMER

480-120/208 3Ø, 4W

FLOOR MOUNTED

FEEDER SCHEDULE

(E) [4-#250 CU; #4 GND]2-1/2"C)

(E) [3-#4 CU; #8 GND]1-1/4"C)

(E) [4-#1/0 CU; #6 GND]2"C)

(E) #6 GND

(E) #2 GND

P

(E) CT CABINET

AREA OF WORK

E-301

ONE-LINE DIAGRAM

GENERAL NOTES - ONELINES

1. ONE LINE DIAGRAMS ARE SHOWN FOR REFERENCE ONLY. ELECTRICAL WORK IS ANTICIPATED TO BE

LIMITED TO THE BRANCH CIRCUIT LEVEL OF THE ELECTRICAL DISTRIBUTION SYSTEM.

SCALE:

ONE-LINE DIAGRAM1

E-301 N/A

UTILITY 12-MONTH PEAK DEMAND: 41 KW

TOTAL EXISTING LOAD: (41KW / 0.8PF) X 100 = 51,250 VA

51,250 VA X 1.25 (NEC 220.87) = 64,062 VA

(X) RTU-1: -19,953 VA

(X) RTU-2: -19,953 VA

(N) RTU-1: 26,604 VA

(X) RTU-2: 19,121 VA

LARGEST MOTOR (NEC 430.24): 0.25 X 26,604 = 6,651 VA

NET LOAD CHANGE ADDED TO 250A SERVICE: 12,470 VA

NEW TOTAL SERVICE LOAD: 76,532 VA OR 92 AMPS @480V, 3PH

SHEET NOTES

EXISTING 30A3P CIRCUIT BREAKER AND BRANCH CIRCUIT SERVING RTU-2 MAY BE REUSED FOR CONNECTION TO NEW EQUIPMENT. EXISTING 30A3P CIRCUIT BREAKER AND BRANCH CIRCUIT SERVING RTU-1 SHALL BE REPLACED WITH NEW 40A3P CIRCUIT BREAKER AND BRANCH CIRCUIT FOR CONNECTION

TO NEW EQUIPMENT. REFER TO HVAC ELECTRICAL CONNECTION SCHEDULE FOR WIRING

CONFIGURATION.

AFTER HVAC EQUIPMENT IS ENERGIZED, THE CONTRACTOR SHALL TEST THE EXISTING GENERATOR AT LOAD. REFER TO SPECIFICATION SECTION 26 60 00 ELECTRICAL SYSTEM TESTING FOR ADDITIONAL

TESTING REQUIREMENTS

SERVICE LOAD JUSTIFICATION

N/A N/A

RTD MECHANICAL UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-12

ELECTRICAL

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

100% CONSTRUCTION DOCUMENTS3 JM 2024-11-25

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

Sheets
G0001 - COVER SHEET