Elati_LRF_Chiller_Stamped_DWGS.pdf

PDF 11 MB Posted

Attached to
HVAC Replacements at Elati, Mariposa, and Security Command Center Locations (15% SBE Goal)
Solicitation number
IFB 325DH003
Issued by
Denver County, Colorado

About this file

These are construction documentation drawings for HVAC replacements and upgrades at the Regional Transportation District's (RTD) Elati Maintenance Facility located in Denver, Colorado. The project involves comprehensive HVAC system replacements, specifically focusing on the Elati Light Rail Facility (LRF), with 100% construction documentation completed on 11/25/2024. The drawings, prepared by HDR Engineering, detail mechanical and electrical upgrades including roof and mezzanine HVAC plans, demolition plans, electrical power plans, one-line electrical diagrams, and equipment schedules. The project scope includes replacing existing HVAC equipment, upgrading chiller systems, modifying electrical connections, and implementing new control systems.

The electrical documentation indicates a significant infrastructure upgrade, with a total service load change adding 30,751 VA to the existing 4000A service, resulting in a new total service load of 760,439 VA (approximately 915 amps at 480V). The project involves removing existing equipment like ACC-1 chiller and installing a new chiller (CH-1), along with heat trace systems. The electrical drawings show detailed conductor schedules, short circuit analysis, and comprehensive electrical connection plans across multiple facility levels. The service load justification accounts for equipment removal, new installations, and adheres to NEC guidelines, suggesting a methodical approach to modernizing the facility's mechanical and electrical infrastructure.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/

2" 1"

2"

SHEET REFERENCE

NUMBER:

4' 8' 16'

FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

/3

1/

0:

:4

A M

\\d en

-s rv

1\ N ew fo rm a\

4\

\1

9\

6.

0_

C A

D _B

IM

\6

.2 _W

IP

\R

T D

_M ec h U pg ra de s.

rv t

G0003

COVER SHEET

THE REGIONAL TRANSPORTATION DISTRICT

HDR Engineering Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

ELATI MAINTENANCE FACILITY

2701 S Elati St, DENVER, CO 80110

100% CONSTRUCTION DOCUMENTATION

ELATI LRF HVAC REPLACEMENTS AND UPGRADES

MARK REVISIONS BY DATE

1 50% DESIGN DEVELOPMENT 1/12/2024

2 75% CONSTRUCTION DOCUMENTS 3/13/2024

3 100% CONSTRUCTION DOCUMENTS 11/25/2024

ELATI LRF HVAC REPLACEMENTS AND UPGRADES

1/2

1"

2"

SHEET REFERENCE

NUMBER:

4' 8' 16'

FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

/2/

3:

:37 P

M \\d en -sr v1 \N ew for ma \15

4\1

4\1

9\6

.0_

CA

D_

BI

M\ 6.2

_W

IP

\R

TD

_M ec h U pg ra de s.r vt

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering

Denver

1670 Broadway, Suite 3400

Denver, CO

80202-4824

MARK REVISIONS BY DATE

1 50% DESIGN DEVELOPMENT 1/12/2024

3 100% CONSTRUCTION DOCUMENTS 11/25/2024

EAB

EAB

3/13/2024EAB2 75% CONSTRUCTION DOCUMENTS

M-001

MECHANICAL COVER SHEET

11-25-20

1"

2"

SHEET REFERENCE

NUMBER:

4' 8' 16'

FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

/2/

3:

:37 P

M \\d en -sr v1 \N ew for ma \15

4\1

4\1

9\6

.0_

CA

D_

BI

M\ 6.2

_W

IP

\R

TD

_M ec h U pg ra de s.r vt

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering

Denver

1670 Broadway, Suite 3400

Denver, CO

80202-4824

MARK REVISIONS BY DATE

1 50% DESIGN DEVELOPMENT 1/12/2024

3 100% CONSTRUCTION DOCUMENTS 11/25/2024

EAB

EAB

3/13/2024EAB2 75% CONSTRUCTION DOCUMENTS

M-201

HVAC PLANS

Scale

1/8" = 1'-0"

0 4' 8' 16'

HVAC ROOF PLAN

KEY PLAN

HVAC ROOF DEMOLITION PLAN

KEY PLAN

KEY PLAN

HVAC MEZZANINE DEMOLITION PLAN

KEY PLAN

HVAC MEZZANINE PLAN

1"

2"

SHEET REFERENCE

NUMBER:

4' 8' 16'

FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

/2/

3:

:37 P

M \\d en -sr v1 \N ew for ma \15

4\1

4\1

9\6

.0_

CA

D_

BI

M\ 6.2

_W

IP

\R

TD

_M ec h U pg ra de s.r vt

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering

Denver

1670 Broadway, Suite 3400

Denver, CO

80202-4824

MARK REVISIONS BY DATE

1 50% DESIGN DEVELOPMENT 1/12/2024

3 100% CONSTRUCTION DOCUMENTS 11/25/2024

EAB

EAB

3/13/2024EAB2 75% CONSTRUCTION DOCUMENTS

M-301

HVAC SCHEDULES, DETAILS, AND CONTROL DRAWINGS

BAS NETWORK DIAGRAM

SCALE: NONE

AIR HANDLING UNIT AND CHILLER CONTROL DIAGRAM

(E)AHU-1, ACC-1

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-26

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

100% CONSTRUCTION DRAWINGS3 JM 2024-11-25

E-701 N/A

E-001

ELECTRICAL SYMBOLS, LEGEND & GENERAL NOTES

DRAWOUT CIRCUIT BREAKER

CIRCUIT BREAKER

INTERRUPTER SWITCH

METERING DEVICE

JUNCTION BOX (SIZE AS REQUIRED UNO)

SHADING INDICATES EGRESS FIXTURE

SHEET NOTE DESIGNATION

EMERGENCY LIGHTING UNIT

DOWNLIGHT

STRIP FIXTURE

SHUNT TRIP DEVICE

GROUND FAULT INTERRUPTER DEVICE

SURFACE MOUNT TROFFER

SPEAKER

TELEVISION OUTLET: 18" AFF (UNO)

TELEPHONE TERMINAL BOARD (TTB)

DATA / VOICE OUTLET: FLOOR MOUNTED

MULTI-OUTLET ASSEMBLY: SPACING PER DWGS

FIXTURE DESIGNATION: F1=TYPE (SEE FIXTURE SCH.)

REVISION DELTA: NUMBER REPRESENTS REVISION

EQUIPMENT CONNECTION

TELEPHONE OUTLET: 18" AFF

NEUTRAL CONDUCTOR

PHASE CONDUCTOR(S)

ISOLATED GROUNDING CONDUCTOR

HOMERUN TO PANELBOARD OR DEVICE

NEUTRAL CONDUCTOR (N=1, 2N=2 NEUTRALS,

PHASE CONDUCTOR(S)

GROUNDING CONDUCTOR

HOMERUN CIRCUIT DESIGNATION

PANELBOARD DESIGNATION

HOMERUN CIRCUIT DESIGNATION

(3 PHASE CIRCUIT SHOWN)

* FIXTURE SCHEDULE HAS PRECEDENCE *

VOLUMETRIC TROFFER

FLANGED TROFFER

WALL PACK

POLE MOUNT

EXIT SIGN FIXTURE - SHADED AREA DENOTES LIGHTED

FACE - ARROWS INDICATE DIRECTION

DATA / VOICE OUTLET: 18" AFF - 1 VOICE, 1 DATA JACK,

TRANSFORMER

MOTOR - # INDICATES HP

FUSE

VOLUME CONTROL

PHASE CONDUCTOR(S)

GROUNDING CONDUCTOR

PANELBOARD DESIGNATION

NORMALLY OPEN (NO) CONTACT

NORMALLY CLOSED (NC) CONTACT

GROUNDING BAR

TICS = NO. OF #12 WIRES (UNO) IF MORE THAN

TWO WITHIN RACEWAY. GROUNDING CONDUCTOR

(NOT SHOWN) ALWAYS REQUIRED.

CURRENT TRANSFORMER

REMOTE METER

GENERATOR

GROUND FAULT RELAY W/ CT OR SENSOR

3N=3 NEUTRALS)

TRANSFER SWITCH (A=AUTOMATIC, M=MANUAL)

# FOR POLES 2, 3 OR 4

THERMOSTAT (PROVIDED BY MECH. CONTRACTOR UNO)

COIL - VOLTAGE PER CONTROL DIAGRAMS

PILOT LIGHT (LED) NON PUSH-TO-TEST

THERMAL OVERLOAD

MAGNETIC OVERLOAD

PUSH BUTTON NORMALLY OPEN (NO)

HAND-OFF-AUTO (HOA) SELECTOR SWITCH

LIMIT SWITCH NORMALLY OPEN (NO)

PUSH BUTTON ILLUMINATED (LED)

PILOT LIGHT (LED) PUSH-TO-TEST. LETTER INDICATES

COLOR (R=RED, G=GREEN, A=AMBER, Y=YELLOW)

PUSH BUTTON NORMALLY CLOSED (NC)

LIMIT SWITCH NORMALLY CLOSED (NC)

A

ADA

AFC

AFCI

AFF

AFG

AHJ

AIC

AL

ATS

AWG

BC

BKR

C

CEC

CKT

CLG

CO

CT

CU

DB

DDC

DPDT

DPST

DWG

(E)

ELEC

EM

EMT

(F)

FLA

FMC

FPEN

GFI

GFR

GND

HID

HOA

HP

HSKP

IMC

J-BOX

K

KVA

KW

LTG

IG

MCB

MCM

MFG

MLO

MS

MSB

MTS

NC

NEC

NEMA

NIC

NL

NO

NTS

NVE

P

PH/Ø

PV

PNL

PTC

PWR

(R)

RAC

RFC

RSC

SE

SPDT

SPST

STC

SW

TE

TTB

TYP

UL

UNO

UNSW

UPS

V

VA

VFD

W

WP

(X)

XFMR OR XF

AMPS

AMERICANS WITH DISABILITIES ACT

ABOVE FINISHED CEILING

ARC-FAULT CIRCUIT INTERRUPTER

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTHORITY HAVING JURISDICTION

AMP INTERRUPTING CAPACITY

ALUMINUM

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BARE COPPER

BREAKER

CONDUIT/RACEWAY

CALIFORNIA ENERGY COMMISSION

CIRCUIT

CEILING

CONDUIT/RACEWAY ONLY

CURRENT TRANSFORMER

COPPER

DISTRIBUTION BOARD

DIRECT DIGITAL CONTROLLER

DOUBLE-POLE, DOUBLE-THROW

DOUBLE-POLE, SINGLE-THROW

DRAWING

EXISTING TO REMAIN

ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

FUTURE

FULL LOAD AMPS

FLEXIBLE METAL CONDUIT (STEEL)

FUSE PER EQUIP. NAMEPLATE

GROUND FAULT INTERRUPT

GROUND FAULT RELAY

GROUND

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTO SWITCH

HORSEPOWER

HOUSEKEEPING

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

kcmil (300K = 300 kcmil)

KILOVOLT AMPS

KILOWATT

LIGHTING

ISOLATED GROUND

MAIN CIRCUIT BREAKER

THOUSAND CIRCULAR MILS

MANUFACTURER

MAIN LUGS ONLY

MOTOR STARTER

MAIN SWITCHBOARD

MANUAL TRANSFER SWITCH

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NOT IN CONTRACT

NIGHTLIGHT

NORMALLY OPEN

NOT TO SCALE

NV ENERGY

POLE

PHASE

PHOTOVOLTAIC

PANEL

PV USA TEST CONDITIONS

POWER

RELOCATE/RELOCATED

RIGID ALUMINUM CONDUIT

RIGID FIBERGLASS CONDUIT

RIGID STEEL CONDUIT

SERVICE ENTRANCE

SINGLE-POLE, DOUBLE-THROW

SINGLE-POLE, SINGLE-THROW

STANDARD TEST CONDITIONS

SWITCH

TELECOM

TELEPHONE TERMINATION BOARD

TYPICAL

UNDERWRITER'S LABORATORY

UNLESS NOTED OTHERWISE

UNSWITCHED

UNINTERRUPTED POWER SUPPLY

VOLTS

VOLT AMPS

VARIABLE FREQUENCY DRIVE

WATTS

WEATHER PROOF

EXISTING TO BE REMOVED

TRANSFORMER

FEEDER DESIGNATION

DATA OUTLET: 18" AFF

SURGE PROTECTION DEVICE

SPD SURGE PROTECTION DEVICE

ELECTRICAL LEGEND

DEVICE MOUNTED AT NON-STANDARD HEIGHT. IF NO HEIGHT

SHOWN VERIFY HEIGHT WITH ARCHITECT

QUAD RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

DUPLEX RECEPTACLE: FLOOR MOUNTED

DUPLEX RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

SINGLE RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

DUPLEX RECEPTACLE: HALF SWITCHED, +18" AFF

ISOLATED GROUND TYPE RECEPTACLE (ORANGE TRIANGLE),

20A, 125V, NEMA 5-20IG, +18" AFF

DUPLEX RECEPTACLE GFI TYPE - 20A, 125V, NEMA 5-20 GFI

SPECIAL PURPOSE RECEPTACLE: SEE DWGS FOR NEMA

DUPLEX RECEPTACLE: CEILING MOUNTED

MULTI-OUTLET ASSEMBLY: SPACING PER DWGS

QUAD RECEPTACLE: FLOOR MOUNTED

BLANK GFCI PROTECTIVE DEVICE IN READILY ACCESSIBLE

LOCATION (LABEL PROTECTED DEVICES)

PHOTOELECTRIC CELL (ON ROOF FACING NORTH UNO)

OCCUPANCY SENSOR - WALL MOUNTED 48" AFF

CONTROL STATION

TIME WALL SWITCH EQUAL TO HUBBELL DT2000W

SWITCH WITH PILOT LIGHT 48" AFF

DIMMER OPERATED SWITCH 48" AFF

KEY OPERATED SWITCH 48"

SINGLE POLE SWITCH 48" AFF

THREE WAY SWITCH 48" AFF

FOUR WAY SWITCH 48" AFF

MANUAL MOTOR STARTER

COMMUNICATIONS OR SIGNAL

PRIMARY

SECONDARY

OVERHEAD SERVICE

CONDUIT/RACEWAY BELOW GRADE OR BELOW FLOOR

CONDUIT/RACEWAY IN WALL OR ABOVE CEILING

LOW VOLTAGE AND/OR CONTROL WIRING

CONDUIT/RACEWAY STUB OUT: MARK AND CAP (SITE)

TELEPHONE

TIMECLOCK

BREAK OR RUN CONTINUES

CONDUIT/RACEWAY SLEEVE

EMERGENCY CIRCUIT

CONTACTOR OR RELAY

OCCUPANCY SENSOR - CEILING MOUNTED. PROVIDE

WITH POWER PACK PER MFG REQUIREMENTS.

SWITCH WITH LIGHTED HANDLE

TELEVISION

0-10V DIMMING OCCUPANCY SENSOR - WALL MOUNTED

48" AFF - EQUAL TO SENSOR SWITCH WSX-D

OCCUPANCY SENSOR - CORNER MOUNTED. PROVIDE

WITH POWER PACK PER MFG REQUIREMENTS.

DUPLEX "CLOCK" RECEPTACLE: 125V, NEMA 5-20R, +60" AFF

QUAD RECEPTACLE: CEILING MOUNTED

LENSED TROFFER

DEVICE MOUNTED AT NON-STANDARD HEIGHT. IF NO HEIGHT

SHOWN VERIFY HEIGHT WITH ARCHITECT

(RR) REMOVE AND REPLACE

HA-[1,3,5,3N]G

HA-(1.3.5)G

XF

PC

TC

GFI

M

ST

S

TV

VC

A

M

G

GFI

X"

T

J

F1

(N)RTU

48" AFF

+18" AFF

COMBO DUAL USB CHARGER / DUPLEX RECEPTACLE, 5.1A, (1)

TYPE A & (1) TYPE C USB (3.1, 3.0, 2.0 AND 1.1 COMPATIBLE),

20A, 125V, NEMA 5-20R, +18AFF

QUAD USB CHARGER, 5.1A, (2) TYPE A & (2) TYPE C USB (3.1,

3.0, 2.0 AND 1.1 COMPATIBLE), +18AFF

CONFIGURATION

2 BLANKS

BRANCH CIRCUIT (WHEN TIC MARKS ARE NOT

SHOWN) = (1) PHASE, (1) NEUTRAL AND (1)

GROUNDING CONDUCTOR

L R

E M M1

K H

= LIGHTING

= RECEPTACLES

= EQUIPMENT = MOTOR

= LARGEST MOTOR

= KITCHEN EQUIP

= ELECTRIC HEAT

PANELBOARD: SURFACE MOUNTED

PANELBOARD: FLUSH MOUNTED

SWITCHBOARD OR DISTRIBUTION PANEL

TRANSFORMER

PULLBOX / VAULT

MOTOR STARTER

COMBINATION MOTOR STARTER

COMBINATION MOTOR STARTER PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

DISCONNECT SWITCH - FUSIBLE (FUSED PER EQUIP.

NAMEPLATE)

DISCONNECT SWITCH - NON-FUSIBLE

DISCONNECT SWITCH PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

VARIABLE FREQUENCY DRIVE

VARIABLE FREQUENCY DRIVE PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

ENCLOSED CIRCUIT BREAKER

GROUND ROD

SHUNT TRIP STATION OR EMERGENCY PUSHBUTTON

REMOTE METER

NOTE: THIS IS A MASTER SYMBOL LIST. IT MAY BE THAT NOT ALL SYMBOLS SHOWN ARE USED WITHIN THIS SET OF PLANS. HEIGHTS GIVEN ARE TO TOP OF BOX.

BREAKERS: 20 = SINGLE POLE CIRCUIT BREAKER 20/2 = TWO POLE CIRCUIT BREAKER 20/3 = THREE POLE CIRCUIT BREAKER 20A = ARC FAULT CIRCUIT BREAKER 20C = CONTROLLABLE CIRCUIT BREAKER 20G = GFI CIRCUIT BREAKER

SHEET DESCRIPTION 75

C O

N

ST

R U

C

TI

O N

D R

AW

IN

G S

/1

3/

NOTE: "(E)" IN HOMERUN INDICATES NEW HOMERUN

TO EXISTING PANEL

SCOPE OF WORK - PHASE 1

REPLACE EXISTING AIR COOLED CHILLER AND CHILLED WATER PUMPS. PROVIDE NEW ELECTRICAL CONNECTIONS TO

NEW AIR COOLED CHILLER. AND NEW CHILLED WATER PUMPS.

GENERAL NOTES

1. INSTALLATION SHALL COMPLY WITH CURRENTLY ADOPTED 2023 NEC AND LOCAL CODES. ALL WORK

PRACTICES SHALL COMPLY WITH NFPA 70E. ENERGIZED WORK IS PROHIBITED UNLESS PERFORMED UNDER AN APPROVED ENERGIZED WORK PERMIT WITH AN IEE 1584 COMPLIANT ARC FLASH ASSESSMENT.

2. DATA PRESENTED ON THESE DRAWINGS REPRESENTS DESIGN INTENT BASED ON AVAILABLE INFORMATION, BUT FIELD VERIFICATION OF ALL DIMENSIONS, LOCATIONS, LEVELS, ETC. TO SUIT FIELD CONDITIONS IS REQUIRED. REVIEW ALL CIVIL DETAILS AND ADJUST WORK TO MEET THE REQUIREMENTS OF CONDITIONS SHOWN. DISCREPANCIES BETWEEN DIFFERENT PLANS OR BETWEEN DRAWINGS AND SPECIFICATIONS, OR REGULATIONS AND CODES GOVERNING THE INSTALLATION SHALL BE BROUGHT TO THE ATTENTION OF THE

ENGINEER IN WRITING.

3. ALL WORK SHALL BE COMPLETED IN A NEAT AND WORKMANLIKE MANNER AND IN ACCORDANCE WITH NECA STANDARDS, INCLUDING NECA 1 STANDARDS FOR GOOD WORKMANSHIP IN ELECTRICAL CONSTRUCTION.

4. ALL WORK SHALL BE SUBJECT TO INSPECTION AND POSSIBLE REJECTION IF NOT IN ACCORDANCE WITH THE

DRAWINGS AND SPECIFICATIONS AND INSTALLED IN A NEAT AND WORKMANLIKE MANNER.

5. WORK REJECTED DUE TO CONTRACT, COD, SPECIFICATION, DRAWINGS, OR COORDINATION DEFICIENCY

SHALL BE REPLACED AT NO ADDITIONAL COST TO THE OWNER.

6. PROVIDE REPRODUCIBLE RECORD DRAWINGS OF ALL COMPLETED WORK. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS

7. THE CONTRACTOR SHALL REMOVE FROM THE JOB SITE ALL DISCARD AND ABANDONED MATERIALS FROM DEMOLITION AND INSTALLATION. THIS INCLUDES BUT IS NOT LIMITED TO CONDUIT, FASTENERS, BOXES, & ETC. MATERIALS EMBEDDED IN GRADE AND / OR CONCRETE MAY BE ABANDONED IN PLACE. ALL ABANDONED

CONDUIT SHALL BE CAPPED. ALL DEMOLISHED CONDUCTORS SHALL BE REMOVED.

8. DO NOT SPLICE FEEDER CONDUCTORS UNLESS WRITTEN PRIOR APPROVAL HAS BEEN OBTAINED FROM THE

ENGINEER. APPROVING SPECIFIC CONTRACTOR PROPOSED LOCATION AND SPLICING METHOD.

9. THE MAXIMUM NUMBER OF CONDUIT BENDS SHALL NOT BE GREATER THAN 270 DEGREES BETWEEN PULLING

STRUCTURES. THIS INCLUDES THE AGGREGATE OF ALL HORIZONTAL AND VERTICAL CHANGES.

10. ALL CONDUIT, PULLBOXES AND VAULTS SHALL BE LABELED PER THE SPECIFICATIONS.

11. EACH SPARE CONDUIT SHALL BE PROVIDED WITH A 1250 LBS. PULL ROPE AND TO/FROM IDENTIFICATION

TAGS.

N/A

D

ES

IG

N

D

EV

EL

O

PM

EN

T

/2 6/

DRAWING SCHEDULE - PHASE 1

E-001 ELECTRICAL SYMBOLS, LEGEND & GENERAL NOTES

ED-201 DEMOLITION POWER PLANS - LEVEL 02

E-101 POWER PLAN - LEVEL 01

E-201 POWER PLANS - LEVEL 02

E-501 ONE-LINE DIAGRAM

E-601 ELECTRICAL SCHEDULES

TOTAL SHEETS IN ISSUE: 6

N/A

0%

C O

N

ST

R U

C

TI

O N

D R

AW

IN

G S

/2

5/

11/25/2024

XF XF

XF

J

J

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-26

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

100% CONSTRUCTION DRAWINGS3 JM 2024-11-25

ED-201

DEMOLITION POWER PLANS - LEVEL 02

GENERAL NOTES - DEMOLITION

KEY PLAN

1. THIS DRAWING REPRESENTS THE EXISTING POWER SYSTEMS WITHIN THE EXISTING BUILDING (AREA TO BE REMODELED). THE CONTRACTOR IS RESPONSIBLE FOR REMOVING, RELOCATING AND REWIRING ALL EQUIPMENT AS INDICATED ON THE DRAWINGS, INCLUDING EQUIPMENT THAT LIES WITHIN WALLS AND

CEILINGS TO BE DEMOLISHED OR REMODELED.

2. (X) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE REMOVED, (R) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE RELOCATED, (E) AND/OR HALFTONE LINES INDICATE EXISTING

EQUIPMENT TO REMAIN UNLESS NOTED OTHERWISE.

3. SALVAGEABLE ITEMS REMOVED DURING DEMOLITION SHALL BE OFFERED TO OWNER PRIOR TO

DISPOSAL OR REMOVAL FROM SITE.

4. EXISTING CIRCUITS AS INDICATED ARE BASED ON LIMITED FIELD INVESTIGATION AND INFORMATION PER RECORD DRAWINGS AND SHALL BE FIELD VERIFIED BY ELECTRICAL CONTRACTOR PRIOR TO START OF

DEMOLITION WORK.

5. THE CONTRACTOR SHALL SALVAGE AND REUSE EXISTING BOXES AND CONDUIT WHERE POSSIBLE.

DAMAGED CONDUIT, FITTINGS BOXES, ETC. MAY NOT BE RE-USED. NEW CIRCUITING AS INDICATED ON THE DRAWINGS IS SHOWN FOR INTENT ONLY AND MAY VARY BASED ON ACTUAL FIELD CONDITIONS

(NEW CIRCUITING SHALL MATCH EXISTING WHERE POSSIBLE TO UTILIZE EXISTING HOME-RUN

CONDUITS, ETC.). KEEP AS-BUILT DRAWINGS CURRENT WITH ANY DEVIATION IN CIRCUITING FROM WHAT

IS INDICATED WITHIN THESE PLANS.

6. THE CONTRACTOR SHALL REMOVE FROM THE JOB SITE ALL DISCARDED AND ABANDONED MATERIALS LEFT OVER FROM DEMOLITION AND INSTALLATION. THIS INCLUDES, BUT IS NOT LIMITED TO, CONDUIT, FASTENERS AND BOXES. MATERIALS EMBEDDED IN GRADE AND / OR CONCRETE MAY BE ABANDONED IN

PLACE. ALL ABANDONED CONDUIT SHALL BE CAPPED.

SHEET NOTES

SCALE:

POWER PLAN - LEVEL 021

ED-201 1/16" = 1'-0"

DEMOLITION

1/16" = 1'-0"

1/ ED-201

(E) PANEL "L1B3"

(E) TRANSFORMER "L1B3"

(E) PANEL "H1B3"

(E) SWITCHBOARD "SBA" (E) PANEL "L1B1"

(E) TRANSFORMER "L1B1"

(E) PANEL "H1B1"

(E) TRANSFORMER "L1B2"

(E) PANEL "H1B2"

(E) PANEL "L1B2"

(E) 2-SECTION PANEL "H1B4"

(E) TRANSFORMER "L1B4"

(E) PANEL "L1B4"

STORAGESTAIR 'B'

FREIGHT

ELEVATOR

MECHANICAL

ROOM

ELECTRONICS

SHOP

MEZZANINE

ELEV.

EQUIP.

ELECTRICAL

ROOM

HVAC

REPAIR SHOP

HVAC

REPAIR SHOP

STAIR 'A'

PARTS /

STOREROOM

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED. DE-ENERGIZE AND SAFE OFF CONDUCTORS FOR RECONNECTION TO NEW EQUIPMENT. REMOVE EXISTING ASSOCIATED VFD. COORDINATE DEMOLITION

WITH GENERAL CONTRACTOR, MECHANICAL CONTRACTOR, AND OWNER PRIOR TO THE START OF

WORK.

CONDUIT SERVING EXISTING CONVENIENCE RECEPTACLE IS ROUTED ALONG EXISTING HVAC

EQUIPMENT. REMOVE EXISTING RECEPTACLE. REMOVE CONDUCTORS AND CONDUIT BACK TO

NEAREST JUNCTION BOX TO REMAIN.

EXISTING ACC-1 CHILLER CONTROL PANEL SHALL BE DEMOLISHED. DE-ENERGIZE AND REMOVE BRANCH CIRCUIT BACK TO NEAREST JUNCTION BOX TO REMAIN. CAP CONDUIT FOR REUSE. EXISTING BRANCH

CIRCUIT SHALL BE REUSED TO POWER NEW CHILLER CONTROL PANEL.

EXISTING MOTOR AND MOTOR STARTER SHALL BE DEMOLISHED AND REMOVED. DE-ENERGIZE AND

SAFE OFF CONDUCTORS FOR RECONNECTION TO NEW PUMP VFD AND MOTOR. COORDINATE

DEMOLITION WITH MECHANICAL CONTRACTOR PRIOR TO THE START OF WORK.

SWITCHBOARD

"MSA" (X) ACC

(E)

0 8' 16' 32'

SCALE: 1/16"=1'-0" (IN FEET)

(E) H1A2-(1.3.5)G

(E) H1A2-(7.9.11)G

(X) P-2

(X) P-1

XFATS

XF

XF

E-101

POWER PLAN - LEVEL 01

SCALE:

POWER PLAN - LEVEL 011

E-101 1/16" = 1'-0"

GENERAL NOTES - NEW WORK

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW

EQUIPMENT UNLESS NOTED OTHERWISE.

2. TERMINAL UNITS SHOWN FOR REFERENCE ONLY. CONTROL WIRING TO EACH UNIT (NOT SHOWN) BY

TEMPERATURE CONTROLS CONTRACTOR. REFER TO TEMPERATURE CONTROL DRAWINGS FOR MORE

INFORMATION.

3. THE CONTRACTOR SHALL OBTAIN ALL WIRING DIAGRAMS ASSOCIATED WITH MECHANICAL EQUIPMENT CONTROLS FROM MECHANICAL/CONTROLS CONTRACTOR. CONTROL WIRING SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR. ANY CONDUIT REQUIRED FOR CONTROL WIRING SHALL BE

PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR AND SHALL BE COMPLETED UNDER THE

SUPERVISION OF MECHANICAL/CONTROLS CONTRACTOR.

4. LOCATE ALL DISCONNECTS, STARTERS AND DRIVES WHERE ACCESSIBLE. PROVIDE ACCESS AND CLEARANCE AS REQUIRED PER NEC. PROVIDE ACCESS HATCH IF LOCATED ABOVE HARD LID CEILING.

5. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR MECHANICAL UNIT MODEL NUMBERS AND

SPECIFIC ELECTRICAL REQUIREMENTS, OPTIONS AND ACCESSORIES.

6. INFORMATION ON MECHANICAL DRAWINGS SUPERSEDE INFORMATION SHOWN ON ELECTRICAL

DRAWINGS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS PRIOR TO

ROUGH-IN.

7. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL REQUIREMENTS FOR FINAL

MECHANICAL EQUIPMENT INSTALLED. SHOULD THERE BE ANY DISCREPANCY BETWEEN ACTUAL

EQUIPMENT INSTALLED AND ELECTRICAL OR MECHANICAL DRAWINGS, CONTRACTOR SHALL NOTIFY

ENGINEER IMMEDIATELY FOR CLARIFICATION AND FURTHER DIRECTION.

KEY PLAN

1/16" = 1'-0"

1/ E-101

(E) PANEL "L1A4"

(E) TRANSFORMER "T-L1A4"

(E) 2-SECTION PANEL "H1A3"

(E) TRANSFORMER "T-L1A3"

(E) GENERATOR REMOTE ANNUNCIATOR

(E) PANEL "H1A4"

(E) PANEL "L1A3"

(E) ATS

(E) MAIN SWITCHBOARD "MSA"

AREA OF WORKAREA OF WORK

(E) PANEL "L1A2"

(E) PANEL "H1A1"

(E) 2 SECTION PANEL "L1A1"

(E) PANEL "H1A2"

(E) TRANSFORMER "T-L1A1"

(E) TRANSFORMER "T-L1A2"

TOOL BOX

STORAGE

PART'S

OFFICE

PARTS

COUNTER

TOOL

ROOM

COMMON

WORK AREA

BATTERY

ROOM

ELECTRICAL

ROOM

MEN

REPORT/

SIGN-OUT

125A

WOMEN

JAN

QUIET

ROOM

FITNESS

ROOM

TELE/DATA

ROOM

133STORAGE

TRANS/MAINT

TRAINERS

COMPUTER

TRAINING

SECURITY

VESTIBULE

CONTROLLER/

SUPERVISOR

COUNSEL

LR ASSIST

MANAGER

REPORT/

SIGN-OUT

LUNCH

ROOM

KITCHEN/

VENDING

PLAN

ROOM

103A

ADMIN

TECH

GENERAL

SUPERINTENDENT

LR TRANS

MANAGER

LR MAINT

MANAGER

SR LEAD

EQUIP ENG

LEAD CNTRL

SUPERVISOR

CONFERENCE

ROOM

COPY

102C

CUSTOMER

SERVICE

VESTIBULE

BREAK

102D

LIBRARY

102F

SECRETARY

102E

SECRETARY

102E LOCKER

ALCOVE

LOBBY

VESTIBULE

HALLWAY

WAITING

102A

RECEPTION

102B

CREW/BREAK ROOM

KITCHENETTE/VENDING

139A

UNIFORM

LOCKER AREA

134C

HALLWAY

134B

PARTS

STOREROOM

FIRE

CONTROL

A/V

STORAGE

WOMEN

MEN

MAINTENANCE

OF WAY

CONFERENCE/

TRAINING

CHR/TBL

STORAGE

118A

HALLWAY

134A

ELECTRICAL

HALLWAY

134G

MEN'S

SHOWER ROOM

HAZARDOUS

MATERIAL STORAGE

LUBE/COMPRESSOR

ROOM

FACILITY MAINTENANCE

SHOP/STORAGE

OFFICE

STAIR 'C'

MEN

MEN'S

LOCKER AREA

138A

HALLWAY

134F

WOMEN

WOMEN'S

LOCKER AREA

137A

STAIR 'B'

STAIR 'A'

142 HALLWAY

134E

HALLWAY

134D

JANITOR

LIBRARY

WORK STATION

RECORD'S

STORAGE

157A

SUPERVISOR'S

OFFICE

LIBRARY

WORK STATION

FREIGHT

ELEVATOR

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-26

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

100% CONSTRUCTION DRAWINGS3 JM 2024-11-25

(E)

(E)

0 8' 16' 32'

SCALE: 1/16"=1'-0" (IN FEET)

FOR REFERENCE ONLY

XF XF

J

J

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-26

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

100% CONSTRUCTION DRAWINGS3 JM 2024-11-25

E-201

POWER PLANS - LEVEL 02

GENERAL NOTES - NEW WORK

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW

EQUIPMENT UNLESS NOTED OTHERWISE.

2. TERMINAL UNITS SHOWN FOR REFERENCE ONLY. CONTROL WIRING INSTALLATION, TERMINATION, AND

TESTING TO EACH UNIT (NOT SHOWN) SHALL BE COMPLETED BY TEMPERATURE CONTROLS

CONTRACTOR. REFER TO TEMPERATURE CONTROL DRAWINGS FOR MORE INFORMATION.

3. THE CONTRACTOR SHALL OBTAIN ALL WIRING DIAGRAMS ASSOCIATED WITH MECHANICAL EQUIPMENT CONTROLS FROM MECHANICAL/CONTROLS CONTRACTOR. CONTROL WIRING SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR. ANY CONDUIT REQUIRED FOR CONTROL WIRING SHALL BE

PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR AND SHALL BE COMPLETED UNDER THE

SUPERVISION OF MECHANICAL/CONTROLS CONTRACTOR.

4. LOCATE ALL DISCONNECTS, STARTERS AND DRIVES WHERE ACCESSIBLE, WITHIN DIRECT LINE OF SITE OF EQUIPMENT. PROVIDE ACCESS AND CLEARANCE AS REQUIRED PER NEC. PROVIDE ACCESS HATCH IF

LOCATED ABOVE HARD LID CEILING.

5. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR MECHANICAL UNIT MODEL NUMBERS AND

SPECIFIC ELECTRICAL REQUIREMENTS, OPTIONS AND ACCESSORIES.

6. INFORMATION ON MECHANICAL DRAWINGS SUPERSEDE INFORMATION SHOWN ON ELECTRICAL

DRAWINGS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS PRIOR TO

ROUGH-IN.

7. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL REQUIREMENTS FOR FINAL

MECHANICAL EQUIPMENT INSTALLED. SHOULD THERE BE ANY DISCREPANCY BETWEEN ACTUAL

EQUIPMENT INSTALLED AND ELECTRICAL OR MECHANICAL DRAWINGS, CONTRACTOR SHALL NOTIFY

ENGINEER IMMEDIATELY FOR CLARIFICATION AND FURTHER DIRECTION.

SHEET NOTES

KEY PLAN

SCALE:

POWER PLAN - LEVEL 021

E-201 1/16" = 1'-0"

1/16" = 1'-0"

1/ E-201

(E) PANEL "L1B3"

(E) TRANSFORMER "L1B3"

(E) PANEL "H1B3"

(E) SWITCHBOARD "SBA" (E) PANEL "L1B1"

(E) PANEL "H1B1"

(E) TRANSFORMER "L1B2"

(E) PANEL "H1B2"

(E) PANEL "L1B2"

(E) 2-SECTION PANEL "H1B4"

(E) TRANSFORMER "L1B4"

(E) PANEL "L1B4"

AREA OF WORK

STORAGESTAIR 'B'

FREIGHT

ELEVATOR

MECHANICAL

ROOM

ELECTRONICS

SHOP

MEZZANINE

ELEV.

EQUIP.

ELECTRICAL

ROOM

HVAC

REPAIR SHOP

HVAC

REPAIR SHOP

STAIR 'A'

PARTS /

STOREROOM

PROVIDE NEW WEATHERPROOF 5-20R GFCI RECEPTACLE. EXTEND EXISTING BRANCH CIRCUIT AND

CONDUIT SERVING PREVIOUS EQUIPMENT RECEPTACLE TO NEW RECEPTACLE.

REUSE EXISTING FEEDER FOR CONNECTION TO NEW HVAC EQUIPMENT PER HVAC EQUIPMENT

ELECTRICAL CONNECTION SCHEDULE. COORDINATE FINAL CONNECTION TO EQUIPMENT WITH

MECHANICAL CONTRACTOR PRIOR TO THE START OF WORK.

REUSE EXISTING BRANCH CIRCUIT FOR CONNECTION TO NEW CHILLER CONTROL PANEL. COORDINATE CONNECTION AND EXACT LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO THE START OF WORK.

EXTEND EXISTING BRANCH CIRCUIT AS REQUIRED FOR FINAL CONNECTION.

PROVIDE 30A, 277V DEDICATED BRANCH CIRCUIT (2#10, #10G) 3/4"C FOR CONNECTION TO NEW HEAT

TRACE CONTROLLER. COORDINATE EXACT CONNECTION AND LOCATION WITH MECHANICAL

CONTRACTOR PRIOR TO THE START OF WORK. HEAT TRACE GFEP PROTECTION IS PROVIDED BY HEAT

TRACE CONTROLLER. REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

(E)

ACC

0 8' 16' 32'

SCALE: 1/16"=1'-0" (IN FEET)

7 H1A3-[73,N]G

REFER TO

ONE-LINE

DIAGRAM

(E) H1A2-(1.3.5)G

(E) H1A2-(7.9.11)G

P

P

E-501

ONE-LINE DIAGRAM

GENERAL NOTES - ONELINE - DEMOLITION

1. (X) AND/OR HATCHING INDICATE EXISTING EQUIPMENT TO BE REMOVED, (R) AND/OR DASHED LINES INDICATE

EXISTING EQUIPMENT TO BE RELOCATED, (E) INDICATE EXISTING EQUIPMENT TO REMAIN UNLESS NOTED

OTHERWISE.

SCALE:

ONE-LINE DIAGRAM1

E-501 N/A

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-26

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

100% CONSTRUCTION DRAWINGS3 JM 2024-11-25

GENERAL NOTES - ONELINE - NEW CONSTRUCTION

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (R) AND/OR DASHED LINES INDICATE RELOCATED

EQUIPMENT, SOLID LINES INDICATE NEW EQUIPMENT UNLESS NOTED OTHERWISE.

2. PANELBOARD AND BREAKER INTERRUPTING CAPACITIES (AIC) SHALL BE FULLY RATED. SERIES RATING OF

BREAKER DEVICES AND EQUIPMENT IS NOT PERMITTED.

3. ALL CONDUCTOR SIZES ARE BASED ON COPPER. ALUMINUM IS NOT PERMITTED.

4. DO NOT SPLICE FEEDER CONDUCTORS UNLESS PRIOR APPROVAL HAS BEEN OBTAINED FROM THE ENGINEER.

SHEET NOTES

M

(E) L1A1 (E) H1A1 (E) H1A2

(E) MAIN DISTRIBUTION SWITCHBOARD "MSA"

3P

4000A, 480/277V, 3 PHASE, 4 WIRE, 65 KAIC

(E)300A

3P MB

(E) 4000A

(E)TVSS

(E)#3/0 CU

BLDG

STEEL

N G

PIPE

COLD WATER

(E)#3/0 CU

(E)500A 3P

(E)400A 3P

(E)3000A 3P

FEEDER

UTILITY

XFMR

(E) UTILITY

METER

(E) UTILITY

(E) L1A4 (E) H1A4

OFFICE AREA

(E)1#2 CU

208/120V

(E) T-L1A1 480V-

75KVA

(E)300A 3P

(E)300A 3P

(E)400A 3P

(E)400A 3P

(E)MCC1 (E)MCC2

(E)#6 CU

(E)T-L1B1 480V-

45KVA

208/120V

(E) H1B1 (E) L1B1

208/120V

75KVA

480V- (E)T-L1B2

(E)#2 CU

(E) H1B2 (E) L1B2 (E) H1B3

(E)T-L1B3 480V-

75KVA

208/120V

(E)#2 CU

(E) L1B3 (E) H1B4

(E)T-L1B4 480V-

45KVA

208/120V

(E)#6 CU

(E) L1B4

(E)225A 3P 3P

(E)400A

MAINTENANCE AREA

(E) DISTRIBUTION SWITCHBOARD "SBA"

3000A, 480/277V, 3 PHASE, 4 WIRE, 65 KAIC

3/4"D x 10'

(E)#3/0 CU TO

3P (E)70A

(E)ELEV

(E)60A 3P

(E)125A 3P

(E)60A 3P

3P (E)60A

3P (E)400A

(E) H1A3

45KVA

1#6 CU

(E) T-L1A3 480V- 208/120V

(E) L1A3

(E)150A 3P

(E)200A 3P

(E)300A 3P

(E)60A 3P

(E)60A 3P

(E)125A 3P

GFR

RELAY

HOUSE 1

(E)SWITCH

HEATER-

(E)SWITCH

HEATER-

RELAY

HOUSE 2

(E)SWITCH

HEATER-

RELAY

HOUSE 3

3P (E)400A

G

(E) 400A/3P A.T.S.

STANDBY GENERATOR

(E) 250KW

480/277V, 3 PHASE, 4 WIRE

GND ROD

3P 200A

3P (E)400A (E)200A

3P

208/120V

(E)1#2 CU

(E)T-L1A2 480V-

75KVA

(E)125A 3P

(E) L1A2

ROOM

TELE/DATA

208/120V

(E)#6 CU

(E)T-L1C1 480V-

45KVA

JANITOR ROOM

(E)L1C1 (E)H1C1

(E)60A 3P

(E)1#2 CU

45KVA

480V-

(E) T-L1A4

208/120V

(E)500A 3P

(E)400A 3P

SPARE

ST

(E)125A 3P

(E)100A 3P

(HOIST)(HOIST)(WASH)

(E)MCC

SPARESPARE

(E)ANNUNCIATOR

PANEL

100% RATED

PHASE NEUTRAL GROUND CONDUIT NO. OF RUNS

500 -500 4" 11

SYMBOL

500 500 400 3 1/2" 8

250 250 2 2 1/2" 2

350 350 4 3" 1

1/0 - 6 1 1/2" 1

1 - 6 1 1/2" 1

14 8- 1 1/4"

6 10-

CONDUCTORS

CONDUCTOR SCHEDULE

2 1/2"33/03/0

1"

6 6 10 1 1/4" 1

350 - 4 2 1/2" 1

250 250 4 2 1/2" 1

4/0 6- 12"

1/0 1/0 6 2" 1

2 2 8 1 1/2" 1

5A

7A

8A

9A

11A

12A

3 4 7A 12 4 8A 7A 5A

6 9A 6 9A

8 12A

12A

10 5 5 4 4 6

9A 4 11A 3

12A 8 9A 6 6 12 8

12A8

P S

AREA OF WORK

4 4 8 1 1/4" 111

110 10- 3/4"13A

OFFICE AREA

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED. EXISTING 200A3P CIRCUIT BREAKER AND FEEDER SHALL BE REUSED TO SERVE NEW AIR COOLED CHILLER AS SHOWN. COORDINATE DEMOLITION WITH

GENERAL CONTRACTOR, MECHANICAL CONTRACTOR, AND OWNER PRIOR TO THE START OF WORK.

REPLACE EXISTING 15A3P CIRCUIT BREAKER WITH NEW 30A1P CIRCUIT AND (2) SPARE 20A1P CIRCUIT BREAKERS. MATCH EXISTING TYPE AND AIC RATING. REFER TO PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

AREA OF WORK SHOWN FOR REFERENCE ONLY. REFER TO NEW CONSTRUCTION PLANS FOR

ADDITIONAL INFORMATION

ACC

1 VD=0.89%

SHORT CIRCUIT ANALYSIS

AVAILABLE AIC

H1B4

L1B1

L1B2

L1A1

L1A2

H1A3

H1B1

H1B2

H1B3

SBA

MSA

PANEL

H1A1

H1A2

3533,717

4,440

7,430

5,716

7,430

PANEL KAIC RATING

8,989

35,074

33,717

29,258

33,717

46,374

48,982

5,801

7,430L1B3 10

4,440L1B4 10

MCC 1,790 42

4,440L1C1 10

H1C1 7,842 18

35,074H1A4 65

4,440L1A3 10

4,440L1A4 10

BASED ON A 2500KVA UTILITY TRANSFORMER WITH 60,200A AVAILABLE

MCC1 7,190 42

MCC2 5,046 42

FAULT CURRENT.

N/AN/A

N/A

22,553ACC-1 65

AREA OF WORK

AREA OF WORK

ELATI LRF HVAC REPLACEMENT AND UPGRADES

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY: MGJM

WP APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

MG

2024-11-25

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

2024-11-25

2024-11-25 2024-11-2550% DESIGN DEVELOPMENT1 JM 2024-01-26

75% CONSTRUCTION DOCUMENTS2 JM 2024-03-13

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

100% CONSTRUCTION DRAWINGS3 JM 2024-11-25

E-601

ELECTRICAL SCHEDULES

SERVICE LOAD JUSTIFICATION- PHASE1

UTILITY 12-MONTH PEAK DEMAND: 467KW

TOTAL EXISTING LOAD: (467KW / 0.8PF) X 1000 = 583,750 VA

583,750 VA X 1.25(NEC 220.87) = 729,688 VA

(X)ACC-1: -133,000 VA

(N)CH-1: 162,951 VA

(N) HEAT TRACE:800VA

LARGEST MOTOR (NEC 430.24): 42,816 VA

NET LOAD CHANGE ADDED TO (E) 4000 A SERVICE: 30,751 VA

NEW TOTAL SERVICE LOAD: 760,439 VA OR 915 AMPS @ 480V, 3PH

N/AN/A

N/A

Sheets
G0003 - COVER SHEET

File details come from the government source that posted it. Updated .