Mariposa_Data_Center_Cooling_Stamped_DWGS.pdf

PDF 10 MB Posted

Attached to
HVAC Replacements at Elati, Mariposa, and Security Command Center Locations (15% SBE Goal)
Solicitation number
IFB 325DH003
Issued by
Denver County, Colorado

About this file

These are the 100% Construction Documentation drawings for the Mariposa Light Rail Facility (LRF) Data Center In-Row Cooling project, prepared by HDR Engineering for the Regional Transportation District (RTD) in Denver, Colorado. The project involves mechanical and electrical upgrades to the existing data center, specifically focusing on replacing and upgrading HVAC equipment. The documents are dated November 25, 2024, and include comprehensive electrical and mechanical plans covering demolition and new construction across multiple building levels, including detailed one-line electrical diagrams, power plans, equipment schedules, and load calculations.

The electrical design includes replacing existing HVAC equipment with new cooling units, modifying electrical connections, and updating the electrical distribution system. The load calculations indicate the project will add approximately 17,076 VA to the existing Generator Distribution Panel (GDP) and increase the total service load to 1,282,371 VA. The electrical design maintains the existing 2000A service and 150kW generator while integrating new Computer Room Air Conditioning (CRAC) units, Air Cooled Condensing Units (ACCU), and associated electrical infrastructure. The documents show careful consideration of existing equipment, demolition requirements, and new equipment placement, with a focus on maintaining operational continuity during the upgrade process.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/

2" 1"

2"

SHEET REFERENCE

NUMBER:

4' 8' 16'

FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

/2

/2

3:

:5

P

M \\d en -s rv 1\

N ew fo rm a\

4\

\1

9\ 6.

0_ C

A D

_B

IM

\6 .2

_W

IP

\R T

D _M ec h

U pg ra de s.

rv t

G0002

MARIPOSA LRF DATA CENTER IN-ROW

COOLING

COVER SHEET

THE REGIONAL TRANSPORTATION DISTRICT

MARIPOSA LIGHT RAIL FACILITY

655 Mariposa St, DENVER, CO 80204

100% CONSTRUCTION DOCUMENTATION

RTD MECHANICAL UPGRADES

HDR Engineering Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

MARK REVISIONS BY DATE

1 50% DESIGN DEVELOPMENT 1/12/2024

2 75% CONSTRUCTION DOCUMENTS 3/13/2024

3 100% CONSTRUCTION DOCUMENTS 11/25/2024

HD

R-

A So rt Co de

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

1/2

1"

2" 6/2

0/2

6 2 :12

:55 P

M Fil e P ath FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

50% DESIGN DEVELOPMENT1 EAB 01/12/2024

The Ballard Group, Inc.

Mechanical Consulting Engineers

(303) 988-4514

75% CONSTRUCTION DOCUMENTS2 EAB 03/13/2024

MARIPOSA LRF DATA CENTER IN-ROW COOLING

100% CONSTRUCTION DOCUMENTS3 EAB 11/25/2024

M-001

MECHANICAL COVER SHEET

11-25-20

A So rt Co de

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

1/2

1"

2" 6/2

0/2

6 2 :12

:55 P

M Fil e P ath FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

50% DESIGN DEVELOPMENT1 EAB 01/12/2024

The Ballard Group, Inc.

Mechanical Consulting Engineers

(303) 988-4514

75% CONSTRUCTION DOCUMENTS2 EAB 03/13/2024

MARIPOSA LRF DATA CENTER IN-ROW COOLING

100% CONSTRUCTION DOCUMENTS3 EAB 11/25/2024

HVAC ROOF DEMOLITION PLAN

HVAC ROOF PLAN

HVAC DEMOLITION FLOOR PLAN

HVAC FLOOR PLAN

M-101

HVAC FLOOR PLANS

Scale

1/8" = 1'-0"

0 4' 8' 16'

KEY PLAN

KEY PLAN

A So rt Co de

HDR Engineering Denver

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

1670 Broadway, Suite 3400 Denver, CO 80202-4824

1/2

1"

2" 6/2

0/2

6 2 :12

:55 P

M Fil e P ath FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

50% DESIGN DEVELOPMENT1 EAB 01/12/2024

The Ballard Group, Inc.

Mechanical Consulting Engineers

(303) 988-4514

75% CONSTRUCTION DOCUMENTS2 EAB 03/13/2024

MARIPOSA LRF DATA CENTER IN-ROW COOLING

100% CONSTRUCTION DOCUMENTS3 EAB 11/25/2024

M-301

HVAC SCHEDULES, DETAILS, AND CONTROL DRAWINGS

COMPUTER ROOM AIR CONDITIONING CONTROL DIAGRAM

BAS NETWORK DIAGRAM

HUMIDIFIER CONTROL DIAGRAM

DATA CENTER CONTROL DIAGRAM

MARIPOSA LRF DATA CENTER IN-ROW COOLING

HDR ENGINEERING

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY:

APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

ELECTRICAL

JM

WP

2024-11-25

2024-11-25 MG

MG 2024-11-25

2024-11-25 1 50% DESIGN DEVELOPMENT 2024-01-23JM

2 75% CONSTRUCTION DRAWINGS 2024-03-13JM

3 100% CONSTRUCTION DRAWINGS 2024-11-25JM

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

E-001

ELECTRICAL SYMBOLS, LEGEND & GENERAL NOTES

DRAWOUT CIRCUIT BREAKER

CIRCUIT BREAKER

INTERRUPTER SWITCH

METERING DEVICE

JUNCTION BOX (SIZE AS REQUIRED UNO)

SHADING INDICATES EGRESS FIXTURE

SHEET NOTE DESIGNATION

EMERGENCY LIGHTING UNIT

DOWNLIGHT

STRIP FIXTURE

SHUNT TRIP DEVICE

GROUND FAULT INTERRUPTER DEVICE

SURFACE MOUNT TROFFER

SPEAKER

TELEVISION OUTLET: 18" AFF (UNO)

TELEPHONE TERMINAL BOARD (TTB)

DATA / VOICE OUTLET: FLOOR MOUNTED

MULTI-OUTLET ASSEMBLY: SPACING PER DWGS

FIXTURE DESIGNATION: F1=TYPE (SEE FIXTURE SCH.)

REVISION DELTA: NUMBER REPRESENTS REVISION

EQUIPMENT CONNECTION

TELEPHONE OUTLET: 18" AFF

NEUTRAL CONDUCTOR

PHASE CONDUCTOR(S)

ISOLATED GROUNDING CONDUCTOR

HOMERUN TO PANELBOARD OR DEVICE

NEUTRAL CONDUCTOR (N=1, 2N=2 NEUTRALS,

PHASE CONDUCTOR(S)

GROUNDING CONDUCTOR

HOMERUN CIRCUIT DESIGNATION

PANELBOARD DESIGNATION

HOMERUN CIRCUIT DESIGNATION

(3 PHASE CIRCUIT SHOWN)

* FIXTURE SCHEDULE HAS PRECEDENCE *

VOLUMETRIC TROFFER

FLANGED TROFFER

WALL PACK

POLE MOUNT

EXIT SIGN FIXTURE - SHADED AREA DENOTES LIGHTED

FACE - ARROWS INDICATE DIRECTION

DATA / VOICE OUTLET: 18" AFF - 1 VOICE, 1 DATA JACK,

TRANSFORMER

MOTOR - # INDICATES HP

FUSE

VOLUME CONTROL

PHASE CONDUCTOR(S)

GROUNDING CONDUCTOR

PANELBOARD DESIGNATION

NORMALLY OPEN (NO) CONTACT

NORMALLY CLOSED (NC) CONTACT

GROUNDING BAR

TICS = NO. OF #12 WIRES (UNO) IF MORE THAN

TWO WITHIN RACEWAY. GROUNDING CONDUCTOR

(NOT SHOWN) ALWAYS REQUIRED.

CURRENT TRANSFORMER

REMOTE METER

GENERATOR

GROUND FAULT RELAY W/ CT OR SENSOR

3N=3 NEUTRALS)

TRANSFER SWITCH (A=AUTOMATIC, M=MANUAL)

# FOR POLES 2, 3 OR 4

THERMOSTAT (PROVIDED BY MECH. CONTRACTOR UNO)

COIL - VOLTAGE PER CONTROL DIAGRAMS

PILOT LIGHT (LED) NON PUSH-TO-TEST

THERMAL OVERLOAD

MAGNETIC OVERLOAD

PUSH BUTTON NORMALLY OPEN (NO)

HAND-OFF-AUTO (HOA) SELECTOR SWITCH

LIMIT SWITCH NORMALLY OPEN (NO)

PUSH BUTTON ILLUMINATED (LED)

PILOT LIGHT (LED) PUSH-TO-TEST. LETTER INDICATES

COLOR (R=RED, G=GREEN, A=AMBER, Y=YELLOW)

PUSH BUTTON NORMALLY CLOSED (NC)

LIMIT SWITCH NORMALLY CLOSED (NC)

A

ADA

AFC

AFCI

AFF

AFG

AHJ

AIC

AL

ATS

AWG

BC

BKR

C

CEC

CKT

CLG

CO

CT

CU

DB

DDC

DPDT

DPST

DWG

(E)

ELEC

EM

EMT

(F)

FLA

FMC

FPEN

GFI

GFR

GND

HID

HOA

HP

HSKP

IMC

J-BOX

K

KVA

KW

LTG

IG

MCB

MCM

MFG

MLO

MS

MSB

MTS

NC

NEC

NEMA

NIC

NL

NO

NTS

NVE

P

PH/Ø

PV

PNL

PTC

PWR

(R)

RAC

RFC

RSC

SE

SPDT

SPST

STC

SW

TE

TTB

TYP

UL

UNO

UNSW

UPS

V

VA

VFD

W

WP

(X)

XFMR OR XF

AMPS

AMERICANS WITH DISABILITIES ACT

ABOVE FINISHED CEILING

ARC-FAULT CIRCUIT INTERRUPTER

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTHORITY HAVING JURISDICTION

AMP INTERRUPTING CAPACITY

ALUMINUM

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BARE COPPER

BREAKER

CONDUIT/RACEWAY

CALIFORNIA ENERGY COMMISSION

CIRCUIT

CEILING

CONDUIT/RACEWAY ONLY

CURRENT TRANSFORMER

COPPER

DISTRIBUTION BOARD

DIRECT DIGITAL CONTROLLER

DOUBLE-POLE, DOUBLE-THROW

DOUBLE-POLE, SINGLE-THROW

DRAWING

EXISTING TO REMAIN

ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

FUTURE

FULL LOAD AMPS

FLEXIBLE METAL CONDUIT (STEEL)

FUSE PER EQUIP. NAMEPLATE

GROUND FAULT INTERRUPT

GROUND FAULT RELAY

GROUND

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTO SWITCH

HORSEPOWER

HOUSEKEEPING

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

kcmil (300K = 300 kcmil)

KILOVOLT AMPS

KILOWATT

LIGHTING

ISOLATED GROUND

MAIN CIRCUIT BREAKER

THOUSAND CIRCULAR MILS

MANUFACTURER

MAIN LUGS ONLY

MOTOR STARTER

MAIN SWITCHBOARD

MANUAL TRANSFER SWITCH

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NOT IN CONTRACT

NIGHTLIGHT

NORMALLY OPEN

NOT TO SCALE

NV ENERGY

POLE

PHASE

PHOTOVOLTAIC

PANEL

PV USA TEST CONDITIONS

POWER

RELOCATE/RELOCATED

RIGID ALUMINUM CONDUIT

RIGID FIBERGLASS CONDUIT

RIGID STEEL CONDUIT

SERVICE ENTRANCE

SINGLE-POLE, DOUBLE-THROW

SINGLE-POLE, SINGLE-THROW

STANDARD TEST CONDITIONS

SWITCH

TELECOM

TELEPHONE TERMINATION BOARD

TYPICAL

UNDERWRITER'S LABORATORY

UNLESS NOTED OTHERWISE

UNSWITCHED

UNINTERRUPTED POWER SUPPLY

VOLTS

VOLT AMPS

VARIABLE FREQUENCY DRIVE

WATTS

WEATHER PROOF

EXISTING TO BE REMOVED

TRANSFORMER

FEEDER DESIGNATION

DATA OUTLET: 18" AFF

SURGE PROTECTION DEVICE

SPD SURGE PROTECTION DEVICE

ELECTRICAL LEGEND

DEVICE MOUNTED AT NON-STANDARD HEIGHT. IF NO HEIGHT

SHOWN VERIFY HEIGHT WITH ARCHITECT

QUAD RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

DUPLEX RECEPTACLE: FLOOR MOUNTED

DUPLEX RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

SINGLE RECEPTACLE: 20A, 125V, NEMA 5-20, +18" AFF

DUPLEX RECEPTACLE: HALF SWITCHED, +18" AFF

ISOLATED GROUND TYPE RECEPTACLE (ORANGE TRIANGLE),

20A, 125V, NEMA 5-20IG, +18" AFF

DUPLEX RECEPTACLE GFI TYPE - 20A, 125V, NEMA 5-20 GFI

SPECIAL PURPOSE RECEPTACLE: SEE DWGS FOR NEMA

DUPLEX RECEPTACLE: CEILING MOUNTED

MULTI-OUTLET ASSEMBLY: SPACING PER DWGS

QUAD RECEPTACLE: FLOOR MOUNTED

BLANK GFCI PROTECTIVE DEVICE IN READILY ACCESSIBLE

LOCATION (LABEL PROTECTED DEVICES)

PHOTOELECTRIC CELL (ON ROOF FACING NORTH UNO)

OCCUPANCY SENSOR - WALL MOUNTED 48" AFF

CONTROL STATION

TIME WALL SWITCH EQUAL TO HUBBELL DT2000W

SWITCH WITH PILOT LIGHT 48" AFF

DIMMER OPERATED SWITCH 48" AFF

KEY OPERATED SWITCH 48"

SINGLE POLE SWITCH 48" AFF

THREE WAY SWITCH 48" AFF

FOUR WAY SWITCH 48" AFF

MANUAL MOTOR STARTER

COMMUNICATIONS OR SIGNAL

PRIMARY

SECONDARY

OVERHEAD SERVICE

CONDUIT/RACEWAY BELOW GRADE OR BELOW FLOOR

CONDUIT/RACEWAY IN WALL OR ABOVE CEILING

LOW VOLTAGE AND/OR CONTROL WIRING

CONDUIT/RACEWAY STUB OUT: MARK AND CAP (SITE)

TELEPHONE

TIMECLOCK

BREAK OR RUN CONTINUES

CONDUIT/RACEWAY SLEEVE

EMERGENCY CIRCUIT

CONTACTOR OR RELAY

OCCUPANCY SENSOR - CEILING MOUNTED. PROVIDE

WITH POWER PACK PER MFG REQUIREMENTS.

SWITCH WITH LIGHTED HANDLE

TELEVISION

0-10V DIMMING OCCUPANCY SENSOR - WALL MOUNTED

48" AFF - EQUAL TO SENSOR SWITCH WSX-D

OCCUPANCY SENSOR - CORNER MOUNTED. PROVIDE

WITH POWER PACK PER MFG REQUIREMENTS.

DUPLEX "CLOCK" RECEPTACLE: 125V, NEMA 5-20R, +60" AFF

QUAD RECEPTACLE: CEILING MOUNTED

LENSED TROFFER

DEVICE MOUNTED AT NON-STANDARD HEIGHT. IF NO HEIGHT

SHOWN VERIFY HEIGHT WITH ARCHITECT

(RR) REMOVE AND REPLACE

HA-[1,3,5,3N]G

HA-(1.3.5)G

XF

F

N

CB

PC

TC

S S3

S4

SK

D

SP

SM

ST

OS

GFI

M

ST

S

TV

VC

C

A

M

M

G

GFI

SL

SPD

OS

D

C

S

P

OH

T

TV

X"

T

J

F1

48" AFF

+18" AFF

COMBO DUAL USB CHARGER / DUPLEX RECEPTACLE, 5.1A, (1)

TYPE A & (1) TYPE C USB (3.1, 3.0, 2.0 AND 1.1 COMPATIBLE),

20A, 125V, NEMA 5-20R, +18AFF

QUAD USB CHARGER, 5.1A, (2) TYPE A & (2) TYPE C USB (3.1,

3.0, 2.0 AND 1.1 COMPATIBLE), +18AFF

CONFIGURATION

2 BLANKS

BRANCH CIRCUIT (WHEN TIC MARKS ARE NOT

SHOWN) = (1) PHASE, (1) NEUTRAL AND (1)

GROUNDING CONDUCTOR

L R

E M M1

K H

= LIGHTING

= RECEPTACLES

= EQUIPMENT = MOTOR

= LARGEST MOTOR

= KITCHEN EQUIP

= ELECTRIC HEAT

PANELBOARD: SURFACE MOUNTED

PANELBOARD: FLUSH MOUNTED

SWITCHBOARD OR DISTRIBUTION PANEL

TRANSFORMER

PULLBOX / VAULT

MOTOR STARTER

COMBINATION MOTOR STARTER

COMBINATION MOTOR STARTER PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

DISCONNECT SWITCH - FUSIBLE (FUSED PER EQUIP.

NAMEPLATE)

DISCONNECT SWITCH - NON-FUSIBLE

DISCONNECT SWITCH PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

VARIABLE FREQUENCY DRIVE

VARIABLE FREQUENCY DRIVE PROVIDED BY OTHERS

(COORDINATE WITHSTAND RATINGS WITH EQUIP SUPPLIER)

ENCLOSED CIRCUIT BREAKER

GROUND ROD

SHUNT TRIP STATION OR EMERGENCY PUSHBUTTON

REMOTE METER

NOTE: THIS IS A MASTER SYMBOL LIST. IT MAY BE THAT NOT ALL SYMBOLS SHOWN ARE USED WITHIN THIS SET OF PLANS. HEIGHTS GIVEN ARE TO TOP OF BOX.

BREAKERS: 20 = SINGLE POLE CIRCUIT BREAKER 20/2 = TWO POLE CIRCUIT BREAKER 20/3 = THREE POLE CIRCUIT BREAKER 20A = ARC FAULT CIRCUIT BREAKER 20C = CONTROLLABLE CIRCUIT BREAKER 20G = GFI CIRCUIT BREAKER

DRAWING SCHEDULE

SHEET DESCRIPTION

E-001 ELECTRICAL SYMBOLS, LEGEND & GENERAL NOTES

E-101 POWER PLAN - LEVEL 01

E-201 POWER PLANS - LEVEL 02

E-301 POWER PLANS - ROOF LEVEL

E-501 ONE-LINE DIAGRAM

E-601 ELECTRICAL SCHEDULES

TOTAL SHEETS IN ISSUE:

C O

N

ST

R U

C

TI

O N

D R

AW

IN

G S

/1

3/

NOTE: "(E)" IN HOMERUN INDICATES NEW HOMERUN

TO EXISTING PANEL

SCOPE OF WORK

REMOVE EXISTING CRAC UNITS AND CONDENSING UNITS SERVING SERVER EQUIPMENT RM 214, AND PROVIDE ELECTRICAL CONNECTIONS TO SERVER RACK IN-ROW COOLING CRAC UNITS AND ASSOCIATED ROOF TOP MOUNTED CONDENSING UNITS. PROVIDE ELECTRICAL CONNECTION TO NEW HUMIDIFIER UNIT IN SERVER EQUIPMENT RM 214.

GENERAL NOTES

1. INSTALLATION SHALL COMPLY WITH CURRENTLY ADOPTED 2023 NEC AND LOCAL CODES. ALL WORK

PRACTICES SHALL COMPLY WITH NFPA 70E. ENERGIZED WORK IS PROHIBITED UNLESS PERFORMED UNDER AN APPROVED ENERGIZED WORK PERMIT WITH AN IEE 1584 COMPLIANT ARC FLASH ASSESSMENT

2. DATA PRESENTED ON THESE DRAWINGS REPRESENTS DESIGN INTENT BASED ON AVAILABLE INFORMATION, BUT FIELD VERIFICATION OF ALL DIMENSIONS, LOCATIONS, LEVELS, ETC. TO SUIT FIELD CONDITIONS IS REQUIRED. REVIEW ALL CIVIL DETAILS AND ADJUST WORK TO MEET THE REQUIREMENTS OF CONDITIONS SHOWN. DISCREPANCIES BETWEEN DIFFERENT PLANS OR BETWEEN DRAWINGS AND SPECIFICATIONS, OR REGULATIONS AND CODES GOVERNING THE INSTALLATION SHALL BE BROUGHT TO THE ATTENTION OF THE

ENGINEER IN WRITING.

3. ALL WORK SHALL BE COMPLETED IN A NEAT AND WORKMANLIKE MANNER AND IN ACCORDANCE WITH NECA STANDARDS, INCLUDING NECA 1 STANDARDS FOR GOOD WORKMANSHIP IN ELECTRICAL CONSTRUCTION.

4. ALL WORK SHALL BE SUBJECT TO INSPECTION AND POSSIBLE REJECTION IF NOT IN ACCORDANCE WITH THE

DRAWINGS AND SPECIFICATIONS AND INSTALLED IN A NEAT AND WORKMANLIKE MANNER.

5. ANY WORK REJECTED DUE TO CONTRACT, COD, SPECIFICATION, DRAWINGS, OR COORDINATION

DEFICIENCIES BE REPLACED AT NO ADDITIONAL COST TO THE OWNER.

6. PROVIDE REPRODUCIBLE RECORD DRAWINGS OF ALL COMPLETED WORK. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS

7. THE CONTRACTOR SHALL REMOVE FROM THE JOB SITE ALL DISCARD AND ABANDONED MATERIALS FROM DEMOLITION AND INSTALLATION. THIS INCLUDES BUT IS NOT LIMITED TO CONDUIT, FASTENERS, BOXES, & ETC. MATERIALS EMBEDDED IN GRADE AND / OR CONCRETE MAY BE ABANDONED IN PLACE. ALL ABANDONED

CONDUIT SHALL BE CAPPED. ALL DEMOLISHED CONDUCTORS SHALL BE REMOVED.

8. DO NOT SPLICE FEEDER CONDUCTORS UNLESS WRITTEN PRIOR APPROVAL HAS BEEN OBTAINED FROM THE

ENGINEER. APPROVING SPECIFIC CONTRACTOR PROPOSED LOCATION AND SPLICING METHOD.

9. THE MAXIMUM NUMBER OF CONDUIT BENDS SHALL NOT BE GREATER THAN 270 DEGREES BETWEEN PULLING

STRUCTURES. THIS INCLUDES THE AGGREGATE OF ALL HORIZONTAL AND VERTICAL CHANGES.

10. ALL CONDUIT, PULLBOXES AND VAULTS SHALL BE LABELED PER THE SPECIFICATIONS.

11. EACH SPARE CONDUIT SHALL BE PROVIDED WITH A 1250 LBS. PULL ROPE. AND TO/FROM IDENTIFICATION

TAGS

D

ES

IG

N

D

EV

EL

O

PM

EN

T

/2 3/

N/A N/A

0%

C O

N

ST

R U

C

TI

O N

D R

AW

IN

G S

/2

5/

11/25/2024

FIRE COMMAND

CENTER

LOBBY

VESTIBULE

FIELD

SUPERVISORS

OFFICE

OFFICE

WOMEN

MEN

JANITOR

LUNCH

LOADING

113OFFICE

TOOLS

ROOM

BOILER

ROOM

PARTS

ELEV

EQUIP

ROOM

DOCK

STAIR

"C"

SPRINKLER

VALVE

FRT

ELEV

PARTS

LUBE

ROOM

XF XF

MARIPOSA LRF DATA CENTER IN-ROW COOLING

HDR ENGINEERING

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY:

APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

ELECTRICAL

JM

WP

2024-11-25

2024-11-25 MG

MG 2024-11-25

2024-11-25 1 50% DESIGN DEVELOPMENT 2024-01-23JM

2 75% CONSTRUCTION DRAWINGS 2024-03-13JM

3 100% CONSTRUCTION DRAWINGS 2024-11-25JM

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

E-101

POWER PLAN - LEVEL 01

SCALE:

POWER PLAN - LEVEL 011

E-101 3/32" = 1'-0"

GENERAL NOTES - NEW WORK

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW

EQUIPMENT UNLESS NOTED OTHERWISE.

2. TERMINAL UNITS SHOWN FOR REFERENCE ONLY. CONTROL WIRING TO EACH UNIT (NOT SHOWN) BY

TEMPERATURE CONTROLS CONTRACTOR. REFER TO TEMPERATURE CONTROL DRAWINGS FOR MORE

INFORMATION.

3. THE CONTRACTOR SHALL OBTAIN ALL WIRING DIAGRAMS ASSOCIATED WITH MECHANICAL EQUIPMENT CONTROLS FROM MECHANICAL/CONTROLS CONTRACTOR. CONTROL WIRING SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR. ANY CONDUIT REQUIRED FOR CONTROL WIRING SHALL BE

PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR AND SHALL BE COMPLETED UNDER THE

SUPERVISION OF MECHANICAL/CONTROLS CONTRACTOR.

4. LOCATE ALL DISCONNECTS, STARTERS AND DRIVES WHERE ACCESSIBLE. PROVIDE ACCESS AND CLEARANCE AS REQUIRED PER NEC. PROVIDE ACCESS HATCH IF LOCATED ABOVE HARD LID CEILING.

5. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR MECHANICAL UNIT MODEL NUMBERS AND

SPECIFIC ELECTRICAL REQUIREMENTS, OPTIONS AND ACCESSORIES.

6. INFORMATION ON MECHANICAL DRAWINGS SUPERSEDE INFORMATION SHOWN ON ELECTRICAL

DRAWINGS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS PRIOR TO

ROUGH-IN.

7. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL REQUIREMENTS FOR FINAL

MECHANICAL EQUIPMENT INSTALLED. SHOULD THERE BE ANY DISCREPANCY BETWEEN ACTUAL

EQUIPMENT INSTALLED AND ELECTRICAL OR MECHANICAL DRAWINGS, CONTRACTOR SHALL NOTIFY

ENGINEER IMMEDIATELY FOR CLARIFICATION AND FURTHER DIRECTION.

N/A 3/32" = 1'-0"

(E) 30 KVA

AREA OF WORK

(E) HPA(E) 45KVA (E) EMB (E) EMA

(E) GDP

AREA OF WORK

(E) 150

GENER

(E) MDS(E) 40KVA UPS

(E) LPA(E) LPA-1

0 16' 32' 64'

SCALE: 3/32"=1'-0" (IN FEET)

KEY PLAN

FOR REFERENCE ONLY

OFFICE

CONFERENCE

ROOM

BREAK

AREA

MEN

WOMEN

OFFICE

SERVER EQUIPMENT

ROOM

CONTROL CENTER

PLATFORM

BREAK ROOM

BRAKE PARTS

REPAIR

UPPER PARTS

WORK OUT

ROOM

JAN.

FIRE CONTROL

ROOM

CORR.

CORR.

ELEC.

CLOSET

XF

FFF F

OFFICE

CONFERENCE

ROOM

BREAK

AREA

MEN

WOMEN

OFFICE

SERVER EQUIPMENT

ROOM

CONTROL CENTER

PLATFORM

BREAK ROOM

BRAKE PARTS

REPAIR

UPPER PARTS

WORK OUT

ROOM

JAN.

FIRE CONTROL

ROOM

CORR.

CORR.

ELEC.

CLOSET

XF

MARIPOSA LRF DATA CENTER IN-ROW COOLING

HDR ENGINEERING

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY:

APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

ELECTRICAL

JM

WP

2024-11-25

2024-11-25 MG

MG 2024-11-25

2024-11-25 1 50% DESIGN DEVELOPMENT 2024-01-23JM

2 75% CONSTRUCTION DRAWINGS 2024-03-13JM

3 100% CONSTRUCTION DRAWINGS 2024-11-25JM

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

E-201

POWER PLANS - LEVEL 02

SCALE:

POWER PLAN - LEVEL 022

E-201 3/32" = 1'-0"

NEW CONSTRUCTION

SCALE:

POWER PLAN - LEVEL 021

E-201 3/32" = 1'-0"

DEMOLITION

GENERAL NOTES - DEMOLITION

1. THIS DRAWING REPRESENTS THE EXISTING POWER SYSTEMS WITHIN THE EXISTING BUILDING (AREA TO

BE REMODELED). THE CONTRACTOR IS RESPONSIBLE FOR REMOVING, RELOCATING AND REWIRING ALL EQUIPMENT AS INDICATED ON THE DRAWINGS, INCLUDING EQUIPMENT THAT LIES WITHIN WALLS AND

CEILINGS TO BE DEMOLISHED OR REMODELED.

2. (X) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE REMOVED, (R) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE RELOCATED, (E) AND/OR HALFTONE LINES INDICATE EXISTING

EQUIPMENT TO REMAIN UNLESS NOTED OTHERWISE.

3. SALVAGEABLE ITEMS REMOVED DURING DEMOLITION SHALL BE OFFERED TO OWNER PRIOR TO

DISPOSAL OR REMOVAL FROM SITE.

4. EXISTING CIRCUITS AS INDICATED ARE BASED ON LIMITED FIELD OBSERVATION AND INFORMATION PER RECORD DRAWINGS AND SHALL BE FIELD VERIFIED BY ELECTRICAL CONTRACTOR PRIOR TO START OF

DEMOLITION WORK.

5. THE CONTRACTOR SHALL SALVAGE AND REUSE EXISTING BOXES AND CONDUIT WHERE POSSIBLE.

DAMAGED CONDUIT, FITTINGS BOXES, ETC. MAY NOT BE RE-USED. NEW CIRCUITING AS INDICATED ON THE DRAWINGS IS SHOWN FOR INTENT ONLY AND MAY VARY BASED ON ACTUAL FIELD CONDITIONS

(NEW CIRCUITING SHALL MATCH EXISTING WHERE POSSIBLE TO UTILIZE EXISTING HOME-RUN

CONDUITS, ETC.). KEEP AS-BUILT DRAWINGS CURRENT WITH ANY DEVIATION IN CIRCUITING FROM WHAT

IS INDICATED WITHIN THESE PLANS.

6. THE CONTRACTOR SHALL REMOVE FROM THE JOB SITE ALL DISCARDED AND ABANDONED MATERIALS LEFT OVER FROM DEMOLITION AND INSTALLATION. THIS INCLUDES, BUT IS NOT LIMITED TO, CONDUIT, FASTENERS AND BOXES. MATERIALS EMBEDDED IN GRADE AND / OR CONCRETE MAY BE ABANDONED IN

PLACE. ALL ABANDONED CONDUIT SHALL BE CAPPED.

SHEET NOTES

GENERAL NOTES - NEW WORK

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW

EQUIPMENT UNLESS NOTED OTHERWISE.

2. THE CONTRACTOR SHALL OBTAIN ALL WIRING DIAGRAMS ASSOCIATED WITH MECHANICAL EQUIPMENT CONTROLS FROM MECHANICAL/CONTROLS CONTRACTOR. CONTROL WIRING SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR. ANY CONDUIT REQUIRED FOR CONTROL WIRING SHALL BE

PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR AND SHALL BE COMPLETED UNDER THE

SUPERVISION OF MECHANICAL/CONTROLS CONTRACTOR.

3. LOCATE ALL DISCONNECTS, STARTERS AND DRIVES WHERE ACCESSIBLE. PROVIDE ACCESS AND CLEARANCE AS REQUIRED PER NEC. PROVIDE ACCESS HATCH IF LOCATED ABOVE HARD LID CEILING.

4. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR MECHANICAL UNIT MODEL NUMBERS AND

SPECIFIC ELECTRICAL REQUIREMENTS, OPTIONS AND ACCESSORIES.

5. INFORMATION ON MECHANICAL DRAWINGS SUPERSEDE INFORMATION SHOWN ON ELECTRICAL

DRAWINGS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS PRIOR TO

ROUGH-IN.

6. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL REQUIREMENTS FOR FINAL

MECHANICAL EQUIPMENT INSTALLED. SHOULD THERE BE ANY DISCREPANCY BETWEEN ACTUAL

EQUIPMENT INSTALLED AND ELECTRICAL OR MECHANICAL DRAWINGS, CONTRACTOR SHALL NOTIFY

ENGINEER IMMEDIATELY FOR CLARIFICATION AND FURTHER DIRECTION.

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED. DE-ENERGIZE AND REMOVE CONDUCTORS BACK

TO SOURCE AND CONDUIT BACK TO NEAREST JUNCTION BOX TO REMAIN. REFER TO NEW

CONSTRUCTION PLAN FOR LOCATIONS OF NEW CRAC UNITS. REFER TO ROOF POWER PLANS FOR

EXISTING CONDUIT ROUTING. COORDINATE PHASING OF EQUIPMENT DEMOLITION WITH GENERAL

CONTRACTOR, MECHANICAL CONTRACTOR, AND OWNER PRIOR TO THE START OF WORK.

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED. DE-ENERGIZE AND REMOVE CONDUCTORS AND

CONDUIT BACK TO SOURCE. REFER TO NEW CONSTRUCTION PLAN FOR LOCATIONS OF NEW CRAC

UNITS. REFER TO ROOF POWER PLANS FOR EXISTING CONDUIT ROUTING. COORDINATE PHASING OF

EQUIPMENT DEMOLITION WITH GENERAL CONTRACTOR, MECHANICAL CONTRACTOR, AND OWNER

PRIOR TO THE START OF WORK.

PROVIDE 5-20R RECEPTACLE FOR CONNECTION TO CORD AND PLUG CONDENSATE PUMP. EXTEND

NEAREST EXISTING CONVENIENCE RECEPTACLE BRANCH CIRCUIT TO SERVE NEW PUMP. COORDINATE

MOUNTING LOCATION OF RECEPTACLE WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.

PROVIDE NEW FEEDER TO SERVE NEW HVAC EQUIPMENT. COORDINATE LOCATION OF ROOF

PENETRATION AND PHASING OF EQUIPMENT INSTALLATION WITH GENERAL CONTRACTOR, MECHANICAL CONTRACTOR, AND OWNER PRIOR TO THE START OF WORK. REFER TO HVAC EQUIPMENT CONNECTION

SCHEDULE FOR ADDITIONAL INFORMATION.

N/A 3/32" = 1'-0"

(E) CRLA

(E)

(E)

(E) CRLB

(E) CRLA-1

(E)

(X) CRAC-1

1 2

(E)

(E)

(X) CRAC-2

(E) 75KVA (E) CRHA

(E) CRLA

(E)

(E)

(E) CRLB

(E) CRLA-1

(E)

(E)

(E)

(E) 75KVA (E) CRHA

5 5

SG

CRAC

CRAC

UP TO ROOF

GDP-

(1.3.5)G

GDP-

(7.9.11)G

UP

TO

ROOF

HPA-

(20.22.24)G

(E) LPA-[41,N]G

CRAC

GDP-

(19,21, 23)G

0 16' 32' 64'

SCALE: 3/32"=1'-0" (IN FEET)

KEY PLAN

J J

F

F

F

J

J

J

F

F

J J

MARIPOSA LRF DATA CENTER IN-ROW COOLING

HDR ENGINEERING

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY:

APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

ELECTRICAL

JM

WP

2024-11-25

2024-11-25 MG

MG 2024-11-25

2024-11-25 1 50% DESIGN DEVELOPMENT 2024-01-23JM

2 75% CONSTRUCTION DRAWINGS 2024-03-13JM

3 100% CONSTRUCTION DRAWINGS 2024-11-25JM

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

E-301

POWER PLANS - ROOF LEVEL

SCALE:

POWER PLAN - ROOF LEVEL2

E-301 3/32" = 1'-0"

NEW CONSTRUCTION

SCALE:

POWER PLAN - ROOF LEVEL1

E-301 3/32" = 1'-0"

DEMOLITION

GENERAL NOTES - DEMOLITION

1. THIS DRAWING REPRESENTS THE EXISTING POWER SYSTEMS WITHIN THE EXISTING BUILDING (AREA TO

BE REMODELED). THE CONTRACTOR IS RESPONSIBLE FOR REMOVING, RELOCATING AND REWIRING ALL EQUIPMENT AS INDICATED ON THE DRAWINGS, INCLUDING EQUIPMENT THAT LIES WITHIN WALLS AND

CEILINGS TO BE DEMOLISHED OR REMODELED.

2. (X) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE REMOVED, (R) AND/OR DASHED LINES INDICATE EXISTING EQUIPMENT TO BE RELOCATED, (E) AND/OR HALFTONE LINES INDICATE EXISTING

EQUIPMENT TO REMAIN UNLESS NOTED OTHERWISE.

3. SALVAGEABLE ITEMS REMOVED DURING DEMOLITION SHALL BE OFFERED TO OWNER PRIOR TO

DISPOSAL OR REMOVAL FROM SITE.

4. EXISTING CIRCUITS AS INDICATED ARE BASED ON CASUAL FIELD OBSERVATION AND INFORMATION PER RECORD DRAWINGS AND SHALL BE FIELD VERIFIED BY ELECTRICAL CONTRACTOR PRIOR TO START OF

DEMOLITION WORK.

5. THE CONTRACTOR SHALL SALVAGE AND REUSE EXISTING BOXES AND CONDUIT WHERE POSSIBLE.

DAMAGED CONDUIT, FITTINGS BOXES, ETC. MAY NOT BE RE-USED. NEW CIRCUITING AS INDICATED ON THE DRAWINGS IS SHOWN FOR INTENT ONLY AND MAY VARY BASED ON ACTUAL FIELD CONDITIONS

(NEW CIRCUITING SHALL MATCH EXISTING WHERE POSSIBLE TO UTILIZE EXISTING HOME-RUN

CONDUITS, ETC.). KEEP AS-BUILT DRAWINGS CURRENT WITH ANY DEVIATION IN CIRCUITING FROM WHAT

IS INDICATED WITHIN THESE PLANS.

6. THE CONTRACTOR SHALL REMOVE FROM THE JOB SITE ALL DISCARDED AND ABANDONED MATERIALS LEFT OVER FROM DEMOLITION AND INSTALLATION. THIS INCLUDES, BUT IS NOT LIMITED TO, CONDUIT, FASTENERS AND BOXES. MATERIALS EMBEDDED IN GRADE AND / OR CONCRETE MAY BE ABANDONED IN

PLACE. ALL ABANDONED CONDUIT SHALL BE CAPPED.

SHEET NOTES

GENERAL NOTES - NEW WORK

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW

EQUIPMENT UNLESS NOTED OTHERWISE.

2. THE CONTRACTOR SHALL OBTAIN ALL WIRING DIAGRAMS ASSOCIATED WITH MECHANICAL EQUIPMENT CONTROLS FROM MECHANICAL/CONTROLS CONTRACTOR. CONTROL WIRING SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR. ANY CONDUIT REQUIRED FOR CONTROL WIRING SHALL BE

PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR AND SHALL BE COMPLETED UNDER THE

SUPERVISION OF MECHANICAL/CONTROLS CONTRACTOR.

3. LOCATE ALL DISCONNECTS, STARTERS AND DRIVES WHERE ACCESSIBLE. PROVIDE ACCESS AND CLEARANCE AS REQUIRED PER NEC. PROVIDE ACCESS HATCH IF LOCATED ABOVE HARD LID CEILING.

4. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR MECHANICAL UNIT MODEL NUMBERS AND

SPECIFIC ELECTRICAL REQUIREMENTS, OPTIONS AND ACCESSORIES.

5. INFORMATION ON MECHANICAL DRAWINGS SUPERSEDE INFORMATION SHOWN ON ELECTRICAL

DRAWINGS. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS PRIOR TO

ROUGH-IN.

6. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL REQUIREMENTS FOR FINAL

MECHANICAL EQUIPMENT INSTALLED. SHOULD THERE BE ANY DISCREPANCY BETWEEN ACTUAL

EQUIPMENT INSTALLED AND ELECTRICAL OR MECHANICAL DRAWINGS, CONTRACTOR SHALL NOTIFY

ENGINEER IMMEDIATELY FOR CLARIFICATION AND FURTHER DIRECTION.

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED. DE-ENERGIZE AND REMOVE CONDUCTORS AND DISCONNECT. REMOVE CONDUCTORS BACK TO SOURCE AND CONDUIT BACK TO NEAREST JUNCTION BOX TO REMAIN. COORDINATE PHASING OF EQUIPMENT DEMOLITION WITH GENERAL CONTRACTOR, MECHANICAL CONTRACTOR, AND OWNER PRIOR TO THE START OF WORK.

DEMOLISH EXISTING ROOF MOUNTED RECEPTACLE. DEMOLISH BRANCH CIRCUIT AND CONDUIT BACK TO

NEAREST JUNCTION BOX TO REMAIN.

EXISTING PULLBOX SERVES (X) CRAC-1, -2 AND CU-1,-2. EXISTING RACEWAY MAY BE REUSED TO SERVE A SINGLE SET OF HVAC EQUIPMENT ( IE CONDENSING UNIT AND ASSOCIATED CRAC UNIT). SEPARATE

RACEWAY(S) WILL BE INSTALLED TO SERVE REMAINING SETS.

SINGLE RACEWAY MAY BE USED TO SERVE A SINGLE SET OF EQUIPMENT (IE CONDENSING UNIT AND ASSOCIATED CRAC UNIT). IF A SINGLE RACEWAY IS INSTALLED, CONTRACTOR SHALL BE RESPONSIBLE

ACCOUNTING FOR CONDUCTOR QUANTITY AND TEMPERATURE DE-RATING OF THE ELECTRICAL

CONDUCTORS WHEN DETERMINING FINAL CONDUCTOR SIZE TO SERVE EACH PIECE OF HVAC

EQUIPMENT. CONTRACTOR SHALL COORDINATE FINAL CONDUCTOR SIZE WITH DESIGN TEAM PRIOR TO

INSTALLATION.

PROVIDE NEW EQUIPMENT MOUNTED RECEPTACLE. EXTEND EXISTING BRANCH CIRCUIT AND CONDUIT

TO NEW RECEPTACLE.

EXTEND EXISTING RACEWAY TO SERVE NEW HVAC EQUIPMENT.

PROVIDE NEW DEDICATED 20A, 120V BRANCH CIRCUIT (2#12,#12G) 3/4" CONDUIT FOR CONNECTION TO

LOW AMBIENT TEMERATURE DAMPER. COORDINATE FINAL CONNECTION WITH MECHANICAL

CONTRACTOR PRIOR TO START OF WORK.

N/A 3/32" = 1'-0"

(X) LPA-41

(E) CONDUIT DOWN

TO LEVEL 02 SERVING

(X) CRAC-2

(X) CU-2 1

TO PANEL GDP

ON LEVEL 01

(X) LPA-41

(E) RTU-1

(X) CU-1 1

(E) CONDUIT DOWN

TO LEVEL 02 SERVING

(X) CRAC-1

TO PANEL GDP

ON LEVEL 01

GDP-(2.4.6)G

(E) RTU-1

(N)

TO LEVEL

02 BELOW

TO LEVEL

02 BELOW

(N)

(N) ACCU

(N) ACCU

ACCU

GDP-(14,16,18)G

GDP-(14,16,18)G

0 16' 32' 64'

SCALE: 3/32"=1'-0" (IN FEET)

CRLA-1[30,N]G

CRLA-1[26,N]G

CRLA-1[28,N]G

KEY PLAN

E-501

ONE-LINE DIAGRAM

SCALE:

ONE-LINE DIAGRAM1

E-501 N/A

MARIPOSA LRF DATA CENTER IN-ROW COOLING

HDR ENGINEERING

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY:

APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

ELECTRICAL

JM

WP

2024-11-25

2024-11-25 MG

MG 2024-11-25

2024-11-25 1 50% DESIGN DEVELOPMENT 2024-01-23JM

2 75% CONSTRUCTION DRAWINGS 2024-03-13JM

3 100% CONSTRUCTION DRAWINGS 2024-11-25JM

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

GENERAL NOTES - ONELINE - DEMOLITION

1. (X) AND/OR HATCHING INDICATE EXISTING EQUIPMENT TO BE REMOVED, (R) AND/OR DASHED LINES

INDICATE EXISTING EQUIPMENT TO BE RELOCATED, (E) AND/OR SOLID LINES INDICATE EXISTING

EQUIPMENT TO REMAIN UNLESS NOTED OTHERWISE.

GENERAL NOTES - ONELINE - NEW CONSTRUCTION

1. (E) AND/OR HALFTONE LINES INDICATE EXISTING EQUIPMENT, (R) AND/OR DASHED LINES INDICATE

RELOCATED EQUIPMENT, (N) AND/OR SOLID LINES INDICATE NEW EQUIPMENT UNLESS NOTED

OTHERWISE.

2. PANELBOARD AND BREAKER INTERRUPTING CAPACITIES (AIC) SHALL BE FULLY RATED AS AN ASSEMBLY.

SERIES RATING OF BREAKER DEVICES AND EQUIPMENT IS NOT PERMITTED.

3. ALL CONDUCTOR SIZES ARE BASED ON COPPER. ALUMINUM IS NOT PERMITTED.

4. DO NOT SPLICE FEEDER CONDUCTORS UNLESS PRIOR APPROVAL HAS BEEN OBTAINED FROM THE

ENGINEER.

5. CONTRACTOR SHALL PREPARE THE SHORT CIRCUIT AND COORDINATION STUDY PRIOR TO ORDERING DISTRIBUTION EQUIPMENT TO VERIFY ALL EQUIPMENT RATINGS, BREAKER TYPES, AND SETTINGS REQUIRED. THE SCOPE OF THE STUDY MUST INCLUDE ALL UPSTREAM BRANCHES OF THE DISTRIBUTION SYSTEM BACK TO THE SERVICE ENTRANCE, EVEN IF NOT BEING MODIFIED BY THIS PROJECT. ANY CHANGES TO EQUIPMENT RATINGS OR BREAKER TYPES IN ORDER TO PROVIDE A CODE REQUIRED

SELECTIVELY COORDINATED SYSTEM SHALL NOT RESULT IN ADDITIONAL COST TO THE OWNER.

6. CONTRACTOR SHALL PROVIDE ARC FLASH STUDY IN ACCORDANCE WITH NFPA 90E AND INSTALL LABELS FOR ALL EQUIPMENT PER NEC 110.6. THE SCOPE OF THE STUDY MUST INCLUDE ALL UPSTREAM BRANCHES OF THE DISTRIBUTION SYSTEM BACK TO THE SERVICE ENTRANCE, EVEN IF NOT BEING MODIFIED BY THIS PROJECT. PERFORM STUDY WITH AID OF COMPUTER SOFTWARE PROGRAM AND BY A

NEVADA LICENSED ELECTRICAL ENGINEER. OBTAIN ACTUAL FAULT DUTY AT NV ENERGY

TRANSFORMERS.

7. CONTRACTOR SHALL PROVIDE ARC FLASH STUDY IN ACCORDANCE WITH NFPA 90E AND INSTALL LABELS FOR ALL EQUIPMENT PER NEC 110.6. PERFORM STUDY WITH AID OF COMPUTER SOFTWARE PROGRAM AND BY A NEVADA LICENSED ELECTRICAL ENGINEER. OBTAIN ACTUAL FAULT DUTY AT NV ENERGY

TRANSFORMERS.

8. PROVIDE ENGRAVED NAMEPLATES SCREW ATTACHED ON ALL PANELS. MINIMUM SIZE 1 1/2"x3".

SHEET NOTES

EXISTING HVAC EQUIPMENT SHALL BE DEMOLISHED AND REPLACED. REMOVED EXISTING CONDUCTORS BACK TO SOURCE. EXISTING CIRCUIT BREAKER SHALL BE REUSED TO SERVE NEW EQUIPMENT. REFER TO POWER PLANS REGARDING DEMOLITION AND/OR REUSE OF EXISTING RACEWAYS. COORDINATE PHASING OF EQUIPMENT DEMOLITION WITH GENERAL CONTRACTOR, MECHANICAL CONTRACTOR, AND

OWNER PRIOR TO THE START OF WORK. DURING DEMOLITION, ONE CRAC UNIT AND ASSOCATED

CONDENSING UNIT WILL NEED TO REMAIN OPERATION AT ALL TIMES.

PROVIDE NEW FEEDER AND DISCONNECT TO SERVE NEW EQUIPMENT. REFER TO HVAC ELECTRICAL

CONNECTION SCHEDULE FOR ADDITIONAL INFORMATION.

PROVIDE NEW 20A, 480V 3PH, DEDICATED FEEDER AND 20A3P CIRCUIT BREAKER TO SERVE NEW

ELECTRIC STEAM HUMIDIER

REMOVE EXISTING 175A3P SPARE CIRCUIT BREAKER AND REPLACE WITH NEW 40A3P CIRCUIT BREAKER TO SERVE NEW CRAC UNIT. MATCH EXISTING TYPE AND AIC RATING. COORDINATE ANY REQUIRED

OUTAGES WITH GC AND OWNER IN ADVANCE OF BREAKER REPLACEMENT

PROVIDE NEW 20A3P CIRCUIT BREAKER IN EXISTING SPACE TO SERVE NEW CONDENSING UNIT. MATCH EXISTING TYPE AND AIC RATING. COORDINATE ANY REQUIRED OUTAGES WITH GC AND OWNER IN

ADVANCE OF BREAKER REPLACEMENT

AFTER HVAC EQUIPMENT IS ENERGIZED, THE CONTRACTOR SHALL TEST THE EXISTING GENERATOR AT LOAD. REFER TO SPECIFICATION SECTION 26 60 00 ELECTRICAL SYSTEM TESTING FOR ADDITIONAL

TESTING REQUIREMENTS

N/A N/A

(E) PAD MOUNTED UTILITY

TRANSFORMER

P

M

(E)100A/3P

100A LPS

(E)2000A/ 3P

2000A

KRPC 3P

200A

LPS

200A/ 3P

200A

LPS

(E) 200A/

200A

LPS

300A

LPS

100A

LPS

200A

LPS

200A

LPS

200A

LPS

200A

LPS

60A

LPS

60A

LPS

(E)HPA

T

(E)LPA(E)45

KVA

(E) (4#1 , 1#6 GND)- 2" C(E) (3#4 , 1#6 GND)- 1 1/4" C

(E) (4#1 , 1#6 GND)- 2" C

(E)200A/3P

200A LPS

(E)100A/3P

60A LPS

G

(E) DOUBLE LUGS

(E) GENERATOR

ANNUNCIATIOR

(E) 150KW/188KVA

GENSET

480/277V, 3PH, 4W

(E) (4#4/0 , 1#1 GND)- 2 1/2" C

(E)100A/3P

ATS

(E)200A/3P

ATS

(E) (4#1 , 1#6 GND)- 2" C

(E) (4#4/0 , 1#1 GND)- 2 1/2" C

(E) (4#1 , 1#6 GND)- 2" C

(E)200A/3P

(E)125/3 (E)125/3 (E)40/3 (E)40/3 (E)20/3 (E)20/3 (E)125/3

(X)

CU-1

(X)

CU-2

(X)

CRAC-1

(X)

CRAC-2

(E) MAIN DISTRIBUTION SWITCHBOARD "MDS"

480/277V, 3PH, 4W

2,000A BUS

100,000 AIC

(E) (#4/0 CU) 1"C. TO

COMM GND BUS

(E) GENERATOR DISTRIBUTION PANEL "GDP"

480/277V, 3PH, 4W

225A BUS

N G

3P

(E) 200A/

3P

(E) 400A/

3P

(E) 100A/

3P

(E) 200A/

3P

(E) 200A/

3P

(E) 200A/

3P

(E) 200A/

3P

(E) 100A/

3P

(E) 100A/

60A

LPS

3P

(E) 100A/

(E) CLRB

T

(E) (4#1/0, #6G)-2"C.

(E) (#3/4, #8G)-1 1/4"C.

(E) 45KVA TRANSFORMER(E) PANEL

"HBP"

(E) PANEL

"PPA"

(E) PANEL

"PPB"

(E) PANEL

"PPC"

(E) PANEL

"MCS"

(E) PANEL

"MCP"

(E) 200AS

"WHEEL

TRUING"

(E) 25 HP

COMPRESSOR

(E) 25 HP

COMPRESSOR(E) (4#3/0 , 1#6 GND)- 2" C

(E) 6[(4#500 CU MCM) 3 1/2"C]

(E) PANEL "EMA"

AREA OF WORKAREA OF WORK

(E) 75KVA

TRANSFORMER

(N) 40A3P

(E) (4#3/0, 1/6 GND)-2"C AREA OF WORK

(E) 40 KVA UPS

F30AS

30.0 A FRS-R

F30AS

30.0 A FRS-R

F30AS

15.0 A FRS-R

F30AS

15.0 A FRS-R

(E)LPA-1

(E) 60/3

(N) CRAC

(N) CRAC

(N) ACCU

(N) ACCU

(N) 20A3P 4 5

F F

(N) CRAC

(N) ACCU

(E)CRHA

T

(E) XFMR

75 KVA

480-208/120V

3PH, 4W

(E)CRLA

(E)100A 3P

(E)CRLA-2

MARIPOSA LRF DATA CENTER IN-ROW COOLING

HDR ENGINEERING

MARK REVISIONS BY DATE SHEET REFERENCE

NUMBER:

Denver 1670 Broadway, Suite 3400 Denver, CO 80202-4824

CHECKED BY:

APPROVED BY: DATE:

DATE:DESIGNED BY:

DRAWN BY: DATE:

DATE: FILE NAME:

HORZ SCALE:

VERT SCALE:

ENGINEERING DIVISION

REGIONAL TRANSPORTATION DISTRICT

1560 BROADWAY, SUITE 700

DENVER, CO 80202

(303) 628-9000

ELECTRICAL

JM

WP

2024-11-25

2024-11-25 MG

MG 2024-11-25

2024-11-25 1 50% DESIGN DEVELOPMENT 2024-01-23JM

2 75% CONSTRUCTION DRAWINGS 2024-03-13JM

3 100% CONSTRUCTION DRAWINGS 2024-11-25JM

681 Sierra Rose Drive, Suite B | Reno, NV 89511 | 775.826.9010 4601 DTC Boulevard, Suite 740 | Denver, CO 80237 | 720.481.3290 pkelectrical.com | PK#23151

E-601

ELECTRICAL SCHEDULES

LOAD JUSTIFICATIONS

PANEL GDP

EXISTING LOAD: 103,400 VA

(X)CRAC-1: -2,826 VA

(X)CRAC-2: -2,826 VA

(X)CU-1: -9,727 VA

(X)CU-2: -9,727 VA

TOTAL DEMOLISHED LOAD: -19,454 VA

(N)CRAC-1: 13,967 VA

(N)CRAC-2: 13,967 VA

(N)ACCU-1: 2,327 VA

(N)ACCU-2: 2,327 VA

CRLA-2 ADDED LOAD: 450VA

LARGEST MOTOR (NEC 430.24): 3,492 VA

TOTAL ADDED LOAD: 36,350 VA

NET LOAD CHANGE ADDED TO PANEL "GDP": 17,076 VA OR 20 AMPS @ 480V, 3PH

NEW TOTAL LOAD ON PANEL "GDP": 120,476 VA OR 144 AMPS @ 480V, 3PH

(E) 40KVA UPS

EXISTING LOAD: 15,099 VA

ADDED LOAD: 350 VA

NEW TOTAL LOAD ON 40KVA UPS: 15,549 VA OR 32.1 AMPS @480V, 3PH

SERVICE CALCULATION

UTILITY 12-MONTH PEAK DEMAND: 805 KW

TOTAL EXISTING LOAD: (805KW / 0.8PF) X 1000 = 1,006,250 VA

1,006,250 VA X 1.25(NEC 220.87) = 1,257,813 VA

NET LOAD CHANGE ADDED TO PANEL "GDP": 17,076 VA

(N) SG-1: 7,482 VA

NET LOAD CHANGE ADDED TO 2000A SERVICE: 24,558 VA or 29 AMPS @ 480V, 3PH

NEW TOTAL SERVICE LOAD: 1,282,371 VA OR 1541 AMPS @ 480V, 3PH

N/A N/A

Sheets
G0002 - COVER SHEET

File details come from the government source that posted it. Updated .