SCB_AWRF_Generator_Controls_&_Switchgear_Replacement_S&S_11x17_Drawings_09-10-25.pdf

PDF 10 MB Posted

Attached to
South Cross Bayou Replacement of Generator Controls and Switchgear (GEN2) (PID 004906A) - STEP 1
Solicitation number
26-0256-ITB-C
Issued by
Pinellas County, Clewiston City, Florida

About this file

This is a technical drawing set for the replacement of generator controls and switchgear at the South Cross Bayou Advanced Water Reclamation Facility (SCBAWRF) in Clearwater, Florida, prepared by Engineering Design Technologies Corp. under the direction of Pinellas County Utilities. The project encompasses the removal and replacement of four 3200-ampere draw-out generator circuit breakers and six 2000-ampere draw-out feeder circuit breakers across two 277/480-volt, 3-phase, 4-wire switchgear lineups, each rated at 6000-ampere main bus capacity, along with removal of six free-standing generator/engine control cabinets and installation of new control systems. The drawings include electrical legends, abbreviations, general notes, existing and proposed switchgear elevations, one-line diagrams for both switchgear lineups (Switchgear A and B), existing and proposed generator control cabinet elevations, comprehensive connection diagrams for the emergency bus and generator buses (Generators 4, 5, 6, and 7), 24 VDC power connection diagrams, network communications schematics, PLC interconnection diagrams for master and individual generator control cabinets, SCADA monitored points documentation, and emergency generator construction plans. The contract performance period shall not exceed 450 consecutive calendar days from the Notice to Proceed, with Step 1 qualification submittals due March 19, 2026, at 3:00 p.m., a non-mandatory pre-bid conference scheduled for March 11, 2026, at 9:00 a.m., and Step 2 sealed bids due March 31, 2026, at 3:00 p.m.

The pricing structure includes a permit allowance of $15,000 and a work line item of $418,000, with liquidated damages assessed at $1,352.17 per calendar day for non-completion beyond the 450-day performance period. A 4 percent Small Business Enterprise (SBE) participation goal has been established for installation of wire and conduit between switchboards and generator control enclosures. Contractors must provide a bid bond equal to 5 percent of the base bid and performance and payment bonds each at 100 percent of the contract value. Required insurance includes Workers' Compensation ($500,000 per employee), Commercial General Liability ($1,000,000 per occurrence/$2,000,000 aggregate), Excess or Umbrella Liability ($2,000,000), and Cyber Risk Liability ($1,000,000), with Pinellas County named as additional insured and all policies issued by AM Best A-VIII or better rated companies. Payment shall be made in accordance with Florida's Local Government Prompt Payment Act with net 45-day payment terms, and the County will retain 5 percent of monthly payments until final completion and acceptance. Contractors must demonstrate FDOT prequalification in electrical work or provide documentation of at least three previous similar projects with owner references, maintain E-Verify work authorization compliance, and submit completed affidavits of compliance with applicable Florida statutes.

View the file

Other files

File Type Posted
South_Cross_Bayou_Replacement_of_Generator_Controls_and_Switchgear_(GEN2)_(PID_004906A)_-_STEP_1_(Addendum_#1_Revision).pdf PDF
South_Cross_Bayou_Replacement_of_Generator_Controls_and_Switchgear_(GEN2)_(PID_004906A)_-_STEP_1.pdf PDF
Appendix_4_-_Special_Notice.pdf PDF
SCB_AWRF_Generator_Controls_&_Switchgear_Replacement_S&S_11x17_Drawings_09-10-25.pdf PDF
26-0256-ITB-C_Pricing_Proposal_(for_reference_only).pdf PDF
26-0256_-_Insurance_Requirements_-_South_Cross_Bayou_Replacement_of_Generator_and_Switchgear.docx DOCX document
26-0256_Sample_P&P_Bonds.pdf PDF
Sample_Change_Order.pdf PDF
E-Verify_Affidavit.pdf PDF
Affdavit_of_Release_and_Guarantee.pdf PDF
APPENDIX_7_-_SBE_COMPLIANCE_FORM.pdf PDF
Florida_Trench_Safety_Form.pdf PDF
26-0256-ITB-C_Sample_Construction_Agreement.pdf PDF
Switchgear_Map_location.pdf PDF
SCB_AWRF_Generator_Controls_&_Switchgear_Replacement_Revised_Specs_04-29-25_(2).pdf PDF
QUALIFICATION_SUBMITTAL_FORM_8-25.pdf PDF
Sample_Application_for_Payment.pdf PDF
OpenGov_Fillable-_Final.pdf PDF
Airport_Security_Program.pdf PDF
Notice_of_Intent_to_Sole_Source_07-25-2023.pdf PDF
Non-Competitive_Oversight_Committee_Justification_Form.docx DOCX document
SCB_AWRF_SBE_Memo_03-24-23.pdf PDF
Bid_Submittal_Form-JOC.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NO.:

DRAWN:

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

COVER

CLEARWATER, FLORIDA 33756

PINELLAS COUNTY UTILITIES

14 S. FT. HARRISON AVENUE

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

INDEX

ENGINEER OF RECORD:

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ELECTRICAL LEGEND

ELECTRICAL LEGEND

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ELECTRICAL ABBREVIATIONS

ABBREVIATIONS

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ELECTRICAL GENERAL NOTES

GENERAL NOTES:

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

EXISTING GENERATOR

BUILDING NO. 2

ELECTRICAL DEMOLITION

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

EXISTING SWITCHGEAR ELEVATION

EXISTING SWITCHGEAR ELEVATION

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

EXISTING SWITCHGEAR A

ELECTRICAL ONE-LINE DIAGRAM

EXISTING SWITCHGEAR A

ELECTRICAL ONE-LINE DIAGRAM

GENERATOR BUILDING NO. 2

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

EXISTING SWITCHGEAR B

ELECTRICAL ONE-LINE DIAGRAM

EXISTING SWITCHGEAR B

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR A

ELECTRICAL ONE-LINE DIAGRAM

PROPOSED SWITCHGEAR A

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR B

ELECTRICAL ONE-LINE DIAGRAM

PROPOSED SWITCHGEAR B

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

EXISTING GENERATOR CONTROL

ELEVATIONS

EXISTING GENERATOR CONTROL CABINETS -

CABINETS - ELEVATIONS

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED GENERATOR CONTROL

CABINETS - ELEVATIONS

PROPOSED GENERATOR CONTROL

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED GENERATOR CONTROL

CABINETS - ELEVATIONS

PROPOSED GENERATOR CONTROL

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR A

CONNECTION DIAGRAM

EMERGENCY BUS -

EMERGENCY BUS -

GENERATOR BUILDING NO. 2

CONNECTION DIAGRAM

SWITCHGEAR A

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR A

CONNECTION DIAGRAM

GENERATOR BUS -

GENERATOR NO. 4 BUS - CONNECTION

GENERATOR BUILDING NO. 2

DIAGRAM (SHEET 1 OF 2)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR A

GENERATOR NO. 4 BUS - CONNECTION

DIAGRAM (SHEET 2 OF 2)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR NO. 4

CONNECTIONS

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR A

CONNECTION DIAGRAM

GENERATOR BUS -

GENERATOR NO. 5 BUS - CONNECTION

GENERATOR BUILDING NO. 2

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR A

GENERATOR NO. 5 BUS - CONNECTION

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR NO. 5

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

24 VDC POWER

CONNECTION DIAGRAM

CONTROL CABINET CC1, C4 & C5

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR B

CONNECTION DIAGRAM

EMERGENCY BUS -

EMERGENCY BUS -

GENERATOR BUILDING NO. 2

CONNECTION DIAGRAM

SWITCHGEAR B

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR B

CONNECTION DIAGRAM

GENERATOR BUS -

GENERATOR NO. 6 BUS - CONNECTION

GENERATOR BUILDING NO. 2

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR B

GENERATOR NO. 6 BUS - CONNECTION

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR NO. 6

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR B

CONNECTION DIAGRAM

GENERATOR BUS -

GENERATOR NO. 7 BUS - CONNECTION

GENERATOR BUILDING NO. 2

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED SWITCHGEAR B

GENERATOR NO. 7 BUS - CONNECTION

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR NO. 7

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

24 VDC POWER

CONNECTION DIAGRAM

CONTROL CABINET CC2, C6 & C7

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED NETWORK

COMMUNICATIONS: GENERATOR 4

& GENERATOR 5

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

PROPOSED NETWORK

COMMUNICATIONS: GENERATOR 6

& GENERATOR 7

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

MASTER CONTROL CABINET CC1

PLC INTERCONNECTION DIAGRAM

(SHEET 1 OF 3)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

MASTER CONTROL CABINET CC1

PLC INTERCONNECTION DIAGRAM

(SHEET 2 OF 3)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

MASTER CONTROL CABINET CC1

(SHEET 3 OF 3)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR 4 CONTROL CABINET

PLC INTERCONNECTION DIAGRAM

(SHEET 1 OF 2)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

GENERATOR 4 CONTROL CABINET

(SHEET 2 OF 2)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR 5 CONTROL CABINET

PLC INTERCONNECTION DIAGRAM

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

GENERATOR 5 CONTROL CABINET

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

MASTER CONTROL CABINET CC2

PLC INTERCONNECTION DIAGRAM

(SHEET 1 OF 3)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

MASTER CONTROL CABINET CC2

(SHEET 2 OF 3)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

MASTER CONTROL CABINET CC2

(SHEET 3 OF 3)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR 6 CONTROL CABINET

PLC INTERCONNECTION DIAGRAM

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

GENERATOR 6 CONTROL CABINET

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

GENERATOR 7 CONTROL CABINET

PLC INTERCONNECTION DIAGRAM

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

ENGINEER OF RECORD:

GENERATOR 7 CONTROL CABINET

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

CONTROL CABINET CC1

SCADA MONITORED POINTS

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33686-2603 P.O. Box 172603

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT

CONTROL CABINET CC2

SCADA MONITORED POINTS

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

EMERGENCY GENERATOR PLAN

FOR CONSTRUCTION

FOR DEMOLITION/CONSTRUCTION

EMERGENCY GENERATOR PLAN

GENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT (SHEET 1 OF 3)

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

EMERGENCY GENERATOR PLAN

FOR CONSTRUCTIONGENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT (SHEET 2 OF 3)

FOR DEMOLITION/CONSTRUCTION

EMERGENCY GENERATOR PLAN

DESIGNED:

DATE:

QC:

SCALE:

Technologies Corp.

engineering@edt1.com 813.289.8080 Tampa, FL 33684-2403 P.O. Box 152403

Engineering Design

PROJECT TASK

NO. DATE BY DESCRIPTION

REVISIONS

FLORIDA REGISTRATION NO. 20761

BOB E. HALLMAN, P.E.

ENGINEER OF RECORD:

EMERGENCY GENERATOR PLAN

FOR CONSTRUCTIONGENERATOR CONTROLS &

SOUTH CROSS BAYOU AWRF

SWITCHGEAR REPLACEMENT (SHEET 3 OF 3)

2025-09-10T13:50:24-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T13:50:37-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T13:50:51-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T13:51:08-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:11:53-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:12:08-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:12:23-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:12:37-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:12:53-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:13:08-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:13:25-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:13:44-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:14:03-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:14:21-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:14:42-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:15:04-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:18:00-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:18:20-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:18:42-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:19:03-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:19:25-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:19:49-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:20:12-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:20:39-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:21:05-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:21:31-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:22:00-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:22:29-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:23:01-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:30:14-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:30:45-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:31:25-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:32:02-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:32:36-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:33:11-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:36:45-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:39:31-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:40:10-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:40:53-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:41:36-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:41:50-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:42:03-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:42:17-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:42:30-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:42:42-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:42:56-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:43:09-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:43:23-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:43:36-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:55:50-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a
2025-09-10T14:56:04-0400
01640bbd-0add-48bb-a9b8-a5b6c2d2e14a

File details come from the government source that posted it. Updated .