Sample ATS 13 VA Commissioning.pdf
PDF 974 KB Posted
- Attached to
- N041--626-24-201 - Replace Chiller #2 Tennessee Valley Healthcare System, Nashville Campus
- Solicitation number
- 36C24923B0023
About this file
This document outlines acceptance checks and tests for an automatic transfer switch. It details visual inspections and electrical tests to verify the physical condition, electrical condition, mechanical condition, lubrication, anchorage, clearances, alignment, connections, grounding, ratings of sensors, cleaning, exercising of active components, manual transfer warning signs, sensing devices, alarms, indicating devices, insulation resistance, simulation of power failures from normal and emergency sources, low phase-to-ground voltage, pickup voltage, dropout voltage, bypass isolation functions, and prevention of nuisance trips or alarms. Follow-up is scheduled. Demonstration of operational function is documented in a report from a third-party testing company.
The related federal contract opportunity is a solicitation to replace Chiller #2 at the Tennessee Valley Healthcare System Nashville Campus. The solicitation number is 36C24923B0023 for project 626-24-201 under the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24923B0023 0003.pdf | ||
| PCRA Memorandum 7-11.doc | DOC document | |
| 626-23-201 Replace Chiller 2 Layout_Rev1.pdf | ||
| Switch Gear Location.pdf | ||
| Painting Standards.pdf | ||
| 36C24923B0023 0002.docx | DOCX document | |
| Pre-Bid Site Walk Sign In_Replace Chiller2_28SEP23.pdf | ||
| 36C24923B0023 0001.docx | DOCX document | |
| Calculation of Self Performance Work.pdf | ||
| VA Provided Chiller Cutsheets.pdf | ||
| UEI _ TAX ID.docx | DOCX document | |
| 626-24-201 Chiller 2 Specs.pdf | ||
| RFI Form.docx | DOCX document | |
| DBA wage determination TN20230178 modification 4 last revised 06302023.pdf | ||
| General Conditions Breakout.xlsx | XLSX spreadsheet | |
| One Line Diagram 8-3-23.pdf | ||
| VA Chiller Details.pdf | ||
| 626-23-201 Replace Chiller 2 Layout.pdf | ||
| 36C24923B0023_1.docx | DOCX document | |
| Current 650 Ton Chiller 160-73-o2 Operating and Maintenance Manual.pdf | ||
| Contractor EMR Certification Form.docx | DOCX document | |
| Sample Chiller Installation Checklist.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date:
Manufacturer's Representative:
Contractor's Representative:
Contracting Officer's Representative:
Nameplate:
Catalog Number:
Serial Number:
Accessories:
Physical Condition OK? YES NO
Electrical Condition OK? YES NO
Mechanical Condition OK? YES NO
Lubricant OK? YES NO
Appropriate Anchorage? YES NO
Clearance acceptable per NEC 110.26? YES NO
Correct Alignment? YES NO
All Bolted Electrical Connections Torqued? YES NO
If not torqued Thermographic Survey
Verified Grounding Connections YES NO
Verified Ratings of Sensors YES NO
Vacuum/Clean all debris from Equipment YES NO
Exercise all active components YES NO
26 36 23 - Automatic Transfer Switches Part 3.2 - Acceptance Checks and Tests
Visual Inspections & Tests
Attach Photo of Thermograph
THVS Upgrade Paralleling System Project 626-18-203
Verify manual transfer warning signs in place YES NO
Verify operation of sening devices YES NO
Verify operation of alarms YES NO
Verify operation of indicating devices YES NO
Perform Insulation Resistance Tests
Test Bypass-isolation YES NO
Simulate Power Failure of Normal Source YES NO
Simulate Power Failure of EM Source YES NO
Simulate Low Phase-to-Ground Voltage YES NO
Verify Settings & Document: YES NO
a. Override Time Delay
b. Transfer Time Delay
c. Return Time Delay
d. Engine Shutdown Time Delay
e. Exerciser
f. Aux Contacts
g. Supplemental Features
Verify & Document Pickup Voltage
Verify & Document Dropout Voltage
NOVerify bypass isolation functions by removing ATS in Bypass YES
Verify ATS will not cause nuisance trips or alarms of Grounds YES NO
Notes:
Follow-up Scheduled:
Electrical Tests:
Demonstration of Operational Function:
See report from 3rd Party NETA testing company