This document contains an amendment to a solicitation for replacing Chiller #2 at the Nashville Campus of the Tennessee Valley Healthcare System. The amendment provides answers to questions from potential offerors. It clarifies that four new 1600 amp feeders are required from the existing switchboard to the automatic transfer switch to support the new chiller. It also specifies that a 1600 amp feeder and disconnect are needed between the automatic transfer switch and the new chiller, rather than reduced 800 amp components as originally illustrated. Commissioning of the automatic transfer switch will be covered under a separate electrical project. The breaker size in the main switchboard is to be determined by the separate contractor performing that work. Coordination is still required for installation. The related federal contract opportunity specifies this is solicitation number 36C24923B0023 from the Department of Veterans Affairs for replacing Chiller #2 at the Nashville Campus of Veterans Integrated Service Network 9. The bid opening is scheduled for October 24, 2023 at 1:00 PM Central Time, which will occur via Microsoft Teams.

View the file

Other files

File Type Posted
PCRA Memorandum 7-11.doc DOC document
626-23-201 Replace Chiller 2 Layout_Rev1.pdf PDF
Switch Gear Location.pdf PDF
Painting Standards.pdf PDF
36C24923B0023 0002.docx DOCX document
Pre-Bid Site Walk Sign In_Replace Chiller2_28SEP23.pdf PDF
36C24923B0023 0001.docx DOCX document
Calculation of Self Performance Work.pdf PDF
VA Provided Chiller Cutsheets.pdf PDF
UEI _ TAX ID.docx DOCX document
626-24-201 Chiller 2 Specs.pdf PDF
Sample ATS 13 VA Commissioning.pdf PDF
RFI Form.docx DOCX document
DBA wage determination TN20230178 modification 4 last revised 06302023.pdf PDF
General Conditions Breakout.xlsx XLSX spreadsheet
One Line Diagram 8-3-23.pdf PDF
VA Chiller Details.pdf PDF
626-23-201 Replace Chiller 2 Layout.pdf PDF
36C24923B0023_1.docx DOCX document
Current 650 Ton Chiller 160-73-o2 Operating and Maintenance Manual.pdf PDF
Contractor EMR Certification Form.docx DOCX document
Sample Chiller Installation Checklist.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 3

626-24-1-4369-0001

626-24-201

90C

Department of Veterans Affairs Network Contracting Office 9 (90C)

NCO 9

1639 Medical Center Parkway, Suite 400 Murfreesboro TN 37129

90C

Network Contracting Office 9 Department of Veterans Affairs Network Contracting Office (90C) 1639 Medical Center Parkway Suite 400 Murfreesboro TN 37129

To all Offerors/Bidders

36C24923B0023

09-14-2023

X x x

626-3640162-4369-854200-3220 23NR3JA31

The purpose of this solicitation amendment is to post additional RFI questions and answers.

See the continuation pages for the additional RFI questions and answers.

The official bid opening will be 10/24/2023, at 1:00PM CT and will occur via Microsoft Teams call in.

Please call 205-235-3524 Conf. No. 637960755#, five minutes before the bid opening to be present for the bid opening.

Vance Rosebush Contracting Officer

CONTINUATION PAGES

The SOW states to “furnish and install (4) new feeders from the existing switchboard MSBA for normal power to ATS -19 in room E-26. Provide and install 480 volt breaker and disconnects to support new chiller to switchboard MSBA”:

1. What size are these (4) feeders? On the one line that was provided the Normal side feeder from ATS 19 to panel MSBA has a note tag of 760. The feed from the new 1600 amp disconnect to the chiller also has a note tag of 760. I assume this is an 800 amp feeder since the disconnect is fused at 800 amps. Please advise size and quantities.

Answer: 760 indicates amperage to existing chiller that will be demo’d as a part of this project. Size all feeders for 1680A new Chiller #2.

2. Are we to provide the new 1600 amp feeder shown on the one line drawing between the ATS 19 and the new 1600 amp disconnect?

Answer: Yes.

3. Are we to provide the reduced 800 amp size feeder from the new 1600 amp disconnect to the new chiller #2 shown on the one line drawing?

Answer: No, provide 1600 amp feeder from disconnect to new Chiller #2.

4. Are we to provide the 1600 amp disconnect fused at 800 amps for the new chiller #2?

Answer: No, provide 1600 amp disconnects.

5. In the government provided SOW C.4, the last sentence states “Contractor to include VA required commissioning of ATS 19”. We cannot provide commissioning of another contractors provided ATS. The providing contractor should include this as a part of their scope for warranty purposes. Please advise.

Answer: Commissioning for ATS will be included in a separate Electrical Project.

Project: 626-24-201, Replace Chiller 2 at the Nashville Campus

Solicitation: 36C24923B0023

Amendment: 0003 - RFI Answers

6. What size frame and breaker are to be provided in MSBA since the feeder is a reduced size to 800 amps but has a 1600 amp ATS and disconnect?

Answer: Breaker provided by separate contractor, coordination for installation still required.

File details come from the government source that posted it. Updated .