RVA1033004_Telecom Set.pdf

PDF 2 MB Posted

Attached to
Y1DA--Renovate Old Dialysis 2H Richmond VA Medical Center
Solicitation number
36C24623B0024
Issued by

About this file

This package includes telecommunications drawings and specifications for a renovation project at the Richmond VA Medical Center. Key details include installation of new Category 6A data outlets, voice outlets, wireless access points, cable tray, grounding infrastructure and other telecommunications equipment. Patch panels, racks, cable managers and other infrastructure will be installed in equipment rooms. Fiber optic and coaxial cabling will also be run. Drawings show demolition, new and existing equipment locations as well as telecommunications and security system details. Specifications provide outlet types and labeling requirements.

View the file

Other files

File Type Posted
BID OPENING Abstract 36C24623B0024.pdf PDF
BID OPENING Attendance Log 36C24623B0024.pdf PDF
SITE VISIT Attendance Log 36C24623B0024.pdf PDF
36C24623B0024 0006.docx DOCX document
36C24623B0024 0005.docx DOCX document
36C24623B0024 0004.docx DOCX document
36C24623B0024 0003.docx DOCX document
36C24623B0024 0002.docx DOCX document
36C24623B0024 0001.docx DOCX document
Attachment A - Itemized Schedule of Values Cost Breakdown.xlsx XLSX spreadsheet
INSTRUCTIONS TO BIDDERS.pdf PDF
36C24623B0024_1.docx DOCX document
RVA1033004_Plumbing-revised.pdf PDF
RVA1033004_Life Safety Set.pdf PDF
RVA1033004_Architecture.pdf PDF
RVA1033004_Electrical.pdf PDF
Specifications Vol 1.pdf PDF
Specifications Vol 2.pdf PDF
RVA1033004_Mechanical.pdf PDF
RVA1033.004_PL_Addendum_1_2023-03-24.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NAMING CONVENTION

T-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DISCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

TV

COMMUNICATIONS

COAXIAL CABLE TELEVISION OUTLET WALL MOUNTED

60" ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

COMMUNICATIONS COMBINATION VOICE/DATA OUTLET

(TWO VOICE & TWO DATA JACKS) MOUNT 18" ABOVE

FINISHED FLOOR, UNLESS INDICATED OTHERWISE

COMMUNICATIONS VOICE OUTLET MOUNT 48" ABOVE

FINISHED FLOOR, UNLESS INDICATED OTHERWISE

COMMUNICATIONS DATA OUTLET, MOUNT 18" ABOVE

FINISHED FLOOR, UNLESS INDICATED OTHERWISE

FLOOR BOX SUITABLE FOR CONCRETE FLOOR POUR;

TWO COMPARTMENTS - POWER AND

TELECOMMUNICATIONS; FLUSH COVER/FLANGE WITH

HINGED ACCESS TO RECEPTACLES AND JACKS

RECESSED BELOW COVER IN FLOOR BOX. PROVIDE 8"

FIRE RATED POKE THRU ABOVE GROUND FLOOR.

COAXIAL CABLE TELEVISION OUTLET CEILING MOUNTED

WALL MOUNTED JUNCTION BOX FOR VOICE/DATA

CONNECTION TO MODULAR WORKSTATION FURNITURE.

CEILING MOUNTED PA SPEAKER, ONE WAY TYPE

WALL MOUNTED PA SPEAKER, ONE WAY TYPE; MOUNT

120" ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

CCTV CAMERA; # IS CAMERA SUBSCRIPT;

A - FIXED DOME

B - FISH EYE

C- 270° 3-WAY MULTISENSOR

D- 360° 3-WAY MULTISENSOR

CONTROL STATION

WALL SWITCH, AC TYPE, SINGLE POLE SINGLE THROW,

MOUNT 48" ABOVE FINISHED FLOOR

LOW VOLTAGE ON/OFF WALL SWITCH, MOUNT 48"

ABOVE FINISHED FLOOR. PROVIDE DIMMER CONTROL

WITH DIMMABLE FIXTURES INTEGRAL WITH SWITCH.

WIRING

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR ABOVE

FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW GRADE

OR CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

LADDER TYPE CABLE TRAY (SIZE AS INDICATED)

WELDED WIRE BASKET TYPE CABLE TRAY (SIZE AS

INDICATED)

ELECTRONIC SECURITY

ACCESS CONTROL JUNCTION BOX

BALANCED MAGNETIC DOOR CONTACT

ELECTRIC STRIKE

SEISMIC VIBRATION SENSOR

CARD READER

ELECTRIC LOCKSET

ELECTRIC HINGE

MOTION DETECTION SENSOR

INTRUSION DETECTION SYSTEM PANEL

ACCESS CONTROL SYSTEM PANEL

INFRARED REQUEST TO EXIT

KEY PAD

MAGLOCK

DOOR RELEASE

BIOMETRIC READER

HIGH SECURITY SWITCH

TELECOMMUNICATIONS LEGEND

DC

ES

S

CR

EL

EH

M

IDS

IR

KP

ML

DR

AC

BR

LV

J

HSS

ACS

TELECOMMUNICATIONS ABBREVIATIONS

A OR AMP

AFF

AWG

BLDG

C

CAT

CATV

CCTV

CFCI

CU

D

DDC

EC

EF

EIA

EMT

EQUIP

ER

ETR

EXIST or EX

FWE

G OR GND

GFGI

GFCI

GRS

H or HT

HVAC

IDF

IDS

IMC

J OR JB

K

KV

KVA

KW

L

LAN

MAX

MDF

MIN

MM

N

NEC

NEMA

NFPA

NIPR

NTS

PDS

PVC

RMC

RPP

RU

SA

SIPR

SM

SPEC

TGB

TIA

TMGB

TP

TR

TYP

UIO

UL

UTP

V

VA

W

WAP

AMPERE(S)

ABOVE FINISHED FLOOR

AMERICAN WIRE GAUGE

BUILDING

CONDUIT

CATEGORY

CABLE TELEVISION

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

COPPER

DEPTH

DIRECT DIGITAL CONTROL FOR HVAC

EMPTY CONDUIT

ENTRANCE FACILITY

ELECTRONICS INDUSTRIAL ALLIANCE

ELECTRICAL METALLIC TUBING

EQUIPMENT

EQUIPMENT ROOM

EXISTING TO REMAIN

EXISTING

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GOVERNMENT FURNISHED CONTRACTOR

INSTALLED

GALVANIZED RIGID STEEL CONDUIT

HEIGHT

HEATING, VENTILATION & AIR CONDITIONING

INTERMEDIATE DISTRIBUTION FRAME

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

KILO

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

LENGTH

LOCAL AREA NETWORK

MAXIMUM

MAIN DISTRIBUTION FRAME

MINIMUM

MULTIMODE

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NON-SECURE INTERNET PROTOCOL ROUTER

NOT TO SCALE

PROTECTIVE DISTRIBUTION SYSTEM

POLYVINYL CHLORIDE

RIGID METAL CONDUIT

REMOTE POWER PANEL

RACK UNIT

SURGE ARRESTOR

SECRET INTERNET PROTOCOL ROUTER

SINGLE MODE

SPECIFICATIONS

TELECOMMUNICATIONS GROUND BAR

TELECOMMUNICATIONS INDUSTRIAL ALLIANCE

TELECOMMUNICATIONS MAIN GROUND BAR

TWISTED PAIR

TELECOMMUNICATIONS ROOM

TYPICAL

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

WATTS or WIRE or WIDTH

WIRELESS ACCESS POINT

TELECOMMUNICATIONS GENERAL NOTES:

1. EQUIPMENT (PIPING, DUCTWORK, MACHINERY, ATC) THAT DOES NOT SERVE ENTRANCE FACILITY, EQUIPMENT ROOM OR TELECOMMUNICATIONS ROOM(S) SHALL NOT BE INSTALLED ABOVE OR IN IT SPACES, NOR SHALL THIS EQUIPMENT PASS THROUGH

OR ENTER THE ENTRANCE FACILITY, EQUIPMENT ROOM OR TELECOMMUNICATIONS ROOM(S).

2. ANY MOTOR, TRANSFORMER OR OTHER ELECTRICAL DEVICE GREATER THAN 5KVA SHALL HAVE A MINIMUM OF 47" SPACE SEPARATION FROM ANY WALL OF ENTRANCE FACILITY, EQUIPMENT ROOM OR TELECOMMUNICATIONS ROOM(S).

3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR TELECOMMUNICATIONS EQUIPMENT CLEARANCE FOR RECESSED

LUMINAIRES AND CORRECT ROUGH-IN LOCATIONS OF TELECOMMUNICATIONS CONNECTIONS.

4. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.

5. REFER TO DETAILS AND RISER DIAGRAMS FOR CABLE AND CONDUIT SIZES NOT SHOWN ON PLANS.

6. "PROVIDE" IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE TELECOMMUNICATIONS SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND

SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

7. PROVIDE WELDED WIRE TYPE CABLE TRAY IN ALL AREAS EXCEPT TELECOMMUNICATIONS ROOM(S). PROVIDE LADDER TYPE CABLE

TRAY IN TELECOMMUNICATIONS ROOM(S).

8. FLOOR BOXES AND POKE THRU'S SHALL BE SIZED TO NOT EXCEED TELECOMMUNICATIONS CABLE MINIMUM BEND RADIUS.

9. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF RATED WALLS. FIRESTOP FIRE RATED BARRIERS IN ACCORDANCE WITH FIRESTOPPING SPECIFICATIONS 07 84 00. SLEEVES AND SLOTS SHALL NOT BE LEFT OPEN AFTER CABLE INSTALLATION. ALL SLEEVES AND SLOTS SHALL BE FIRESTOPPED IN ACCORDANCE WITH FIRESTOPPING SPECIFICATION 07 84 00.

10. EMT: COMPLY WITH ANSI C80.3 AND 797. ALL EMT SHALL BE FACTORY PAINTED. PROVIDE THE FOLLOWING COLORS FOR EACH

SYSTEM:

• TELECOMMUNICATIONS - ORANGE

• SECURITY - PURPLE

11. PROVIDE A MINIMUM OF 12" SEPARATION BETWEEN ALL DATA OUTLETS AND ANY POWER LOAD GREATER THAN 5KVA.

12. PROVIDE 3.28’ OF CLEAR, UNOBSTRUCTED SPACE FOR THE INSTALLATION OF ALL CABLING AND EQUIPMENT MOUNTED ON WALLS, RACKS (FRONT AND REAR), CABINETS (FRONT AND REAR) AND ENCLOSURES. PROVIDE AT LEAST 6” DEPTH OFF THE WALL FOR WALL-MOUNTED EQUIPMENT. ALLOCATE SPACE OF 3.28’ WIDE, 3.28’ DEEP AND 7.5’ HIGH FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. PROVIDE SPACE FOR AN AISLE OF AT LEAST 3.28’ WIDE IN THE FRONT AND IN THE REAR OF THE SPACE FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. THIS SPACE SHALL TAKE INTO ACCOUNT THE DEPTH OF RACK-MOUNTED EQUIPMENT

AS WELL AS WALL-MOUNTED EQUIPMENT AND HARDWARE.

13. LOCATE LIGHT SWITCHES NEAR THE ENTRANCE(S) TO THE TELECOMMUNICATION ROOM. DIMMERS AND VACANCY SENSORS ARE NOT PERMITTED TO BE USED WITHIN THE TELECOMMUNICATION ROOM. PROVIDE A MINIMUM OF 50 FOOT-CANDLES OF LIGHT AT

THE POINT OF CABLE TERMINATION.

14. MINIMUM SIZE OF TELECOMMUNICATION ROOMS BASED ON THE AREA IT IS SERVING:

• 5,000 SQ FT. OR LESS, 10' x 8' MINIMUM.

• 5,000 SQ FT. TO 8,000 SQ FT., 10' x 9' MINIMUM.

• 8,000 SQ FT. TO 10,000 SQ FT., 10' x 11' MINIMUM.

15. DO NOT SERVICE MORE THAN 10,000 SQ FT. FROM ONE TELECOMMUNICATION ROOM.

16. PROVIDE TWO RACK UNITS OF HORIZONTAL CABLE MANAGEMENT FOR EVERY ONE RACK UNIT PATCH PANEL.

17. PROVIDE AT LEAST TWO WALLS IN EACH TELECOMMUNICATION ROOM WITH AC GRADE OR BETTER, FIRE-RESISTANT VOID FREE PLYWOOD PAINTED LIGHT GRAY IN COLOR. THE PLYWOOD SHOULD BE 8 FT. HIGH WITH A MINIMUM THICKNESS OF 3/4”. PLYWOOD SHOULD BE KILN-DRIED TO MAXIMUM MOISTURE CONTENT OF 15%. MOUNT PLYWOOD AT 8” AFF MINIMUM.

18. COORDINATE CABLE TRAY, LUMINAIRE AND MECHANICAL UNIT INSTALLATION WITHIN A TELECOMMUNICATION ROOM WITH ALL

TRADES PRIOR TO INSTALLATION.

19. SLEEVES OR CONDUITS ENTERING INTO THE TELECOMMUNICATION ROOM SHALL EXTEND INTO THE SPACE A MINIMUM OF 3” FROM

THE FLOOR, WALL OR CEILING.

20. PROVIDE A MINIMUM OF (2) 3” CONDUITS BETWEEN ALL TELECOMMUNICATION ROOMS LOCATED ON THE SAME FLOOR. PROVIDE (3) 1-1/4” INNERDUCT IN ONE OF THE CONDUITS. PROVIDE PULLSTRING IN ALL EMPTY CONDUIT AND INNERDUCT.

21. BOND ALL TELECOMMUNICATIONS MAIN GROUND BARS AND TELECOMMUNICATIONS GROUND BARS TO STRUCTURAL STEEL, ALL DATA RACKS, CABINETS OR ENCLOSURES, CABLE TRAY AND THE ELECTRICAL PANEL GROUND BUS WITHIN THE TELECOMMUNICATION ROOMS AS APPLICABLE. ALL BONDING CONDUCTORS WITHIN A TELECOMMUNICATION ROOM SHALL BE #4 AWG COPPER, UNLESS INDICATED OTHERWISE. ALL BONDS TO THE TELECOMMUNICATIONS MAIN GROUND BAR OR TELECOMMUNICATIONS GROUND BAR SHALL BE BY IRREVERSIBLE COMPRESSION-TYPE CONNECTIONS.

22. REFER TO ARCHITECTURAL DRAWINGS FOR HOURS OF DEMOLITION.

23. TELECOMMUNICATIONS FACEPLATES:

a) 4-PORT STAINLESS STEEL FACEPLATES SHALL BE CONTEMPORARY CONTOUR STYLE

b) PHYSICAL SPECIFICATIONS: 4.5-IN. H x 2.75-IN. W x 0.24-IN D

c) 4-PORT SURFACE MOUNT BOXES (SMB) SHALL FEATURE COMPACT LOW PROFILE OUTLINE.

d) PHYSICAL SPECIFICATIONS: 1.22" D x 2.27" H x 2.59" W

e) TWO (2) PORT FACEPLATE: STAINLESS STEEL

f) JACK ADAPTER FOR STAINLESS STEEL FP

g) TWO (2) PORT SURFACE MOUNT BOX: IVORY.

24. CATEGORY 6A PATCHING CORDS

a) ALL PATCH CORDS SHALL EXCEED TIA/EIA AND ISO/IEC CATEGORY 6A/CLASS E SPECIFICATIONS.

b) THE PATCH CORDS SHALL INCORPORATE AN ANTI-SNAG FEATURE THAT PROVIDES MAXIMUM PROTECTION FROM SNAGGING

DURING MOVES AND RE-ARRANGEMENTS.

c) PATCH CORDS SHALL SUPPORT NETWORK LINE SPEEDS IN EXCESS OF 1 GIGABIT PER SECOND. CATEGORY 6A/CLASS E PATCH

CORDS PLUG-PLUG, 4 PAIR, STRANDED B WIRING PATCH CORD.

d) ALL PATCH CORDS SHALL BE BACKWARD COMPATIBLE WITH CATEGORY 5 AND CATEGORY 5E SYSTEMS.

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

E.O.F.K.

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

TELECOMMUNICATIONS GENERAL

NOTES, ABBREVIATIONS & LEGEND

T-001

-2

T -0

/2

/1

.p d f

NOTE:

1. NOT ALL SYMBOLS OR ABBREVIATIONS SHOWN WILL BE USED

ON THIS PROJECT.

NOTES:

1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.

ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,

DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT

IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF

EACH:

EXISTING EQUIPMENT

NEW OR RELOCATED EQUIPMENT

HATCH INDICATES EQUIPMENT TO BE DEMOLISHED

2022.05.20 15:33:25-04'00'

W W

X X

Y Y

Z Z

AA AA

16 17 18 19 20

W

X

Y

Z

AA

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

E.O.F.K.

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

TELECOMMUNICATIONS DEMOLITION

PLAN

TD101

-2

T D

/0

/1

.p d f

SHEET NOTES:

1. REFER TO T-001 FOR TELECOMMUNICATIONS GENERAL

NOTES, ABBREVIATIONS & LEGEND.

T V

16 17 18 19 20 21

W

X

Y

Z

AA

TOUCHDOWN

2H-103

BREAK/MEETING

ROOM

2H-104

CORRIDOR

C2H-6

TOUCHDOWN

2H-121

TOUCHDOWN

2H-120

RESIDENTS

2H-122

CORRIDOR

C2H-5

STORAGE

2H-105

IT CLOSET

2H-107

ELEC. CLOSET

2H-106

ANESTHESIA

2-PERSON

OFFICE

2H-115

ANESTHESIA

ADMIN.

2H-112

ANESTHESIA

OFFICE

2H-119

ANESTHESIA

OFFICE

2H-118

TOUCHDOWN

2H-111

ANESTHESIA

OFFICE

2H-116

ANESTHESIA

OFFICE

2H-117

NEW 2-PERSON

ENGINEERING

OFFICE

2K-140A

STAFF TOILET

2H-109

WELLNESS ROOM

2H-108

NEW

ENGINEERING

OFFICE

2H-140B

STAFF LOCKER

2H-110

3/4" PLYWOOD

ANESTHESIA

OFFICE

2H-114

ANESTHESIA

OFFICE

2H-113

OR

OR OR

OR

OR

OR

OR

OR

OR

OR

OR

OR

EASY PASS

OR

OR

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

E.O.F.K.

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

TELECOMMUNICATIONS PLAN

TA101

-2

T A

/0

/1

.p d f

SHEET NOTES:

1. REFER TO T-001 FOR TELECOMMUNICATIONS GENERAL NOTES,

ABBREVIATIONS & LEGEND.

2. COORDINATE ALL WORK WITH OTHER TRADES.

3. CONTRACTOR SHALL DISTRIBUTE ALL CABLE VIA CABLE TRAY

AND SURFACE MOUNTED CONDUIT. CABLE TRAYS SHALL BE

FOR MAIN DISTRIBUTION WHILE CONDUIT WILL BE USED FOR

BRANCHING OFF INTO SPACES.

4. REFER TO T-501, T-502, AND T-503 FOR TELECOMMUNICATIONS

DETAILS.

5. DATA RECEPTACLES DENOTED "OR" ARE FOR OR CONTROL BOARD

DATA REQUIREMENTS. COORDINATE EXACT MOUNTING HEIGHT WITH

COR. CONTRACTOR SHALL PROVIDE AND INSTALL BLOCKING FOR

ORC BOARDS.

KEYNOTES:

1. DATA RECEPTACLE MOUNTING HEIGHT SHALL BE AT SCREEN

HEIGHT. COORDINATE WITH COR.

2. COORDINATE FINAL LOCATION OF RECEPTACLES WITH

SCRUB- X MACHINES.

CR

ES

HSS

IR

CR

ES

HSS

IR

CR

ES

HSS

IR

CR

ES HSS

IR

CR

ESHSS

IR

16 17 18 19 20

W

X

Y

Z

AA

TOUCHDOWN

2H-103

CORRIDOR

C2H-6

BREAK/MEETING

ROOM

2H-104

TOUCHDOWN

2H-120

TOUCHDOWN

2H-121

STORAGE

2H-105

ELEC. CLOSET

2H-106

IT CLOSET

2H-107

RESIDENTS

2H-122

ANESTHESIA

OFFICE

2H-116

ANESTHESIA

OFFICE

2H-117

ANESTHESIA

ADMIN.

2H-112

ANESTHESIA

OFFICE

2H-119

TOUCHDOWN

2H-111

CORRIDOR

C2H-5

STAFF LOCKER

2H-110

STAFF TOILET

2H-109

WELLNESS ROOM

2H-108

NEW 2-PERSON

ENGINEERING

OFFICE

2K-140A

VESTIBULE

2K-140C

NEW

ENGINEERING

OFFICE

2H-140B

D

D

D

D

D

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

AuthorChecker

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

ELECTRONIC SECURITY SYSTEM

PLAN

TY101

-2

T Y

/0

/1

.p d f

SHEET NOTES:

1. REFER TO T-001 FOR TELECOMMUNICATIONS GENERAL

NOTES, ABBREVIATIONS & LEGEND.

2. ALL WIRING/CABLING AND OTHER TELCO/DATA DEVICES

SHALL BE PROVIDED BY TELCO/DATE CONTRACTOR.

GENERAL CONTRACTOR SHALL VERIFY LOCATIONS OF

DEVICES AND PROVIDE NECESSARY ROUGH-INS.

3. COORDINATE HEIGHT AND LOCATION OF DATA RECEPTACLES

AND CABLE BOXES WITH ARCHITECTURAL DRAWINGS. FEILD

VERIFY PRIOR TO INSTALLATION.

4. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF PIV

CARD READERS WITH VA TELECOM DEPARTMENT PRIOR TO

ROUGH-IN AND INSTALLATION.

532-3B-48

CABLE LABEL

(TYP)

JACK LABEL

(TYP)

532-3B-47

TWO CAT 6A - 1"C TO

CLOSEST CABLE TRAY

532-3B-48 532-3B-47

A

A

B

RG 6 - 1"C TO TAP BOX

IN COMM ROOM VIA

CABLE TRAY

532-1

JACK LABEL

(ROOM#-

JACK#)

532-3B-46

532-3B-46

ONE CAT 6 - 1"C TO

CLOSEST CABLE TRAY

CABLE LABEL

(TYP)

WALL PHONE MOUNTING STUD

(TYPICAL FOR 2)

JACK LABEL

(TYP)

JACK COLOR & JACKET COLOR

NIPR VOIP & DATA = GREEN

SIPR = RED

JWICS = YELLOW

OUTLET JACK, PATCH PANEL JACK, AND CABLE LABELING

aaa - bc - dd aaa = ROOM NUMBER b = RACK NUMBER c = PATCH PANEL ID d = PORT NUMBER

IE: 532-3B-46 = ROOM 532, RACK 3, PATCH PANEL B, PORT 46

DUPLEX LC FIBER OPTIC CONNECTOR

COAXIAL TYPE F CONNECTOR

8 PIN / 8 POSITION, CATEGORY 6

UNKEYED, T568A PIN OUT ANGLED JACK

BLANK PLUG IN FACEPLATE PORT

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

E.O.F.K.

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

TELECOMMUNICATIONS DETAILS

T-501

-2

T -5

/2

/1

.p d f

SHEET NOTES:

SCALE: N.T.S.A1

TYPICAL OUTLET

SCALE: N.T.S.A2

TYPICAL TV OUTLET

SCALE: N.T.S.A3

TYPICAL TELEPHONE OUTLET

SCALE: N.T.S.C4

LABELING AND COLOR CODING

SCALE: N.T.S.C3

JACK TYPES

1. REFER TO T-001 FOR TELECOMMUNICATIONS GENERAL

NOTES, ABBREVIATIONS & LEGEND.

TYPICAL TMGB DRILLED HOLE DIMENSIONS

TYPICAL TGB DRILLED HOLE DIMENSIONS

COMPRESSION

CONNECTOR W/

VIEWING WINDOW

1 1/2" NOMINAL

INSULATOR

STAINLESS STEEL

STANDOFF BRACKET

ELECTRO-TIN PLATED

COPPER GROUND BAR

STAINLESS STEEL HARDWARE

TYPE

TMGB

TGB

20"

20"

WIDTH

4"

2"

THICKNESS

1/4"

1/4"

MINIMUM

LENGTH

MINIMUM NUMBER OF

PAIRS OF 5/16"

DIAMETER HOLES

MINIMUM NUMBER OF

PAIRS OF 7/16"

DIAMETER HOLES

TELECOMMUNICATIONS MAIN GROUND BAR (TMGB) &

TELECOMMUNICATIONS GROUND BAR (TGB) SCHEDULE ANSI-J-STD-607-A

5/16" DIAMETER HOLE PAIR (TYP)

7/16" DIAMETER HOLE PAIR (TYP)

2"

/8

1 1/8" TYP

1 1/8" TYP

5/16" DIAMETER HOLE PAIR (TYP)

7/16" DIAMETER HOLE PAIR (TYP)

/8

/8

MOUNT CONDUIT TO CABLE TRAY

OR 'J-HOOKS' WHERE PERMITTED.

MINIMUM 1" EMT CONDUIT

STUB-OUT TO CABLE TRAY.

ROUTE CABLE TO TR. ROOM.

SINGLE OR DOUBLE

GANG EXTENSION.

CONDUIT AND CABLE TRAY

CONNECTED BY BONDING

JUMPER

CABLE PATHWAY HOME

RUN TO TR. SEE FLOOR

PLANS FOR ROUTING.

(NOTE 4)

4" X 4" DEEP SET

JUNCTION BOX

1. MOUNT JUNCTION BOX SAME HEIGHT AS ELECTRICAL

OUTLET, UIO.

2. OUTLET CONFIGURATION SHALL BE AS INDICATED ON

PLANS.

3. OUTLETS TO BE LABELED IN ACCORDANCE WITH

TIA/EIA 606-A.

4. PROVIDE GROUNDING JUMPER AT EACH CABLE TRAY

MECHANICAL JOINT.

5. PROVIDE POWER OUTLET WITHIN 12" OF

COMMUNICATIONS OUTLET.

6. MAXIMUM DISTANCE FROM CONDUIT TO CABLE TRAY

SHALL BE 6".

NOTES:

SHEET NOTES:

SCALE: N.T.S.A1

TMGB & TGB GROUND BAR DETAIL

1. REFER TO T-001 FOR TELECOMMUNICATIONS GENERAL

NOTES, ABBREVIATIONS & LEGEND.

SCALE: N.T.S.A3

WALL MOUNT COMMUNICATIONS OUTLET DETAIL

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

E.O.F.K.

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

TELECOMMUNICATIONS DETAILS

T-502

-2

T -5

/2

/1

.p d f

TELECOMMUNICATIONS ROOM XXX

U

IO

U

IO

(TYP.)

(TYP.)

(TYP.)

TMGB

G

G

G

#6G

TYP.

TYP.

FOR 5

X

TYP. FOR 2

P A

IR

J

TV

J

WAP

PET

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

TYP.

FOR 6

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

TYP.

FOR 3

#6G

4 3 16

RACK 1

DATA

RACK 3

DATA

5 RU

UPS

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96 1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96 1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

RACK 2

NETWORK

EQUIPMENT

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96 1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

E.O.F.K.

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

TELECOMMUNICATIONS RISER

DIAGRAM

T-601

-2

T -6

/0

/1

.p d f

SCALE: N.T.S.A1

TELECOMMUNICATIONS RISER DIAGRAM

SHEET NOTES:

1. REFER TO T-001 FOR TELECOMMUNICATIONS GENERAL NOTES, ABBREVIATIONS

& LEGEND.

2. REFER TO E-600 FOR TELECOMMUNICATIONS BONDING BACKBONE SCHEDULE.

3. All Category 6A patch panels shall meet or exceed Category 6A transmission requirements for connecting hardware, as specified in ANSI/TIA 568-C.1, Balanced Twisted- Pair Telecommunications Cabling and Components Standard ISO Class E (ISO/IEC-11801, 2nd edition) and comply with the following Richmond VA Medical Center Specifications:

a. The 1U 1.75 X 19 HD Category 6A, 48 port – angled unloaded patch panels are designed with rear loading.

b. Shall have a Cat 6A technology design to alleviate crosstalk & EMI interference.

c. The 2U Category 6A, patch panel shall be of a universal design supporting TIA 568A &

568B wiring scheme.

d. Strain relief design to secure cable terminations.

e. The 1U Patch panel shall support current IEEE 802.3 Ethernet based transmission speeds, high-bandwidth and high-speed applications including 1000BASE-T and 1.2 Gbps ATM. Also be capable of dissipating heat from IEEE 802.3af (PoE) and 802.3at (PoE+) compliant equipment.

f. Meets or exceeds the mechanical, electrical, and clearance specifications in FCC Rules and Regulations, Part 68, Subpart F

Standard Patch Panel color is as follows:

• Category 6A Angled Panel, 48 Port unloaded Patch Panel 1RU:

White

KEYNOTES:

1. TELECOMMUNICATION NIPR OUTLET (TWO CATEGORY 6A, 8-PIN,

8-CONDUCTOR UNKEYED ANGLED JACKS).

2. TELECOMMUNICATION OUTLET (ONE CATEGORY 6A, 8-PIN, 8-

CONDUCTOR UNKEYED JACK).

3. TWO CATEGORY 6 UTP CABLES - 1" EMT CONDUIT.

4. ONE CATEGORY 6 UTP CABLE - 1" EMT CONDUIT.

5. 48 PORT CATEGORY 6A PATCH PANEL FOR HORIZONTAL VOICE

AND DATA DISTRIBUTION.

6. 1/4" x 5/8" x 72" COPPER VERTICAL RACK GROUND BAR, PREDRILLED WITH (26) 1/4" TAPPED HOLES.

7. 2 POST EQUIPMENT RACK, 19" EIA RAILS, 45U SPACE, 21" WIDE.

8. WELDED WIRE CABLE TRAY, SIZE AS NOTED ON PLANS.

9. PROVIDE AT LEAST TWO WALLS IN EACH TELECOMMUNICATION

ROOM WITH AC GRADE OR BETTER, FIRE-RESISTANT VOID

FREE PLYWOOD PAINTED LIGHT GRAY IN COLOR. THE

PLYWOOD SHOULD BE 8 FT. HIGH WITH A MINIMUM THICKNESS

OF 3/4". PLYWOOD SHOULD BE KILN-DRIED TO MAXIMUM

MOISTURE CONTENT OF 15%. MOUNT PLYWOOD AT 8"AFF

MINIMUM.

10. TELECOMMUNICATIONS GROUNDING BUSBAR.

11. DOUBLE SIDED VERTICAL CABLE MANAGERS WITH DOORS. 7"H

x 6"W x 20"D WITH GUIDE FINGERS AT 1 RU INTERVALS IN

FRONT AND BACK.

12. PROVIDE (2) NEMA L6-30R SIMPLEX ON CABLE TRAY ABOVE

EACH RACK.

13. 100 PAIR WALL MOUNTED 110 BLOCK.

14. HORIZONTAL CABLE MANAGERS 2RU.

15. MULTI-COMPARTMENT FLOOR BOX OR FIRE RATED POKE THRU.

SEE PLANS FOR JACK QUANTITIES AND FLOOR SERVICE TYPE.

16. RG-6A CABLE - 1" EMT CONDUIT.

17. BOND TO CLOSEST STRUCTURAL STEEL.

18. COAXIAL, TYPE F CATV OUTLET. HEIGHT AS NOTED.

19. 20' MAINTENANCE LOOP.

20. 48 PORT CATEGORY 6A PATCH PANEL FOR VOICE CABLE

PATCHING.

21. LADDER RACK CABLE TRAY SIZE AS NOTED ON PLANS.

22. WALL MOUNTED JUNCTION BOX WITH FLEXIBLE CONDUIT

CONNECTION TO SYSTEMS FURNITURE. SEE PLAN DRAWINGS

FOR CABLE QUANTITIES AND CONDUIT SIZE. EXTEND CAT 6A

CABLES THROUGH SYSTEMS FURNITURE WIRING CHANNELS

AND TERMINATE ON TWO CAT 6A JACKS AT EACH

WORKSTATION.

23. FOUR POST EQUIPMENT RACK 24"" x 36"". 19"" EIA RAILS, 45RU

SPACE.

24. FIBER OPTIC ENCLOSURE EQUIPPED WITH SIX 12 PORT

DUPLEX LC TERMINATION MODULES.

25. JUNCTION BOX FOR WIRELESS ACCESS POINTS.

26. PROVIDE DEDICATED NEMA L6-30R MOUNTED ON CABLE TRAY

FOR TELECOM EQUIPMENT.

27. PROVIDE DEDICATED NEMA L5-20 DOUBLE DUPLEX MOUNTED

ON CABLE TRAY FOR TELECOM EQUIPMENT.

File details come from the government source that posted it. Updated .