RVA1033004_Architecture.pdf
PDF 4 MB Posted
- Solicitation number
- 36C24623B0024
About this file
This set of construction documents outlines the scope of work for renovating an old dialysis area at the Richmond VA Medical Center. The project involves demolishing existing walls, floors, ceilings and casework to accommodate new layouts and finishes. Key work includes installing temporary barrier walls; removing non-load bearing walls; upgrading casework, millwork, flooring, wall finishes and ceilings; and modifying mechanical, plumbing and electrical systems. Bidders should carefully review all architectural, structural, mechanical, plumbing and electrical drawings along with specifications to fully understand the scope of the renovation work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BID OPENING Abstract 36C24623B0024.pdf | ||
| BID OPENING Attendance Log 36C24623B0024.pdf | ||
| SITE VISIT Attendance Log 36C24623B0024.pdf | ||
| 36C24623B0024 0006.docx | DOCX document | |
| 36C24623B0024 0005.docx | DOCX document | |
| 36C24623B0024 0004.docx | DOCX document | |
| 36C24623B0024 0003.docx | DOCX document | |
| 36C24623B0024 0002.docx | DOCX document | |
| 36C24623B0024 0001.docx | DOCX document | |
| Attachment A - Itemized Schedule of Values Cost Breakdown.xlsx | XLSX spreadsheet | |
| INSTRUCTIONS TO BIDDERS.pdf | ||
| 36C24623B0024_1.docx | DOCX document | |
| RVA1033004_Plumbing-revised.pdf | ||
| RVA1033004_Life Safety Set.pdf | ||
| RVA1033004_Electrical.pdf | ||
| RVA1033004_Telecom Set.pdf | ||
| Specifications Vol 1.pdf | ||
| Specifications Vol 2.pdf | ||
| RVA1033004_Mechanical.pdf | ||
| RVA1033.004_PL_Addendum_1_2023-03-24.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
COVER SHEET
GI100
-2
G I1
.p d f
Department of Veterans Affairs
RENOVATION OF OLD DIALYSIS AREA 2H
RICHMOND VA MEDICAL CENTER (RICVAMC)
1201 BROAD ROCK BLVD
RICHMOND, VA 23249
DRAWING LIST PROJECT DIRECTORY
Medical Center Director
Director of Facility Management Service
Medical Director
Project COR
Project CO
Infection Control
Safety Officer
CONTRACTING OFFICER REPRESENTATIVE (COR)
Jeffrey Anderson
Hunter Holmes McGuire VA Hospital 1201 Broad Rock Blvd Richmond, VA 23249 Phone: (804) 675-5000 x4294 jeffrey.anderson9@va.gov
ARCHITECT
Ken Jones
11720 Beltsville Drive, Suite 350 Calverton, MD 20705 Phone: (443) 388-7351 kjones@cbdg-ae.com
ARCHITECT/ENGINEER
Christianna Raber
Raymond Engineering 1601 Summit Ave Richmond, VA 23219 Phone: (804) 726-9540 x 700 christianna.raber@raymondllc.com
CONTRACTING OFFICER (CO)
Tonya Bradley
Department of Veterans Affairs | Contracting 101 Emancipation Dr.
Hampton, Virginia 23667 Phone: (757) 315-3969 tonya.bradley@va.gov
APPROVALS
CONSTRUCTION BID SET
RAYMOND ENGINEERING (SEE RIGHT)
ARCHITECTURAL
GI100 COVER SHEET
GI200 SYMBOLS, ABBREVIATIONS & NOTES
GI300 GENERAL NOTES
GI301 TYPICAL MOUNTING HEIGHTS AND DIMENSIONING CONVENTIONS
GC200 EXISTING CONDITIONS PLAN
GC400 ICRA PLAN
AD100 DEMOLITION PLAN
AE100 FLOOR PLAN
AE300 DOOR SCHEDULE
AE301 WALL TYPES
AE302 FINISH SCHEDULE AND MATERIAL LEGEND
AE303 SIGN TYPES
AE500 DETAILS
AE600 INTERIOR ELEVATIONS
AE700 REFLECTED CEILING PLAN
AE701 ENLARGED REFLECTED CEILING PLANS & DETAILS
AE900 EQUIPMENT PLANS / SCHEDULES
FIRE PROTECTION AND LIFE SAFETY
LS001 LIFE SAFETY BUILDING CODES ANALYSIS
LS101 LIFE SAFETY PLAN
FA001 FIRE ALARM ABBREVIATIONS, LEGEND, AND GENERAL NOTES
FD101 FIRE ALARM DEMOLITION PLAN
FA101 FIRE ALARM NEW PLAN
FA501 FIRE ALARM DETAILS
FX001 FIRE SUPPRESSION ABBREVIATIONS, LEGEND, AND GENERAL NOTES
FD111 FIRE SUPPRESSION DEMOLITION PLAN
FX101 FIRE SUPPRESSION NEW PLAN
FX501 FIRE SUPPRESSION DETAILS
MECHANICAL
M001 MECHANICAL GENERAL NOTES AND DESIGN CRITERIA
M002 MECHANICAL ABBREVIATIONS AND LEGENDS
M101 LEVEL 1 MECHANICAL FLOOR PLAN
M501 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M801 MECHANICAL CONTROLS
MD101 LEVEL 1 MECHANICAL DEMOLITION PLAN
MP101 MECHANICAL PIPING PLAN
PLUMBING
P001 PLUMBING GENERAL NOTES, ABBREVIATIONS, AND LEGENDS
P101A LEVEL 1 WASTE AND VENT NEW WORK
P101B LEVEL 1 WATER NEW WORK
P401 PLUMBING RISER DIAGRAMS
P601 PLUMBING SCHEDULES
PD101A LEVEL 1 SANITARY AND VENT DEMOLITION PLAN
PD101B LEVEL 1 WATER DEMOLITION PLAN
PD101C LEVEL 1 MEDICAL GAS DEMOLITION PLAN
ELECTRICAL
E001 ELECTRICAL GENERAL NOTES AND ABBREVIATIONS
E002 ELECTRICAL LEGEND
ED101 ELECTRICAL DEMOLITION PLAN
ED102 ELECTRICAL LIGHTING DEMOLITION PLAN
EL101 LIGHTING PLAN
EP101 POWER PLAN
EM101 MECHANICAL POWER PLAN
E501 ELECTRICAL DETAILS
E502 ELECTRICAL DETAILS
E600 ELECTRICAL FEEDER SCHEDULES
E601 ELECTRICAL ONE-LINE DIAGRAM
E611 LUMINAIRE AND MECHANICAL EQUIPMENT SCHEDULE
E621 PANELBOARD SCHEDULES
TELECOMMUNICATIONS
T001 TELECOMMUNICATIONS GENERAL NOTES, ABBREVIATIONS, & LEGEND
TD101 TELECOMMUNICATIONS DEMOLITION PLAN
TA101 TELECOMMUNICATIONS PLAN
T501 TELECOMMUNICATIONS DETAILS
T502 TELECOMMUNICATIONS DETAILS
T601 TELECOMMUNICATIONS RISER DIAGRAM
WOOD
ALUMINUM
STEEL
EARTH
CONCRETE MASONRY UNITS
RIGID INSULATION
CONCRETE
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE REMOVED
BRICK
WOOD-FINISHED
WOOD ROUGH
PLYWOOD
GYPSUM - PLASTER
ACOUSTIC TILE
CAST STONE
ALL METALS - SMALL SCALE
GLASS - LARGE SCALE
BATT INSULATION
CERAMIC TILE
CARPET
GRAVEL
CENTER LINE
DETAIL INDICATOR
DETAIL INDICATIOR
DETAIL INDICATOR FOR SMALL CONDITIONS
DIMENSION LINE
NEW DOOR OPENING / BORROWED LIGHT
INDENTIFIER
DRAWING BLOCK TITLE, TYPICAL
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR, INTERIOR, MULTIPLE VIEW
ELEVATION INDICATOR, INTERIOR, SINGLE VIEW
SECTION INDICATOR
TYPICAL DETAIL INDICATOR
FURNITURE, FIXTURE, & EQUIPMENT INDICATOR
COLUMN GRID
KEYNOTE
WALL OR PARTITION TYPE
FIRE EXTINGUISHER CABINET
NORTH ARROW
FEC
A
DETAIL NUMBER
SHEET WHERE
DRAWN
XXxxx
XXxxx
X
DRAWING TITLE
SCALE: 1 1/2" = 1'-0"
1 3/16"
D2
XX-XX
XXxxx
XXxxx
CL
XXxxx x'-x" VERTICAL HEIGHT INDICATOR
REVISION
REVISION CLOUD
NORTH
BREAK LINE
X
DEMOLITION KEYNOTE
NEW ROOM NAME AND NUMBERCORRIDOR
C2
XX
A
XXxxx
D
BC
COLUMN NUMBER
COLUMN LETTER
XXxxx
ELEVATION NUMBER
SHEET WHERE
DRAWN
ELEVATION NUMBER
SHEET WHERE
DRAWN
ELEVATION NUMBER
SHEET WHERE
DRAWN
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL NUMBER
SHEET WHERE DRAWN
WALL MOUNTED FIRE EXTINGUISHERFE
XX
SHEET WHERE
DRAWN
ELEVATION NUMBER
& AND
@ AT
C CENTERLINE
# NUMBER
AB ANCHOR BOLT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH
DISABILITIES ACT
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF
ARCHITECTS
ALUM ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AUTO AUTOMATIC
AVG AVERAGE
BD BOARD
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BRG BEARING
BEL BELOW
BR BUMPER RAIL
BRK BRICK
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CCT CUBICLE CURTAIN TRACK
CG CORNER GUARD
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CT CERAMIC TILE
CLG CEILING
CL CLOSET
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CU CUBIC
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DOZ DOZEN
DP DAMPPROOFING
DR DOOR
DWG DRAWING
DWGS DRAWINGS
DWR DRAWER
E EAST
EA EXHAUST AIR, EACH
EL ELEVATION
ELEV ELEVATION
ELEC ELECTRICAL
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXP EXPANSION
EJ EXPANSION JOINT
EXIST EXISTING
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK
FD FLOOR DRAIN
FDC FIRE DEPARTMENT
CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FF FINISH FACE
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FLUOR FLUORESCENT
FO __ FACE OF __
FOC FACE OF CONCRETE
FOS FACE OF STUD
FOW FACE OF WALL
FPRF FIREPROOF(ING)
FR FIRE RATING, FRAME
FRMG FRAMING
FS FULL SIZE
FT FOOT OR FEET
FTG FOOTING
FUR FURRING
FUT FUTURE
GC GENERAL CONTRACTOR
GA GAUGE
GAL GALLON
GALV GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GUARD
GL GLASS
GND GROUND
GR GRADE
GWB GYPSUM WALLBOARD
GYP BD GYPSUM WALLBOARD
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDWR HARDWARE
HDWD HARDWOOD
HT HEIGHT
HNDRL HANDRAIL
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HR HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HVAC HEATING, VENTILATION, AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE
DIAMETER / DIMENSION
IN INCH
INCL INDLUDE(D)
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JST JOIST
JT JOINT
KP KICK PLATE
KO KNOCKOUT
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LH LEFT HAND
LIN LINEAR
LIQ LIQUID
LKR LOCKER
LG LONG
LL LEAD LINED
LLV LONG LEG VERTICAL
LP LOW POINT
LRG LARGE
LT LIGHT
LT WT LIGHTWEIGHT
LVR LOUVER
MATL MATERIAL
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP MOP PLATE
MTD MOUNTED
N NORTH
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OFF OFFICE
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OH OVERHEAD
OZ OUNCE
PAV PAVING
PC PRECAST CONCRETE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PLBG PLUMBING
PMF PREMOLDED FILLER
PR PAIR
PT POINT
PTN PARTITION
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE, RUBBER
BASE
RD ROOF DRAIN
RL ROOF LEADER
REF REFERENCE
REFR REFRIGERATOR
REQ'D REQUIRED
REV REVISION
RFI REQUEST FOR
INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SH SPRINKLER HEAD
SHT SHEET
SIM SIMILAR
SM SMOKE
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
STA STATION
STD STANDARD
STO STORAGE
STL STEEL
SS STAINLESS STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TEL TELEPHONE
TEMP TEMPERED
T&G TONGUE AND GROOVE
THK THICK
TOC TOP OF CONCRETE
TOP TOP OF PAVEMENT
TOS TOP OF STEEL
TOW TOP OF WALL
TV TELEVISION
TYP TYPICAL
UNFIN UNFINISHED
UON UNLESS OTHERWISE
NOTED
VB BAPOR BARRIER
VERT VERTICAL
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VTR VET THRU ROOF
W WEST
W/ WITH
WD WOOD
W/O WITHOUT
WP WATERPROOF
WT WEIGHT
WWF WELDED WIRE FRAME
NOTE: ALL ABBREVIATIONS SHOWN
MAY NOT BE USED ON THIS PROJECT.
CERTAIN COMMON ABBREVIATIONS
MAY NOT BE SHOWN.
L
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
SYMBOLS, ABBREVIATIONS & NOTES
GI200
-2
G I2
.p d f
SYMBOLS OF MATERIALS DRAWING KEY ARCHITECTURAL ABBREVIATIONS
G1 ITEMS AND CONDITIONS NOTED, DETAILED, OR OTHERWISE IDENTIFIED ON DRAWINGS ARE APPLICABLE AND BINDING TO SIMILAR CONDITIONS ON ALL DRAWINGS. FOR CONDITIONS NOT NOTED OR NOT DETAILED, PROVIDE MATERIALS OF EQUAL QUALITY AND PERFORMANCE TO OTHER SIMILAR
CONDITIONS ON THE JOB.
G2 SECTIONS SHOWN ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE INDEXED AS WELL AS ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR SECTIONS THROUGHOUT THE PROJECT WHICH DO NOT HAVE SPECIFIC SECTIONS DRAWN. THE MOST SIMILAR SECTION SHALL BE ADAPTED TO ANY SECTION NOT DETAILED. ANY SPECIFIC QUESTIONS CONCERNING CONSTRUCTION NOT ADEQUATELY COVERED BY THE ABOVE
SHOULD BE DIRECTED TO THE ARCHITECT DURING THE BID PERIOD.
G3 ALL CONSTRUCTION IS TO BE ASSUMED NEW AND FURNISHED AND INSTALLED BY THE CONTRACTOR, UNLESS NOTED OTHERWISE.
G4 REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR NOTED PERTAINING TO THEIR PARTICULAR TRAFES. COORDINATE THE WORK OF ALL TRADES AND REPORT TO THE ARCHITECT ANY PERCEIVED DISCREPENCIES. CONTRACTOR SHALL BE RESPONSIBLE FOR ESTABLISHING SEQUENCES OF CONSTRUCTION AND MEANS AND METHODS FOR HOW TO PERFORM THE WORK REQUIRED IN THE CONTRACT DOCUMENTS. ALL CONTRACTORS SHALL CAREFULLY REVIEW ALL EXISTING CONDITIONS AND DETERMINE THE MOST FEASIBLE SEQUENCE FOR PERFORMING THE NEW WORK SO AS TO AVOID
CONFLICTS IN THE FIELD.
G5 ANY AREAS OR SPACES NOT CLEARLY DEFINED OR INDICATED BY NOTED SHALL BE OF SAME MATERIAL AND FINISH AS AREAS OF SIMILAR USE OR
FUNCTION ELSEWHERE IN THE BUILDING.
G6 WALL AND CEILING FINISHES SHALL INCLUDE PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, PILASTERS AND
G7 ALL APPURTENANCES BUILT INTO OR THROUGH WALLS, INCLUDING DOORS, WINDOWS, DUCTS, FRAMES, LOUVRES, GRILLES, MECHANICAL WORK, ETC., SHALL FIT SNUGLY AND BE THOROUGHLY SEALED AROUND PERIMETERS. INSTALL FIRE SEALANT AROUND ALL PENETRATIONS THROUGH FLOORS, FIRE RATED WALLS AND SMOKE PARTITIONS. WORK AT EXTERIOR WALLS SHALL BE FLASHED OR OTHERWISE WATERPROOF SEALED.
G8 FIELD CHECK ROUGH AND/OR FINISHED DIMENSIONS FOR ACCURATE FITTING OF CABINETS, COUNTERS, STOREFRONT, DOORS, FRAMES, FIXTURES, MILLWORK, AND ALL OTHER INSTALLATIONS PRIOR TO SHOP OR FACTORY FABRICATION. PROVIDE AND INSTALL NECESSARY FILLER STRIPS, SCRIBE STRIPS, BASES, CLOSURES, FINISHES AND TRIM TO COMPLETE SUCH INSTALLATIONS. DIMENSIONS OF SUCH INSTALLATIONS SHALL BE CONSIDERED "NOMINAL." CONTRACOTRS SHALL ACCOUNT FOR ALL MANUFACTURER'S REQUIRED TOLERANCES, CLEARANCES AND SHIM SPACE TO ENSURE PROPER
INSTALLATION OF THE NEW WORK.
G9 SEE EQUIPMENT PLANS AND FLOOR PLANS FOR CASEWORK, CABINETS, MILLWORK AND OTHER BUILT-IN ITEMS. COORDINATE WITH MEP DRAWINGS FOR
SINKS, OUTLETS, AND OTHER ITEMS TO BE BUILT INTO SUCH ITEMS.
G10 IF A DISCREPANCY APPEARS TO EXIST BETWEEN DRAWINGS OF DIFFERENT SCALES, CONSULT ARCHITECT FOR CLARIFICATION.
G11 IF A DISCREPANCY APPEARS TO EXIST BETWEEN DRAWINGS AND/OR SPECIFICATIONS, THE MORE STRINGENT (TYPICALLY THE MORE COSTLY) REQUIREMENT SHALL APPLY. ITEMS DESCRIBED ON DRAWINGS, BUT NOT SPECIFIED, SHALL BE PROVIDED. CONTRACTOR SHALL BE RESPONSIBLE TO SUBMIT AN RFI TO SEEK CLARIFICATION OF ANY PERCEIVED DISCREPENCY DURING BID PHASE.
G12 WRITTEN INFORMATION ON DRAWINGS TAKES PRECEDENT OVER DRAWING LINES.
G13 IN THE ABSENCE OF A WRITTEN DIMENSION, OR IN CASE OF DOUBT AS TO THE PROPER MEASUREMENT, CONSULT ARCHITECT. DO NOT SCALE DRAWINGS. ASSUMPTIONS MADE, OR ACTIONS TAKEN, BASED ON SCALED DIMENSIONS SHALL BE AT THE CONTRACTOR'S RISK AND ANY RESULTING CORRECTIONS SHALL BE PERFOMRED BY CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
G14 EACH CONTRACTOR OR SUB-CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH THE WORK OF OTHER TRADES SHOWN THROUGHOUT THE COMPLETE SET OF CONTRACT DOCUMENTS. CHANGES RESULTING FROM A CONTRACTOR OR SUB-CONTRACTOR'S FAILURE TO OPTAIN AND REVIEW A COMPLETE SET OF CONTRACT DOCUMENTS SHALL BE CORRECTED AT NO ADDITIONAL COST TO THE GOVERNMENT.
G15 AT ALL CHANGES IN FLOOR FINISHES, PROVIDE AND INSTALL AN APPROPRIATE TRANSITION STRIP AS SHOWN ON THE DRAWINGS.
G16 CONSULT HVAC AND ELECTRICAL DRAWINGS FOR LOCATIONS AND DESCRIPTIONS OF ACCESS PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, VALVE CABINETS, FIRE DAMPERS OR OTHER APPURTENANCES AFFECTING WALLS, CEILINGS OR FLOORS AND PROVIDE NECESSARY LINTELS, SUPPORT
OR ANCHORING
G17 ELECTRIC SWITCHES, OUTLETS, THERMOSTATS, CONTROLS, CLOCKS, SPEAKERS, OR OTHER WALL-MOUNTED ACCESSORIES SHALL BE INSTALLED IN LOCATIONS WHICH ARE UNOBSTRUCTED BY CABINETS, COUNTERS, RACKS, MARKER AND TACKBOARDS, FIXTURES, SHELVING OR OTHER FURNISHING OR EQUIPMENT DESIGNATED FOR SPACES SHOWN ON DRAWINGS. ITEMS FOR WALL-MOUNTING ARE NOT TO BE INSTALLED ON, THROUGH, OR INTO, ANY
EQUIPMENT OTHER THAN WALLS, UNLESS SPECIFICALLY NOTED OTHERWISE.
G18 ELECTRICAL OUTLETS, CLOCKS, P.A. SPEAKERS, PULL STATIONS, EXIT SIGNS, OR OTHER DEVICES SHOWN DIAGRAMMATICALLY ON THE ARCHITECTURAL DRAWINGS SERVE TO ALERT CONTRACTORS OF THE PRESENCE OF SUCH DEVICES. CONSULT THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION AND ADVISE ARCHITECT OF ANY PERCEIVED DISCREPENCY BETWEEN ARCHITECTURAL AND ELECTRICAL DRAWINGS REGARDING LOCATION OR TYPE OF
DEVICES SHOWN PRIOR TO PREPARING SUBMITTALS.
G19 ELECTRIC SWITCHES, THERMOSTATS OR OTHER ELECTRONIC CONTROLS IN THE SAME VICINITY SHALL BE MOUNTED AT THE SAME HEIGHT FROM FLOOR
(UNLESS NOTED OTHERWISE) IN A UNIFORM, ORDERLY FASHION.
G20 SUBMITTAL REVIEW - THE CONTRACT DOCUMENTS PROVIDE SIZES, DIMENSIONS, PRODUCT REQUIREMENTS, ETC. CONTRACTOR SHALL VERIFY THAT SUBMITTALS ARE COORDINATED WITH THE REQUIREMENT OF THE CONTRACT DOCUMENTS PRIOR TO SUBMISSION. A/E REVIEW OF SUBMITTALS IS NOT FOR THE PURPOSE OF DETERMINING THAT SIZES, DIMENSIONS, ETC MATCH WHAT HAS ALREADY BEEN PROVIDED IN THE CONTRACT DOCUMENTS. ALL DEVIATIONS FROM WHAT IS SHOWN ON THE CONTRACT DOCUMENTS SHALL BE CLOUDED ON THE SUBMITTAL OR OTHERWISE CLEARLY BROUGHT TO THE ATTENTION OF THE REVIEWER. FAILURE TO CLEARLY BRING ANY DEVIATION(S) TO THE ATTENTION OF THE REVIEWER SHALL BE UNDERSTOOD BY ALL PARTIES THAT WHAT IS SHOWN IN THE SUBMITTAL COMPLIES WITH THE CONTRACT DOCUMENTS REGARDLESS OF WHETHER OR NOT THE REVIEWER DISCOVERS THE DEVIATION. CHANGES RESULTING FROM THE CONTRACTOR'S FAILURE TO CLEARLY IDENTIFY DEVIATIONS IN SUBMITTALS SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY AND SHALL BE CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
G21 CONTRACTORS SHALL CAREFULLY REVIEW EXISTING FIELD CONDITIONS AND COORDINATE ALL QUANTITIES, DIMENSIONS, AND TOLERANCES REQUIRED TO PERFORM THE WORK SHOWN ON THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR DETERMINING INFORMATION THAT PERTAINS SOLELY TO FABRICATION PROCESSES, INSTALLATION TECHNIQUES (MEANS AND METHODS), AND SEQUENCING OF THE WORK TO MEET THE REQUIREMENTS OF THE PROJECT SCHEUDLE. EACH SUBCONTRACTOR SHALL COORDINATE WITH OTHER TRADES PRIOR TO BEGINNING THEIR PORTION
OF THE WORK.
G22 PUBLIC EXITS SHALL REMAIN CLEAR AT ALL TIMES WHILE THE BUILDING IS OCCUPIED. NO STORAGE SHALL BE PERMITTED IN THE EXIT ACCESS.
G23 PATCH ALL HOLES IN FLOORS, WALLS, AND CEILINGS WITHIN THE PROJECT LIMITS AFTER DEMOLITION AND NEW WORK IS COMPLETE.
G24 UNLESS SPECIFIC DIMENSIONS ARE PROVIDED, MEP DRAWINGS ARE CONSIDERED "DIAGRAMMATIC." IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR(S) TO FIELD COORDINATE LOCATIONS, SEQUENCES, ETC FOR UNOBSTRUCTURED INSTALLATION OF ITEMS THAT ARE SHOWN ON MEP DRAWINGS IN DIAGRAMMITIC FORM. COORDINATE ABOVE-CEILING WORK OF MEP TRADES TO THAT EACH TRADE LOCATES THEIR WORK AS TIGHT TO THE STRUCTURE/DECK ABOVE AS IS FEASIBLE. EACH SUCCESSIVE TRADE SHALL LOCATE THEIR WORK AS TIGHT TO THE TRADE BEFORE.
G25 THE DRAWINGS AND SPECIFICATIONS ARE COMPLIMENTARY AND NEITHER SHALL TAKE PRECEDENT OVER THE OTHER. WHAT IS REQUIRED BY EITHER THE DRAWINGS OR SPECIFICATIONS SHALL BE INTERPRETED AS BEING REQUIRED AS PART OF THE SCOPE OF WORK FOR THIS PROJECT. ITEMS SPECIFIED, BUT NOT INDICATED ON THE DRAWINGS, SHALL BE PROVIDED. ITEMS SHOWN ON THE DRAWINGS, BUT NOT SPECIFIED, SHALL BE PROVIDED.
IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO SEEK CLARIFICATION OF AN APPARENT DISCREPENCY BETWEEN DRAWINGS AND/OR SPECIFICATIONS DURING THE BIDDING PHASE. OTHERWISE, THE CONTRACTOR SHALL ASSUME THE MOST STRINGENT (TYPICALLY THE MOST
EXPENSIVE) REQUIREMENT SHALL APPLY
IN STRIVING TO PROVIDE A HEALTHY AND SAFE ENVIRONMENT AT VA FACILITIES, VHA IS IMPLEMENTING A SMOKE-FREE POLICY FOR ALL VHA HEALTH CARE FACILITIES AND PROPERTY ASSIGNED TO VHA THAT IS UNDER THE CHARGE AND CONTROL OF VA. THE POLICY APPLIES TO CIGARETTES, CIGARS, PIPES OR ANY OTHER COMBUSTION OF TOBACCO, INCLUDING BUT NOT LIMITED TO ELECTRONIC OR E-CIGARRETES, VAPE PENS OR E-CIGARS.
UNDER VHA DIRECTIVE 1085, ALL VHA HEALTH CARE FACILITIES WILL BE SMOKE-FREE FOR PATIENTS, VISITORS, CONTRACTORS, VOLUNTEERS AND
VENDORS EFFECTIVE OCTOBER 1, 2019.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
GENERAL NOTES
GI300
-2
G I3
.p d f
GENERAL NOTES
SMOKING POLICY
(THESE NOTES APPLY TO THE COMPLETE SET OF CONSTRUCTION DOCUMENTS)
CLOCK OR
CLOCK
OUTLET
MANUAL
FIRE ALARM
PULL
STATION
LIGHT
SWITCH &
DIMMER
DUPLEX
OUTLET
(LOW)
DUPLEX
OUTLET
(HIGH)
DESK
INTERCOM
OUTLET
INTERCOM
STATION
PHONE/DATA
OUTLET
THERMOSTAT SPECIAL
PURPOSE
OUTLETS
OR
JUNCTION
BOX
SPECIAL
PURPOSE
OUTLETS
DARK ROOM
STATUS
LIGHT
SWITCH AT
DOOR OR
CASED
OPENING
AUDIBLE
AND/OR VISUAL
FIRE ALARM
SECURITY
STROBE LIGHT
(BLUE LIGHT)
FIREMAN'S
TELEPHONE
JACK
EMERGENCY
STROBE OR
LIGHT
RACEWAY
7'
T O
C O
N T
R O
LS
4'
-0
M A
X H
IG
H
R E
A C
H
3' -0
M
IN
T
O C
O N
T R
O
LS
1' -3
M
IN
L
O W
R E
A C
H
1'
A
LI
G N
W
IT
H T
O P
O F
A D
JA
C
E N
T F
R A
M
E 8" TYP 8" TYP
T O
P O
F B
O X
4'
7'
7'
7'
NURSE
CALL
STATION
WITH
CONTROLS
NURSE
CALL
STATION
WITHOUT
CONTROLS
5'
NURSE CALL
CORRIDOR
LIGHT (DOME
LIGHT)
7'
DUPLEX
OUTLET
ABOVE
COUNTER /
BACKSPLASH
3"
WALL-MTD
TELEPHONE
OUTLET
CARD
READER,
LOCAL
ALARM, OR
ARMING
STATION
3'
COUNTER
TOP / TOP
OF
BACKSPLAS
H
COAT
HOOKS
(WALL-MTD)
COAT HOOK
(DOOR-MTD)
6"
5'
EQ EQ
6'
T O
C O
N T
R O
LS
4'
-0
M A
X H
IG
H
R E
A C
H
3' -0
M
IN
T
O C
O N
T R
O
LS
1' -3
M
IN
L
O W
R E
A C
H
MEDICAL
GAS ALARM
PANEL
FEC OR
FHV CABINET
1' - 0"
5'
4'
4'
"12" 42"
40"
P
LU
M B
IN
G
W A
L L
6" 42"
T O
IL
E
T S
ID
E
W A
LL
6" 36"
S
ID
E W
A
LL
12"36"
C O
N T
R O
L W
A
LL
T O
IL
E
T S
ID
E
W A
LL
9" MAX
7" MIN
IF A DOUBLE ROLL
DISPENSER IS PROVIDED,
DIMENSION IS TO ROLL
CLOSEST TO TOILET
TOILET PAPER
DISPENSER
S
ID
E W
A
LL
15"
COUNTER
MOUNTED
LAVATORY
S
ID
E W
A
LL
15"
WALL
MOUNTED
LAVATORY
C O
U N
T E
R H
E
IG
H T
WALL MOUNTED
POSTURE MIRROR
WALL MOUNTED
MIRROR
T O
R
E F
LE
C
T
IN
G S
U R
F A
C E
18"
MIRROR TO
BE 18" X 36" U.N.O
T O
O P
E R
T A
T
IO
N
CENTER
MIRROR
OVER SINK
U.N.O
S H
O W
E R
W A
L L
WALL MOUNTED
SHOWER SEAT
T O
WALL MOUNTED
SOAP DISPENSER
T O
O P
E R
A T
IO
N
S H
O W
E R
W A
LL
T O
IL
E
T C
.L
18"
SWING UP
GRAB BAR
T O
T O
P
WALL MOUNTED
MOP HOLDER
T O
F R
O N
T T
O P
D G
E O
F D
E C
K
LI
P
W H
N
LO
W E
R E
D
WALL MOUNTED
HORIZONTAL
DIAPER CHANGING
STATION
WALL MOUNTED
GRAB BAR
(TOILET SIDE)
WALL MOUNTED
GRAB BAR
(TOILET REAR)
WALL MOUNTED
SHOWER
GRAB BARS
WALL MOUNTED PAPER
TOWEL DISPENSER
(WITH OR WITHOUT
INTEGRAL
TRASH RECEPTICLE)
F
IL
LE
R
S O
F T
T O
U C
H C
O N
T R
O L
(M A
X
T O
T O
P O
F B
O T
T
LE
BOTTLE
FILLER
EQUIPMENT, PANEL BOARD,
CABINET, OR SIMILAR FEATURE
CRASH RAIL (ALL TYPES), UON
CORNER GUARD
WHERE BUMPER/CRASH
RAILS TERMINATE OR DO NOT
TURN CORNER
BUMPER GUARD /
RAIL (ALL TYPES),
UON
DOOR FRAME OR
CASED OPENING
FRAME
OUTLET OR SIMILAR
OUTLET OR
SIMILAR WHEN ADJ
TO FRAME
WHERE
BUMPER/CRASH
RAILS TURN CORNER
CORNER OR EDGE
GUARD
CORNER OR EDGE
GUARD
COMBINATION
HANDRAIL/CRASH
RAIL (ALL TYPES), UON
WHERE
TERMINATES
WHERE
COMBINATION
HANDRAIL / CRASH
RAIL
TURNS CORNER
DOOR FRAME OR CASED
OPENING FRAME
CORNER OR EDGE
GUARD
RECESSED CORNER OR EDGE GUARD
EXTENDING FROM FLOOR TO CEILING OR
HEADER, TYPICAL UNLESS OTHERWISE NOTED
EQUIPMENT, PANEL BOARD,
CABINET, OR SIMILAR FEATURE
2'
0"
U O
N
1'
U O
N
6" 3'
2" TYP 2" TYP 2" TYP
4" TYP 4" TYP
2" TYP
2'
0"
T O
P O
F R
A
IL
2" TYP 2" TYP 2" TYP
6" 6'
2" TYP 2" TYP 2" TYP
2'
0"
T O
P O
F R
A
IL
6" 6'
2" TYP
8" 4" TYP
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
TYPICAL MOUNTING HEIGHTS AND
DIMENSIONING CONVENTIONS
GI301
-2
G I3
/2
/2
.p d f
GENERAL MOUNTING HEIGHT NOTESTYPICAL MOUNTING HEIGHTS AND CLEARANCES
CORNER GUARD / BUMPER RAIL / CRASH RAIL / CORRIDOR HANDRAIL TYPICAL MOUNTING HEIGHTS AND CONFIGURATION DIAGRAMS
A. IT IS THE INTENT OF THE DESIGN THAT ALL ITEMS SHOWN MOUNTED AT TYPICAL HEIGHTS
BE ACCESSIBLE TO PERSONS WITH DISABILITIES.
B. THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE TYPICAL MOUNTING HEIGHTS AND - WHERE
APPLICABLE - TYPICAL MINIMUM OR MAXIMUM CLEARANCES AND/OR TYPICAL MOUNTING
CONFIGURATIONS FOR A VARIETY OF ITEMS. CAUTION: THIS SHEET MAY ILLUSTRATE ITEMS
OR CONFIGURATIONS WHICH DO NOT OCCUR AS PART OF THE WORK OF THIS PROJECT.
REFER TO THE PLANS, ELEVATIONS, SECTIONS, DETAILS, AND SCHEDULES TO DETERMINE
WHICH ITEMS AND CONFIGURATIONS APPLY TO THE WORK OF THIS PROJECT.
C. THE MOUNTING HEIGHTS, CLEARANCES, AND CONFIGURATIONS SHOWN ON THIS SHEET ARE
TYPICAL AND SHALL APPLY TO ALL INSTANCES OF THE ITEM (OR GROUP OF ITEMS) SHOWN
UNLESS SPECIFICALLY NOTED OR DIMENSIONED OTHERWISE.
D. SPECIAL OR NON-TYPICAL MOUNTING HEIGHTS OCCUR ONLY WHERE INDICATED BY
ANNOTATED SYMBOLS; BY KEY NOTES; BY NOTES ON PLANS, ELEVATIONS, OR DETAILS; OR
BY UNIQUE DIMENSIONS ON ELEVATIONS OR DETAILS.
E. MOUNTING CONFIGURATION DIAGRAMS ARE ELEVATIONS WHICH ILLUSTRATE TYPICAL
RULES GOVERNING THE RELATIONSHIPS BETWEEN, AND PLACEMENT OF, ITEMS WHICH
OCCUR IN GROUPS OF RELATED ITEMS OR IN CLOSE PROXIMITY TO OTHER PARTS OF THE
WORK (SUCH AS SWITCHES AND DOOR FRAMES). UNLESS OTHER MOUNTING
CONFIGURATIONS ARE SPECIFICALLY NOTED, DIMENSIONED, OR ELEVATED, THE TYPICAL
RELATIONSHIPS, ARRANGEMENTS, AND THE TYPICAL CONFIGURATION DIAGRAMS APPLY
THROUGHOUT THE WORK OF THIS PROJECT.
HOME HEMO
TRAINING
2H-214
ISOLATION
2H-211
TOILET
2H-212
ANTE RM
2H-210
GURNEY
ALCOVE
2H-254
ASSISTANT
TECH
2H-253
TOILET
2H-255
MATER
TREATMENT
2H-252
WAITING
2H-207
WHEELCHAIR
ALCOVE
2H-201
CORRIDOR
C2H-2
SECRETARY
2H-208
NOURISHMENT
2H-209
SOCIAL
WORKER
2H-202
TOILET
2H-203
PD TRAINING
EXAM
2H-205
ANEMIA
MANAGER
2H-206
ELECTRIC
2H-200
TOILET
2H-260
16 17 18 19 20
V
TR
EA
TM
EN
T
TR
EA
TM
EN
T
TR
EA
TM
EN
T
TR
EA
TM
EN
T
CORRIDOR
C2H-9
TOILET
2H-261
CORRIDOR
C2H-1
22' - 4" 22' - 4" 25' - 1 1/2" 25' - 1 1/2" 22' - 4" 22' - 4"
PHYSICIAN
2H-129
CONFERENCE
ROOM
2H-133
SOCIAL
WORKER
2H-134
NURSE
MANGER
2H-136
FEMALE
LOCKER
2H-127
HAC
CH-125
TOILET
2H-126
TOILET
2H-124A
MALE LOCKER
2H-125
CLEAN
EQUIPMENT
2H-130
EQUIPMENT
REPAIR
2H-122
EQUIPMENT
STORAGE
2H-132
MACH
STORAGE
2H-135
WATER
TREATMENT
2H-131
EXAM
ROOM
2H-139
FELLOWS
2H-138
EXAM
2H-140A
OFFICE
2H-140
WAITING
2H-103
PATIENT
TOILET
2H-104
RECOVERY
AREA
2A-113
DIRTY
UTILITY
2H-101
KITCHEN
2H-107
TOILET
2H-112
TOILET
2H-113
CLEAN
UTILITY
2H-117
ANTE ROOM
2H-116
STAFF
LOUNGE
2H-119
ELECTRICAL
CLOSET
2H-120
STORAGE
2H-121
LINEN
CLOSET
2H-123
SOILED
UTILITY
2H-118
CHIEF
2K-144
EQUIPMENT
2K-141A
OFFICE
2K-140
PHARMACY
SATELLITE
2H-141
ANTE
2H-108
BED ROOM
2H-111
BED ROOM
2H-114
NURSES
STATION
C2H-3
SHOWER
2H-105
FAMILY
WAITING
2G-132
NURSE
MANAGER
2G-131
ON CALL
ROOM
2G-130
MALE LOCKER
2G-126
UNISEX
TOILET
2G127
SHOWER
2G-129 SHOWER
2G-129
FEMALE
STAFF
LOCKER
2G-123
PROJECT
SECTION
2K-137
OFFICE
2K-147
OFFICE
2K-146=5
OFFICE
2K-146
OFFICE
CUBICLES
2K-143
BIOMED
REPAIR SHOP
2K-141
CONFERENCE
2K-139
MALE
TOILET
2G-134
FEMALE
TOILET
2G-132
W
X
Y
Z
AA
BB
STORAGE
2H-137
BIOMED
C2K-4
CORRIDOR
C2H-9
CORRIDOR
C2H-6
SCOPE OF WORK
1. EXISTING CONDITIONS DRAWING IS FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY
LOCATIONS OF ALL ITEMS SHOWN ON THIS SHEET PRIOR TO BEGINNING WORK.
EXISTING CONDITIONS NOTES
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
EXISTING CONDITIONS PLAN
GC200
-2
G C
/2
/2
.p d f
1/8" = 1'-0"A12
EXISTING FLOOR PLAN
16 17 18 19 20
V
W
X
Y
Z
AA
BB
TACKY MATS ON EACH SIDE
OF DOOR. REPLACE MATS
WHEN NO LONGER EFFECTIVE.
7'
1/
2"
TACKY MATS ON EACH SIDE OF DOOR.
REPLACE MATS WHEN NO LONGER
EFFECTIVE.
ICRA ANTEROOM. PROVIDE COAT HOOKS,
STORAGE SHELF FOR COVERALLS AND A BENCH.
TEMPORARY DOOR WITH CLOSER AND
EXIT DEVICE LOCKED FROM NON-
CONSTRUCTION SIDE. PROVIDE SMOKE
SEALS ON JAMBS AND HEAD OF DOOR.
ICRA ANTEROOM. PROVIDE COAT
HOOKS, STORAGE SHELF FOR
COVERALLS AND A BENCH.
TEMPORARY DOOR WITH CLOSER AND
EXIT DEVICE LOCKED FROM NON-
CONSTRUCTION SIDE. PROVIDE SMOKE
SEALS ON JAMBS AND HEAD OF DOOR.
"EMERGENCY EXIT" SIGN ON
CONSTRUCTION SIDE OF DOOR.
"EMERGENCY EXIT" SIGN ON CONSTRUCTION
SIDE OF DOOR.
T1
T1
T1
R1
R1
T1
R1
TEMPORARY ZIP WALL FOR
CASED OPENING
R1
T1
T1
3'
R1
R1
R1REMOVE DOOR / FRAME AND
INFILL OPENING WITH R1
WALL TYPE
REMOVE DOOR
DOOR / FRAME AND
INFILL OPENING
WITH R1 WALL TYPE
T1T1
1'
8"
MAINTAIN ACCESS THROUGH THIS CORRIDOR DURING
CONSTRUCTION. THE CONTRACTOR WILL NEED TO
COORDINATE DEMOLITION OF THIS SPACE WITH THE COR.
NEED A TEMPORARY 4' X 8' DOOR FOR ACCESS.
INSTALL TEMPORARY PLASTIC FOR DUST
CONTROL.
6"
DEMOLISH PORTION OF WALL PRIOR TO
CONSTRUCTING TEMPORARY
CONSTRUCTION BARRIER.
R1R1
1. SEE WALL TYPE T1 ON SHEET AE301 FOR TEMPORARY CONSTRUCTION BARRIER
DETAIL.
2. SEE DETAILED NOTES ON THIS SHEET FOR PROCEDURES TO BE FOLLOWED DURING
AND AFTER CONSTRUCTION.
3. CONTRACTOR SHALL PREPARE A DETAILED ICRA PLAN FOR REVIEW AND APPROVAL
BY THE VAMC'S COR AND INFECTION CONTROL REPRESENTATIVE.
4. CONTRACTOR SHALL PROVIDE INTERIM LIFE SAFETY PLAN FOR APPROVAL BY VAMC.
UPON COMPLETION OF EACH PHASE, PERFORM THE FOLLOWING:
1. CLEAN UP CEILING TILE AND FLOORING SURFACES WITH HEPA FILTERED VACUUM OR
DAMP MOP.
2. WET MOP AND/OR VACUUM WITH HEPA-FILTERED VACUUM BEFORE LEAVING WORK
AREA AND WIPE WORK SURFACES WITH DISINFECTANT.
3. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED
CONTAINERS. SEAL WITH TAPE TO ENSURE A TIGHT COVER.
4. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHEN WORK AND AREA CLEANUP HAS
BEEN COMPLETED.
5. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION.
6. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
INSPECTED AND AUTHORIZED BY COR, SAFETY AND INSPECTION CONTROL.
DURING CONSTRUCTION, THE FOLLOWING MUST BE PERFORMED DAILY:
1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION
OPERATIONS.
2. FOR VISUAL INSPECTION ONLY, DAMPEN CEILING TILE(S) WITH WATER SPRAY BEFORE
REMOVING. REPLACE CEILING TILE IMMEDIATE AFTER INSPECTION; DO NOT LEAVE
UNATTENDED.
3. PROVIDE ACTIVE MEANS TO PREVENT DUST FROM DISPERSING. DUST LEFT ON THE
FLOORS, CLOTHING AND/OR BODY IS NOT ALLOWED IN ORDER TO PREVENT SPEADING
AND TRACKING. "ACTING MEANS" ARE:
A. VACUUM ATTACHMENTS ON TOOLS WITH HEPA VACUUM, OR HEPA VACUUMING
IMMEDIATELY AS DUST IS GENERATED.
B. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING
PERFORMED.
C. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.
D. SEAL UNUSED DOORS WITH DUCT TAPE.
E. BLOCK OFF AND SEAL ALL HVAC AIR VENTS.
F. PLACE TACKY MAT AT INSIDE OF ENTRANCE OF WORK AREA AND CHANGE
FREQUENTLY OR WHEN INEFFECTIVE.
G. WET MOP AND/OR VACUUM WITH HEPA-FILTERED VACUUM THE WORK AREA
BEFORE LEAVING THE SITE. BROOM SWEEPING IS NOT SUFFICIENT.
4. WHENEVER TRANSPORTING OUTSIDE OF THE CONSTRUCTION SITE, WIPE MATERIALS,
EQUIPMENT AND WORK SURFACES WITH EPA REGISTERED, UNSCENTED
DISINFECTANT, WHICH HAS MANUFACTURER'S LABELING AS A BACTERICIDE,
TUBERCULOCIDE, VIRUCIDE AND FUNGICIDE.
5. THERE SHALL BE NO STANDING, UNCOVERED WATER PERMITTED TO ACCUMULATE
DURING CONSTRUCTION. THIS INCLUDES WATER IN EQUIPMENT DRIP PANS AND OPEN
CONTAINERS WITHIN THE CONSTRUCTION AREAS. ALL INCIDENTAL SPILLS MUST BE
CLEANED UP AND DRIED WITHIN 12 HOURS. REMOVE AND DISPOSE OF POROUS
MATERIALS THAT REMAIN DAMP FOR MORE THAN 72 HOURS.
6. COMPLETE ALL CRITICAL BARRIERS (SEE TEMPORARY CONSTRUCTION BARRIER
SHOWN ON SHEET AE301) TO SEAL AREA FROM NON-WORK AREA BEFORE
CONSTRUCTION BEGINS.
7. MAINTAIN NEGATIVE PRESSURE VENTILATION (NPV) AT 0.01 WATER COLUMN (WC)
WITHIN THE WORK SITE UTILIZING NPV MACHINE.
8. NPV MONITORING DEVICES SHOULD BE VISIBLE FROM OUTSIDE THE WORKSITE AND
READINGS SHALL BE DOCUMENTED DAILY OR MORE OFTEN AS NEEDED. KEEP
TRACKING MONITORING DEVICE AND TRACKING LOG AT OUTSIDE OF ENTRANCE AT THE
SITE.
9. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED
CONTAINERS. TAPE COVERING, UNLESS USING FORM-FITTING SOLID LID.
10. SEAL HOLES, PIPES, CONDUITS AND PUNCTURES ETC APPROPRIATELY DURING
CONSTRUCTION.
11. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS
ROOM TO BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK
SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH
TIME THEY LEAVE THE WORK SITE.
12. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE
COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA.
TEMPORARY CONSTRUCTION BARRIER
NOTES
A. LOCATION OF TEMPORARY CONSTRUCTION BARRIERS IS CONCEPTUAL. CONTRACTORS
SHALL SUBMIT A DETAILED TEMPORARY CONSTRUCTION BARRIER PLAN FOR APPROVAL
BY THE COR PRIOR TO BEGINNING ANY WORK.
B. PRIOR TO INSTALLATION OF TEMPORARY CONSTRUCTION BARRIER WALLS. DOCUMENT
EXISTING FINISHES WITH PHOTOS. PROVIDE COR WITH PHOTOS. DO NOT PERFORM ANY
WORK UNTIL PHOTOS HAVE BEEN DISTRIBUTED AND ACCEPTED BY COR.
C. INSTALL TEMPORARY CONSTRUCTION BARRIER WALLS PRIOR TO PERFORMING ANY
DEMOLITION WORK.
D. TEMPORARY CONSTRUCTION BARRIER WALL OPENINGS SHALL EXTEND FROM FLOOR TO
DECK ABOVE AND SHALL BE SEALED WITH FIRE RATED SEALANT. SEE TEMPORARY
CONSTRUCTION BARRIER DETAIL ON THIS SHEETS.
E. TEMPORARY CONSTRUCTION BARRIER WALL OPENINGS SHALL HAVE 45 MIN. RATED
DOORS WITH CLOSERS. PROVIDE A SIGN ON OCCUPANT SIDE OF DOOR THAT STATES
THE FOLLOWING: "CAUTION - CONSTRUCTION ZONE - AUTHORIZED PERSONNEL ONLY".
F. PROVIDE STICKY MATS ON BOTH SIDES OF CONSTRUCTION BARRIER DOORS. REPLACE
STICKY MATS WHEN NO LONGER STICKY.
G. REFER TO INFECTION CONTROL RISK ASSESSMENT NOTES FOR ADDITIONAL
REQUIREMENTS.
H. PROVIDE DIRECTIONAL SIGNS THAT SAY "EMERGENCY EXIT" WHERE INDICATED ON
TEMPORARY CONSTRUCTION BARRIER PLANS.
I. PATCH / REPAIR HOLES, SCRATCHES AND ANY OTHER DAMAGE AFTER REMOVAL OF
TEMPORARY CONSTRUCTION BARRIER WALLS. RESTORE FINISHES TO THE SAME
CONDITION AS BEFORE TEMPORARY CONSTUCTION BARRIER WALLS WERE INSTALLED.
OBTAIN APPROVAL OF COR.
J. SUBMIT PLAN SHOWING REQUIRED INTERIM LIFE SAFETY MEASURES (ILSM) FOR
APPROVAL BY THE COR.
K. MAINTAIN 5'-0", MIN. ON NON-CONSTRUCTION SIDE OF ICRA BARRIERS IN CORRIDORS.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ICRA PLAN
GC400
-2
G C
/2
/2
.p d f
1/8" = 1'-0"A12
ICRA PLAN
ICRA GENERAL NOTES
INFECTION CONTROL RISK ASSESSMENT
REQUIREMENTS
TR
EA
TM
EN
T
TR
EA
TM
EN
T
TR
EA
TM
EN
T
TR
EA
TM
EN
T
W
X
Y
Z
AA
BB
1 1
4 4 4 4
4 4
1 1 11
111 11
6 6
1 1
111 1
1 1
1 1
1 111 111 1
10 10
8 7
8 8
8 8
12 12 12 12 12 12
GURNEY
ALCOVE
2H-254
ASSISTANT
TECH
2H-253
TOILET
2H-255
MATER
TREATMENT
2H-252
WAITING
2H-207
WHEELCHAIR
ALCOVE
2H-201
SECRETARY
2H-208
NOURISHMENT
2H-209
SOCIAL
WORKER
2H-202
TOILET
2H-203
ELECTRIC
2H-200
TOILET
2H-260
CORRIDOR
C2H-9
TOILET
2H-261
CORRIDOR
C2H-1
PHYSICIAN
2H-129
CONFERENCE
ROOM
2H-133
SOCIAL
WORKER
2H-134
NURSE
MANGER
2H-136
FEMALE
LOCKER
2H-127
HAC
CH-125
TOILET
2H-126
TOILET
2H-124A
MALE LOCKER
2H-125
CLEAN
EQUIPMENT
2H-130
EQUIPMENT
REPAIR
2H-122
EQUIPMENT
STORAGE
2H-132
MACH
STORAGE
2H-135
WATER
TREATMENT
2H-131
EXAM
ROOM
2H-139
FELLOWS
2H-138
EXAM
2H-140A
OFFICE
2H-140
WAITING
2H-103
PATIENT
TOILET
2H-104
RECOVERY
AREA
2A-113
DIRTY
UTILITY
2H-101
KITCHEN
2H-107
TOILET
2H-112
TOILET
2H-113
CLEAN
UTILITY
2H-117
ANTE ROOM
2H-116 STAFF
LOUNGE
2H-119
ELECTRICAL
CLOSET
2H-120
STORAGE
2H-121
LINEN
CLOSET
2H-123
SOILED
UTILITY
2H-118
CHIEF
2K-144
EQUIPMENT
2K-141A
PHARMACY
SATELLITE
2H-141
ANTE
2H-108
BED ROOM
2H-111
BED ROOM
2H-114
NURSES
STATION
C2H-3
SHOWER
2H-105
FAMILY
WAITING
2G-132
NURSE
MANAGER
2G-131
ON CALL
ROOM
2G-130
SHOWER
2G-129 SHOWER
2G-129
OFFICE
2K-147MALE
TOILET
2G-134
FEMALE
TOILET
2G-132
STORAGE
2H-137
1. REMOVE ENTIRE WALL STRUCTURE DOWN TO SLAB (INCLUDING MASONRY, DOORS, AND
WINDOWS).
2. REMOVE PORTION OF WALL. COORDINATE WITH NEW WORK PLANS FOR EXTENT OF WALL
REMOVAL. PATCH AND LEVEL FLOOR TO RECEIVE NEW FINISHES.
3. ENLARGE OPENING FOR NEW DOOR OPENING. SEE NEW WORK PLANS FOR SIZE OF
OPENINGS. PATCH AND LEVEL FLOOR TO RECEIVE NEW FINISHES.
4. REMOVE DOOR(S) AND FRAME(S). (TO INCLUDE STOPS & HOLD OPENS WHERE THEY
OCCUR)
5. REMOVE DOOR ONLY, FRAME TO REMAIN AND BE REUSED WITH NEW DOOR.
6. REMOVE EXISTING WINDOW, INCLUDING FRAME, CLIPS, ETC.
7. REMOVE IN-FLOOR SCALE. PATCH AND LEVEL FLOOR TO RECEIVE NEW FINISHES.
8. REMOVE ALL FINISHES INCLUDING FLOORING, FIXTURES, CASEWORK, SHELVING,
COUNTERTOPS, LOCKERS, BASE, CHALK & TACK BOARDS, PROJECTION SCREEN, CHASES,
CEILING & CEILING SUPPORT MEMBERS & ALL BULKHEADS. COORD. W/ M.E.P. FOR
ADDITIONAL DEMO.
9. REMOVE PLUMBING FIXTURES & ACCESSORIES. SEE M.E.P. DWGS. FOR FIXTURE & PIPING
DEMOLITION. PATCH FLOOR & WALL FINISHES TO MATCH. REMOVE WING WALLS AT
STALLS & TOILET PARTITIONS.
10. REMOVE EXISTING NURSE STATION
11. REMOVE PORTION OF EXISTING WALL FOR NEW CASED OPENING. COORDINATE WITH NEW
WORK PLANS FOR EXTENT OF WALL REMOVAL. PATCH AND LEVEL FLOOR TO RECEIVE
NEW FINISHES.
12. REMOVE PORTION OF EXISTING WALL FOR NEW CLERESTORY WINDOW. COORDINATE
LOCATION AND SIZE WITH NEW WORK PLANS.
DEMOLITION KEY NOTES
A. AT ALL EXISTING WALLS AND COLUMN ENCLOSURES SHOWN TO REMAIN, REMOVE GYPSUM
BOARD DOWN TO STUDS.
B. CONTRACTORS SHALL NOTIFY COR IMMEDIATELY OF ANY DEVIATIONS BETWEEN EXISTING
CONDITIONS AND DEMOLITION DRAWINGS DISCOVERED DURING DEMOLITION ACTIVITIES.
C. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING AND COORDINATING ALL
EXISTING AND NEW CONSTRUCTION,
D. ALL ITEMS SHOWN AS DASHED INDICATE ITEMS TO BE DEMOLISHED. SEE SPECIFIC KEY
NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. REFER TO MECHANICAL, PLUMBING,
ELECTRICAL, AND TELECOM DRAWINGS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
E. ALL OPENINGS AND SURFACES MADE BARE BY DEMOLITION AND/OR REMOVAL OF
MATERIALS SHALL BE REPAIRED AND/OR PATCHED TO MATCH ADJACENT FINISH. PREPARE
SURFACES TO RECEIVE NEW FINISHE(S)
F. HAZARDOUS MATERIAL ABATEMENT IS REQUIRED IN THIS PROJECT SCOPE. REFER TO
SPECIFICATION SECTION 02 82 11, ACM SURVEY AND LOCATION PLAN (PROVIDED IN
SPECIFICATION BOOK VOLUME 1 AS PART OF THE CONSTRUCTION DOCUMENTS) FOR
ADDITIONAL INFORMATION.
G. COORDINATE AREAS WHERE FLOOR SLABS SHALL BE CHIPPED OUT AT FLOOR DRAINS, SEE
FLOOR PLANS.
H. FLOOR LEVELING NEEDED AT AREAS OF EXISTING TILE FLOOR INCLUDING SHOWERS AND
TOILETS 2H-104, 2H-105, TOILETS 2H-112, 2H-113. 2H-124A, 2H-127, AND ASSOCIATED
VESTIBULES.
I. PATCH AND FILL EXISTING FLOOR DRAINS AT SHOWER 2H-105 AND WATER TREATMENT
2H-131.
J. PATCH AND FILL EXISTING DUMBWAITER SHAFT TO MATCH SURROUNDING FLOOR
CONSTRUCTION TYPE IB.
GENERAL DEMOLITION NOTES
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
DEMOLITION PLAN
AD100
-2
A D
.p d f
DEMOLITION PLAN
W
X
Y
Z
AA
BB
917 SF
BREAK/MEETING
ROOM
2H-104
CLOSET
2H-123
578 SF
TOUCHDOWN
2H-103
534 SF
TOUCHDOWN
2H-120
167 SF
ANESTHESIA
2-PERSON OFFICE
2H-115
82 SF
ANESTHESIA
OFFICE
2H-114
328 SF
TOUCHDOWN
2H-121
88 SF
STORAGE
2H-105
56 SF
ELEC. CLOSET
2H-106
111 SF
IT CLOSET
2H-107
233 SF
RESIDENTS
2H-122
134 SF
NEW 2-PERSON
ENGINEERING
OFFICE
2K-140A
101 SF
NEW ENGINEERING
OFFICE
2H-140B
721 SF
TOUCHDOWN
2H-111
129 SF
ANESTHESIA
OFFICE
2H-118
176 SF
ANESTHESIA
OFFICE
2H-119
82 SF
ANESTHESIA
OFFICE
2H-113
92 SF
STAFF LOCKER
2H-110
CORRIDOR
C2H-6
CORRIDOR
C2H-7
CORRIDOR
C2H-5
CORRIDOR
C2H-4
812 SF
ANESTHESIA
ADMIN.
2H-112
88 SF
WELLNESS ROOM
2H-108
84 SF
STAFF TOILET
2H-109
123 SF
ANESTHESIA
OFFICE
2H-116
112 SF
ANESTHESIA
OFFICE
2H-117
A1
C1C1 A2
A2
C1
A2
A2
C1 C1 A1
A1
A1
A1
A1
A1
A1
A2
A1
A1
C1
A1
A1 A1
A1
A1
A1
A1
A1 A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1A1 A2
A1
A1
A1
A1
C1
C1C1 C1
C1
C1
C1
C1
2H-112
2H-118
2H-119
2H-113
2H-117
2H-116
2H-115 2H-114
2H-120
2H-121
2H-122
2H-108
2H-109
2H-111
2H-103
2H-104
2H-104B
2H-104A
2H-105
2H-107
C2H-5
AE900
G16
AE900
A15
AE900
C16
AE500
G7
9'
4" 9'
7/ 8"
9'
7/
8" 9'
7/ 8"
9'
1/
2"
14' - 8 1/4" 5' - 9" 17' - 10 3/8" 11' - 6 3/8" 6' - 0" 10' - 9 7/8"
C1 C1C1
C1C1
C1
C1
C1
C1 C1C1
C1
C1
ANESTHESIA
CUBICLE
ANESTHESIA
CUBICLE
RECEPTION
CUBICLE
ANESTHESIA
CUBICLE
A1
86 SF
VESTIBULE
2K-140C
A2
EQ
EQ
2'
0"
FEC
FEC
R1
SW1
TYPE D
SIGN TYPE
TYPE D SIGN TYPE
TYPE E
SIGN
TYPE
TYPE E
SIGN TYPE
TYPE E
SIGN TYPE
AE600
A1
A2
C1
C1C1 C1C1
AE500
C7
A2A2
A1
AE600
I11
G11
AE600
I7
1'
6"
/8
8'
7/ 8"
/8
/8
6'
1/
8" 7'
1/ 4"
6'
1/
4"
A
LI
G N
A
LI
G N
ALIGN
ALIGN
ALIGN
A
LI
G N
A
LI
G N
4'
1/
4" 4'
3/ 4"
6'
7/
8"
/8
AE500
A7
19' - 1 1/8" 9' - 7 3/4" 9' - 6 3/4" 8' - 4 1/4" 23' - 9 1/8" 6' - 4 1/4"
A1
3' - 6 3/8" 26' - 7 5/8"
A2
1' - 4 7/8"
A1A1
A1
C1
2'
3/
4"
4'
0"
1'
7/
8"
9'
4"
1/ 4"
ALIGN
6'
5/
8"
11' - 7 1/2"
1'
1/
8" 9'
5/ 8"
9'
1/
4"
C1
C1
/4
9'
4"
/8
C1
C1
C1
C1
E8
AE600
A1
G-2 G-2 G-2 G-2 G-2 G-2
C1
3'
/4
2K-140C
A1
4' - 0" 2' - 8" 4' - 0" 1' - 0" 4' - 0" 1' - 0" 4' - 0" 1' - 11 5/8"11 1/2" 4' - 0" 1' - 0" 4' - 0" 2' - 2 3/4"
CORRIDOR
C2H-4
91 SF
STORAGE
2H-141B
2H-141B
BIOMED
CORRIDOR
I8
A1
14' - 0 1/4"
C2H-7
C2H-4
2K -1
A
EQ EQ
C2H-6
A1
A1
A1
18' - 2 3/4"
NEW ONSED
OPENING
AE600
G10
C1
R1
ALIGN
CORRIDOR
C2H-6
4'
0"
2' - 6"
2'
0"
EQ
EQ
LEGEND
EXISTING 2HR SMOKE FIRE RATING
EXISTING WALL TO REMAIN
NEW CONSTRUCTION
EXISTING 2HR FIRE RATING
EXISTING 30MIN SMOKE RATING
NEW 30MIN SMOKE RATING
NEW 2HR SMOKE FIRE RATING
GENERAL PLAN NOTES
1. UNLESS OTHERWISE NOTED, DIMENSIONS ARE TO FACE OF FINISHED
DRYWALL, FACE OF CMU, OR COLUMN CENTER LINES. UNLESS SPECIFICALLY
SHOWN CENTERED ON A PARTICULAR BUILDING ELEMENT I.E. A CHASE WALL,
WINDOW MULLION, ETC.
2. CONTRACTOR SHALL PROVIDE ALL BLOCKING REQUIRED TO ANCHOR ALL
WALL AND CEILING MOUNTED ITEMS, INCLUDING BUT NOT LIMITED TO TOILET
ROOM ACCESSORIES, MILLWORK, CASEWORK, HANDRAILS, ETC.
3. REFER TO AE300 FOR DOOR SCHEDULE AND DOOR AND FRAME TYPES.
REFER TO AE301 FOR WALL TYPES.
4. DISTANCE FROM HINGE SIDE OF DOOR (MEASURED FROM OUTSIDE FRAME)
TO INTERSECTING STUD WALL SHALL BE 4" UNLESS NOTED OTHERWISE.
5. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LAY OUT WALLS ON
FLOOR PRIOR TO INITIATING CONSTRUCTION. REPORT DISCREPANCIES TO
COR PRIOR TO COMMENCING WORK.
6. ALL PENETRATIONS THROUGH RATED FLOOR/CEILING ASSEMBLIES AND
THROUGH FIRE RATED WALL AND SMOKE BARRIER ASSEMBLIES MUST BE
FIRE SEALED AS PART OF THIS CONTRACT. SEAL PENETRATIONS THROUGH
THE FLOOR OF THE INTERSTITIAL SPACE WITH 2-HOUR RATED SEALANT.
7. REFER TO A10/AE500 FOR FLOOR DRAIN DETAIL AT STAFF TOILET ROOM.
8. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS IN CORRIDORS.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
FLOOR PLAN
AE100
-2
A E
.p d f
FLOOR PLAN
1. WHEN EXPOSED CLEAR FINISHED WOOD DOORS ARE PAIRED, TAKE CARE TO SELECT
MATCHING GRAIN TYPE AND COLOR FOR EACH DOOR IN PAIR.
2. VERIFY ALL DIMENSIONS AND CLEARANCES, AND COORDINATE UNDERCUTTING REQUIRED
TO CLEAR ADJACENT FLOOR MATERIALS.
3. SEE SPECIFICATIONS FOR SCHEDULED HARDWARE SETS.
4. SEE S1, H1 AND J1 FOR H/S/J AT CLERESTORY WINDOWS. PROVIDE 1/2"X1/2" HOLLOW
METAL GLASS STOP ON ALL SIDES.
5. PROVIDE H2 AND J2 AT ALL CASED OPENINGS.
TYPICAL DOOR NOTES
BASE BID: PROVIDE ALL HM-2 CLERESTORY WINDOWS AS SHOWN AND DETAILED.
DEDUCT ALTERNATE #1: DO NOT PROVIDE HM-2 CLERESTORY WINDOWS. EXISTING WALL TO
REMAIN IN TACT AND FINISHED PER FINISH SCHEDULE.
DEDUCT ALTERNATE #1
1. MODIFY FRAME FOR DOUBLE EGRESS DOOR.
2. PROVIDE PIV CARD READER. BASIS OF DESIGN IS COVERGENT TECHNOLOGIES.
3. PROVIDE AUTOMATIC OPERATORS.
4. INTEGRATED DOOR ASSEMBLY.
REMARKS COLUMN NOTES
7'
0"
WIDTH AS SCHED.
FR
RATED
DBL
7'
0"
7'
0"
WIDTH AS SCHED.
F
WIDTH AS SCHEDULED
DOOR TYPES
7'
0"
WIDTH AS SCHED.
HM-1
HOLLOW METAL FRAME TYPES
2"2"
2"
7'
0"
WIDTH AS SCHED.
FG
HM-2
6'
6"
2" 3' - 8" 2"
2" 2"
1'
8"
2'
0"
4' - 0"
G-2
G-1: 1/4" CLEAR TEMPERED GLASS
G-2: 1/4" CLEAR TEMPERED FIRE-RATED GLASS
GLASS TYPES
CORR
RATED RATED
WIDTH AS SCHED.
7'
0"G-2G-2G-1
JAMB ANCHOR
DOOR: SEE SCHEDULE
5/8" GYPSUM BOARD
SEALANT, TYP. BOTH
SIDES, FULL
PERIMETER
5/8" GYPSUM BOARD
METAL STUD TRACK
SEALANT TYP, BOTH SIDES
FULL PERIMETER
DOOR: SEE SCHEDULE 5/8" GYPSUM BOARD
METAL STUD TRACK
SEALANT TYP, BOTH SIDES
FULL PERIMETER
5/8" GYPSUM BOARD
METAL STUD TRACK
5/8" GYPSUM BOARD
5/8" GYPSUM BOARD
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ARCHITECTURE:
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD.
SUITE 275
COLUMBIA, MD 21046
410-290-9301
RAYMOND ENGINEERING
1601 SUMMIT AVE.
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
OLKJ
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
DOOR SCHEDULE
AE300
-2
A E
.p d f
DOOR
NO. ROOM NAME
DOOR FRAME DOOR
LABEL
FIRE
RATING
HARD
WARE
SET
SIGN
TYPE REMARKS
NOMINAL SIZE
TYPE MATL MATL TYPE
SECTIONS
WIDTH HEIGHT THK. JAMB HEAD SILL
2H-103 TOUCHDOWN 3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3E TYPE C
2H-104 BREAK/MEETING
ROOM
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 4J TYPE C -
SLIDER
2H-104A CLOSET 3' - 0" 7' - 0" 1 3/4" F SCWD HM HM-1 J1 H1 5B TYPE C
2H-104B BREAK/MEETING
ROOM
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 4J TYPE C -
SLIDER
2H-105 STORAGE 3' - 0" 7' - 0" 1 3/4" FR SCWD HM HM-1 J1 H1 45MIN 5B TYPE C
2H-107 IT CLOSET 3' - 0" 7' - 0" 1 3/4" F SCWD HM HM-1 J1 H1 TYPE C
2H-108 WELLNESS ROOM 3' - 0" 7' - 0" 1 3/4" F SCWD HM HM-1 J1 H1 2C TYPE C
& E
2H-109 STAFF TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM HM-1 J1 H1 2 TYPE B
2H-111 TOUCHDOWN 3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3E TYPE C
2H-112 ANESTHESIA
ADMIN.
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 S1 3E TYPE C S1 FOR CLERESTORY WINDOWS
2H-113 ANESTHESIA
OFFICE
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3G TYPE C
2H-114 ANESTHESIA
OFFICE
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3G TYPE C
2H-115 ANESTHESIA
ADMIN.
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3E TYPE C
2H-116 ANESTHESIA
OFFICE
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3G TYPE C
2H-117 ANESTHESIA
OFFICE
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3G TYPE C
2H-118 ANESTHESIA
OFFICE
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3G TYPE C
2H-119 ANESTHESIA
OFFICE
3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 S1 3G TYPE C S1 FOR CLERESTORY WINDOWS
2H-120 TOUCHDOWN 3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3E TYPE C
2H-121 TOUCHDOWN 3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3E TYPE C
2H-122 RESIDENTS 3' - 0" 7' - 0" 1 3/4" FG SCWD HM HM-1 J1 H1 3E TYPE C
2H-141B STORAGE 3' - 0" 7' - 0" 1 3/4" FR SCWD HM HM-1 J1 H1 45MIN 5B TYPE C
2K-140A NEW 2-PERSON
ENGINEERING
OFFICE
3' - 0" 7' - 0" 1 3/4" F SCWD HM HM-1 J1 H1 3G TYPE C
2K-140C VESTIBULE 4' - 0" 7' - 0" - J2 H2 - - - - CASED OPENING
C2H-4 CORRIDOR 6' - 0" 7' - 0" 1 3/4" CORR SCWD-PLAM HM HM-1 J1 H1 90MIN SH-3 TYPE C & E
PL-2 ON DOOR, NOTES 2, 3, 4
C2H-5 CORRIDOR 6' - 0" 7' - 0" 1 3/4" CORR SCWD-PLAM HM HM-1 J1 H1 45MIN SH-3 TYPE C & E
PL-2 ON DOOR, NOTES 2, 3, 4
C2H-6 CORRIDOR 6' - 0" 7' - 0" 1 3/4" HM-1 J1 H1 90MIN SH-3 TYPE C
& E
PL-2 ON DOOR, NOTES 1, 2, 3, 4
C2H-7 CORRIDOR 6' - 0" 7' - 0" 1 3/4" CORR SCWD-PLAM HM HM-1 J1 H1 90MIN SH-3 TYPE C & E
PL-2 ON DOOR, NOTES 2, 3, 4
DOOR SCHEDULEHEAD, JAMB & SILL DETAILS
J1 - DOOR JAMB DETAIL H1 - DOOR HEAD DETAIL S1 - CLERESTORY WINDOW SILL DETAIL
H2 - DOOR HEAD DETAILJ2 - DOOR JAMB DETAIL
CORR SCWD-PLAM HM
UNDERSIDE OF STRUCTURE
CEILING
5/8" GYPSUM BOARD ON
EACH SIDE
FLOOR AS SCHEDULED
3 5/8" METAL STUD
1"
DEFLECTION TRACK AT
TOP OF WALL
A1
STC 49
UNDERSIDE OF
STRUCTURE
CEILING
5/8" GYPSUM BOARD
ON 3 5/8" METAL
STUDS
FLOOR AS
SCHEDULED
6"
C1
UNDERSIDE OF
STRUCTURE
CEILING
TWO LAYERS OF 5/8"
GYPSUM BOARD ON EACH
SIDE OF METAL STUDS
FLOOR AS SCHEDULED
3 1/2" BATT INSULATION
1"
FIRE RATED DEFLECTION
TRACK AT TOP OF WALL
5/8" GYPSUM WALL BOARD
3 5/8" METAL STUD
SECURE TO FLOOR AND
SEAL WITH 1HR RATED
FIRESTOP SEALANT
SEAL ALL PENETRATIONS
(PIPES, DUCTS, CONDUITS,
ETC) WITH 1 HR RATED
FIRESTOP SEALANT
R1
UL U465
(1HR RATING)
WALL TYPE NOTES
1. WALL TYPE ADJACENT TO OPENING IN WALL SHALL BE WALL TYPE OVER AND BELOW
OPENING UNLESS OTHERWISE NOTED.
2. WALL TYPES ARE GRAPHIC REPRESENTATIONS OF WALL COMPONENTS ONLY AND ARE
NOT TO SCALE.
3. CONTRACTOR MAY SUBMIT A SUBSTITUTE DEFLECTION TRACK FOR REVIEW AND
ACCEPTENCE BY ARCHITECT.
4. A1 WALL TYPE AT CORRIDOR WALLS SHALL BE SMOKE RESISTIVE. SEAL WALL AT TOP AND
BOTTOM AND AT ALL PENETRATIONS TO RESIST THE PASSAGE OF SMOKE. PROVIDE
SMOKE SEALS AT ALL CORRIDOR DOORS.
5. WALLS INDICATED TO EXTEND TO STRUCTURE OR DECK ABOVE SHALL EXTEND TO
UNDERSIDE OF INTERSTITIAL SPACE FLOOR STURCTURE.
6. PROVIDE BACKER BOARD BELOW TILE ON ALL WET / PLUMBING WALLS. REFER TO
SPECIFICATIONS FOR MORE REQUIREMENTS.
SW1
UL U415
(1HR RATED)
CEILING
5/8" GYPSUM BOARD
FLOOR AS SCHEDULED
2 1/2" CH METAL STUD
1" GYPSUM LINER PANEL
J RUNNERS ALONG THE
BASE AND HEAD OF THE
WALL, VERTICALLY ALONG
BOTH ENDS OF WALLS
J RUNNERS
EXISTING WALL
UNDERSIDE OF STRUCTURE
CEILING
5/8" GYPSUM BOARD ON
3 5/8" METAL STUDS
FLOOR AS…
This is the start of the file's text. The full file is on GovTribe.