RVA1033004_Plumbing-revised.pdf

PDF 1 MB Posted

Attached to
Y1DA--Renovate Old Dialysis 2H Richmond VA Medical Center
Solicitation number
36C24623B0024
Issued by

About this file

This package includes construction drawings and specifications for a plumbing renovation project at the Richmond VA Medical Center. The project involves demolishing existing plumbing fixtures and piping in an old dialysis area and installing new sanitary, vent, water, and medical gas systems to serve renovated office spaces. Drawings show demolition plans, new work layouts, riser diagrams, schedules, notes and details. Renovations will update plumbing for a meeting room, offices, corridors and support spaces. The project is identified as solicitation number 36C24623B0024 and involves renovating area 2H. The contract will be awarded by the Department of Veterans Affairs Veterans Health Administration VISN 6. Completion is required by the prime contractor and any subcontractors must adhere to all local, state and federal codes and regulations.

View the file

Other files

File Type Posted
BID OPENING Abstract 36C24623B0024.pdf PDF
BID OPENING Attendance Log 36C24623B0024.pdf PDF
SITE VISIT Attendance Log 36C24623B0024.pdf PDF
36C24623B0024 0006.docx DOCX document
36C24623B0024 0005.docx DOCX document
36C24623B0024 0004.docx DOCX document
36C24623B0024 0003.docx DOCX document
36C24623B0024 0002.docx DOCX document
36C24623B0024 0001.docx DOCX document
Attachment A - Itemized Schedule of Values Cost Breakdown.xlsx XLSX spreadsheet
INSTRUCTIONS TO BIDDERS.pdf PDF
36C24623B0024_1.docx DOCX document
RVA1033004_Life Safety Set.pdf PDF
RVA1033004_Architecture.pdf PDF
RVA1033004_Electrical.pdf PDF
RVA1033004_Telecom Set.pdf PDF
Specifications Vol 1.pdf PDF
Specifications Vol 2.pdf PDF
RVA1033004_Mechanical.pdf PDF
RVA1033.004_PL_Addendum_1_2023-03-24.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING LEGEND

DIRECTION OF FLOW

PIPE TURNED DOWN

PIPE TURNED UP

RISE OR DROP

BRANCH BOTTOM CONNECTION

TEE OUTLET UP

TEE OUTLET DOWN

CAP ON END OF PIPE

SANITARY WASTE

VENT PIPING

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER SUPPLY PIPING

THERMOMETER

TEMPERATURE & PRESSURE RELIEF VALVE

FLOW MEASURING / BALANCING / SHUT-

OFF VALVE

BALL VALVE

CHECK VALVE

GATE VALVE

STRAINER

UNION

HOSE BIBB

FLOOR DRAIN

PLUMBING ABBREVIATIONSPLUMBING GENERAL NOTES

1. PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF INTERNATIONAL PLUMBING CODE AND

INTERNATIONAL FUEL GAS CODE.

2. SLOPES AND INVERT ELEVATIONS SHALL BE ESTABLISHED BEFORE ANY PIPE IS INSTALLED IN ORDER TO MAINTAIN PROPER SLOPES. ANY DISCREPANCIES SHALL BE REPORTED TO CONTRACTING OFFICER'S REPRESENTATIVE. ALL PIPING SHALL BE

LOCATED AND DETERMINED WHEN TO BE INSTALLED TO AVOID CONFLICT WITH OTHER TRADES.

3. PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED.

4. KEEP ALL BURIED PIPING CLEAR OF FOOTINGS. COORDINATE WITH STRUCTURAL.

5. ALL WALL CLEANOUTS SHALL BE PROVIDED WITH WALL COVERS AND MOUNTED IN UNOBTRUSIVE LOCATIONS WHILE MAINTAINING ACCESSIBILITY. ALL FLOOR CLEANOUTS SHOWN SHALL BE SET FLUSH WITH FLOOR AREAS OR FINISHED GRADE.

6. COORDINATE LOCATION OF PIPING AND DRAINS WITH ALL MECHANICAL AND ELECTRICAL EQUIPMENT. NO PIPING SHALL BE INSTALLED ABOVE ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT OR PANELS. COMPLY WITH ARCHITECTURAL PLANS FOR EXACT LOCATION OF PLUMBING FIXTURES, COMPLIANCE TO ADA CLEARANCES, AND FINISHES.

7. PROVIDE REQUIRED WATER, WASTE, AND VENT PIPING, FITTINGS, AND INSULATION, AND MAKE FINAL CONNECTIONS TO EQUIPMENT. THESE PLANS ARE SCHEMATIC AND DIAGRAMMATIC ONLY. THEY DO NOT SHOW ALL REQUIRED BENDS, OFFSETS, VALVES, AND MISCELLANEOUS FITTINGS FOR A COMPLETE INSTALLATION. ALL PIPING, EQUIPMENT, AND CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH SPECIFICATIONS, LOCAL CODES AND ORDINANCES, AND MANUFACTURER'S INSTRUCTIONS.

8. WASTE PIPING SHALL BE INSTALLED TO PROVIDE A MINIMUM SLOPE OF 1%. WASTE PIPING 3" AND SMALLER SHALL BE INSTALLED

TO PROVIDE A MINIMUM SLOPE OF 2%.

9. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURE DRAWINGS FOR EXACT DIMENSIONS, FIXTURE LOCATIONS, ROOM NAMES, AND NUMBERS.

10. PROVIDE EXTENSION OF EQUIPMENT DRAINS TO FLOOR DRAINS, FLOOR SINKS, AND OPEN SITE DRAINS.

11. WHERE POSSIBLE, INSTALL SHUT-OFF VALVES AND EQUIPMENT REQUIRING MAINTENANCE, CLEANING AND ADJUSTMENT ABOVE ACCESSIBLE CEILINGS OR IN SERVICE AREAS SUCH AS JANITOR'S CLOSETS. IN OTHER LOCATIONS, PROVIDE ACCESS PANELS IN

INCONSPICUOUS LOCATIONS WITH FINISH TO MATCH ARCHITECTURAL.

12. ALL HOSE BIBBS, WALL HYDRANTS, AND VALVES WITH THREADED HOSE CONNECTIONS SHALL BE EQUIPPED WITH VACUUM

BREAKER.

13. WHERE CONNECTING TO A UTILITY OR SERVICE, VERIFY LOCATION, SIZES, MATERIALS, FLUID BEING HANDLED, AND INVERTS OF ALL EXISTING UTILITIES AND CONFIRM THAT NEW PIPES BEING ROUTED TO EXISTING UTILITIES CAN BE INSTALLED CONFORMING TO CODE AND AS SHOWN. NOTIFY [CONTRACTING OFFICER] [GENERAL CONTRACTOR] [ARCHITECT] OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO PURCHASING ANY MATERIALS OR PERFORMING ANY WORK OR EXTENSION OF CONNECTION, WITH THE EXCEPTION OF EXCAVATION OR OTHER WORK TO PROVIDE ACCESS TO THE CONCEALED UTILITY.

14. PROVIDE INSULATION, PIPE IDENTIFICATION, AND OTHER REQUIREMENTS AS LISTED IN SPECIFICATIONS.

15. ALL PIPING ABOVE GRADE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR

BE SUPPORTED FROM CEILING TILES.

16. WATER PIPING ROUTED ABOVE CEILINGS AND IN EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE (UNDERSIDE) OF CEILING

INSULATION AND HEATED SIDE (INSIDE) OF WALL INSULATION.

17. TOPS OF ALL FLOOR DRAINS AND CLEANOUTS SHALL BE SET FLUSH WITH FINISHED FLOOR, UNLESS NOTED OTHERWISE.

18. LOCATE ALL SECTIONAL OR MAIN CONTROL VALVES WITHIN 1'-0" FROM ACCESS PANELS, CEILING TILES, OR OTHER POINT OF

ACCESS.

19. PROVIDE WATER HAMMER ARRESTORS SIZED PER PLUMBING DRAINAGE INSTITUTE SPECIFICATIONS ON ALL DOMESTIC WATER LINES SERVING FLUSH VALVE FIXTURES, WASHING MACHINES SUPPLIES, PRV STATIONS, AND OTHER INSTALLATIONS WITH

QUICK CLOSING VALVES.

20. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING SYSTEMS CROSSING

BUILDING EXPANSION JOINTS.

21. COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL PLUMBING EQUIPMENT WITH THE ELECTRICAL DRAWINGS AND THE ELECTRICAL CONTRACTOR, AND FURNISH EQUIPMENT WIRED FOR THE VOLTAGES SHOWN THEREIN.

22. ALL PLUMBING EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE YEAR AFTER OWNER'S FINAL

ACCEPTANCE.

23. ALL PIPE PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE ASSEMBLY TO ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY 3M COMPANY, CP25 CAULK, CS195 COMPOSITE PANEL, FS195 WRAP/STRIP, OR PSS 7900 SERIES SYSTEMS AS RECOMMENDED BY MANUFACTURER FOR PARTICULAR APPLICATION, OR EQUIVALENT SYSTEM AS APPROVED BY LOCAL CODE OFFICIALS.

24. ALL WATER CLOSET FLUSH VALVE LEVERS SHALL BE LOCATED ON THE APPROACH SIDE OF THE WATER CLOSET.

25. ALL GAS REGULATORS REQUIRING VENTS SHALL BE VENTED TO THE EXTERIOR PER THE INTERNATIONAL GAS CODE REQUIREMENTS. VENT TERMINALS SHALL BE A MINIMUM OF 10'-0" FROM ANY AIR INTAKE OR SOURCE OF IGNITION.

26. ALL VENTS THROUGH ROOF SHALL BE LOCATED A MINIMUM OF 10'-0" FROM ANY OUTSIDE AIR INTAKE.

27. ALL COLD WATER, HOT WATER, AND DRAIN PIPING AT HANDICAPPED FIXTURES SHALL BE INSULATED WITH HANDI-LAV GUARD

MODELS 102 AND 105 (OR APPROVED EQUAL) INSULATION KITS.

28. NOT ALL PLUMBING ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

TRAP PRIMER

FLOOR CLEANOUT

WALL CLEANOUT

WATER HAMMER ARRESTOR

PLAN ELEV

TP

FCOFCO

WCO WCO

BRANCH TOP CONNECTION

DOMESTIC HOT WATER RETURN PIPING

S

W

SANITARY RISER DIAGRAM DESIGNATION

RISER DIAGRAM NUMBER

DOMESTIC WATER RISER DIAGRAM DESIGNATION

RISER DIAGRAM NUMBER

A/C ABOVE CEILING

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ARCH ARCHITECTURE, ARCHITECTURAL

BFP BACKFLOW PREVENTER

B/F BELOW FLOOR

B/G BELOW GRADE

BLDG BUILDING

BV BALL VALVE

CA COMPRESSED AIR

CD CONDENSATE DRAIN

CONT. CONTINUATION

CO CLEANOUT

CV CHECK VALVE

CONTR CONTRACTOR

CW COLD WATER (POTABLE / DOMESTIC)

DEG. DEGREES

DF DRINKING FOUNTAIN

DHWR DOMESTIC HOT WATER RETURN

DN DOWN

DSN DOWNSPOUT NOZZLE

DWGS DRAWINGS

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EMEW EMERGENCY EYEWASH

EMSH EMERGENCY SHOWER

ESEW EMERGENCY SHOWER / EYEWASH

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

GC GENERAL CONTRACTOR

GPF GALLONS PER FLUSH

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GV GATE VALVE

GWH GAS WATER HEATER

HB HOSE BIBB

H/C HANDICAP

HW HOT WATER (POTABLE / DOMESTIC)

I.E. INVERT ELEVATION

IBC INTERNATIONAL BUILDING CODE

IFGC INTERNATIONAL FUEL GAS CODE

IMB ICE MAKER BOX

IPC INTERNATIONAL PLUMBING CODE

IW INDIRECT WASTE

KW KILOWATT

L LAUNDRY

LP LIQUID PETROLEUM

LV LAVATORY

MFG MANUFACTURER

MS MOP SINK

NFWH NON-FREEZE WALL HYDRANT

NG NATURAL GAS

NIC NOT IN CONTRACT

ORD OVERFLOW ROOF DRAIN

P, PLBG PLUMBING

PDI PLUMBING DRAINAGE INSTITUTE

PSI POUNDS PER SQUARE INCH

RD ROOF DRAIN

RL RAIN LEADER

RPZ REDUCED PRESSURE ZONE

SAN, S SANITARY PIPING

SANS SANITARY SEWER

SH SHOWER

SK SINK

SOV SHUT-OFF VALVE

STR STRAINER

SS STAINLESS STEEL

TMV THERMOSTATIC MIXING VALVE

T&P TEMPERATURE AND PRESSURE RELIEF VALVE

TP TRAP PRIMER

TYP TYPICAL

UR URINAL

U/G UNDERGROUND

U/SAN UNDERGROUND SANITARY

V VENT PIPING

VTR VENT THROUGH ROOF

W WASTE PIPING

WB CLOTHES WASHER OUTLET BOX

WC WATER CLOSET

WCO WALL CLEANOUT

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

W/O WITHOUT

W/ WITH

YCO YARD CLEANOUT

DEMOLISHED

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

MEDICAL VACUUM

MEDICAL AIR

MV

MA

OXYGENO

LAB VACUUMLV

LAB AIRLA

AIR TRAP VENT PIPING

SHEET NAMING CONVENTION

P-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DISCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS

P-001

-2

P -0

/3

/2

.p d f

NOTES:

1. EXISTING EQUIPMENT IS SHOWN WITH THIN LINEWORK.

2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK,

DASHED, AND HATCHED.

3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD

LINEWORK.

4. BELOW IS AN EXAMPLE OF EACH:

EXISTING EQUIPMENT

EQUIPMENT TO BE DEMOLISHED

NEW OR RELOCATED EQUIPMENT

17 18 19 20

W

X

Y

Z

AA

4" S

3" V

2" ATV2" ATV2" ATV

1 1

V

V

V

V

V

4" S4" S4" S 4" S 4" S

1 1/2" V1 1/2" V

3" V

V

2" ATV

3" V

1 1/2" V

1 1 1

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

LEVEL 1 SANITARY AND VENT

DEMOLITION PLAN

PD101A

-2

P D

A

/3

/2

.p d f

SHEET NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

2. EXISTING FIXTURES AND PIPING SHOWN ARE APPROXIMATE.

CONTRACTOR TO FIELD VERIFY AND COORDINATE FOR EXACT

LOCATIONS AND SIZES.

3. CONTRACTOR TO ENSURE NO DEADLEGS ARE LEFT IN ANY

PIPING WITHIN THE AREA OF WORK.

4. PIPING AS SHOWN ON PLAN ARE SHOWN AS HIGHLIGHTED /

BOLDED ARE TO BE DEMOLISHED. ALL PIPING THAT IS NOT

TERMINATING IN THE SCOPE OF WORK AREA FOR THIS

PROJECT SHALL BE REMOVED. CONTRACTOR SHALL FOLLOW

ALL LOCAL, STATE, & FEDERAL CODES WITH APPROPRIATE

SAFETY REQUIREMENTS.

5. PIPING AS SHOWN ON THIS PLAN AS NOT HIGHLIGHTED /

BOLDED SHALL BE REUSED IN THIS SCOPE OF WORK FOR USE

AS SHOWN ON P-101A, AS PHASING PERMITS. ALL PIPING THAT

IS RUNNING THROUGH THROUGH THIS SCOPE OF WORK AREA

THAT CONTINUES ELSEWHERE SHALL NOT BE MODIFIED OR

AFFECTED IN ANY PHASE OF CONSTRUCTION.

SCALE: 3/16" = 1'-0"A13

LEVEL 1 WASTE AND VENT DEMOLITION PLAN

1 KEY NOTES:

1. REMOVE EXISTING FIXTURE AND ASSOCIATED PIPING. REMOVE

EXISTING SANITARY AND VENT PIPES FROM FIXTURES TO MAIN

AND CAP AS SHOWN ON PLAN, AS PHASING PERMITS.

2. EXISTING AIR TRAP VENT (ATV) PIPING THAT CONTINUES

THROUGH SCOPE OF WORK AREA.

3. EXISTING SANITARY PIPING THAT CONTINUES THROUGH

SCOPE OF WORK AREA TO REMAIN.

DEMO PLAN LEGEND

EXISTING SANITARY VENT

DEMO SANITARY VENT

EXISTING SANITARY

DEMO SANITARY

X

Y

Z

AA

33 3

1 3

3" CW 2 1/2" CW 2" CW

2" HW 2" HW 1 1/2" HW 3/4" HW

3/4" DHWR 3/4" DHWR 1/2" DHWR

/2

/2

/2

/2

/2

/2

/2

/2

/2

/2

D

H W

R

H W

C W

31 31

CONTRACTOR TO VERIFY

ACTUAL LOCATION OF

WATER LINES DROPPING

INTO INDICATED AREA

CONTRACTOR TO VERIFY

ACTUAL LOCATION OF

WATER LINES DROPPING

INTO INDICATED AREA

WATER TREATMENT

(2H-131)5

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

LEVEL 1 WATER DEMOLITION PLAN

PD101B

-2

P D

B

/3

/2

.p d f

SCALE: 3/16" = 1'-0"A13

LEVEL 1 WATER DEMOLITION PLAN

SHEET NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

2. EXISTING FIXTURES AND PIPING SHOWN ARE APPROXIMATE.

CONTRACTOR TO FIELD VERIFY AND COORDINATE FOR EXACT

LOCATIONS AND SIZES.

3. CONTRACTOR TO ENSURE NO DEADLEGS ARE LEFT IN ANY

PIPING WITHIN THE AREA OF WORK.

4. PIPING AS SHOWN ON PLAN ARE SHOWN AS HIGHLIGHTED /

BOLDED ARE TO BE DEMOLISHED. ALL PIPING THAT IS NOT

TERMINATING IN THE SCOPE OF WORK AREA FOR THIS PROJECT

SHALL BE REMOVED. CONTRACTOR SHALL FOLLOW ALL LOCAL,

STATE, & FEDERAL CODES AND SAFETY REQUIREMENTS.

5. PIPING AS SHOWN ON THIS PLAN AS NOT HIGHLIGHTED / BOLDED

SHALL BE REUSED IN THIS SCOPE OF WORK FOR USE AS SHOWN

ON P-101A, AS PHASING PERMITS. ALL PIPING THAT IS RUNNING

THROUGH THIS SCOPE OF WORK AREA THAT CONTINUES

ELSEWHERE SHALL NOT BE MODIFIED OR AFFECTED IN ANY

PHASE OF CONSTRUCTION.

1 KEY NOTES:

1. REMOVE EXISTING COLD WATER AND HOT WATER PIPES FROM

FIXTURES TO MAIN PIPE. SHOWN AS HIGHLIGHTED / BOLDED.

2. REMOVE EXISTING HOT WATER RETURN PIPE AS SHOWN TO

MAIN AND CAP.

3. REMOVE EXISTING PLUMBING FIXTURES AS SHOWN

APPROXIMATELY ON PLAN AS PHASING PERMITS.

4. CONTRACTOR SHALL NOT DEMO PORTION OF WATER PIPING

MAINS THAT CONTINUE THROUGH PROJECT SCOPE OF WORK.

APPROXIMATE PORTIONS OF EXISTING TO REMAIN PORTIONS

OF PIPING ARE SHOWN.

5. DEMO ALL EQUIPMENT, STORAGE TANKS, AND ASSOCIATED

EQUIPMENT RELATING TO WATER TREATMENT IN WATER

TREATMENT ROOM.

WATER DEMO PLAN LEGEND

EXISTING DOMESTIC COLD WATER

DEMO DOMESTIC COLD WATER

EXISTING DOMESTIC HOT WATER

DEMO DOMESTIC HOT WATER

EXISTING DOMESTIC RECIRCULATING

DEMO DOMESTIC RECIRCULATING

16 17 18 19 20

X

Y

Z

AA

1 1/2" MV

1" MA

1" O

3/4" NG

1"

1" 1 1/4"

1 1/4" 1" 1"

CUT AND CAP MED GAS LINES AT THIS APPROXIMATE

LOCATION. ALL PIPING DOWNSTREAM TO BE

REMOVED AND EXISTING SYSTEMS SHALL BE RE-

CERTIFIED PER SPECIFICATIONS. ADD GAS VALVE

WHERE MED GAS LINES ARE CUT. (TYP)

CONTRACTOR TO VERIFY ACTUAL

TERMINATION LOCATION OF MEDICAL

GAS PIPING. 36" GAS STORAGE TANK

IS ON WALL LOCATED PLAN NORTH

ALONG GRID ROW 'W'.

1 1/4"

1"

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

LEVEL 1 MEDICAL GAS DEMOLITION

PLAN

PD101C

-2

P D

C

/3

/2

.p d f

SCALE: 3/16" = 1'-0"A13

LEVEL 1 MEDICAL GAS DEMOLITION PLAN

SHEET NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

2. EXISTING EQUIPMENT AND PIPING SHOWN ARE APPROXIMATE.

CONTRACTOR TO FIELD VERIFY AND COORDINATE FOR EXACT

LOCATIONS AND SIZES. CONTRACTOR TO ALSO FIELD VERIFY

PORTIONS OF MEDICAL GAS MAIN PIPING THAT CONTINUE

THROUGH THIS SCOPE OF WORK. CONTRACTOR TO BE

CAREFUL AS TO NOT DISTURB, DAMAGED, OR AFFECT PIPING

NEGATIVELY.

3. CONTRACTOR TO ENSURE NO DEADLEGS ARE LEFT IN ANY

PIPING WITHIN THE AREA OF WORK. CONTRACTOR TO REMOVE

ALL RESPECTIVE PIPING AND CAP AT NEAREST UPSTREAM

SEGMENT AS PHASING PERMITS. CONTRACTOR TO FOLLOW

ALL LOCAL, STATE, & FEDERAL CODES WITH APPROPRIATE

SAFELY PRACTICES DURING DEMOLITION PHASE AND DISPOSE

OF MEDICAL GAS AND NATURAL GAS AS REQUIRED BY LAW.

4. ALL MEDICAL GAS PIPING THAT TERMINATES AT A DEVICE OR

FIXTURE IN THE SCOPE OF WORK SHALL BE DEMOLISHED.

5. CONTRACTOR SHALL VERIFY EXISTING LOCATION OF MEDICAL

GAS CONTROLLER FOR MEDICAL GAS LINE WITHIN SCOPE OF

WORK. IF EXISTING CONTROLLER LOCATION IS BEING

DEMOLISHED OR CONTROLLER IS REQUIRED TO BE

RELOCATED, CONTRACTOR SHALL INFORM CLIENT AND

CONSULTING ENGINEERS PRIOR TO BIDDING.

X KEY NOTES:

1. DISCONNECT AND REMOVE EXISTING MEDICAL GAS

EQUIPMENT. REMOVE ASSOCIATED MEDICAL GAS PIPING TO

MAIN AS SHOWN.

2. DISCONNECT AND REMOVE EXISTING MEDICAL GAS CONTROL

VALVES. REMOVE ASSOCIATED MEDICAL GAS PIPING TO MAIN

AS SHOWN.

X

Y

Z

AA

4" S

3" V

2" ATV2" ATV

BREAK/MEETING

ROOM

2H-104

CLOSET

2H-123

TOUCHDOWN

2H-103

TOUCHDOWN

2H-120

ANESTHESIA

2-PERSON

OFFICE

2H-115

ANESTHESIA

OFFICE

2H-114

TOUCHDOWN

2H-121

STORAGE

2H-105

ELEC. CLOSET

2H-106

IT CLOSET

2H-107

RESIDENTS

2H-122

NEW 2-PERSON

ENGINEERING

OFFICE

2K-140A

NEW

ENGINEERING

OFFICE

2H-140B

TOUCHDOWN

2H-111

ANESTHESIA

OFFICE

2H-118

ANESTHESIA

OFFICE

2H-119

STAFF LOCKER

2H-110

CORRIDOR

C2H-6

CORRIDOR

C2H-7

CORRIDOR

C2H-5

CORRIDOR

C2H-4

ANESTHESIA

ADMIN.

2H-112

WELLNESS ROOM

2H-108

STAFF TOILET

2H-109

ANESTHESIA

OFFICE

2H-116

ANESTHESIA

OFFICE

2H-117

VESTIBULE

2K-140C

V

V

V

V

3" V

4" S

2 1/2" V

2" S

2" S

2" V

2" V

4" S 4" S

S

2" V

2" S

2" V 2" S

ANESTHESIA

OFFICE

2H-113

4" S

2" S

P-528

P-528

P-418

P-604

P-103

CLEANOUT

2" V

WCO

FCO

P-604

P-604

ALL ABOVE FLOOR HORIZONTAL PIPING

RUNS SHALL BE RUN IN INTERSTITIAL

SPACE BETWEEN FIRST AND SECOND

FLOOR UNLESS OTHERWISE NOTED.

CONTRACTOR TO VERIFY EXACT

ELEVATIONS. (TYP)

S

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

ADDENDUM #1 2023-03-24

03/24/2023

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

LEVEL 1 WASTE AND VENT NEW

WORK

P-101A

-2

P -1

A

/3

/2

.p d f

SCALE: 3/16" = 1'-0"A13

LEVEL 1 WASTE AND VENT NEW WORK

SHEET NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

2. CONTRACTOR TO FIELD VERIFY EXISTING PIPE SIZES THAT

WILL HAVE NEW PIPING INSTALLED AND REPORT ALL FIELD

DISCREPANCIES PRIOR TO BID.

1 KEY NOTES:

1. CONTRACTOR TO CONNECT NEW PIPING TO EXISITNG VENT

LINE AS SHOWN ON PLAN. CONTRACTOR TO VERIFY SIZE OF

EXISTING VENT LINE PRIOR TO BID.

2. CONTRACTOR TO INSTALL NEW PIPING AT APPROXIMATE

LOCATION OF EXISTING SANITARY OR VENT PIPE.

X

Y

Z

AA

3" CW 2 1/2" CW 2" CW 2" CW

2" HW 2" HW 3/4" HW

3/4" DHWR 3/4" DHWR 1/2" DHWR

BREAK/MEETING

ROOM

2H-104

CLOSET

2H-123

TOUCHDOWN

2H-103

TOUCHDOWN

2H-120

ANESTHESIA

2-PERSON

OFFICE

2H-115

TOUCHDOWN

2H-121

STORAGE

2H-105

ELEC. CLOSET

2H-106

IT CLOSET

2H-107

RESIDENTS

2H-122

TOUCHDOWN

2H-111

ANESTHESIA

OFFICE

2H-118

ANESTHESIA

OFFICE

2H-119

STAFF LOCKER

2H-110

CORRIDOR

C2H-6

CORRIDOR

C2H-7

CORRIDOR

C2H-5

CORRIDOR

C2H-4

ANESTHESIA

ADMIN.

2H-112

WELLNESS ROOM

2H-108

STAFF TOILET

2H-109

ANESTHESIA

OFFICE

2H-116

/2

C

W

/2

H

W

1/2" HW

1/2" CW

/2

C

W

2" CW

3/4" HW

1/2" DHWR

H W

H W

1" CW

1/2" HW

1" CW

1/2" CW

1/2" HW

3/4" CW

1/2" CW

P-528

P-528

ANESTHESIA

OFFICE

2H-114

ANESTHESIA

OFFICE

2H-117

1/2" CW

1/2" CW

ANESTHESIA

OFFICE

2H-113

P-604

P-604

P-604

P-103

P-418

1/2"

BALANCING

2" SHUTOFF

3/4" SHUTOFF

1/2" CHECK

1/2" CW

1/2"

BALANCING

3/4" SHUTOFF

1/2" SHUTOFF

1/2" SHUTOFF

1/2" SHUTOFF

/2

D

H W

R

1/2" SHUTOFF

1/2" CW to TP-2.

EXTEND 1/2" LINE

TO 4" FD-C.

CONTRACTOR

TO REBALANCE

FLOW IN DHWR

PIPE TO 1 GPM.

3/4" CW

1/2" SHUTOFF

/2

S

H U

T O

F F

P-812

P-812

1/2" SHUTOFF

P-812

ALL ABOVE FLOOR HORIZONTAL PIPING

RUNS SHALL BE RUN IN INTERSTITIAL SPACE

BETWEEN FIRST AND SECOND FLOOR

UNLESS OTHERWISE NOTED. CONTRACTOR

TO VERIFY EXACT ELEVATIONS. (TYP)

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

ADDENDUM #1 2023-03-24

03/24/2023

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

LEVEL 1 WATER NEW WORK

P-101B

-2

P -1

B

/3

/2

.p d f

SHEET NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

2. CONTRACTOR TO FIELD VERIFY EXISTING PIPE SIZES THAT

WILL HAVE NEW PIPING INSTALLED AND REPORT ALL FIELD

DISCREPANCIES PRIOR TO BID.

SCALE: 3/16" = 1'-0"A13

LEVEL 1 WATER NEW WORK

1 KEY NOTES:

1. CONTRACTOR TO REUSE EXISTING PIPE SEGMENT FOR INDICATED

WATER CIRCUIT AND INSTALL NEW PIPING AS SHOWN.

2. CONTRACTOR TO DISCONNECT AND CAP HOT WATER RETURN

PIPING FROM PREVIOUS HOT WATER LINE AND RECONNECT TO

NEW HOT WATER PIPING AS PHASING PERMITS.

2" V

2" S

2" S

3" V

2" V

2 1/2" V

4" S

2" S

2" S

2" S

2" S

2" V

2" V

2" S 3" V

3" V

4" S

4" S

2" V

ALL ABOVE FLOOR HORIZONTAL PIPING

RUNS SHALL BE RUN IN INTERSTITIAL SPACE

BETWEEN FIRST AND SECOND FLOOR

UNLESS OTHERWISE NOTED. CONTRACTOR

TO VERIFY EXACT ELEVATIONS. (TYP)

2" V

INTERSTITIAL SPACE

BETWEEN FIRST AND SECOND

FLOOR IS APPROXIMATELY

BETWEEN 8'-0" AND 14'-0" AFF.

3/4" CW

3/4" CW

1/2" DHWR

1/2" HW

1/2" CW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" CW

2" CW

2" CW

3/4" HW

1/2" DHWR

2" CW

1/2" CW

1/2" HW

1/2" DHWR 1" CW

1/2" HW

1/2" CW

1" CW

1/2" CW

1/2" HW

1" CW

ALL ABOVE FLOOR HORIZONTAL PIPING

RUNS SHALL BE RUN IN INTERSTITIAL SPACE

BETWEEN FIRST AND SECOND FLOOR

UNLESS OTHERWISE NOTED. CONTRACTOR

TO VERIFY EXACT ELEVATIONS. (TYP)

INTERSTITIAL SPACE

BETWEEN FIRST AND SECOND

FLOOR IS APPROXIMATELY

BETWEEN 8'-0" AND 14'-0" AFF.

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

PLUMBING RISER DIAGRAMS

P-401

-2

P -4

/1

/2

.p d f

SCALE:F16

OVERALL WASTE AND VENT RISER DIAGRAM

SCALE:F9

OVERALL DOMESTIC WATER RISER DIAGRAM

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION

WASTE PIPE VENT PIPE WASTE

FIXTURE

UNITS

WATER

FIXTURE

UNITS

WRIST

BLADE

HANDLES

ELECTRIC

SENSOR

REMARKS

IN [mm] IN [mm]

P-103

WATER CLOSET,

WALL HUNG,

MANUAL FLUSH VALVE

4 [100] 2 [50] 1.25 [31] .5 [13] 4 4 N/A NO

P-418 LAVATORY 1.25 [31] 1.25 [31] .5 [13] .5 [13] 2 2 N/A YES (NOTE 1)

P-528 SINK 1.5 [38] 1.5 [38] .5 [13] .75 [19] 3 4 N/A NO

P-604

ELECTRIC WATER

COOLER

1.25 [31] 1/25 [31] .5 [13] 1 1 N/A NO

P-812 ICE MAKER BOX .5 [13] 5 N/A NO

COLD WATER

IN [mm]

HOT WATER

IN [mm]

BOD:

ELKAY BOTTLE

FOUNTAINS

BOD:

CHICAGO FAUCETS

NOTE 1: POWER TO BE PROVIDED BY BATTERY BACKUP

[4 m m

[8 m m

FINISHED

FLOOR

FINISHED

WALL

MANUAL HANDLE

SPLIT GRAB BAR

SEE ARCH. DWGS

WATER CLOSET

PLAN

ELEVATION

[450mm]

F O

R F

IX

T

U R

E H

E

IG

H T

S E

E A

R C

H

IT

E C

T U

R A

L D

R A

W

IN

G S

18"

WALL HUNG

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

ADDENDUM #1 2023-03-24

03/24/2023

652-20121

MBCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

PLUMBING SCHEDULES

P-601

-2

P -6

/3

/2

.p d f

SCALE: N.T.S.F16

PLUMBING SCHEDULE

SCALE: N.T.S.F6

WATER CLOSET DETAIL - MANUAL FLUSH

Sheets
P-001 - PLUMBING GENERAL NOTES, ABBREVIATIONS, AND LEGENDS
PD101A - LEVEL 1 SANITARY AND VENT DEMOLITION PLAN
PD101B - LEVEL 1 WATER DEMOLITION PLAN
PD101C - LEVEL 1 MEDICAL GAS DEMOLITION PLAN
P-101A - LEVEL 1 WASTE AND VENT NEW WORK
P-101B - LEVEL 1 WATER NEW WORK
P-401 - PLUMBING RISER DIAGRAMS
P-601 - PLUMBING SCHEDULES

File details come from the government source that posted it. Updated .