RVA1033004_Plumbing-revised.pdf
PDF 1 MB Posted
- Solicitation number
- 36C24623B0024
About this file
This package includes construction drawings and specifications for a plumbing renovation project at the Richmond VA Medical Center. The project involves demolishing existing plumbing fixtures and piping in an old dialysis area and installing new sanitary, vent, water, and medical gas systems to serve renovated office spaces. Drawings show demolition plans, new work layouts, riser diagrams, schedules, notes and details. Renovations will update plumbing for a meeting room, offices, corridors and support spaces. The project is identified as solicitation number 36C24623B0024 and involves renovating area 2H. The contract will be awarded by the Department of Veterans Affairs Veterans Health Administration VISN 6. Completion is required by the prime contractor and any subcontractors must adhere to all local, state and federal codes and regulations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BID OPENING Abstract 36C24623B0024.pdf | ||
| BID OPENING Attendance Log 36C24623B0024.pdf | ||
| SITE VISIT Attendance Log 36C24623B0024.pdf | ||
| 36C24623B0024 0006.docx | DOCX document | |
| 36C24623B0024 0005.docx | DOCX document | |
| 36C24623B0024 0004.docx | DOCX document | |
| 36C24623B0024 0003.docx | DOCX document | |
| 36C24623B0024 0002.docx | DOCX document | |
| 36C24623B0024 0001.docx | DOCX document | |
| Attachment A - Itemized Schedule of Values Cost Breakdown.xlsx | XLSX spreadsheet | |
| INSTRUCTIONS TO BIDDERS.pdf | ||
| 36C24623B0024_1.docx | DOCX document | |
| RVA1033004_Life Safety Set.pdf | ||
| RVA1033004_Architecture.pdf | ||
| RVA1033004_Electrical.pdf | ||
| RVA1033004_Telecom Set.pdf | ||
| Specifications Vol 1.pdf | ||
| Specifications Vol 2.pdf | ||
| RVA1033004_Mechanical.pdf | ||
| RVA1033.004_PL_Addendum_1_2023-03-24.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING LEGEND
DIRECTION OF FLOW
PIPE TURNED DOWN
PIPE TURNED UP
RISE OR DROP
BRANCH BOTTOM CONNECTION
TEE OUTLET UP
TEE OUTLET DOWN
CAP ON END OF PIPE
SANITARY WASTE
VENT PIPING
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER SUPPLY PIPING
THERMOMETER
TEMPERATURE & PRESSURE RELIEF VALVE
FLOW MEASURING / BALANCING / SHUT-
OFF VALVE
BALL VALVE
CHECK VALVE
GATE VALVE
STRAINER
UNION
HOSE BIBB
FLOOR DRAIN
PLUMBING ABBREVIATIONSPLUMBING GENERAL NOTES
1. PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF INTERNATIONAL PLUMBING CODE AND
INTERNATIONAL FUEL GAS CODE.
2. SLOPES AND INVERT ELEVATIONS SHALL BE ESTABLISHED BEFORE ANY PIPE IS INSTALLED IN ORDER TO MAINTAIN PROPER SLOPES. ANY DISCREPANCIES SHALL BE REPORTED TO CONTRACTING OFFICER'S REPRESENTATIVE. ALL PIPING SHALL BE
LOCATED AND DETERMINED WHEN TO BE INSTALLED TO AVOID CONFLICT WITH OTHER TRADES.
3. PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED.
4. KEEP ALL BURIED PIPING CLEAR OF FOOTINGS. COORDINATE WITH STRUCTURAL.
5. ALL WALL CLEANOUTS SHALL BE PROVIDED WITH WALL COVERS AND MOUNTED IN UNOBTRUSIVE LOCATIONS WHILE MAINTAINING ACCESSIBILITY. ALL FLOOR CLEANOUTS SHOWN SHALL BE SET FLUSH WITH FLOOR AREAS OR FINISHED GRADE.
6. COORDINATE LOCATION OF PIPING AND DRAINS WITH ALL MECHANICAL AND ELECTRICAL EQUIPMENT. NO PIPING SHALL BE INSTALLED ABOVE ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT OR PANELS. COMPLY WITH ARCHITECTURAL PLANS FOR EXACT LOCATION OF PLUMBING FIXTURES, COMPLIANCE TO ADA CLEARANCES, AND FINISHES.
7. PROVIDE REQUIRED WATER, WASTE, AND VENT PIPING, FITTINGS, AND INSULATION, AND MAKE FINAL CONNECTIONS TO EQUIPMENT. THESE PLANS ARE SCHEMATIC AND DIAGRAMMATIC ONLY. THEY DO NOT SHOW ALL REQUIRED BENDS, OFFSETS, VALVES, AND MISCELLANEOUS FITTINGS FOR A COMPLETE INSTALLATION. ALL PIPING, EQUIPMENT, AND CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH SPECIFICATIONS, LOCAL CODES AND ORDINANCES, AND MANUFACTURER'S INSTRUCTIONS.
8. WASTE PIPING SHALL BE INSTALLED TO PROVIDE A MINIMUM SLOPE OF 1%. WASTE PIPING 3" AND SMALLER SHALL BE INSTALLED
TO PROVIDE A MINIMUM SLOPE OF 2%.
9. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURE DRAWINGS FOR EXACT DIMENSIONS, FIXTURE LOCATIONS, ROOM NAMES, AND NUMBERS.
10. PROVIDE EXTENSION OF EQUIPMENT DRAINS TO FLOOR DRAINS, FLOOR SINKS, AND OPEN SITE DRAINS.
11. WHERE POSSIBLE, INSTALL SHUT-OFF VALVES AND EQUIPMENT REQUIRING MAINTENANCE, CLEANING AND ADJUSTMENT ABOVE ACCESSIBLE CEILINGS OR IN SERVICE AREAS SUCH AS JANITOR'S CLOSETS. IN OTHER LOCATIONS, PROVIDE ACCESS PANELS IN
INCONSPICUOUS LOCATIONS WITH FINISH TO MATCH ARCHITECTURAL.
12. ALL HOSE BIBBS, WALL HYDRANTS, AND VALVES WITH THREADED HOSE CONNECTIONS SHALL BE EQUIPPED WITH VACUUM
BREAKER.
13. WHERE CONNECTING TO A UTILITY OR SERVICE, VERIFY LOCATION, SIZES, MATERIALS, FLUID BEING HANDLED, AND INVERTS OF ALL EXISTING UTILITIES AND CONFIRM THAT NEW PIPES BEING ROUTED TO EXISTING UTILITIES CAN BE INSTALLED CONFORMING TO CODE AND AS SHOWN. NOTIFY [CONTRACTING OFFICER] [GENERAL CONTRACTOR] [ARCHITECT] OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO PURCHASING ANY MATERIALS OR PERFORMING ANY WORK OR EXTENSION OF CONNECTION, WITH THE EXCEPTION OF EXCAVATION OR OTHER WORK TO PROVIDE ACCESS TO THE CONCEALED UTILITY.
14. PROVIDE INSULATION, PIPE IDENTIFICATION, AND OTHER REQUIREMENTS AS LISTED IN SPECIFICATIONS.
15. ALL PIPING ABOVE GRADE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR
BE SUPPORTED FROM CEILING TILES.
16. WATER PIPING ROUTED ABOVE CEILINGS AND IN EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE (UNDERSIDE) OF CEILING
INSULATION AND HEATED SIDE (INSIDE) OF WALL INSULATION.
17. TOPS OF ALL FLOOR DRAINS AND CLEANOUTS SHALL BE SET FLUSH WITH FINISHED FLOOR, UNLESS NOTED OTHERWISE.
18. LOCATE ALL SECTIONAL OR MAIN CONTROL VALVES WITHIN 1'-0" FROM ACCESS PANELS, CEILING TILES, OR OTHER POINT OF
ACCESS.
19. PROVIDE WATER HAMMER ARRESTORS SIZED PER PLUMBING DRAINAGE INSTITUTE SPECIFICATIONS ON ALL DOMESTIC WATER LINES SERVING FLUSH VALVE FIXTURES, WASHING MACHINES SUPPLIES, PRV STATIONS, AND OTHER INSTALLATIONS WITH
QUICK CLOSING VALVES.
20. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING SYSTEMS CROSSING
BUILDING EXPANSION JOINTS.
21. COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL PLUMBING EQUIPMENT WITH THE ELECTRICAL DRAWINGS AND THE ELECTRICAL CONTRACTOR, AND FURNISH EQUIPMENT WIRED FOR THE VOLTAGES SHOWN THEREIN.
22. ALL PLUMBING EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE YEAR AFTER OWNER'S FINAL
ACCEPTANCE.
23. ALL PIPE PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE ASSEMBLY TO ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY 3M COMPANY, CP25 CAULK, CS195 COMPOSITE PANEL, FS195 WRAP/STRIP, OR PSS 7900 SERIES SYSTEMS AS RECOMMENDED BY MANUFACTURER FOR PARTICULAR APPLICATION, OR EQUIVALENT SYSTEM AS APPROVED BY LOCAL CODE OFFICIALS.
24. ALL WATER CLOSET FLUSH VALVE LEVERS SHALL BE LOCATED ON THE APPROACH SIDE OF THE WATER CLOSET.
25. ALL GAS REGULATORS REQUIRING VENTS SHALL BE VENTED TO THE EXTERIOR PER THE INTERNATIONAL GAS CODE REQUIREMENTS. VENT TERMINALS SHALL BE A MINIMUM OF 10'-0" FROM ANY AIR INTAKE OR SOURCE OF IGNITION.
26. ALL VENTS THROUGH ROOF SHALL BE LOCATED A MINIMUM OF 10'-0" FROM ANY OUTSIDE AIR INTAKE.
27. ALL COLD WATER, HOT WATER, AND DRAIN PIPING AT HANDICAPPED FIXTURES SHALL BE INSULATED WITH HANDI-LAV GUARD
MODELS 102 AND 105 (OR APPROVED EQUAL) INSULATION KITS.
28. NOT ALL PLUMBING ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
TRAP PRIMER
FLOOR CLEANOUT
WALL CLEANOUT
WATER HAMMER ARRESTOR
PLAN ELEV
TP
FCOFCO
WCO WCO
BRANCH TOP CONNECTION
DOMESTIC HOT WATER RETURN PIPING
S
W
SANITARY RISER DIAGRAM DESIGNATION
RISER DIAGRAM NUMBER
DOMESTIC WATER RISER DIAGRAM DESIGNATION
RISER DIAGRAM NUMBER
A/C ABOVE CEILING
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ARCH ARCHITECTURE, ARCHITECTURAL
BFP BACKFLOW PREVENTER
B/F BELOW FLOOR
B/G BELOW GRADE
BLDG BUILDING
BV BALL VALVE
CA COMPRESSED AIR
CD CONDENSATE DRAIN
CONT. CONTINUATION
CO CLEANOUT
CV CHECK VALVE
CONTR CONTRACTOR
CW COLD WATER (POTABLE / DOMESTIC)
DEG. DEGREES
DF DRINKING FOUNTAIN
DHWR DOMESTIC HOT WATER RETURN
DN DOWN
DSN DOWNSPOUT NOZZLE
DWGS DRAWINGS
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EMEW EMERGENCY EYEWASH
EMSH EMERGENCY SHOWER
ESEW EMERGENCY SHOWER / EYEWASH
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
GC GENERAL CONTRACTOR
GPF GALLONS PER FLUSH
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GATE VALVE
GWH GAS WATER HEATER
HB HOSE BIBB
H/C HANDICAP
HW HOT WATER (POTABLE / DOMESTIC)
I.E. INVERT ELEVATION
IBC INTERNATIONAL BUILDING CODE
IFGC INTERNATIONAL FUEL GAS CODE
IMB ICE MAKER BOX
IPC INTERNATIONAL PLUMBING CODE
IW INDIRECT WASTE
KW KILOWATT
L LAUNDRY
LP LIQUID PETROLEUM
LV LAVATORY
MFG MANUFACTURER
MS MOP SINK
NFWH NON-FREEZE WALL HYDRANT
NG NATURAL GAS
NIC NOT IN CONTRACT
ORD OVERFLOW ROOF DRAIN
P, PLBG PLUMBING
PDI PLUMBING DRAINAGE INSTITUTE
PSI POUNDS PER SQUARE INCH
RD ROOF DRAIN
RL RAIN LEADER
RPZ REDUCED PRESSURE ZONE
SAN, S SANITARY PIPING
SANS SANITARY SEWER
SH SHOWER
SK SINK
SOV SHUT-OFF VALVE
STR STRAINER
SS STAINLESS STEEL
TMV THERMOSTATIC MIXING VALVE
T&P TEMPERATURE AND PRESSURE RELIEF VALVE
TP TRAP PRIMER
TYP TYPICAL
UR URINAL
U/G UNDERGROUND
U/SAN UNDERGROUND SANITARY
V VENT PIPING
VTR VENT THROUGH ROOF
W WASTE PIPING
WB CLOTHES WASHER OUTLET BOX
WC WATER CLOSET
WCO WALL CLEANOUT
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
W/O WITHOUT
W/ WITH
YCO YARD CLEANOUT
DEMOLISHED
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
MEDICAL VACUUM
MEDICAL AIR
MV
MA
OXYGENO
LAB VACUUMLV
LAB AIRLA
AIR TRAP VENT PIPING
SHEET NAMING CONVENTION
P-001A
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS
P-001
-2
P -0
/3
/2
.p d f
NOTES:
1. EXISTING EQUIPMENT IS SHOWN WITH THIN LINEWORK.
2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK,
DASHED, AND HATCHED.
3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD
LINEWORK.
4. BELOW IS AN EXAMPLE OF EACH:
EXISTING EQUIPMENT
EQUIPMENT TO BE DEMOLISHED
NEW OR RELOCATED EQUIPMENT
17 18 19 20
W
X
Y
Z
AA
4" S
3" V
2" ATV2" ATV2" ATV
1 1
V
V
V
V
V
4" S4" S4" S 4" S 4" S
1 1/2" V1 1/2" V
3" V
V
2" ATV
3" V
1 1/2" V
1 1 1
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
LEVEL 1 SANITARY AND VENT
DEMOLITION PLAN
PD101A
-2
P D
A
/3
/2
.p d f
SHEET NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
2. EXISTING FIXTURES AND PIPING SHOWN ARE APPROXIMATE.
CONTRACTOR TO FIELD VERIFY AND COORDINATE FOR EXACT
LOCATIONS AND SIZES.
3. CONTRACTOR TO ENSURE NO DEADLEGS ARE LEFT IN ANY
PIPING WITHIN THE AREA OF WORK.
4. PIPING AS SHOWN ON PLAN ARE SHOWN AS HIGHLIGHTED /
BOLDED ARE TO BE DEMOLISHED. ALL PIPING THAT IS NOT
TERMINATING IN THE SCOPE OF WORK AREA FOR THIS
PROJECT SHALL BE REMOVED. CONTRACTOR SHALL FOLLOW
ALL LOCAL, STATE, & FEDERAL CODES WITH APPROPRIATE
SAFETY REQUIREMENTS.
5. PIPING AS SHOWN ON THIS PLAN AS NOT HIGHLIGHTED /
BOLDED SHALL BE REUSED IN THIS SCOPE OF WORK FOR USE
AS SHOWN ON P-101A, AS PHASING PERMITS. ALL PIPING THAT
IS RUNNING THROUGH THROUGH THIS SCOPE OF WORK AREA
THAT CONTINUES ELSEWHERE SHALL NOT BE MODIFIED OR
AFFECTED IN ANY PHASE OF CONSTRUCTION.
SCALE: 3/16" = 1'-0"A13
LEVEL 1 WASTE AND VENT DEMOLITION PLAN
1 KEY NOTES:
1. REMOVE EXISTING FIXTURE AND ASSOCIATED PIPING. REMOVE
EXISTING SANITARY AND VENT PIPES FROM FIXTURES TO MAIN
AND CAP AS SHOWN ON PLAN, AS PHASING PERMITS.
2. EXISTING AIR TRAP VENT (ATV) PIPING THAT CONTINUES
THROUGH SCOPE OF WORK AREA.
3. EXISTING SANITARY PIPING THAT CONTINUES THROUGH
SCOPE OF WORK AREA TO REMAIN.
DEMO PLAN LEGEND
EXISTING SANITARY VENT
DEMO SANITARY VENT
EXISTING SANITARY
DEMO SANITARY
X
Y
Z
AA
33 3
1 3
3" CW 2 1/2" CW 2" CW
2" HW 2" HW 1 1/2" HW 3/4" HW
3/4" DHWR 3/4" DHWR 1/2" DHWR
/2
/2
/2
/2
/2
/2
/2
/2
/2
/2
D
H W
R
H W
C W
31 31
CONTRACTOR TO VERIFY
ACTUAL LOCATION OF
WATER LINES DROPPING
INTO INDICATED AREA
CONTRACTOR TO VERIFY
ACTUAL LOCATION OF
WATER LINES DROPPING
INTO INDICATED AREA
WATER TREATMENT
(2H-131)5
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
LEVEL 1 WATER DEMOLITION PLAN
PD101B
-2
P D
B
/3
/2
.p d f
SCALE: 3/16" = 1'-0"A13
LEVEL 1 WATER DEMOLITION PLAN
SHEET NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
2. EXISTING FIXTURES AND PIPING SHOWN ARE APPROXIMATE.
CONTRACTOR TO FIELD VERIFY AND COORDINATE FOR EXACT
LOCATIONS AND SIZES.
3. CONTRACTOR TO ENSURE NO DEADLEGS ARE LEFT IN ANY
PIPING WITHIN THE AREA OF WORK.
4. PIPING AS SHOWN ON PLAN ARE SHOWN AS HIGHLIGHTED /
BOLDED ARE TO BE DEMOLISHED. ALL PIPING THAT IS NOT
TERMINATING IN THE SCOPE OF WORK AREA FOR THIS PROJECT
SHALL BE REMOVED. CONTRACTOR SHALL FOLLOW ALL LOCAL,
STATE, & FEDERAL CODES AND SAFETY REQUIREMENTS.
5. PIPING AS SHOWN ON THIS PLAN AS NOT HIGHLIGHTED / BOLDED
SHALL BE REUSED IN THIS SCOPE OF WORK FOR USE AS SHOWN
ON P-101A, AS PHASING PERMITS. ALL PIPING THAT IS RUNNING
THROUGH THIS SCOPE OF WORK AREA THAT CONTINUES
ELSEWHERE SHALL NOT BE MODIFIED OR AFFECTED IN ANY
PHASE OF CONSTRUCTION.
1 KEY NOTES:
1. REMOVE EXISTING COLD WATER AND HOT WATER PIPES FROM
FIXTURES TO MAIN PIPE. SHOWN AS HIGHLIGHTED / BOLDED.
2. REMOVE EXISTING HOT WATER RETURN PIPE AS SHOWN TO
MAIN AND CAP.
3. REMOVE EXISTING PLUMBING FIXTURES AS SHOWN
APPROXIMATELY ON PLAN AS PHASING PERMITS.
4. CONTRACTOR SHALL NOT DEMO PORTION OF WATER PIPING
MAINS THAT CONTINUE THROUGH PROJECT SCOPE OF WORK.
APPROXIMATE PORTIONS OF EXISTING TO REMAIN PORTIONS
OF PIPING ARE SHOWN.
5. DEMO ALL EQUIPMENT, STORAGE TANKS, AND ASSOCIATED
EQUIPMENT RELATING TO WATER TREATMENT IN WATER
TREATMENT ROOM.
WATER DEMO PLAN LEGEND
EXISTING DOMESTIC COLD WATER
DEMO DOMESTIC COLD WATER
EXISTING DOMESTIC HOT WATER
DEMO DOMESTIC HOT WATER
EXISTING DOMESTIC RECIRCULATING
DEMO DOMESTIC RECIRCULATING
16 17 18 19 20
X
Y
Z
AA
1 1/2" MV
1" MA
1" O
3/4" NG
1"
1" 1 1/4"
1 1/4" 1" 1"
CUT AND CAP MED GAS LINES AT THIS APPROXIMATE
LOCATION. ALL PIPING DOWNSTREAM TO BE
REMOVED AND EXISTING SYSTEMS SHALL BE RE-
CERTIFIED PER SPECIFICATIONS. ADD GAS VALVE
WHERE MED GAS LINES ARE CUT. (TYP)
CONTRACTOR TO VERIFY ACTUAL
TERMINATION LOCATION OF MEDICAL
GAS PIPING. 36" GAS STORAGE TANK
IS ON WALL LOCATED PLAN NORTH
ALONG GRID ROW 'W'.
1 1/4"
1"
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
LEVEL 1 MEDICAL GAS DEMOLITION
PLAN
PD101C
-2
P D
C
/3
/2
.p d f
SCALE: 3/16" = 1'-0"A13
LEVEL 1 MEDICAL GAS DEMOLITION PLAN
SHEET NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
2. EXISTING EQUIPMENT AND PIPING SHOWN ARE APPROXIMATE.
CONTRACTOR TO FIELD VERIFY AND COORDINATE FOR EXACT
LOCATIONS AND SIZES. CONTRACTOR TO ALSO FIELD VERIFY
PORTIONS OF MEDICAL GAS MAIN PIPING THAT CONTINUE
THROUGH THIS SCOPE OF WORK. CONTRACTOR TO BE
CAREFUL AS TO NOT DISTURB, DAMAGED, OR AFFECT PIPING
NEGATIVELY.
3. CONTRACTOR TO ENSURE NO DEADLEGS ARE LEFT IN ANY
PIPING WITHIN THE AREA OF WORK. CONTRACTOR TO REMOVE
ALL RESPECTIVE PIPING AND CAP AT NEAREST UPSTREAM
SEGMENT AS PHASING PERMITS. CONTRACTOR TO FOLLOW
ALL LOCAL, STATE, & FEDERAL CODES WITH APPROPRIATE
SAFELY PRACTICES DURING DEMOLITION PHASE AND DISPOSE
OF MEDICAL GAS AND NATURAL GAS AS REQUIRED BY LAW.
4. ALL MEDICAL GAS PIPING THAT TERMINATES AT A DEVICE OR
FIXTURE IN THE SCOPE OF WORK SHALL BE DEMOLISHED.
5. CONTRACTOR SHALL VERIFY EXISTING LOCATION OF MEDICAL
GAS CONTROLLER FOR MEDICAL GAS LINE WITHIN SCOPE OF
WORK. IF EXISTING CONTROLLER LOCATION IS BEING
DEMOLISHED OR CONTROLLER IS REQUIRED TO BE
RELOCATED, CONTRACTOR SHALL INFORM CLIENT AND
CONSULTING ENGINEERS PRIOR TO BIDDING.
X KEY NOTES:
1. DISCONNECT AND REMOVE EXISTING MEDICAL GAS
EQUIPMENT. REMOVE ASSOCIATED MEDICAL GAS PIPING TO
MAIN AS SHOWN.
2. DISCONNECT AND REMOVE EXISTING MEDICAL GAS CONTROL
VALVES. REMOVE ASSOCIATED MEDICAL GAS PIPING TO MAIN
AS SHOWN.
X
Y
Z
AA
4" S
3" V
2" ATV2" ATV
BREAK/MEETING
ROOM
2H-104
CLOSET
2H-123
TOUCHDOWN
2H-103
TOUCHDOWN
2H-120
ANESTHESIA
2-PERSON
OFFICE
2H-115
ANESTHESIA
OFFICE
2H-114
TOUCHDOWN
2H-121
STORAGE
2H-105
ELEC. CLOSET
2H-106
IT CLOSET
2H-107
RESIDENTS
2H-122
NEW 2-PERSON
ENGINEERING
OFFICE
2K-140A
NEW
ENGINEERING
OFFICE
2H-140B
TOUCHDOWN
2H-111
ANESTHESIA
OFFICE
2H-118
ANESTHESIA
OFFICE
2H-119
STAFF LOCKER
2H-110
CORRIDOR
C2H-6
CORRIDOR
C2H-7
CORRIDOR
C2H-5
CORRIDOR
C2H-4
ANESTHESIA
ADMIN.
2H-112
WELLNESS ROOM
2H-108
STAFF TOILET
2H-109
ANESTHESIA
OFFICE
2H-116
ANESTHESIA
OFFICE
2H-117
VESTIBULE
2K-140C
V
V
V
V
3" V
4" S
2 1/2" V
2" S
2" S
2" V
2" V
4" S 4" S
S
2" V
2" S
2" V 2" S
ANESTHESIA
OFFICE
2H-113
4" S
2" S
P-528
P-528
P-418
P-604
P-103
CLEANOUT
2" V
WCO
FCO
P-604
P-604
ALL ABOVE FLOOR HORIZONTAL PIPING
RUNS SHALL BE RUN IN INTERSTITIAL
SPACE BETWEEN FIRST AND SECOND
FLOOR UNLESS OTHERWISE NOTED.
CONTRACTOR TO VERIFY EXACT
ELEVATIONS. (TYP)
S
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
ADDENDUM #1 2023-03-24
03/24/2023
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
LEVEL 1 WASTE AND VENT NEW
WORK
P-101A
-2
P -1
A
/3
/2
.p d f
SCALE: 3/16" = 1'-0"A13
LEVEL 1 WASTE AND VENT NEW WORK
SHEET NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
2. CONTRACTOR TO FIELD VERIFY EXISTING PIPE SIZES THAT
WILL HAVE NEW PIPING INSTALLED AND REPORT ALL FIELD
DISCREPANCIES PRIOR TO BID.
1 KEY NOTES:
1. CONTRACTOR TO CONNECT NEW PIPING TO EXISITNG VENT
LINE AS SHOWN ON PLAN. CONTRACTOR TO VERIFY SIZE OF
EXISTING VENT LINE PRIOR TO BID.
2. CONTRACTOR TO INSTALL NEW PIPING AT APPROXIMATE
LOCATION OF EXISTING SANITARY OR VENT PIPE.
X
Y
Z
AA
3" CW 2 1/2" CW 2" CW 2" CW
2" HW 2" HW 3/4" HW
3/4" DHWR 3/4" DHWR 1/2" DHWR
BREAK/MEETING
ROOM
2H-104
CLOSET
2H-123
TOUCHDOWN
2H-103
TOUCHDOWN
2H-120
ANESTHESIA
2-PERSON
OFFICE
2H-115
TOUCHDOWN
2H-121
STORAGE
2H-105
ELEC. CLOSET
2H-106
IT CLOSET
2H-107
RESIDENTS
2H-122
TOUCHDOWN
2H-111
ANESTHESIA
OFFICE
2H-118
ANESTHESIA
OFFICE
2H-119
STAFF LOCKER
2H-110
CORRIDOR
C2H-6
CORRIDOR
C2H-7
CORRIDOR
C2H-5
CORRIDOR
C2H-4
ANESTHESIA
ADMIN.
2H-112
WELLNESS ROOM
2H-108
STAFF TOILET
2H-109
ANESTHESIA
OFFICE
2H-116
/2
C
W
/2
H
W
1/2" HW
1/2" CW
/2
C
W
2" CW
3/4" HW
1/2" DHWR
H W
H W
1" CW
1/2" HW
1" CW
1/2" CW
1/2" HW
3/4" CW
1/2" CW
P-528
P-528
ANESTHESIA
OFFICE
2H-114
ANESTHESIA
OFFICE
2H-117
1/2" CW
1/2" CW
ANESTHESIA
OFFICE
2H-113
P-604
P-604
P-604
P-103
P-418
1/2"
BALANCING
2" SHUTOFF
3/4" SHUTOFF
1/2" CHECK
1/2" CW
1/2"
BALANCING
3/4" SHUTOFF
1/2" SHUTOFF
1/2" SHUTOFF
1/2" SHUTOFF
/2
D
H W
R
1/2" SHUTOFF
1/2" CW to TP-2.
EXTEND 1/2" LINE
TO 4" FD-C.
CONTRACTOR
TO REBALANCE
FLOW IN DHWR
PIPE TO 1 GPM.
3/4" CW
1/2" SHUTOFF
/2
S
H U
T O
F F
P-812
P-812
1/2" SHUTOFF
P-812
ALL ABOVE FLOOR HORIZONTAL PIPING
RUNS SHALL BE RUN IN INTERSTITIAL SPACE
BETWEEN FIRST AND SECOND FLOOR
UNLESS OTHERWISE NOTED. CONTRACTOR
TO VERIFY EXACT ELEVATIONS. (TYP)
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
ADDENDUM #1 2023-03-24
03/24/2023
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
LEVEL 1 WATER NEW WORK
P-101B
-2
P -1
B
/3
/2
.p d f
SHEET NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
2. CONTRACTOR TO FIELD VERIFY EXISTING PIPE SIZES THAT
WILL HAVE NEW PIPING INSTALLED AND REPORT ALL FIELD
DISCREPANCIES PRIOR TO BID.
SCALE: 3/16" = 1'-0"A13
LEVEL 1 WATER NEW WORK
1 KEY NOTES:
1. CONTRACTOR TO REUSE EXISTING PIPE SEGMENT FOR INDICATED
WATER CIRCUIT AND INSTALL NEW PIPING AS SHOWN.
2. CONTRACTOR TO DISCONNECT AND CAP HOT WATER RETURN
PIPING FROM PREVIOUS HOT WATER LINE AND RECONNECT TO
NEW HOT WATER PIPING AS PHASING PERMITS.
2" V
2" S
2" S
3" V
2" V
2 1/2" V
4" S
2" S
2" S
2" S
2" S
2" V
2" V
2" S 3" V
3" V
4" S
4" S
2" V
ALL ABOVE FLOOR HORIZONTAL PIPING
RUNS SHALL BE RUN IN INTERSTITIAL SPACE
BETWEEN FIRST AND SECOND FLOOR
UNLESS OTHERWISE NOTED. CONTRACTOR
TO VERIFY EXACT ELEVATIONS. (TYP)
2" V
INTERSTITIAL SPACE
BETWEEN FIRST AND SECOND
FLOOR IS APPROXIMATELY
BETWEEN 8'-0" AND 14'-0" AFF.
3/4" CW
3/4" CW
1/2" DHWR
1/2" HW
1/2" CW
1/2" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1/2" CW
2" CW
2" CW
3/4" HW
1/2" DHWR
2" CW
1/2" CW
1/2" HW
1/2" DHWR 1" CW
1/2" HW
1/2" CW
1" CW
1/2" CW
1/2" HW
1" CW
ALL ABOVE FLOOR HORIZONTAL PIPING
RUNS SHALL BE RUN IN INTERSTITIAL SPACE
BETWEEN FIRST AND SECOND FLOOR
UNLESS OTHERWISE NOTED. CONTRACTOR
TO VERIFY EXACT ELEVATIONS. (TYP)
INTERSTITIAL SPACE
BETWEEN FIRST AND SECOND
FLOOR IS APPROXIMATELY
BETWEEN 8'-0" AND 14'-0" AFF.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
PLUMBING RISER DIAGRAMS
P-401
-2
P -4
/1
/2
.p d f
SCALE:F16
OVERALL WASTE AND VENT RISER DIAGRAM
SCALE:F9
OVERALL DOMESTIC WATER RISER DIAGRAM
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION
WASTE PIPE VENT PIPE WASTE
FIXTURE
UNITS
WATER
FIXTURE
UNITS
WRIST
BLADE
HANDLES
ELECTRIC
SENSOR
REMARKS
IN [mm] IN [mm]
P-103
WATER CLOSET,
WALL HUNG,
MANUAL FLUSH VALVE
4 [100] 2 [50] 1.25 [31] .5 [13] 4 4 N/A NO
P-418 LAVATORY 1.25 [31] 1.25 [31] .5 [13] .5 [13] 2 2 N/A YES (NOTE 1)
P-528 SINK 1.5 [38] 1.5 [38] .5 [13] .75 [19] 3 4 N/A NO
P-604
ELECTRIC WATER
COOLER
1.25 [31] 1/25 [31] .5 [13] 1 1 N/A NO
P-812 ICE MAKER BOX .5 [13] 5 N/A NO
COLD WATER
IN [mm]
HOT WATER
IN [mm]
BOD:
ELKAY BOTTLE
FOUNTAINS
BOD:
CHICAGO FAUCETS
NOTE 1: POWER TO BE PROVIDED BY BATTERY BACKUP
[4 m m
[8 m m
FINISHED
FLOOR
FINISHED
WALL
MANUAL HANDLE
SPLIT GRAB BAR
SEE ARCH. DWGS
WATER CLOSET
PLAN
ELEVATION
[450mm]
F O
R F
IX
T
U R
E H
E
IG
H T
S E
E A
R C
H
IT
E C
T U
R A
L D
R A
W
IN
G S
18"
WALL HUNG
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
ADDENDUM #1 2023-03-24
03/24/2023
652-20121
MBCH
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
PLUMBING SCHEDULES
P-601
-2
P -6
/3
/2
.p d f
SCALE: N.T.S.F16
PLUMBING SCHEDULE
SCALE: N.T.S.F6
WATER CLOSET DETAIL - MANUAL FLUSH
| Sheets |
| P-001 - PLUMBING GENERAL NOTES, ABBREVIATIONS, AND LEGENDS |
| PD101A - LEVEL 1 SANITARY AND VENT DEMOLITION PLAN |
| PD101B - LEVEL 1 WATER DEMOLITION PLAN |
| PD101C - LEVEL 1 MEDICAL GAS DEMOLITION PLAN |
| P-101A - LEVEL 1 WASTE AND VENT NEW WORK |
| P-101B - LEVEL 1 WATER NEW WORK |
| P-401 - PLUMBING RISER DIAGRAMS |
| P-601 - PLUMBING SCHEDULES |
File details come from the government source that posted it. Updated .