RVA1033004_Electrical.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24623B0024
About this file
This package includes construction documents and specifications for the renovation of an old dialysis area at the Richmond VA Medical Center. The project involves demolishing existing electrical, lighting, and mechanical systems and installing new systems to support renovated medical exam rooms, offices, and common areas. Key details include electrical demolition and new work plans showing the scope of work, lighting plans designating fixture types and control requirements, schedules for feeders and panels, and specifications for luminaires and mechanical equipment. The solicitation number and agency - Department of Veterans Affairs Veterans Health Administration Networks 6 - indicate this project is a federal construction contract opportunity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BID OPENING Abstract 36C24623B0024.pdf | ||
| BID OPENING Attendance Log 36C24623B0024.pdf | ||
| SITE VISIT Attendance Log 36C24623B0024.pdf | ||
| 36C24623B0024 0006.docx | DOCX document | |
| 36C24623B0024 0005.docx | DOCX document | |
| 36C24623B0024 0004.docx | DOCX document | |
| 36C24623B0024 0003.docx | DOCX document | |
| 36C24623B0024 0002.docx | DOCX document | |
| 36C24623B0024 0001.docx | DOCX document | |
| Attachment A - Itemized Schedule of Values Cost Breakdown.xlsx | XLSX spreadsheet | |
| INSTRUCTIONS TO BIDDERS.pdf | ||
| 36C24623B0024_1.docx | DOCX document | |
| RVA1033004_Plumbing-revised.pdf | ||
| RVA1033004_Life Safety Set.pdf | ||
| RVA1033004_Architecture.pdf | ||
| RVA1033004_Telecom Set.pdf | ||
| Specifications Vol 1.pdf | ||
| Specifications Vol 2.pdf | ||
| RVA1033004_Mechanical.pdf | ||
| RVA1033.004_PL_Addendum_1_2023-03-24.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
E-001A
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
ELECTRICAL GENERAL NOTES:
1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:
A. NFPA 70-2017 (NATIONAL ELECTRICAL CODE)
B. ANSI C2-2017 (NATIONAL ELECTRICAL SAFETY CODE)
C. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.
2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40%
FULL.
3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND
CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL
DESCRIPTIONS INDICATED.
5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.
6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.
7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE
RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE
ROUGHING-IN.
9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA
COMPENSATION WILL BE GRANTED.
10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM THE
EXISTING SHALL BE REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.
11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND
SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE
CONTRACTOR'S RESPONSIBILITY.
14. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY
MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/8” IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN
WITH AN INDELIBLE MARKER.
17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.
18. REFER TO ARCHITECTURAL DRAWINGS FOR DEMOLITION HOURS.
19. EMT SHALL COMPLY WITH ANSI C80.3 AND UL 797. ALL EMT SHALL BE FACTORY PAINTED. PROVIDE THE FOLLOWING COLORS FOR
EACH SYSTEM:
• FIRE ALARM - RED
• TELECOMMUNICATIONS - ORANGE
• 480/277V POWER - YELLOW
• 208/120V POWER - BLUE
• GENERATOR POWER - GREEN
• SECURITY - PURPLE
ELECTRICAL ABBREVIATIONS
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS
THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE
DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT
SYSTEM HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY
SYSTEM
HWRP
HWSP
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
XFMR
Z
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR
SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
TRANSFORMER
IMPEDANCE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.BF.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL GENERAL NOTES AND
ABBREVIATIONS
E-001
-2
E -0
/2
/1
.p d f
NOTE:
1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS
PROJECT.
WIRE SIZE FOR ALL 277V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 170 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 280 FT
AND GREATER THAN OR EQUAL TO 170 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 440 FT
AND GREATER THAN OR EQUAL TO 280 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 700 FT
AND GREATER THAN OR EQUAL TO 440 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
WIRE SIZE FOR ALL 120V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT
AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT
AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT
AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
NOTES:
1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.
ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,
DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT
IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF
EACH:
EXISTING EQUIPMENT
NEW OR RELOCATED EQUIPMENT
HATCH INDICATES EQUIPMENT TO BE DEMOLISHED
2022.05.20 15:33:25-04'00'
1/2
B
W
SB
M
M
2/60/40/1
60/40/3/3R
40/3/3R
CB
T
M
EM
J J
J
G
G4
A
AE
M
X X
C
D a b
LUMINAIRES
LUMINAIRE AND OUTLET BOX. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
LUMINAIRE AND OUTLET BOX WIRED FOR
MULTILEVEL SWITCHING, LOWER CASE LETTER
INDICATES SWITCHLEG DESTINATION.
LUMINAIRE AND OUTLET BOX, WITH PROVISIONS
FOR EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED EXIT SIGN AND
OUTLET BOX. PROVIDE NUMBER OF ARROWS
AND FACES INDICATED. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNT AT 96" ABOVE FINISHED FLOOR.
RECESSED OR PENDANT MOUNTED LUMINAIRE
AND OUTLET BOX. LETTER INDICATES LUMINAIRE
TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED LUMINAIRE AND
OUTLET BOX WITH PROVISIONS FOR
EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
EMERGENCY LIGHT UNIT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
REMOTE HEAD OR FLOOD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
WALL WASH DOWNLIGHT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POLE MOUNTED LUMINAIRE. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POST-TOP OR BOLLARD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
EQUIPMENT
MOTOR, HORSEPOWER AS INDICATED
MOTORIZED DAMPER
3-POLE COMBINATION MAGNETIC MOTOR
STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/
NEMA ENCLOSURE) NF = NONFUSED
DISCONNECT SWITCH, (SWITCH AMPS/ FUSE
SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-
FUSED
INDIVIDUALLY MOUNTED CIRCUIT BREAKER,
(CIRCUIT BREAKER SIZE/ POLES/ NEMA
ENCLOSURE)
DRY TYPE TRANSFORMER, KVA AS INDICATED
METER
ELECTRONIC METER
PANELBOARD, SEE SCHEDULES
DISTRIBUTION PANELBOARD, SEE SCHEDULES
EQUIPMENT AS INDICATED
CEILING OR WALL MOUNTED JUNCTION BOX
NEW WALL MOUNTED POWER, VOICE AND DATA
FURNITURE FEED. PROVIDE EMT IN ALL AND
SEALITE WHIPS AS FOLLOWS: (1) 3/4" POWER, (1)
1" EC FOR DATA & (1) 1" EC FOR VOICE.
PULL OR JUNCTION BOX
CEILING MOUNTED BLUE LIGHT SYSTEM
ROTATING BEACON
WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE
DROP CEILING
BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT
48" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
WHITE NOISE ROTARY VOLUME CONTROL;
MOUNT 48" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE.
CR
ST
TR
M
R
LA-1,3,5
WIRING DEVICES
LOW VOLTAGE ON/OFF WALL SWITCH, WALL
MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE
DIMMER CONTROL WITH DIMMABLE FIXTURES
INTEGRAL WITH SWITCH.
CEILING MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR
CEILING MOUNTED DUAL TECHNOLOGY
VACANCY SENSOR
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOELECTRIC CELL
WIRING
CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5
ADJACENT TO ARROW INDICATES HOMERUN OF
CIRCUITS, 1,3,5 TO PANEL LA. MARKS ACROSS
RACEWAY INDICATE THE NUMBER OF PHASE
CONDUCTORS AND NEUTRAL IN RACEWAY.
GROUND CONDUCTORS ARE INDICATED BY
LONGER HASHMARKS. NO MARKS ACROSS
RACEWAY INDICATES 2#12 CONDUCTORS AND 1
#12 GROUND CONDUCTOR. CONDUCTOR SIZE #
12 UNLESS INDICATED OTHERWISE. MINIMUM
RACEWAY SIZE SHALL BE 3/4"
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR
ABOVE FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
PLUG-IN BUSWAY, UNLESS INDICATED
OTHERWISE
SURFACE METAL RACEWAY OR MULTIOUTLET
ASSEMBLY AS INDICATED
LADDER TYPE CABLE TRAY (SIZE AS INDICATED
ON PLAN)
DUCTBANK, TEXT INDICATES QUANTITY AND
SIZE OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)
LIGHTNING PROTECTION
3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG
GROUND ROD TEST WELL
BARE COPPER GROUND CONDUCTOR, 1/0
UNLESS INDICATED OTHERWISE.
4/0 BARE COPPER GROUND CONDUCTOR
LIGHTNING PROTECTION SYSTEM AIR TERMINAL
LIGHTNING PROTECTION ROOF CONDUCTOR
ELECTRICAL CONNECTION
SITE
ELECTRICAL MANHOLE
ELECTRICAL HANDHOLE
PAD MOUNTED TRANSFORMER
POWER POLE
DOWN GUY AND ANCHOR (QUANTITY AS
INDICATED)
2W4"
WIRING DEVICES
SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE.
DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"
ABOVE FINISHED FLOOR OR ABOVE COUNTER
TOP/BACKSPLASH
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
18" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
EMERGENCY DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
EMERGENCY DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
EMERGENCY DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
EMEGENCY DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 48" ABOVE FINISHED FLOOR OR
ABOVE COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX GFI RECEPTACLE, NEMA
5-20R, MOUNTED CONCEALED BEHIND ELECTRIC
WATER COOLER
FLOOR BOX WITH DUPLEX RECEPTACLE NEMA
5-20R. PROVIDE FIRE RATED POKE THRU
DEVICES ON ALL FLOORS ABOVE GROUND
LEVEL.
SPECIAL RECEPTACLE, NEMA TYPE AS
INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
CEILING BOX WITH DUPLEX RECEPTACLE, NEMA
5-20R
RECEPTACLE WP = IN-USE WEATHER PROOF
SUBSCRIPTS TR = TAMPER RESISTANT
TV = TELEVISION, MOUNT AT 60" ABOVE
FINISHED FLOOR
AFCI = ARC FAULT CIRCUIT INTERRUPTER
FLOOR BOX SUITABLE FOR CONCRETE FLOOR
POUR; TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE
WITH HINGED ACCESS TO RECEPTACLES AND
JACKS RECESSED BELOW COVER IN FLOOR
BOX. PROVIDE 8" FIRE RATED POKE THRU
ABOVE GROUND FLOOR.
WALL SWITCH, AC TYPE, SPST, MOUNT 48"
ABOVE FINISHED FLOOR
WALL SWITCH, AC TYPE, DPDT, MOUNT 48"
ABOVE FINISHED FLOOR
3-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
4-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
SLIDE DIMMER, MOUNT 48" ABOVE FINISHED
FLOOR
MOTOR RATED DISCONNECT SWITCH WITH
THERMAL OVERLOADS, SINGLE POLE SINGLE
THROW, MOUNT ON UNIT, UNLESS INDICATED
OTHERWISE.
WALL MOUNTED, DUAL TECHNOLOGY VACANCY
SWITCH, MOUNT 48" ABOVE FINISHED FLOOR
WALL MOUNTED, DUAL TECHNOLOGY
OCCUPANCY SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
ELECTRICAL LEGEND
D
M
V
O
LV
OS
DS
PE
5-30R
EWC
ONE-LINE
TRANSFORMER
CURRENT TRANSFORMER
FUSE
ELECTRICAL CONNECTION
CIRCUIT BREAKER
SWITCH
SURGE ARRESTORS
SEPARABLE CONNECTION
DRY TYPE TRANSFORMER, K-4 RATED, KVA AS
INDICATED
GROUND
SCHEMATIC
PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)
CONTROL RELAY COIL
SHUNT TRIP COIL
TIME DELAY RELAY COIL
MOTOR STARTER COIL
SW
S
S
S
S
S
S
S
S
S
VS
D
F
G
H
P
J
LP
W
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
E.O.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL LEGEND
E-002
-2
E -0
/2
/1
.p d f
NOTE:
1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.
W W
X X
Y Y
Z Z
AA AA
16 17 18 19 2015
W
X
Y
Z
AA
N U
R S
E C
A L L
D E
V
IC
E
P2GC
L2GC
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL DEMOLITION PLAN
ED101
-2
E D
/0
/1
.p d f
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. NO WORK REQUIRED WITHIN HATCHED AREAS. ALL POWER
AND SPECIAL SYSTEM DEVICES, CIRCUITING AND
ASSOCIATED WIRING SHALL BE EXISTING TO REMAIN AND
PROTECTED DURING CONSTRUCTION.
3. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
ELECTRICAL DEVICES AND EQUIPMENT LOCATIONS.
4. DISCONNECT AND REMOVE ALL EXISTING
POWER/DATA/SPECIAL SYSTEM DEVICES ALONG WITH
WIRING, CONDUIT AND ALL ACCESSORIES BACK TO SOURCE.
5. DISCONNECT AND REMOVE ALL ELECTRICAL PANELS AND ITS
ASSOCIATED CONDUCTORS, CONDUITS AND ALL
ACCESSORIES BACK TO SOURCE.
6. DISCONNECT AND REMOVE ALL DISCONNECT SWITCHES
SERVING DEMOLISHED MECHANICAL EQUIPMENT. REMOVE
ALL ASSOCIATED CONDUCTORS, CONDUITS AND
ACCESSORIES BACK TO SOURCE. SEE MECHANICAL
DEMOLITION PLANS FOR MORE INFORMATION.
7. THE SCOPE OF DEMOLITION AS DOCUMENTED IS SCHEMATIC
IN NATURE. ANY ADDITIONAL COORDINATION BETWEEN THIS
SCOPE OF DEMOLITION AND EXISTING SYSTEMS IN THE
SPACE SHALL BE DETERMINED IN THE FIELD.
8. REFER TO ARCHITECTURAL DEMOLITION PLANS FOR
ADDITIONAL INFORMATION.
SCALE: 3/16" = 1'-0"1
LEVEL 1 ELECTRICAL DEMOLITION POWER PLAN
S
S
S
S S
S
S S
S S
S S S S
S
S
S
S
S
S
S S
S S
S
S
S
S
S
S
S
S
S
S S
S S
SSS
S S
16 17 18 19 20
W
X
Y
Z
AA
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
E.O.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL LIGHTING DEMOLITION
PLAN
ED102
-2
E D
/1
/2
.p d f
SCALE: 3/16" = 1'-0"1
LEVEL 1 ELECTRICAL DEMOLITION LIGHTING PLAN
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. NO WORK REQUIRED WITHIN HATCHED AREAS. ALL POWER
AND SPECIAL SYSTEM DEVICES, CIRCUITING AND
ASSOCIATED WIRING SHALL BE EXISTING TO REMAIN AND
PROTECTED DURING CONSTRUCTION.
3. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
ELECTRICAL DEVICES AND EQUIPMENT LOCATIONS.
4. DISCONNECT AND REMOVE ALL LIGHT FIXTURES INCLUDING
EXIT AND EMERGENCY FIXTURES AND LIGHT SWITCHES
ALONG WITH WIRING, CONDUIT AND ALL ACCESSORIES BACK
TO SOURCE.
5. THE SCOPE OF DEMOLITION AS DOCUMENTED IS SCHEMATIC
IN NATURE. ANY ADDITIONAL COORDINATION BETWEEN THIS
SCOPE OF DEMOLITION AND EXISTING SYSTEMS IN THE
SPACE SHALL BE DETERMINED IN THE FIELD.
6. REFER TO ARCHITECTURAL DEMOLITION PLANS FOR
ADDITIONAL INFORMATION.
D
SD
O
S
DO
S D
O
S D
O
S D
S
DO
VS
VS
VS
VS
VS
VS
VS
VS
VS
SO
S S
S O
VS
VS
SD
SD
S D
S
D
S D
S D
S 3D
S3 D
OS
OS OS
SD
VS
VS
OS
OS
VS
S
DO
S D
O
SO
OS
OS
OS
16 17 18 19 20 2115
W
X
Y
Z
AA
BBBE
BB
BEBB
BE
B
BE
BBEBBE
BE B BE B
BE
B
BE
BE
B
BE
B BE B BE B
BE
B
BE
B
B
BE
B
B
B
B
BE
B
BE
BBB BBB
B B
B B
B B
B B B
B B
BE B B B
BE B
B B
B B
B B
B B
A A
BE B B
B B
BE B BE
BE B BE
B B B
B B BE
B
BE B
B
AE
AE A A A
BE
B
B
B
B
B
B B B
BE B
C
C C C C
C C C
C
C
C
B B
BE
C
C
BREAK/MEETING
ROOM
2H-104
CLOSET
2H-123
TOUCHDOWN
2H-103
TOUCHDOWN
2H-120
ANESTHESIA
2-PERSON
OFFICE
2H-115
ANESTHESIA
OFFICE
2H-114
TOUCHDOWN
2H-121
STORAGE
2H-105
ELEC. CLOSET
2H-106
IT CLOSET
2H-107
RESIDENTS
2H-122
NEW 2-PERSON
ENGINEERING
OFFICE
2K-140A
NEW
ENGINEERING
OFFICE
2H-140B
TOUCHDOWN
2H-111
ANESTHESIA
OFFICE
2H-118
ANESTHESIA
OFFICE
2H-119
STAFF LOCKER
2H-110
CORRIDOR
C2H-6
CORRIDOR
C2H-7
CORRIDOR
C2H-5
CORRIDOR
C2H-4
ANESTHESIA
ADMIN.
2H-112
WELLNESS ROOM
2H-108
STAFF TOILET
2H-109
ANESTHESIA
OFFICE
2H-116
ANESTHESIA
OFFICE
2H-117
V E
S T
IB
U
L E
K
-1
C
A
X
X
X
X
X
X
X
CORRIDOR
C2H-6
C
P2GC-1 P2GC-1 P2GC-1
P2GC-1 P2GC-1
P2GC-1 P2GC-1 P2GC-1
P2GC-3 P2GC-3 P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-1P2GC-1P2GC-1P2GC-1P2GC-1
P2GC-1 P2GC-1 P2GC-1 P2GC-1 P2GC-1
P2GC-3
P2GC-3
P2GC-1P2GC-1P2GC-1P2GC-1P2GC-1P2GC-1
P2GC-3 P2GC-3 P2GC-3 P2GC-3
P2GC-3 P2GC-3 P2GC-3 P2GC-3
P2GC-3P2GC-3P2GC-3P2GC-3
P2GC-3 P2GC-3 P2GC-3
P2GC-3 P2GC-3 P2GC-3
P2GC-3
P2GC-3 P2GC-3
P2GC-3P2GC-3
P2GC-3
P2GC-3P2GC-3
P2GC-3
P2GC-3P2GC-3P2GC-3
P2GC-1 P2GC-1
P2GC-1 P2GC-1 P2GC-1
P2GC-1P2GC-1P2GC-1
P2GC-1 P2GC-1
P2GC-1P2GC-1
P2GC-1 P2GC-1 P2GC-1
P2GC-1P2GC-1
P2GC-1
P2GC-1
P2GC-1 P2GC-1 P2GC-1
P2GC-1 P2GC-1
P2GC-1 P2GC-1 P2GC-1
P2GC-1P2GC-1
P2GC-1 P2GC-1 P2GC-1
P2GC-3
P2GC-3
P2GC-3
P2GC-3 P2GC-3 P2GC-3 P2GC-3
P2GC-3P2GC-3
P2GC-3P2GC-3
P2GC-3 P2GC-3 P2GC-3 P2GC-3
P2GC-3P2GC-3P2GC-3P2GC-3P2GC-3P2GC-3
P2GC-3
P2GC-3 P2GC-3 P2GC-3 P2GC-3
P2GC-3
P2GC-3
P2GC-3P2GC-3P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
P2GC-3
BE
P2GC-1
ANESTHESIA
OFFICE
2H-113
B
CORRIDOR
C2H-4
STORAGE
2H-141B
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
LIGHTING PLAN
EL101
-2
E L
/0
/1
.p d f
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR LUMINAIRE SCHEDULE AND LIGHTING
CONTROL REQUIREMENTS.
SCALE: 3/16" = 1'-0"1
LEVEL 1 LIGHTING PLAN
16 17 18 19 20 21
W W
X X
Y Y
Z Z
AA AA
P2GC
L2GC
VAV-2
VAV-3
VAV-8
VAV-9
VAV-7 VAV-10
VAV-6
VAV-1
VAV-4
VAV-5
VAV-11
VAV-13
L2GC-1
L2GC-1
L2GC-1 L2GC-1
L2GC-1
L2GC-1
L2GC-1
L2GC-3 L2GC-3
L2GC-3
L2GC-3
L2GC-3
L2GC-3
L2GC-1
VAV-10
VAV-15
VAV-14
AC-1
L2GC-34,36
IT CLOSET
2H-107
ELEC. CLOSET
2H-106
STORAGE
2H-141B
STORAGE
2H-105
CORRIDOR
C2H-4
BREAK/MEETING
ROOM
2H-104CORRIDOR
C2H-6
TOUCHDOWN
2H-103
TOUCHDOWN
2H-120
ANESTHESIA
ADMIN.
2H-112
ANESTHESIA
OFFICE
2H-113
ANESTHESIA
OFFICE
2H-114
ANESTHESIA
2-PERSON
OFFICE
2H-115
ANESTHESIA
OFFICE
2H-116
ANESTHESIA
OFFICE
2H-117
ANESTHESIA
OFFICE
2H-118
ANESTHESIA
OFFICE
2H-119
TOUCHDOWN
2H-111
WELLNESS ROOM
2H-108
NEW 2-PERSON
ENGINEERING
OFFICE
2K-140A
NEW
ENGINEERING
OFFICE
2H-140B
STAFF LOCKER
2H-110
STAFF TOILET
2H-109
VESTIBULE
2K-140C
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
MECHANICAL POWER PLAN
EM101
-2
E M
/0
/1
.p d f
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR MECHANICAL EQUIPMENT CONNECTION
SCHEDULE.
KEYNOTES:
1. PROVIDE AND INSTALL 30A/2P/NF DISCONNECT FOR AC/ACU-1
WITH 2#10,1#10G-3/4"C.
SCALE: 3/16" = 1'-0"1
LEVEL 1 MECHANICAL POWER PLAN
P P
W
W
J
J
J
J
J
J
16 17 18 19 20 21
W
X
Y
Z
AA
TOUCHDOWN
2H-103
BREAK/MEETING
ROOM
2H-104
CORRIDOR
C2H-6
TOUCHDOWN
2H-121
TOUCHDOWN
2H-120
RESIDENTS
2H-122
CORRIDOR
C2H-5
STORAGE
2H-105
IT CLOSET
2H-107
ELEC. CLOSET
2H-106
ANESTHESIA
OFFICE
2H-114ANESTHESIA
2-PERSON
OFFICE
2H-115
ANESTHESIA
ADMIN.
2H-112
ANESTHESIA
OFFICE
2H-119
ANESTHESIA
OFFICE
2H-119
ANESTHESIA
ADMIN.
2H-112
TOUCHDOWN
2H-111
ANESTHESIA
OFFICE
2H-116
ANESTHESIA
OFFICE
2H-117
NEW 2-PERSON
ENGINEERING
OFFICE
2K-140A
STAFF TOILET
2H-109
WELLNESS ROOM
2H-108
NEW
ENGINEERING
OFFICE
2H-140B
STAFF LOCKER
2H-110
P2GC
L2GC
MW
MW
L2GC-5
L2GC-5L2GC-5
L2GC-5
L2GC-5
L2GC-7
L2GC-7
L2GC-11
L2GC-7 L2GC-7
L2GC-7
L2GC-13
L2GC-9
L2GC-9
L2GC-9
L2GC-5
L2GC-48
L2GC-10
L2GC-23
L2GC-21
L2GC-19
L2GC-12
L2GC-20
L2GC-2 L2GC-2 L2GC-2
L2GC-2
L2GC-15 L2GC-15 L2GC-6
L2GC-4
L2GC-48
L2GC-8
L2GC-8L2GC-8L2GC-8L2GC-15L2GC-15
L2GC-43
L2GC-17 L2GC-17 L2GC-17
L2GC-17
L2GC-14
L2GC-16
L2GC-16 L2GC-16 L2GC-16
L2GC-18
L2GC-18 L2GC-18 L2GC-18
L2GC-18
L2GC-18
STORAGE
2H-141B
L2GC-20
L2GC-20
L2GC-20
L2GC-31
L2GC-31L2GC-20
L2GC-22
L2GC-24
L2GC-25
L2GC-25
L2GC-27,29
L2GC-26
L2GC-26
L2GC-26
L2GC-26
L2GC-28
L2GC-25
L2GC-25
L2GC-30
L2GC-30 L2GC-30
WELLNESS ROOM
2H-108
NEW 2-PERSON
ENGINEERING
OFFICE
2K-140A
VESTIBULE
2K-140C
L2GC-31
L2GC-31
L2GC-31
L2GC-31
L2GC-48
L2GC-16
L2GC-31
L2GC-33
L2GC-33
L2GC-33 L2GC-33 L2GC-33
L2GC-35
L2GC-32
L2GC-32
L2GC-32
L2GC-32
L2GC-32
L2GC-41
L2GC-41
L2GC-41
GROUND BAR
L2GC-37
L2GC-39
L2GC-38
L2GC-38
L2GC-38
L2GC-41
L2GC-41
L2GC-41
L2GC-40
L2GC-40
L2GC-40
L2GC-40
L2GC-40
L2GC-40
L2GC-42
L2GC-42
L2GC-42
L2GC-42
L2GC-42
L2GC-43
L2GC-43
L2GC-43
L2GC-45
L2GC-47
L2GC-44
L2GC-44
L2GC-44
L2GC-44
ANESTHESIA
OFFICE
2H-118
L2GC-26
L2GC-25
L2GC-46
L2GC-49
L2GC-51
SECURITY PANEL
ECL2GC-42
ECL2GC-42
ECL2GC-38
ANESTHESIA
OFFICE
2H-113
ECL2GC-42
ECL2GC-42 ECL2GC-42 ECL2GC-38
ECL2GC-38
ECL2GC-38
ECL2GC-38
L2GC-44
L2GC-48
L2GC-32
ESP2GB ECL2GC ECL2GB
L2GC-44
3 3
ECL2GC-38
ECL2GC-8,10
ECL2GC-12,14
L2GC-13
GROUND BAR
L2GC-49
ECL2GC-36
FACP
ECL2GC-34
ECL2GC-34
ECL2GC-34
L2GC-53
L2GC-50
L2GC-48
L2GC-52
ECL2GC-27
ECL2GC-27
ECL2GC-27
ECL2GC-27
V
W
ECL2GB
ECL2GC
ESP2GB
2H-2002
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
POWER PLAN
EP101
-2
E P
/0
/1
.p d f
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
KEYNOTES:
1. CONTRACTOR SHALL PROVIDE THE WHIP CONNECTION TO
JUNCTION BOX TO SYSTEMS FURNITURE WHIP.
2. ELECTRICAL PANELBOARDS ARE EXISTING TO REMAIN.
3. RECEPTACLES FOR OPERATING ROOM CASES MONITOR.
COORDINATE EXACT LOCATION PRIOR TO ROUGH-IN AND
INSTALLATION.
4. NEW 5 RU UPS WITH 208V INPUT TO 120V OUTPUT. PROVIDE
WITH STEP DOWN TRANSFORMER. PROVIDE WITH (2) L6-30R
RECEPTACLES.
5. COORDINATE FINAL LOCATION OF RECEPTACLES WITH SCRUB-
X MACHINES.
6. POWER FOR PIV CARD READER. COORDINATE EXACT
LOCATION WITH SECURITY VENDOR.
SCALE: 3/16" = 1'-0"1
LEVEL 1 POWER PLAN
SCALE: 1/8" = 1'-0"2
ELEC RM 2H-200
TV
TV TV
MAX.
6"
MAX.
6"
AV
MAX.
12"
" DATA
OUTLET
MAX.
12"
" POWER
RECEPTACLE
T-STAT
T $
LIGHT
SWITCH
OR OS
SWITCH
VOICE
OUTLET
MAX.
6"
12" MAX.
PROJECTOR
MOMENTARY
TOGGLE
SWITCH
18" MAX. 6"
~ M A
R K
E R
B O
A R
D
6" MIN.
POWER
RECEPTACLE
6" MIN.
6" MIN.
FLOOR
CEILING
FACEPLATE COLOR PER
SPECIFICATION 26 27 26
PNL-CKT
CLEAR LABEL TAPE WITH
TYPED, BLACK LETTERING
DESIGNATING PANEL AND
CIRCUIT NUMBER.
PROVIDE RECEPTACLES IN THE
FOLLOWING COLORS:
• WHITE: NORMAL POWER
• RED: GENERATOR POWER
• BLUE: UPS POWER
PROVIDE DURABLE
WIRE MARKERS OR
TAGS INSIDE THE
OUTLET BOX.
INSTALL GROUND PIN
ON TOP
FACEPLATE COLOR PER
SPECIFICATION 26 09 23
PNL-CKT
CLEAR LABEL TAPE WITH
TYPED, BLACK LETTERING
DESIGNATING PANEL AND
CIRCUIT NUMBER.
PROVIDE DURABLE
WIRE MARKERS OR
TAGS INSIDE THE
OUTLET BOX.
P21A
150A MCB, 208V, 3Ø, 4W, 10KAIC
SOURCE: T-P21A
/4
M
IN
1/8" MIN
/4
M
IN
1/8" MIN
(PANEL NAME)
(PANEL MAIN RATING, VOLTAGE, PHASE , AIC RATING)
(SOURCE PANEL OR TRANSFORMER)
SELF-ADHESIVE BACKING
BACKGROUND COLOR:
• NORMAL POWER - BLACK
• GENERATOR POWER - RED
• UPS POWER - BLUE
WHITE LETTERING,
1/4" ARIAL FONT,
TYPED EXAMPLE:
N L 4 1 A 1
BRANCH DESIGNATION1:
N: NORMAL
E: EMERGENCY
C: CRITICAL
LS: LIFE SAFETY
PANEL LOAD DESIGNATION2,3:
L: LIGHTING
M: MECHANICAL EQUIPMENT
P: POWER
C: COMMUNICATIONS
PANEL VOLTAGE:
1: 240V/120, 1Ø 2: 208V/120, 3Ø 3: 240V/120, 3Ø 4: 480V/277, 3Ø
PANEL SECTION
DESIGNATION6
PANEL DESIGNATION5
FLOOR DESIGNATION4
NOTES:
1. BRANCH DESIGNATION IS OMITTED WHEN BUILDING HAS ONE BRANCH TYPE ONLY.
2. IF BUILDING IS LESS THAN 25,000FT2, ONLY PANEL LOAD DESIGNATIONS "P" AND "C" WILL BE USED.
3. IF BRANCH DESIGNATION "LS" IS USED, PANEL LOAD DESIGNATION WILL BE OMITTED.
4. FLOOR DESIGNATION IS OMITTED FOR ONE STORY BUILDINGS.
5. PANEL DESIGNATION IS OMITTED WHEN ONE PANEL OF BRANCH DESIGNATION AND PANEL LOAD DESIGNATION IS TO BE INSTALLED.
6. PANEL SECTION DESIGNATION IS OMITTED WHEN PANEL IS ONE SECTION ONLY.
SCALE: N.T.S.A1
MOUNTING HEIGHT DETAIL
SHEET NOTES:
SCALE: N.T.S.C1
RECEPTACLE DETAIL (TYP.)
SCALE: N.T.S.C3
LIGHT SWITCH DETAIL (TYP.)
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
E.O.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL DETAILS
E-501
-2
E -5
SCALE: N.T.S.A3
PANELBOARD LABEL
SCALE: N.T.S.B3
BRANCH PANEL NAMING CONVENTION
COPPER BAR,
24"L X 4"H X 1/4"D
2700 VOLT INSULATORS
STEEL BRACKETS
2"
JUNCTION BOX
POWER PACK
J
LOW VOLTAGE CONTROL WIRING
SPLIT SWITCHED/
NON-SWITCHED
DOUBLE DUPLEX
RECEPTACLE
RECEPTACLE CIRCUITLIGHTING CIRCUIT
OS
SWITCHED
RECEPTACLE
POWER PACK
JUNCTION BOX
NON-SWITCHED
RECEPTACLE
PP
VS
J
PP
LTG
S
LIGHT SWITCH
NOTE:
1. RECEPTACLE TO BE CONTROLLED BY AN OCCUPANCY
SENSOR (OS) OR VACANCY SENSOR (VS) LOCATED IN
THE SAME ROOM AS THE RECEPTACLE AND BE
WITHIN 15'-0" HORIZONTALLY FROM THE OS OR VS.
PROVIDE ADDITIONAL OS OR VS AS REQUIRED.
LUMINAIRE REQUIREMENTS:
4 3/8"
NOMINAL
1. HOUSING & FINISH - ONE-PIECE COLD-ROLLED STEEL COATED POLYESTER,
PAINTED AFTER FABRICATION WITH EMBOSSED FACETS. END PLATES
INCLUDE INTEGRAL T-BAR CLIPS. FIXTURE MAY BE MOUNTED AND WIRED IN
CONTINUOUS ROWS.
2. REFLECTORS - IMPACT-MODIFIED, SINGLE CLEAR RIBBED ACRYLIC DIFFUSER
PROVIDING A NON-GLARY WIDE UNIFORM LIGHT PATTERN WHILE PRODUCING
“NO VISIBLE LED SOURCE IMAGE”.
3. LAMPS - LED LAMP TO HAVE 3500K KELVIN COLOR TEMPERATURE OF LIGHT
WITH A CRI OF 80 OR GREATER AND AN L90 OF 60,000 HOURS OR GREATER.
4. DRIVER - FIXTURE TO HAVE A DIGITALLY ADDRESSABLE DRIVER OR LOW
VOLTAGE DIGITAL ADDRESSABLE CONTROL DEVICE. LED DRIVER TO BE
AUTOSENSING 120-277 VOLT AND MUST BE ACCESSIBLE FROM BELOW THE
CEILING. FIXTURE IS TO BE DIMMABLE DOWN TO 1 PERCENT USING 0 TO 10
VOLT DRIVER BEING FLICKER FREE DURING DIMMING PROCESS.
5. CERTIFICATION - FIXTURE MUST BE DLC QUALIFIED (DESIGN LIGHT
CONSORTIUM) AND UL LISTED.
6. WARRANTY - PROVIDE A MINIMUM 10-YEAR WARRANTY BY MANUFACTURER.
PROVIDE IES FILE AND PROVIDE SPECIFICATION SHEET FOR REVIEW.
7. FIXTURE TYPES -
FIXTURE TYPES 'A1' & 'A1E' - 4000 LUMENS, 2' X 4', RECESSED
FIXTURE TYPES 'A2' & 'A2E' - 2000 LUMENS, 2' X 2', RECESSED
FIXTURE TYPES 'A3' & 'A3E' - 3000 LUMENS, 2' X 4', SURFACE MOUNTED
FIXTURE TYPES 'A4' & 'A4E' - 7200 LUMENS, 2' X 4', RECESSED
LUMINAIRE REQUIREMENTS:
NOMINAL
7" NOMINAL
1. HOUSING & FINISH - CONSTRUCTION OF HOUSING TO BE
GALVANIZED STEEL MOUNTING/PLASTER FRAME WITH
TORSION SPRINGS TO MOUNT CONICAL SHAPE
REFLECTOR. VERTICALLY ADJUSTABLE MOUNTING
BRACKETS OR CHANNEL T BAR FASTENERS.
SECONDARY HOUSING ADJUSTMENT SYSTEM FOR
PRECISE, FINAL CEILING-TO-FLANGE ALIGNMENT.
2. REFLECTORS - LENS TO BE SEMI RECESSED INTO TRIM
HOUSING PRODUCING LITTLE TO NO GLARE OR LED
IMAGE.
3. LAMPS - LED LAMP TO HAVE 3500K KELVIN COLOR
TEMPERATURE OF LIGHT WITH A CRI OF 80 OR GREATER
AND AN L70 OF 60,000 HOURS OR GREATER.
4. DRIVER - FIXTURE TO HAVE A DIGITALLY ADDRESSABLE
DRIVER OR LOW VOLTAGE DIGITAL ADDRESSABLE
CONTROL DEVICE. LED DRIVER TO BE 277 VOLT. FIXTURE
SHALL HAVE 0 TO 10 VOLT DIMMING, 1-100%.
5. CERTIFICATION - FIXTURE SHALL BE UL LISTED.
6. WARRANTY - PROVIDE A MINIMUM 10-YEAR WARRANTY
BY MANUFACTURER.
7. FIXTURE TYPES -
TYPE D1 - 6" DIA. - 1000 LUMENS
TYPE D1E - 6" DIA. - 1000 LUMENS, WITH EMERGENCY
BATTERY BACKUP
TYPE D2 - 6" DIA. - 1000 LUMENS, ACRYLIC LENS, WET
LOCATION LISTED
TYPE D2E - 6" DIA. - 1000 LUMENS, ACRYLIC LENS, WET
LOCATION LISTED WITH EMERGENCY BATTERY BACKUP
LUMINAIRE REQUIREMENTS:
HOUSING - POWDER COATED COLD-ROLLED STEEL, WITH TABBED AND SCREWED
ON END PLATES. FIXTURE SHALL NOT PERMANENTLY DEFORM OUT OF "SQUARE"
WHEN PICKED UP FROM ANY CORNER.
REFLECTORS - HIGHLY REFLECTIVE OPTICAL COMPOSITE COATING.
LAMP - LED, TYPICALLY WITH WATTAGES
AS INDICATED. SEE LUMINAIRE SCHEDULE.
CERTIFICATION - UL LISTED AND LABELED.
1.
2.
3.
4.
23-13/16"
3-5/8"
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL DETAILS
E-502
-2
E -5
SHEET NOTES:
SCALE: N.T.S.4
ELECTRICAL GROUND BAR DETAIL
SCALE: N.T.S.5
LIGHTING AND RECEPTACLE CONTROL SCHEMATIC
SCALE: N.T.S.1
2'X4' LED TROFFER LIGHT FIXTURE
SCALE: N.T.S.3
6" DIAMETER RECESSED LED
DOWNLIGHT
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
SCALE: N.T.S.2
2X2 LED TROFFER LIGHT FIXTURE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL FEEDER SCHEDULES
E-600
-2
E -6
/2
/1
.p d f
FEEDER SCHEDULE
FEEDER
TAG COPPER FEEDER
FEEDER
TAG ALUMINUM FEEDER
20CU 4#12 & 1#12G, 1/2"C. 20AL N.A.
25CU 4#10 & 1#10G, 3/4"C. 25AL N.A.
30CU 4#10 & 1#10G, 3/4"C. 30AL N.A.
35CU 4#8 & 1#10G, 1"C. 35AL N.A.
40CU 4#8 & 1#10G, 1"C. 40AL N.A.
45CU 4#6 & 1#10G, 1"C. 45AL N.A.
50CU 4#6 & 1#10G, 1"C. 50AL N.A.
60CU 4#4 & 1#10G, 1-1/4"C. 60AL 4#2 & 1#6G, 1-1/4"C.
70CU 4#4 & 1#8G, 1-1/4"C. 70AL 4#2 & 1#6G, 1-1/4"C.
80CU 4#2 & 1#8G, 1-1/2"C. 80AL 4#1 & 1#6G, 1-1/4"C.
90CU 4#2 & 1#8G, 1-1/2"C. 90AL 4-1/0 & 1#6G, 1-1/2"C.
100CU 4#1 & 1#8G, 2"C. 100AL 4-1/0 & 1#6G, 1-1/2"C.
110CU 4#1 & 1#6G, 2"C. 110AL 4-2/0 & 1#4G, 2"C.
125CU 4#1 & 1#6G, 2"C. 125AL 4-3/0 & 1#4G, 2"C.
150CU 4-1/0 & 1#6G, 2"C. 150AL 4-3/0 & 1#4G, 2"C.
175CU 4-2/0 & 1#6G, 2"C. 175AL 4-4/0 & 1#4G, 2"C.
200CU 4-3/0 & 1#6G, 2-1/2"C. 200AL 4-250 KCMIL & 1#4G, 2-1/2"C.
225CU 4-4/0 & 1#4G, 2-1/2"C. 225AL 4-300 KCMIL & 1#2G, 2-1/2"C.
250CU 4-250 KCMIL & 1#4G, 3"C. 250AL 4-350 KCMIL & 1#2G, 3"C.
300CU 4-350 KCMIL & 1#4G, 3"C. 300AL 4-500 KCMIL & 1#2G, 3"C.
350CU 4-500 KCMIL & 1#2G, 4"C. 350AL 4-750 KCMIL & 1#1G, 4"C.
400CU 4-500 KCMIL & 1#2G, 4"C. 400AL 4-750 KCMIL & 1#1G, 4"C.
450CU TWO 2-1/2-INCH CONDUITS, EACH
WITH FOUR 4/0 AND ONE #2G
450AL TWO 2-1/2-INCH CONDUITS, EACH WITH
FOUR 300 KCMIL AND ONE 1/0G
500CU TWO 3-INCH CONDUITS, EACH WITH
FOUR 250 KCMIL AND ONE #2G
500AL TWO 3-INCH CONDUITS, EACH WITH
FOUR 350 KCMIL AND ONE 1/0G
600CU TWO 3-INCH CONDUITS, EACH WITH
FOUR 350 KCMIL AND ONE #1G
600AL TWO 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 2/0G
700CU TWO 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 1/0G
700AL TWO 4-INCH CONDUITS, EACH WITH
FOUR 750 KCMIL AND ONE 3/0G
800CU TWO 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 1/0G
800AL TWO 4-INCH CONDUITS, EACH WITH
FOUR 750 KCMIL AND ONE 3/0G
1000CU THREE 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 2/0G
1000AL THREE 4-INCH CONDUITS, EACH WITH
FOUR 750 KCMIL AND ONE 4/0G
1200CU FOUR 3-INCH CONDUITS, EACH WITH
FOUR 350 KCMIL AND ONE 3/0G
1200AL FOUR 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 250 KCMIL G
1600CU FIVE 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 4/0G
1600AL FIVE 4-INCH CONDUITS, EACH WITH
FOUR 750 KCMIL AND ONE 350KCMIL G
2000CU SIX 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 250KCMIL G
2000AL SIX 4-CONDUITS, EACH WITH FOUR 750
KCMIL AND ONE 500 KCMIL G
EPO 2#12 & 1#12G, 1/2"C. EPO N.A.
FP (SIZE IS JOB SPECIFIC) FP NOT PERMITTED FOR FIRE PUMPS
MTR1 (SIZE IS JOB SPECIFIC) MTR1 N.A.
MTR2 (SIZE IS JOB SPECIFIC) MTR2 N.A.
SE (SIZE IS JOB SPECIFIC) SE (SIZE IS JOB SPECIFIC)
TRANSFORMER FEEDER SCHEDULE
FEEDER
TAG PRIMARY FEEDER
FEEDER
TAG SECONDARY FEEDER
FEEDER
TAG
SECONDARY FEEDER
(DOUBLE TAP)
BOND
JUMPER
T15P 3#10 & 1#10G, 1/2"C. T15S 4#6 & 1#10G, 1"C. T15S2 N.A. #8G
T30P 3#6 & 1#10G, 3/4"C. T30S 4#1 & 1#8G, 1-1/2"C. T30S2 N.A. #6G
T45P 3#4 & 1#8G, 1"C. T45S 4-1/0 & 1#6G, 2"C. T45S2 N.A. #6G
T75P 3#1 & 1#6G, 1-1/2"C. T75S 4-250 KCMIL & 1#4G, 2-1/2"C. T75S2 4-1/0 & 1#6G, 2"C. #2G
T112.5P 3-2/0 & 1#6G, 2"C. T112.5S 4-500 KCMIL & 1#2G, 3"C. T112.5S2 4-3/0 & 1#6G, 2-1/2"C. 1/0G
T150P 3-4/0 & 1#4G, 2"C. T150S TWO 2-1/2-INCH CONDUITS, EACH
WITH FOUR 250 KCMIL AND ONE #2G
T150S2 4-250 KCMIL & 1#4G, 3"C. 1/0G
T225P 3-500 KCMIL & 1#2G, 3"C. T225S TWO 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 1/0G
T225S2 4-500 KCMIL &1#2G, 3-1/2"C. 2/0G
T300P TWO 2-INCH CONDUITS, EACH WITH
THREE 4/0 AND ONE #2G
T300S THREE 3-1/2-INCH CONDUITS, EACH
WITH FOUR 500 KCMIL AND ONE 2/0G
T300S2 TWO 3-INCH CONDUITS, EACH WITH
FOUR 250 KCMIL AND ONE #2G
4/0G
T500P TWO 3-INCH CONDUITS, EACH WITH
THREE 500 KCMIL AND ONE 1/0G
T500S FIVE 3-1/2-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 250 KCMIL G
T500S2 TWO 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 1/0G
350 KCMIL G
NOTES:
1. FEEDER TAGS WITH A " * " IN THE TAG HAVE BEEN INCREASED IN SIZE TO ACCOUNT FOR VOLTAGE DROP.
2. COORDINATE PANEL LUG SIZE AND QUANTITIES WITH THE SPECIFIED CONDUCTOR SIZES AND NUMBER OF PARALLEL RUNS AS APPLICABLE. LUG SIZES AND QUANTITIES MUST ACCOUNT FOR CONDUCTORS THAT WERE INCREASED IN SIZE AND/OR PARALLEL RUNS ADDED TO ACCOUNT FOR VOLTAGE DROP.
3. ALUMINUM CONDUCTORS ARE NOT PERMITTED TO BE SUBSTITUTED FOR COPPER CONDUCTORS SIZED #
4 CU AWG OR SMALLER.
NOTE:
1. ALL PRIMARY AND SECONDARY CONDUCTORS FOR DRY-TYPE TRANSFORMERS SHALL BE COPPER.
(CONDUCTOR SIZE VS LENGTH)
SCHEDULE
BONDING BACKBONE (TBB)
TELECOMMUNICATIONS
TBB LINEAR LENGTH
(FT)
TBB SIZE
(AWG)
LESS THAN 13 6
14 - 20 4
21 - 26 3
27 - 33 2
34 - 41 1
42 - 52 1/0
53 - 66 2/0
67 - 84 3/0
85 - 105 4/0
106 - 125 250 KCMIL
126 - 150 300 KCMIL
151 - 175 350 KCMIL
176 - 250 500 KCMIL
251 - 300 600 KCMIL
GREATER THAN 301 750 KCMIL
NOTES:
1. THE BONDING CONDUCTOR FOR
TELECOMMUNICATIONS (BCT) SHALL BE, AS
MINIMUM, THE SAME SIZE AS THE LARGEST TBB.
2. THE BCT AND TBB SHALL BE GREEN OR MARKED
WITH A DISTINCTIVE GREEN COLOR.
LD2G
500A
MCB
XFMR - T2G
150 KVA
480:
208/120V
TO EXISTING SWITCHGEAR S3L
IN VAULT 4, BASEMENT LEVEL
L2GC
225A
MCB
CKTS
225CU
ECB
150A
TO EXISTING SWITCHGEAR S3L
IN VAULT 4, BASEMENT LEVEL
P2GC
100A
MCB
100CU
SPD
20CU
UL 1449
5TH EDITION
SPD
20CU
UL 1449
5TH EDITION
PD2G
400A
MCB
LD2G
500A
MCB
XFMR - T2G
150 KVA
480:
208/120V
TO EXISTING SWITCHGEAR S3L
IN VAULT 4, BASEMENT LEVEL
L2GC
225A
MCB
ECB
150A
TO EXISTING SWITCHGEAR S3L
IN VAULT 4, BASEMENT LEVEL
P2GC
100A
MCB
PD2G
400A
MCB
ELECTRICAL DEMOLITION ONE-LINE DIAGRAM ELECTRICAL NEW WORK ONE-LINE DIAGRAM
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
ELECTRICAL ONE-LINE DIAGRAM
E-601
-2
E -6
/0
/1
.p d f
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-600 FOR ELECTRICAL FEEDER SCHEDULES.
3. REFER TO E-602 FOR GROUNDING RISER DIAGRAM.
SCALE: N.T.S.1
ELECTRICAL ONE LINE DIAGRAM
PLAN LEGEND
DEMOLISHED
NEW WORK
EXISTING
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
LIFE SAFETY AND FIRE PROTECTION:
STANTON ENGINEERING SERVICES
10280 OLD COLUMBIA RD
STE 275
COLUMBIA, MD 21046
(410) 290-9301
PROFESSIONAL SEAL:
Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR
SUITE 350
CALVERTON, MD 20705
443-388-7351
ARCHITECTURE & MEP:
RAYMOND ENGINEERING
1601 SUMMIT AVE
RICHMOND, VA 23230
804-726-9540
05/20/2022
652-20121
C.B.F.K.
RENOVATION OF OLD DIALYSIS
AREA 2H
CONSTRUCTION BID SET
LUMINAIRE AND MECHANICAL
EQUIPMENT SCHEDULE
E-602
-2
E -6
/0
/1
.p d f
SHEET NOTES:
LUMINAIRE SCHEDULE
FIXTUR
E DESCRIPTION MANUFACTURER Model LAMP
LUMEN
S CRI CCT Voltage Wattage MOUNTING NOTES
A 2x4 LED TROFFER LIGHT FIXTURE LITHONIA LIGHTING 2VTL4-40L-ADP-EZ1-LP835 LED 4000 82 3500K 277 40 W RECESSED
AE 2x4 LED TROFFER LIGHT FIXTURE EMERGENCY LITHONIA LIGHTING 2VTL4-40L-ADP-EZ1-LP835-EL14L LED 4000 82 3500K 277 40 W RECESSED PROVIDE UL-924 90 MINS BATTERY BACKUP TO ALL EMERGENCY FIXTURES SHOWN
B 2X2 LED TROFFER LIGHT FIXTURE LITHONIA LIGHTING 2BLT2-RB-40L-ADP-EZ1-LP83 LED 82 3500K 277 32 W RECESSED
BE 2X2 LED TROFFER LIGHT FIXTURE EMERGENCY LITHONIA LIGHTING 2BLT2-RB-40L-ADP-EZ1-LP835-EL14LSD LED 82 3500K 277 32 W RECESSED
C 6" LED DOWNLIGHT FXUTRE CREE LIGHTING S-DL6T-M-SS-C LED 2678 90 3500K 277 34 W RECESSED
X LED EXIT SIGN EXITRONIX S900U-WB-SR-RM-AG LED N/A N/A N/A 277 SURFACE
NOTES:
1. DESIGN BASIS SHOWN FOR REFERENCE ONLY. FIXTURES OF EQUAL QUALITY AND PERFORMANCE ARE ACCEPTABLE. ALL FIXTURES MUST BE EQUAL IN MATERIAL, QUALITY, WARRANTY, PHOTOMETRIC, SIZE AND FINISH.
2. VERIFY CEILING TYPES WITH ARCHITECTURAL DRAWINGS PRIOR TO ORDERING.
3. WIRE EXIT SIGNS AHEAD OF ALL LOCAL SWITCHING.
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
LUMINAIRE CONTROL SCHEDULE
SPACE TYPE ROOM NUMBER M
A
N U
A L O
N
M A
N U
A L O
F F
L O
W -V
O L
T A
G E
D
IM
M
IN
G S
Y S
T E
M
L
IN
E V
O L T
A G
E D
IM
M
IN
G
S W
IT
C
H
O C
C U
P A
N C
Y S
E N
S O
R O
N
O C
C U
P A
N C
Y S
E N
S O
R O
F F
V A
C A
N C
Y S
E N
S O
R O
F F
A U
T O
B I-
L E
V E
L C
O N
T R
O L
A S
T R
O N
O M
IC
A
L T
IM
E
C L O
C K
A S
T R
O N
O M
IC
A
L T
C W
IT
H
P H
O T
O C
E L
L C
O N
T R
O L
IN
T
E G
R A
L M
O T
IO
N
C O
N T
R O
L
D A
Y L
IG
H T
D
IM
M
IN
G C
O N
T R
O L
CONTROLS NARRATIVE
MECHANICAL/ ELECTRICAL/ ELEVATOR MACHINE X X PROVIDE MANUAL ON/OFF SWITCH(ES) AT EACH ROOM ENTRY. NO OCCUPANCY SENSORS PERMITTED.
LOBBY X X PROVIDE ON/OFF OCCUPANCY CONTROL WITH LOCAL OVERRIDE SWITCH.
CORRIDOR X X PROVIDE ON/OFF OCCUPANCY CONTROL.
VESTIBULE X X PROVIDE ON/OFF OCCUPANCY CONTROL.
BREAK X X X X PROVIDE VACANCY OFF CEILING.WALL MOUNTED SENSOR(S) WITH LOCAL OVERRIDE SWITCH.
STORAGE X X X PROVIDE VACANCY OFF CEILING/WALL MOUNTED SENSOR(S) WITH LOCAL OVERRIDE SWITCH.
STAIR X X PROVIDE STAIRWELL LUMINAIRE WITH INTEGRAL OCCUPANCY SENSOR CONTROL TO FULL OUTPUT UPON SENSING OCCUPANCY. SET INTEGRAL DIMMING DRIVER TO 20%
LIGHT OUTPUT SETTING AFTER 20 MINUTES OF VACANCY.
IT/ COMM ROOMS X X PROVIDE MANUAL ON/OFF SWITCH(ES) AT EACH ROOM ENTRY. NO OCCUPANCY SENSORS PERMITTED.
JANITOR X X X PROVIDE VACANCY OFF CEILING/WALL MOUNTED SENSOR(S) WITH LOCAL OVERRIDE SWITCH.
PRIVATE OFFICE X X X X PROVIDE VACANCY OFF WALL MOUNTED SENSOR(S) WITH LOCAL OVERRIDE SWITCH.
OPEN OFFICE X X X X PROVIDE VACANCY OFF CEILING/WALL MOUNTED SENSOR(S) WITH LOCAL OVERRIDE SWITCHES.
BATHROOMS X X PROVIDE ON/OFF OCCUPANCY CONTROL WITH LOCAL OVERRIDE SWITCH FOR RESTROOM AND LOCKER AREAS. PROVIDE VACANCY OFF WALL MOUNTED SENSOR WITH LOCAL
OVERRIDE SWITCH FOR SHOWER AREAS.
SMALL CONFERENCE X X X X X PROVIDE LOW-VOLTAGE VACANCY OFF - MANUAL ON CEILING MOUNTED SENSOR(S) WITH LOCAL OVERRIDE LOW-VOLTAGE DIMMING CONTROL SWITCH. UPON LOSS OF POWER THE EMERGECNY LIGHT FIXTURES SHALL BE ILLUMINATED AT 100% FROM ANY LIGHTING CONTROL POSIT.ION
LARGE CONFERENCE ROOM X X X X X PROVIDE LOW-VOLTAGE VACANCY OFF - MANUAL ON CEILING MOUNTED SENSOR(S) WITH LOCAL OVERRIDE LOW-VOLTAGE DIMMING CONTROL SWITCHES. UPON LOSS OF POWER THE EMERGECNY LIGHT FIXTURES SHALL BE ILLUMINATED AT 100% FROM ANY LIGHTING CONTROL POSIT
EXTERIOR/ BUILDING MOUNTED…