RVA1033004_Mechanical.pdf

PDF 2 MB Posted

Attached to
Y1DA--Renovate Old Dialysis 2H Richmond VA Medical Center
Solicitation number
36C24623B0024
Issued by

About this file

This is a solicitation for renovating the old dialysis area at the Richmond VA Medical Center. The solicitation seeks mechanical, electrical, and plumbing (MEP) construction services including installation of new HVAC equipment, ductwork, piping, controls, and associated construction. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6. The response due date is not provided. Construction is to begin upon award. Pricing is to be provided using the Standard Form 1442 lump sum pricing format. The solicitation is unrestricted and open to all responsible sources.

View the file

Other files

File Type Posted
BID OPENING Abstract 36C24623B0024.pdf PDF
BID OPENING Attendance Log 36C24623B0024.pdf PDF
SITE VISIT Attendance Log 36C24623B0024.pdf PDF
36C24623B0024 0006.docx DOCX document
36C24623B0024 0005.docx DOCX document
36C24623B0024 0004.docx DOCX document
36C24623B0024 0003.docx DOCX document
36C24623B0024 0002.docx DOCX document
36C24623B0024 0001.docx DOCX document
Attachment A - Itemized Schedule of Values Cost Breakdown.xlsx XLSX spreadsheet
INSTRUCTIONS TO BIDDERS.pdf PDF
36C24623B0024_1.docx DOCX document
RVA1033004_Plumbing-revised.pdf PDF
RVA1033004_Life Safety Set.pdf PDF
RVA1033004_Architecture.pdf PDF
RVA1033004_Electrical.pdf PDF
RVA1033004_Telecom Set.pdf PDF
Specifications Vol 1.pdf PDF
Specifications Vol 2.pdf PDF
RVA1033.004_PL_Addendum_1_2023-03-24.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NAMING CONVENTION

M-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DISCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

GENERAL MECHANICAL NOTES

1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS MADE. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. ALL TRANSITIONS, ELBOWS, ETC.

REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER

TRADES SHALL BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.

2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED

OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.

3. AT START OF CONSTRUCTION PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK, AND

SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.

4. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

5. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, UNIFIED FACILITIES

CRITERIA, AND INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.

6. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING

REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.

7. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT

BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.

8. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR.

9. CAULK WITH SILICONE ALL GAPS BETWEEN WALL, CEILING AND FLOOR OPENINGS AND HVAC EQUIPMENT PENETRATIONS.

PATCH LARGE GAPS BEFORE CAULKING IS APPLIED. [REFER TO SPECIFICATION SECTION 23 00 00 - AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS, SUBSECTION 2.1.2].

10. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE. REFER TO STRUCTURAL DRAWINGS AND SPECIFICATIONS FOR CONSTRUCTION TYPES. PROCURE AND INSTALL UPON APPROVAL FROM [CONTRACTING OFFICER] [GENERAL CONTRACTOR] [ARCHITECT]. PROVIDE STRUCTURAL STEEL SUPPORT SUBMITTAL TO ENGINEER OF RECORD FOR REVIEW.

11. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE PRESSURE

CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.

12. VOLUME DAMPERS SHALL BE PROVIDED AT EACH NEW MAIN BRANCH TAKE-OFF AND IN SUCH OTHER LOCATIONS WHERE

REQUIRED TO PROPERLY BALANCE THE SYSTEM.

13. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE INSTALLED.

14. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF [CONTRACTING OFFICER] [GENERAL CONTRACTOR] [ARCHITECT]. PROVIDE TURNING VANES IN ALL 45° AND 90° SQUARE ELBOWS. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. TURNING VANES LONGER THAN

36 INCHES SHALL BE DOUBLE THICKNESS TYPE.

15. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET

CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.

16. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH.

BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE

CRUSHED OR DISTORTED IN ITS FINAL CONFIGURATION.

17. ROUND DUCTWORK CONNECTIONS BETWEEN MAIN DUCT AND TERMINAL UNITS SHALL BE RIGID DUCT OF THE SAME DIAMETER

AS TERMINAL UNIT INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.

18. PROVIDE SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT.

TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT CONNECTORS SHALL BE USED ON FINAL CONNECTION TO

AIR HANDLING EQUIPMENT.

19. DIMENSIONS SHOWN FOR DIFFUSERS AND GRILLES ARE NECK DIMENSIONS.

20. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY ARCHITECTURAL REFLECTED

CEILING PLAN.

21. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS.

ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.

22. EXACT LOCATIONS OF THERMOSTATS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL

AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS MINIMUM 48" AFF.

23. SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 90.1. EXTERIOR SUPPLY

AND RETURN AIR DUCTWORK SHALL BE PROVIDED WITH WEATHER-PROOF COVER.

24. SIZE REFRIGERANT LINES PER MANUFACTURER'S INSTRUCTIONS FOR ACTUAL LINE LENGTHS AND EQUIPMENT ELEVATIONS INSTALLED. USE OF HCFC AND CFC REFRIGERANTS IS PROHIBITED. EXTERIOR REFRIGERANT LINES SHALL BE INSULATED AND

HAVE ALUMINUM JACKETING.

25. COORDINATE LOCATIONS OF CONDENSATE DRAIN PIPING. PROVIDE CONDENSATE PUMPS AS REQUIRED WHERE SUFFICIENT SLOPE IS NOT AVAILABLE FOR STANDARD GRAVITY DRAIN, WITH OVERRIDE SWITCH TO POWER DOWN THE ASSOCIATED AIR HANDLING EQUIPMENT IN CASE OF CONDENSATE PUMP FAILURE. CONDENSATE DRAIN LINE SHALL SLOPE DOWN TOWARDS DISCHARGE LOCATION AT A MINIMUM OF 1/8" PER LINEAR FOOT. INSULATE INDOOR CONDENSATE PIPING WITH 3/4" CLOSED CELL

FOAM INSULATION.

26. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.

27. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL DUCTWORK AND PIPING SYSTEMS

CROSSING BUILDING EXPANSION JOINTS.

28. PROVIDE EXPANSION LOOPS OR APPROVED FLEXIBLE PIPE EXPANSION DEVICES FOR PIPING SYSTEMS WITH OPERATING TEMPERATURES ABOVE 70°F OR BELOW 50°F. PIPE SUPPORTS FOR PIPING SYSTEMS WITH EXPANSION DEVICES OR EXPANSION

LOOPS SHALL HAVE ROLLER SUPPORTS.

29. PROVIDE AUTOMATIC AIR VENTS AT HIGH POINTS OF HYDRONIC PIPING SYSTEMS. PROVIDE DRAIN VALVES AT THE LOW POINTS

IN HYDRONIC PIPING SYSTEMS FOR DRAINAGE.

30. PROVIDE SHUT-OFF VALVES AND FLEXIBLE CONNECTIONS AT PIPE CONNECTIONS TO HVAC EQUIPMENT.

31. FOR WALL, FLOOR, AND SLAB PENETRATIONS SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING OR AS

SHOWN ON MECHANICAL DETAILS SHEET.

32. INSTALL EXPOSED CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.

33. BRANCH VALVES AND DRAINS SHALL BE PROVIDED TO ENABLE ISOLATING A SECTION FOR MAINTENANCE WITHOUT SHUTTING

DOWN ENTIRE SYSTEM.

34. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY. REFER TO SPECIFICATIONs FOR COMPLETE REQUIREMENTS.

35. PIPING INSULATION SHALL BE PROVIDED ON ALL PIPING SYSTEMS INCLUDING (BUT NOT LIMITED TO) CHILLED WATER, HEATING HOT WATER, CONDENSER WATER, REFRIGERANT, AND CONDENSATE DRAIN IN ACCORDANCE WITH ASHRAE 90.1.

36. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE

OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

37. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.

38. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

39. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, SPIRAL

DUCTWORK WITH COATING.

40. IF ASBESTOS IS FOUND, STOP WORK IMMEDIATELY AND NOTIFY OWNER AND GENERAL CONTRACTOR. OWNER IS RESPONSIBLE

FOR ABATEMENT OF ASBESTOS.

41. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

MECHANICAL GENERAL NOTES AND

DESIGN CRITERIA

M-001

-2

M -0

/1

/1

.p d f

HVAC DESIGN CRITERIA

PROJECT LOCATION: WEATHER STATION,

STATE

LATITUDE: 37.18 N

ELEVATION: 194 FT.

STANDARD DESIGN CONDITIONS

WINTER DESIGN DRY BULB (99.0%): 19.3 °F

SUMMER DESIGN DRY BULB (1.0%): 94.6 °F

SUMMER DESIGN WET BULB (1.0%): 76.4 °F

INDOOR DESIGN CONDITIONS

SPACE CATEGORY

COOLING HEATING

OCC.

DRY

BULB

(°F)

UNOCC.

DRY

BULB

(°F)

OCC.

DP

(°F)

OCC.

DRY

BULB

(°F)

UNOCC.

DRY

BULB

(°F)

AMB. +

[10°F]

AMB. +

[10°F]

N / A 55 55

ADMINISTRATION SPACES 75 85 57.9 68 55

COMM ROOMS 75 75 62.5 40 40

ENTRANCE VESTIBULES N / A N / A N / A 55 40

STORAGE 78 85 57.9 68 55

NOTES:

1. EXISTING EQUIPMENT IS SHOWN WITH THIN LINEWORK.

2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK,

DASHED, AND HATCHED.

3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD

LINEWORK.

4. BELOW IS AN EXAMPLE OF EACH:

EXISTING EQUIPMENT

EQUIPMENT TO BE DEMOLISHED

NEW OR RELOCATED EQUIPMENT

GENERAL MECHANICAL ABBREVIATIONS

@ AT

& AND

AFF ABOVE FINISHED FLOOR

A/C ABOVE CEILING

AC AIR CONDITIONER

AD AUTOMATIC DAMPER

ADJ ADJUSTABLE

AMB AMBIENT

ARCH ARCHITECT, ARCHITECTURAL

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATING, AND AIR CONDITIONING

ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING AND

MATERIALS

AUX AUXILIARY

BD BACKDRAFT DAMPER

BLDG BUILDING

BOD BOTTOM OF DUCT

B/F BELOW FLOOR

B/S BELOW SLAB

BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CLG COOLING

CO2 CARBON DIOXIDE

CONN CONNECT, CONNECTING, CONNECTION

CONT CONTINUED

COP COEFFICIENT OF PERFORMANCE

COR CONTRACTING OFFICER'S (OWNER'S)

REPRESENTATIVE

CU CONDENSING UNIT

D DEPTH

DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS

DDC DIRECT DIGITAL CONTROLS

DEG. F (°F) DEGREES FAHRENHEIT

DIA DIAMETER

DIV DIVISION

DN DOWN

DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP

DSCU DUCTLESS SPLIT CONDENSING UNIT

DSS DUCTLESS SPLIT SYSTEM (INDOOR UNIT)

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRICAL

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXT EXTERIOR

EXH EXHAUST

EXST, (E) EXISTING

FD FIRE DAMPER

FFE FINISHED FLOOR ELEVATION

FLA FULL LOAD AMPS

FPM FEET PER MINUTE

FSD FIRE SMOKE DAMPER

FT FOOT, FEET

FT WG FEET WATER GAUGE

GA GAGE

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

H HEIGHT

HR HOUR

HTG HEATING

HTR HEATER

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HZ HERTZ

IMC INTERNATIONAL MECHANICAL CODE

IN INCH, INCHES

IN WC INCHES WATER COLUMN

IN WG INCHES WATER GAUGE

IPLV INTEGRATED PART LOAD VALUE

KW KILOWATTS

L LENGTH, LOUVER (WALL)

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LBF/IN2 POUNDS FORCE PER SQUARE INCH

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MECH MECHANICAL

MFR, MFG MANUFACTURER, MANUFACTURING

MIN MINIMUM

MOCP, MOP MAXIMUM OVER CURRENT PROTECTION

MOD MOTOR OPERATED DAMPER

MTD MOUNTED

MVD MANUAL VOLUME DAMPER

NC NOISE CRITERIA

N.C. NORMALLY CLOSED

NO. NUMBER

N.O. NORMALLY OPEN

NPLV NET PART LOAD VALUE

NTS NOT TO SCALE

OA OUTSIDE AIR

OD OUTSIDE DAMPER

PD PRESSURE DROP

PH PHASE

PLBG PLUMBING

PPM PARTS PER MILLION

PRV PRESSURE RELIEF VALVE

QTY QUANTITY

RA RETURN AIR

RG RETURN GRILLE

RH RELATIVE HUMIDITY, ROOF HOOD

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID

RM ROOM

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

SA SUPPLY AIR

SD SMOKE DAMPER, SMOKE DETECTOR

SEER SEASONAL ENERGY EFFICIENCY RATIO

SF SUPPLY FAN

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTOR'S NATIONAL ASSOCIATION

SP STATIC PRESSURE

SS STAINLESS STEEL

TSTAT THERMOSTAT

TEMP TEMPERATURE

TYP TYPICAL

UL UNDERWRITER'S LABORATORY

V VOLTAGE, VOLTS

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VELO VELOCITY

W WATT(S)

W/ WITH

W/O WITHOUT

WB, Twb WET BULB (TEMPERATURE)

WD WIDE, WIDTH

WMS WIRE MESH SCREEN

AIR DISTRIBUTION DEVICE TAGS

DIFFUSER TYPE

A

400 AIRFLOW (CFM), "PLENUM", OR "TRANSFER"

A1

M-501

PLAN NORTH

TRUE

NORTH

DRAWING REFERENCE KEY

REFER TO

DETAIL NUMBER

SHEET NUMBER OF DETAIL

RE:A1/M-501

NORTH ARROW

A CONTROL WIRING

ROUND

MISCELLANEOUS LEGENDPIPING LEGEND

EXPANSION JOINT

FLEXIBLE CONNECTION

CLEANOUT

WATER METER

FLOOR CLEANOUT

THERMOMETER

PRESSURE REDUCING VALVE

MANUAL AIR VENT

PRESSURE/TEMPERATURE TAP WITH

BALL VALVE

PRESSURE SWITCH

PLUG VALVE

FLOW SWITCH

T&P RELIEF VALVE

AUTOMATIC AIR VENT

PRESSURE GAUGE WITH GAUGE COCK

PS

FS

BUTTERFLY VALVE

STRAINER WITH BLOWDOWN VALVE,

CAP, AND CHAIN

FLOW MEASURING/BALANCING/SHUT-

OFF VALVE

GATE VALVE

CHECK VALVE

BALL VALVE

CONCENTRIC REDUCER

DIRECTION OF FLOW

DIRECTION OF SLOPE DOWN

ECCENTRIC REDUCER

PIPE FLANGE

PIPE CAP

PIPE GUIDE (PG)

PIPE ANCHOR (PA)X

UNION

TEE OUTLET UP

CONDENSATE DRAIN

BRANCH BOTTOM CONNECTION

BRANCH TOP CONNECTION

ELBOW UP

ELBOW DOWN

RISE OR DROP

TEE OUTLET DOWN

M

M

FIRE DAMPER

H

DUCT MOUNTED HUMIDIFIER

EXHAUST AIR DUCT DOWN

EXHAUST AIR DUCT UP

RETURN AIR DUCT DOWN

30"x14"

SQUARE TO ROUND DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

FLARED SPIN-IN WITH DAMPER AND

FLEX DUCT (DIFFUSER CONNECTION)

ROUND DUCT BRANCH TAKE-OFF FROM

RECTANGULAR MAIN WITH CONICAL TAP

FLEXIBLE DUCT CONNECTION FLOW ARROW

DUCT SIZE TRANSITION

RECTANGULAR DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

90 DEGREE DUCT ELBOW WITH TURNING VANES

24"Ø

DUCTWORK LEGEND

RETURN AIR DEVICE

ROUND DUCT. DIAMETER INDICATED IN INCHES.

IN-LINE 90 DEGREE RISE/DROP IN

SUPPLY DUCT (RIGHT SIDE IS HIGHER)

IN-LINE 90 DEGREE RISE/DROP IN

SUPPLY DUCT (LEFT SIDE IS HIGHER)

FD

SD

P - PNEUMATIC-ACTUACTED DAMPER

DAMPER TYPE:

M - MOTORIZED DAMPER (ELECTRIC)

VD

SMOKE DAMPER

VOLUME/BALANCING DAMPER

(LABEL MAY BE OMITTED)

BD

BACKDRAFT DAMPER

(COUNTER-BALANCED UNLESS

OTHERWISE NOTED)

RADIUS DUCT ELBOW - ROUND OR

RECTANGULAR (MIN. 1.5 RADIUS UNLESS

OTHERWISE NOTED)

RECTANGULAR DUCT. SIZE INDICATED IN

INCHES, FIRST NUMBER IS SIDE SHOWN.

DASHED LINES INDICATE ACOUSTICAL LINER

SUPPLY AIR DIFFUSER -

FLOW ARROWS INDICATE AIR PATTERN.

NO FLOW ARROWS SHOWN INDICATES

4-WAY PATTERN.

FSD

COMBINATION

FIRE/SMOKE DAMPER

EXHAUST AIR DEVICE

SERVICE CLEARANCE

T THERMOSTAT

REFRIGERANT LIQUIDRL

HEATING HOT WATER RETURNHWR

HEATING HOT WATER SUPPLYHWS

REFRIGERANT SUCTIONRS

CD

DEMOLISHED

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

IN-LINE 90 DEGREE RISE/DROP IN

RETURN DUCT (RIGHT SIDE IS HIGHER)

DUCT SIZE TRANSITION RECTANGULAR TO

ROUND

30"/14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES,

FIRST NUMBER IS SIDE SHOWN

RETURN AIR DUCT UP

SUPPLY OR OUTSIDE AIR DUCT DOWN

SUPPLY OR OUTSIDE AIR DUCT UP

IN-LINE 90 DEGREE RISE/DROP IN

RETURN DUCT (LEFT SIDE IS HIGHER)

IN-LINE 90 DEGREE RISE/DROP IN

EXHAUST DUCT (RIGHT SIDE IS HIGHER)

IN-LINE 90 DEGREE RISE/DROP IN

EXHAUST DUCT (LEFT SIDE IS HIGHER)

DEMOLITION KEY

CONNECTION SIZE

(X"xX" INDICATES RECTANGULAR, X"/X"

INDICATES OVAL, X"Ø INDICATES ROUND)

X"xX"

TYP. OF #

TYPICAL OF QUANTITY INDICATED

FLEXIBLE PIPE CONNECTION

SKD

DUCT MOUNTED SMOKE DETECTOR

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

MECHANICAL ABBREVIATIONS AND

LEGENDS

M-002

-2

M -0

/2

/1

.p d f

16 17 18 19 2015

X

Y

Z

AA

"x

"x

"x

"x

"x

16"x10"

14"x10" 16"x10"10"x8"8"x6"

14"x8"

20"x12"18"x12"

18"x12"

14"x12"

28"x12"

18"x8"18"x8"

16"x8"12"x8" 1 "x

10"x6"

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

LEVEL 1 MECHANICAL DEMOLITION

PLAN

MD-101

-2

M D

-1

/2

/1

.p d f

SHEET NOTES:

SCALE: 3/16" = 1'-0"A1

LEVEL 1 OVERALL HVAC DEMOLITION PLAN

1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL,

STRUCTURAL PLANS AND ELECTRICAL PLANS.

2. UNLESS NOTED OTHERWISE, MECHANICAL DEMOLITION SHALL

BE CARRIED OUT TO THE EXTENT SHOWN AND DEEMED

NECESSARY. CONTRACTOR SHALL VERIFY ALL EXISTING FIELD

CONDITIONS IN ORDER TO DETERMINE THE EXTENT OF WORK

UNDER THIS SECTION.

3. EXISTING EQUIPMENT AND ASSOCIATED DUCTWORK SHOWN

ON THE PLANS MAY NOT EXACTLY MATCH WITH THE FIELD

CONDITIONS. EQUIPMENT AND DUCTWORK LOCATION

DEPICTED HERE IS FOR PURPOSE OF COORDINATION.

CONTRACTOR SHALL VERIFY EXISTING DUCTWORK ROUTING

AND LOCATIONS AND MAKE ADJUSTMENTS AS REQUIRED TO

AVOID CONFLICTS WITH NEW DUCTWORK, EQUIPMENT, LIGHT

FIXTURES ETC.

4. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING DUCT

DIMENSIONS AFTER PARTIAL DEMOLITION THAT REQUIRE

CONNECTION TO NEW DUCTWORK AND PROVIDE REQUIRED

TRANSITION PIECE TO NEW DUCTWORK.

5. BUILDING WILL BE IN OPERATION DURING CONSTRUCTION. ALL

SERVICE INTERRUPTIONS TO THE EXISTING FACILITY SHALL BE

SCHEDULED AND COORDINATED 3 WEEKS IN ADVANCE.

COORDINATE ALL DISRUPTIVE AND OUTAGE REQUIREMENTS

WITH COR.

6. CONTRACTOR TO PROTECT EXPOSED DUCT OPENINGS

DURING CONSTRUCTION.

7. REMOVE ALL DUCT INSULATION WHERE DUCT IS BEING

DEMOLISHED AND REPLACE PER SPECIFICATIONS. DUCT

LABELS SHALL BE INSTALLED EVERY 12 FT IN EXPOSED AREAS.

COLORS SHALL BE INDUSTRY STANDARD.

8. VAVs AND DUCTWORK SHOWN ON THE PLANS ARE LOCATED IN

THE INTERSTITIAL SPACE ABOVE THIS FLOOR.

9. DURING DEMOLITION TURN OVER THE EXISTING THERMOSTATS

TO COR OR THE FACILITIES TEAM.

10. CONTRACTOR TO PROVIDE PROTECTIVE DUCT FILM WRAP TO

EXISTING DUCTWORK AND ALL ASSOCIATED FITTINGS AND

VALVES DURING DEMOLITION AND CONSTRUCTION.

11. DEMOLISH ALL EXISTING CONTROLS INCLUDED BUT NOT

LIMITED TO THERMOSTATS, CONTROL WIRING.

1 DEMOLISH SUPPLY DIFFUSER, ASSOCIATED DAMPER, SUPPLY

DUCT AND VAV UPTO THE MAIN SUPPLY DUCT AND PROTECT

OPENING DURING CONSTRUCTION.

(TYP.)

KEY NOTES:

2 DEMOLISH RETURN REGISTER, ASSOCIATED VOLUME DAMPER

AND RETURN DUCT UPTO THE MAIN RETURN DUCT AND

PROTECT OPENING DURING CONSTRUCTION.

(TYP.)

(TYP.)

3 DEMOLISH EXHAUST GRILLE, ASSOCIATED VOLUME DAMPER

AND EXHAUST DUCT UPTO THE MAIN EXHAUST DUCT AND

PROTECT OPENING DURING CONSTRUCTION.

16 17 18 19 20

W

X

Y

Z

AA

T

VAV-1

VAV-2

VAV-3

VAV-4

VAV-13

VAV-5

VAV-8

VAV-7

VAV-9

VAV-10 VAV-11

VAV-6

1" HWR

1" HWS

1" HWR

1" HWS

1" HWS 1" HWR

1" HWR

1" HWS

1" HWS

1" HWR

1" HWR 1" HWS

/4

H

W S

/4

H

W R

VAV-14

VAV-15

AC-1

BREAK/MEETING

ROOM

2H-104

CLOSET

2H-123

TOUCHDOWN

2H-103

TOUCHDOWN

2H-120

ANESTHESIA

2-PERSON

OFFICE

2H-115

ANESTHESIA

OFFICE

2H-114

TOUCHDOWN

2H-121

STORAGE

2H-105

ELEC. CLOSET

2H-106

IT CLOSET

2H-107

RESIDENTS

2H-122

NEW 2-PERSON

ENGINEERING

OFFICE

2K-140A

NEW

ENGINEERING

OFFICE

2H-140B

TOUCHDOWN

2H-111

ANESTHESIA

OFFICE

2H-118

ANESTHESIA

OFFICE

2H-119

ANESTHESIA

OFFICE

2H-113

STAFF LOCKER

2H-110

CORRIDOR

C2H-6

CORRIDOR

C2H-7

CORRIDOR

C2H-5

CORRIDOR

C2H-4

ANESTHESIA

ADMIN.

2H-112

WELLNESS ROOM

2H-108

STAFF TOILET

2H-109

ANESTHESIA

OFFICE

2H-116

ANESTHESIA

OFFICE

2H-117

VESTIBULE

2K-140C

CORRIDOR

C2H-4

STORAGE

2H-141B

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

MECHANICAL PIPING PLAN

MP-101

-2

M P

-1

/1

/2

.p d f

SCALE: 3/16" = 1'-0"1

LEVEL 1 OVERALL HVAC PIPING PLAN

SHEET NOTES:

1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND

DESIGN CRITERIA.

2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND

LEGENDS.

3. DUCTWORK , VAVs , REHEAT COILS , HOT WATER PIPING AND

ASSOCIATED VALVES SHOWN ON THE FLOOR PLAN FOR

CONNECTIVITY AND CLARITY ARE LOCATED IN THE

INTERSTITIAL SPACE ABOVE THIS FLOOR.

4. REFER TO MECHANICAL SCHEDULES FOR RUN OUT PIPE SIZES

TO THE VAVs.

5. ALL HOT WATER PIPING AND ASSOCIATED VALVES SHOWN ON

THE FLOOR PLAN ARE LOCATED IN THE INTERSTITIAL SPACE

ABOVE THIS FLOOR.

1 EXISTING HOT WATER LINES FROM EXISTING BOILER ROOM

2 POINT OF CONNECTION OF NEW HOT WATER LINES WITH THE

EXISTING HOT WATER LINES.

KEY NOTES:

3 ROUTE CONDENSATE DRAIN FROM AC-1 TO SANITARY LINE AT

THE TOILET AS SHOWN.

16 17 18 19 20

W

X

Y

Z

AA

TOUCHDOWN

2H-103

BREAK/MEETING

ROOM

2H-104

CORRIDOR

C2H-6

TOUCHDOWN

2H-121

TOUCHDOWN

2H-120

RESIDENTS

2H-122

CORRIDOR

C2H-5

IT CLOSET

2H-107

ELEC. CLOSET

2H-106

ANESTHESIA

ADMIN.

2H-112

TOUCHDOWN

2H-111

ANESTHESIA

OFFICE

2H-116

NEW 2-PERSON

ENGINEERING

OFFICE

2K-140A

STAFF TOILET

2H-109

WELLNESS ROOM

2H-108

NEW

ENGINEERING

OFFICE

2H-140B

STAFF LOCKER

2H-110

10"Ø

SD-1

325 CFM

10"Ø

SD-1

325 CFM

10"Ø

SD-1

350 CFM

10"Ø

SD-1

350 CFM

12"Ø

SD-1

450 CFM

8"Ø

SD-1

260 CFM

8"Ø

SD-1

260 CFM

8"Ø

SD-1

260 CFM

8"Ø

SD-1

250 CFM

6"Ø

SD-1

150 CFM

6"Ø

SD-1

100 CFM

6"Ø

SD-1

100 CFM

6"Ø

SD-1

100 CFM

8"Ø

SD-1

200 CFM

6"Ø

SD-1

100 CFM

6"Ø

SD-1

100 CFM

6"Ø

SD-1

50 CFM

10"Ø

SD-1

300 CFM

10"Ø

SD-1

300 CFM

10"Ø

SD-1

300 CFM

10"Ø

SD-1

300 CFM

6"Ø

SD-1

125 CFM

6"Ø

SD-1

125 CFM

6"Ø

SD-1

125 CFM

6"Ø

SD-1

125 CFM

12"x10"10"Ø

"x

"x

12"Ø

14"x10"10"Ø

"Ø

12"x10"10"Ø

"x

16"x10"8"Ø

12"x10"

RG-1

650 CFM

12"x10"

"x

12"x10"

RG-1

500 CFM

6"x6"

RG-1

100 CFM8"x8"

RG-1

150 CFM

16"x8"

"x

12"x10"

"x

10"x10"

RG-1

450 CFM

12"x10"

RG-1

700 CFM

8"x8"

RG-1

250 CFM

6"x6"

RG-1

100 CFM

6"x6"

RG-1

100 CFM

6"x6"

RG-1

200 CFM

T

T

T

T

T

T

T

T T

T

T

VAV-1

VAV-2

VAV-3

VAV-4

VAV-5

VAV-6

VAV-7

VAV-8

VAV-9

VAV-10 VAV-11

VAV-13

ANESTHESIA

OFFICE

2H-117

6"Ø

SD-1

100 CFM

6"Ø

SD-1

100 CFM

ANESTHESIA

OFFICE

2H-119

10"x8"

6"x6"

RG-1

100 CFM

6"Ø

8"Ø

10"x8"

12"x10"

RG-1

390 CFM

12"x10"

RG-2

600 CFM

10"x8"

SD-2

300 CFM

10"x8"

10"x8"

EG-2

300 CFM

10"x8"

6"x6"

RG-1

100 CFM

ANESTHESIA

2-PERSON

OFFICE

2H-115

ANESTHESIA

OFFICE

2H-113 6"x6"

RG-1

100 CFM

STORAGE

2H-105

STORAGE

2H-141B

ANESTHESIA

OFFICE

2H-118 8"x8"

EG-1

100 CFM

8"x8"

EG-1

100 CFM

6"Ø

SD-1

100 CFM

6"x6"

EG-1

50 CFM

6"x6"

RG-1

100 CFM

10"x8"

"x

"x

"x

6"x6"

RG-1

100 CFM

6"Ø

SD-1

100 CFM

6"Ø

SD-1

50 CFM

"x

6"x6"

RG-1

100 CFM

T

T

6"Ø

SD-1

50 CFM

VAV-14

VAV-15

T

8"x8"

RG-1

150 CFM

12"x10"

RG-1

600 CFM

12"x10"

RG-1

390 CFM

AC-1

ANESTHESIA

OFFICE

2H-114

8"x6"

EG-1

50 CFM

8"x6"

EG-1

50 CFM

12"x8"

8"x6"

8"x6"

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

LEVEL 1 MECHANICAL FLOOR PLAN

M-101

-2

M -1

/2

/1

.p d f

SCALE: 3/16" = 1'-0"A1

LEVEL 1 MECHANICAL PLAN

SHEET NOTES:

1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND

DESIGN CRITERIA.

2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND

LEGENDS.

3. REFER TO ARCHITECTURAL DWGS FOR EXACT LOCATIONS AND

MOUNTING HEIGHTS FOR SUPPLY DIFFUSERS, RETURN

REGISTERS AND EXHAUST GRILLES.

4. RUNOUTS TO TERMINAL UNITS SHALL BE SAME SIZE AS INLET

DIAMETERS TO VAV BOXES AS SCHEDULED.

5. RUNOUTS TO SUPPLY DIFFUSERS, RETURN REGISTERS AND

EXHAUST GRILLES SHALL BE SAME SIZE AS NECK SIZE OF THE

RESPECTIVE DIFFUSERS, REGISTERS AND GRILLES.

6. DUCTWORK , VAVs , REHEAT COILS , HOT WATER PIPING AND

ASSOCIATED VALVES SHOWN ON THE FLOOR PLAN FOR

CONNECTIVITY AND CLARITY ARE LOCATED IN THE

INTERSTITIAL SPACE ABOVE THIS FLOOR.

1 PROVIDE NEW VAV AS SCHEDULED. DUCT RUNOUT TO VAV

BOX SHALL BE THE SAME AS INLET DIAMETER TO VAV AS

SCHEDULED. PROVIDE NEW ASSOCIATED THERMOSTATS AND

INTEGRATE WITH EXISITNG BUILDING DDC SYSTEM.

2 PROVIDE NEW DIFFUSER WITH ASSOCIATED MANUAL VOLUME

DAMPER. FLEX DUCT RUNOUT TO SUPPLY AIR DIFFUSER

SHALL BE THE SAME AS NECK SIZE OF THE DIFFUSER.

3 PROVIDE NEW RETURN REGISTER WITH ASSOCIATED MANUAL

VOLUME DAMPER. FLEX DUCT RUNOUT TO SUPPLY AIR DIFFUSER

SHALL BE THE SAME AS NECK SIZE OF THE DIFFUSER.

KEY NOTES:

4 PROVIDE WALL MOUNTED INDOOR AC UNIT AS SHOWN.

OUTDOOR UNIT SHALL BE LOCATED ON THE ROOF. PROVIDE

REFRIGERANT PIPING FROM INDOOR UNIT TO THE OUTDOOR

UNIT PER MANUFACTURER'S RECOMMENDATIONS. ROUTE

CONDENSATE FROM THE INDOOR AC UNIT TO STAFF TOILET

2H-109 TO DRAIN INTO THE TOILET FIXTURE. REFER TO

MECHANICAL SCHEDULES M601 FOR MORE INFORMATION ON

AC-1 AND ACU-1.

SECTION "A-A"

"B" "B"

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING

GASKET

HANDLE INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

NOTE:

1.

2.

3.

4.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM

SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE

VANE TYPE.

W

W1

VANE

VANE

NOTE:

1.

2.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL

SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W

R

R

2/3W

/3

W

W W

1/2W

/3

W

1/6W

R

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED

CONNECTION ON FAN

SIDE

WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS ON

12" [300mm] CENTERS

RIVET ON 4"

[100mm] CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEMALTERNATE

POSITION

OF BOLT 1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

[15mm] [15mm] [40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

1/2" 1/2" 1 1/2"

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW AIR

FLOW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" [100mm]

MIN.

BRANCH DUCT

VD

W

2500 [1133]

1320 [598]

420 [190]ONE 1 [25] x 18 GA STRAP36 [900]

TWO 1/2 [13]∅ RODS

TWO 3/8 [10]∅. RODS

ONE 1 [25] x 16 GA STRAP

84 [2100]

60 [1500]

50 [1250] 700 [317]

ONE 1 [25] x 22 GA STRAP

QUANTITY/SIZEMAX. DUCT ∅

26 [650]

HANGER STRAPS OR RODS

MAX. LOAD

LBS. [kg]

260 [119]

MAX.

144 [3600]

IN. [mm]

SPACING

IN. [mm] IN. [mm]

144 [3600]

144 [3600]

144 [3600]

144 [3600]

NOTE:

TABULATED DATA FROM SMACNA

ALLOWS FOR DUCT REINFORCING AND

INSULATION, BUT NO EXTERNAL LOAD.

BAND

OVER 50"

[1250mm]∅

HANGER RODS

BAND OF SAME

SIZE AS HANGER

STRAP

LOAD RATED

FASTENERS

50" [1250mm]∅

& UNDER

AIR SPLIT DUCT TAKE-OFF PLAN

VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER TAKE-OFF

PLAN VIEW

AIR

FLOW

AIR

FLOW

A

IR

F L O

W

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

PROVIDE VOLUME

DAMPER

PROVIDE VOLUME

DAMPER

ADJUSTABLE

METAL ROD

OR LINKAGE

TOP REGISTER

MAIN

SUPPLY

DUCT

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

AIR

FLOW

AIR

FLOW

1/4 W OR 4" [100mm] MIN.

AIR

FLOW

MAIN SUPPLY

DUCT

A

IR

F L O

W

W

FROM STRUCTURE

SAME AS DIFFUSER

INLET: 5'-0" MAX

FLEXIBLE DUCT SIZE

LENGTH.

12"

CEILING

SUPPORT SADDLE

VOLUME DAMPER W/

LOCKING QUADSADDLE

SHEET METAL

CONICAL OUTLET

BRANCH DUCT

FOR CHANGE OF

DIRECTION GREATER

USE RIGID ELBOWS

THAN 45°

[300mm]

SEE SPECIFICATIONS FOR CLAMPS

AND SEALANT (TYP.)

NOTE:

THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR

THE DEDICATED AHU SERVING THE SURGICAL SUITE.

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

m m

M A

X

SIDE VIEW TRAPEZE HANGER FOR UP TO

453KG [1000 LB.] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

mm

[IN]

mm

[FT]

mm

[FT]

THRU 20

[THRU 3/4]

[7]

[5]

[1]

[7]

[6]

[11/4]

[7]

[7]

[11/2]

[9]

[8]

[2]

[10]

[8]

[21/2]

[11]

[9]

[3]

[12]

[10]

[4]

[14]

[12]

[5]

[16]

[13]

[6]

[17]

[14]

[8]

[19]

[16]

[10]

[22]

[12]

[23]

[14]

[25]

[16]

[27]

[18]

[28]

[20]

[30]

[24]

[32]

PROVIDE INSULATION

SHIELD

& INSERT FOR ALL

PIPING

(200mm [8"] MIN.)

BAND

43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm

[2"X2"X1/4"] ANGLE

15mm [1/2"] DIA.

HANGER RODS WITH

900mm [36"] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9

PSF MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NOTE:

SEE SPECIFER FOR DETAILED HANGER

REQUIREMENTS

4" THICK CONCRETE PAD

(MIN. 4" EXTENSION ALL

SIDES)

OUTDOOR UNIT. SECURE

TO CONCRETE PAD.

PROVIDE VIBRATION

PANS UNDER UNIT.

POWER & HIGH

VOLTAGE

CONTROL

TO INDOOR UNIT

THERMISTOR

CABLE

CONDENSATE

LINE.

WALL SLEEVE WITH CAPS

FURNISHED BY FCU

MFGR.

WALL MOUNTING

BRACKET FURNISHED BY

FCU MFGR.

INDOOR

UNIT

INSULATED RS AND RL

REFRIGERANT LINES

CONNECTION CABLE

TO THERMOSTAT

TOP OF

UNIT ± 8' AFF

AIRFLOW

SA

AIRFLOW

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

MECHANICAL DETAILS

M-501

-2

M -5

/1

/1

.p d f

SCALE: N.T.S.A12

ACCESS DOORS AND PANELS

SCALE: N.T.S.H12

DUCTWORK - SQUARE ELBOWS SCALE: N.T.S.H8

DUCTWORK -RADIUS ELBOWS

SCALE: N.T.S.D12

FLEXIBLE CONNECTORS

SCALE: N.T.S.H4

RETURN/EXHAUST BRANCH DUCTWORK

SCALE: N.T.S.D8

ROUND DUCT HANGERS

SCALE: N.T.S.H16

SUPPLY DUCTWORK TAKEOFFS

SCALE: N.T.S.D16

VAV FLEXIBLE DUCT CONNECTOR

SCALE: N.T.S.A7

PIPE HANGERS

SCALE: N.T.S.A16

WALL MOUNTED DUCTLESS SPLIT SYSTEM

(in.) (CFM) (°F)

(in)

VAV-1 TOUCHDOWN 2H-103 8 650 200

VAV-2 BREAKROOM 2H-104 8 1200 500

VAV-8

OFFICE 2H-119

8 500

VAV-9 6 200

VAV-10 10 780

VAV-11

OFFICE 2K-140A, 2H-140B,

WELLNESS 2H-108

6 300

VAV-3 TOUCHDOWN 2H-120 10 700 250

VAV-4 8 450 150

VAV-5 OFFICE 2H-113,114 ,115 6 350 125

VAV-6 RESIDENTS 2H-122 6 250 100

VAV-7 OFFICE 2H-116, 117, 118 6 300 125

VAV-13 ELECTRICAL 6 300

VARIABLE AIR VALVE (VAV) SCHEDULE

TAG SERVICE INLET

DIA. SIZE

MAX.

COOLING

EAT PIPE

SIZE

TOUCHDOWN 2H-121

ADMIN 2H-112

TOUCHDOWN 2H-111

MIN.

HEATING

(CFM)

AIRFLOW RANGE

MAX. NC

LEVEL AT

MAX.

AIRFLOW

(NC)

(°F)

LAT FLOW

(GPM)

MIN.

HEATING

CAP.

BASIS OF

DESIGN

NOTES

AIRSIDE WATERSIDE

6.5

3.7

2.0

6.5

2.7

3.9

1.4

2.7

2.7

16.2

6.3

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV

TITUS DESV0.65

1.62

0.63

0.39

0.27

0.14

0.27

0.37

0.2

0.65

0.27

1. DISCONNECT BY ELECTRICAL CONTRACTOR.

2. PRESSURE INDEPENDENT CONTROLS.

3. BAS INTERFACE: MONITORING AND CONTROLS.

4. MANUFACTURER PROVIDED CONTROL PANEL.

5. PROVIDE INTEGRAL 24V TRANSFORMER WITHIN ENCLOSURE AND INCLUDE SWITCH.

6. MAX NC LEVEL SHALL NOT EXCEED 30.

7. 1" INSULATION PRE-INSTALLED BY MANUFACTURER.

NOTES:

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

VAV-14 CORRIDOR 4 150 30 55 75 TITUS DESV3/4100 2.00.20

REHEAT COIL

VAV-15 LOCKERS 4 100 30 55 75 TITUS DESV3/450 2.00.20

SD-1 SUPPLY AL RADIAL HORIZONTAL SQUARE PLAQUE DIFFUSER TITUS OMNI

1. REFER TO DRAWINGS FOR NECK SIZES.

2. REFER TO ARCHITECTURAL RCP DRAWINGS FOR COORDINATION WITH CEILING.

3. COORDINATE FINISH WITH ARCHITECT.

4. COORDINATE MOUNTING HEIGHTS WITH ARCHITECTURAL ELEVATIONS.

RG-1 RETURN STEEL TITUS 350RL

NOTES:

GRILLE AND DIFFUSER SCHEDULE

TAG SERVICE MOUNTING

MODULE SIZE

MATERIAL DESCRIPTION BASIS OF DESIGN NOTES(in. x in.)

SEE DWGS 24 x 24

SIDE WALL SEE DWGS

RG-2 RETURN CEILING 24 x 24 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE RETURN GRILLE TITUS 50F 1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

DOUBLE DEFLECTION GRILLE

EG-1 EXHAUST CEILING 12 x 12 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE EXHAUST GRILLE TITUS 50F 1,2,3,4,5

SD-2 SUPPLY SIDE WALL SEE DWGS STEEL

SINGLE DEFLECTION RETURN GRILLE

TITUS 350FL 1,2,3,4,5

EG-2 EXHAUST SIDE WALL SEE DWGS STEEL SINGLE DEFLECTION RETURN GRILLE TITUS 350RL 1,2,3,4,5

AC-1 COMM RM DUCTLESS SPLIT 738 0 0 9,800 24,000 20.5 80 67 95 N/A 1.00 20.00 208 60 1

MITSUBISHI MY-GL24NA,

MUY-GL24NA

1-8

DB (F) WB (F) MCA MCA

MIN

CAPACITY

(BTU/H)

RATED

CAPACITY

(BTU/H)

SEER

EAT OSA

DESIGN

TEMP (F)

INDOOR UNIT OUTDOOR UNIT

VOLT HZ PHASE

SPLIT SYSTEM AIR CONDITIONER (INDOOR AND OUTDOOR UNIT) SCHEDULE

TAG

SERVICE TYPE

TOTAL SUPPLY

AIRFLOW (CFM)

MIN. OUTSIDE

AIR FLOW

(CFM)

EXT STATIC

PRESSURE

(IN)

COOLING CAPACITY

HEATING

CAPACITY

ELECTRICAL DATA

BASIS OF DESIGN NOTES

INDOOR OUTDOOR

ACU-1 208 60 1

VOLT HZ PHASE

NOTES:

1. PROVIDE WALL MOUNTED THERMOSTAT TO THE UNIT AS INDICATED ON MECHANICAL FLOOR PLANS.

2. PROVIDE HARD WIRED THERMOSTAT TO CONTROL THE UNIT.

3. DISCONNECT TO BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.

4. PROVIDE WALL MOUNTED KIT FOR INDOOR UNIT.

5. INDOOR UNIT AND OUTDOOR CONDENSING UNIT SHALL BE INTERLOCKED.

6. PROVIDE HAIL GUARD ON OUTDOOR UNIT.

7. REFER TO PLAN FOR CONDENSATE DRAIN LOCATION.

8. LOW AMBIENT COOLING.

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

MECHANICAL SCHEDULES

M-601

-2

M -6

/2

/1

.p

END OF RUN:

M

SASA

T

FS

M

T

SEQUENCE OF OPERATION - VARIABLE AIR VOLUME (VAV) UNIT

EQUIPMENT

THE AIRSIDE SYSTEMS, AS IT APPLIES TO THE BUILDING AUTOMATION SYSTEM

(BAS), CONSISTS OF THE FOLLOWING EQUIPMENT:

VARIABLE AIR VOLUME (VAV) UNITS,

GENERAL

AIR TERMINAL UNITS SHALL BE PRESSURE INDEPENDENT UNITS, WITH HOT

WATER REHEAT COILS (WHERE APPLICABLE). EACH UNIT SHALL BE SUPPLIED

WITH CUSTOM PROGRAMMABLE APPLICATION CONTROLLERS. THE BAS SHALL

PERFORM THE FOLLOWING TERMINAL UNIT CONTROL STRATEGIES AND PROVIDE

THE POINTS AS REQUIRED FOR THE SPECIFIED MONITORING AND DIAGNOSTICS:

SETPOINT CONTROL: THE BAS SHALL EDIT THE OPERATING MODE, AIRFLOW

SETPOINTS, DAMPER POSITIONS, AND ZONE TEMPERATURE SETPOINT OF EACH

BOX. ALL SETPOINTS SHALL BE OPERATOR ADJUSTABLE. INDIVIDUAL ZONE

SETPOINT AND CONTROL LOGIC SHALL RESIDE AT THE ZONE LEVEL, AND NOT BE

DEPENDENT UPON THE BAS FOR CONTROL. UPON LOSS OF COMMUNICATION, THE

TERMINAL UNIT WILL CONTINUE TO CONTROL TO CURRENT SETPOINTS.

RUN CONDITIONS

TERMINAL UNIT/ AHU INTERFACE:

AT MINIMUM, ALL TERMINAL UNITS (TU) SERVED BY AN AIR HANDLING UNIT (AHU)

SHALL BE LINKED WITH THE RESPECTIVE AHU CONTROLLER TO PERFORM THE

FOLLOWING FUNCTIONS:

ZONE OCCUPANCY SCHEDULE: THE SCHEDULE SHALL AUTOMATICALLY SELECT

THE OCCUPIED OR UNOCCUPIED OPERATING MODE OF THE AHU. ACTIVATION OF

TIMED OVERRIDE SWITCH ON ZONE TEMPERATURE SENSORS (WHERE

APPLICABLE)SHALL ONLY RESET ZONE HEATING AND COOLING SETPOINTS TO

"OCCUPIED" VALUES, BUT SHALL NOT OTHERWISE AFFECT SCHEDULED

UNOCCUPIED OPERATING MODE OF AHU.

DUCT STATIC PRESSURE ALGORITHM: SEE AHU CONTROL SEQUENCE.

ZONE OPTIMAL START:

THE UNITS SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP.

THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN

PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF THE

SCHEDULED OCCUPIED PERIOD. THE LEARNING ADAPTIVE ALGORITHM SHALL

COMPARE THE ZONE TEMPERATURE TO ITS SETPOINT AT THE BEGINNING OF

SCHEDULED OCCUPIED PERIOD AND SHALL AUTOMATICALLY ADAPT THE HEATING

OR COOLING RESPONSE TIME FOR THE NEXT UNOCCUPIED PERIOD. THE INITIAL

DEFAULT STARTING TIME PRIOR TO OCCUPANCY SHALL BE 60 MINS (ADJ).

ZONE TEMPERATURE AND AIRFLOW CONTROL

OCCUPIED ZONE TEMPERATURE:

UNITS SHALL RUN TO MAINTAIN THE FOLLOWING TEMPERATURES:

75°F (ADJ) COOLING SETPOINT

70°F (ADJ) HEATING SETPOINT

UNOCCUPIED ZONE TEMPERATURE:

UNITS SHALL RUN TO MAINTAIN THE FOLLOWING TEMPERATURES:

85°F (ADJ) COOLING SETPOINT

55°F (ADJ) HEATING SETPOINT

AIRFLOW SETPOINTS:

PROVIDE OPERATOR DEFINABLE, INDEPENDENT HEATING AND COOLING AIRFLOW

SETPOINTS PER VAV TERMINAL UNIT SCHEDULES.

SPACE CONDITION CONTROL:

THE TERMINAL UNIT (TU) SHALL MAINTAIN ZONE TEMPERATURE AND AIRFLOW SETPOINTS

BY CONTROLLING THE TU AIR DAMPER AND ZONE HEATING COIL VIA THE FOLLOWING:

OCCUPIED:

WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER

SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ) AND MAXIMUM

OCCUPIED AIRFLOW (ADJ) UNTIL ZONE TEMPERATURE IS SATISFIED. HEATING COIL VALVE

REMAINS CLOSED.

WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING

SETPOINT, THE ZONE DAMPER SHALL MODULATE TO ITS MINIMUM OCCUPIED AIRFLOW

(ADJ). HEATING COIL VALVE REMAINS CLOSED.

VAV W/ REHEAT (VAV) : WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SETPOINT,

THE CONTROLLER SHALL ENABLE THE HEATING COIL AND MODULATE THE HEATING COIL

VALVE TO MAINTAIN THE ZONE TEMPERATURE SETPOINT. THE HEATING AIRFLOW SHALL BE

LIMITED TO MINIMUM OCCUPIED AIRFLOW.

UNOCCUPIED:

THE TERMINAL UNITS SHALL CYCLE BETWEEN MINIMUM AND MAXIMUM AIRFLOW SETPOINTS

DURING UNOCCUPIED PERIODS. APPLY ± 3°F (ADJ) ALLOWABLE DRIFT FROM UNOCCUPIED

HEATING AND COOLING SETPOINTS AS DESCRIBED BELOW:

COOLING: WHEN CRITICAL ZONE (CZ) TEMPERATURE HAS RISEN ABOVE ITS UNOCCUPIED

SPACE TEMPERATURE COOLING SETPOINT PLUS THE DRIFT (3°F ADJ, AS STATED ABOVE),

THE AHU SHALL BEGIN STARTUP. THE CZ DAMPER SHALL OPEN TO ITS RESPECTIVE

MAXIMUM UNOCCUPIED COOLING MODE AIRFLOW SETPOINT AND REMAIN IN THIS POSITION

UNTIL THE ZONE TEMPERATURE IS AT SETPOINT MINUS THE DRIFT. THE ZONE CONTROLLER

SHALL THEN MODULATE THE ZONE DAMPER TO THE MINIMUM UNOCCUPIED COOLING MODE

AIRFLOW SETPOINT UNTIL CYCLE REPEATS.

HEATING: WHEN CRITICAL ZONE (CZ) TEMPERATURE HAS FALLEN BELOW ITS UNOCCUPIED

SPACE TEMPERATURE HEATING SETPOINT MINUS THE DRIFT, THE TU CONTROLLER SHALL

MODULATE THE ZONE DAMPER TO MINIMUM UNOCCUPIED HEATING MODE AIRFLOW

SETPOINT AND SHALL MODULATE THE HEATING COIL VALVE TO 100% OPEN. THIS SHALL

CONTINUE UNTIL ZONE TEMPERATURE IS AT SETPOINT PLUS THE DRIFT. THE ZONE

CONTROLLER SHALL THEN CLOSE THE HEATING COIL VALVE.

OVERRIDE: WHEN UNOCCUPIED MODE IS OVERRIDDEN BY USER AT LOCAL THERMOSTAT,

AHU IS TO ENERGIZE AND RUN IN OCCUPIED MODE FOR A 1 HOUR (ADJ) PERIOD BEFORE

RETURNING TO UNOCCUPIED MODE.

ALARMS AND SHUTDOWNS

NOTE: ALL ALARMS TO BE TIMESTAMPED ON BAS GRAPHIC

INTERFACE.

HIGH ZONE TEMPERATURE: IF THE ZONE TEMPERATURE IS GREATER

THAN THE COOLING SETPOINT BY 5°F (ADJ) FOR A MINIMUM OF 30

MINS (ADJ).

LOW ZONE TEMPERATURE: IF THE ZONE TEMPERATURE IS LESS

THAN THE HEATING SETPOINT BY 5°F (ADJ) FOR A MINIMUM OF 30

MINS (ADJ).

HIGH DISCHARGE AIR TEMPERATURE: IF THE TERMINAL UNIT

DISCHARGE AIR TEMPERATURE IS GREATER THAN 105°F (ADJ) FOR A

MINIMUM OF 30 MINS (ADJ).

HIGH AIRFLOW: IF THE ZONE AIRFLOW IS GREATER THAN THE

SETPOINT BY 25% (ADJ) FOR A MINIMUM OF 60 MINS (ADJ).

LOW AIRFLOW: IF THE ZONE AIRFLOW IS LESS THAN THE SETPOINT

BY 25% (ADJ) FOR A MINIMUM OF 60 MINS (ADJ).

DDC INPUT OUTPUT SUMMARY

VARIABLE AIR VOLUME (VAV) UNIT

S Y

S T

E M

G R

A P

H

IC

D

IS

P L A

Y

OUTPUTS INPUTS

SOFTWARE

REMARKS

DIGITAL ANALOG DIGITAL ANALOG

EQUIPMENT POINT DESCRIPTION

S T

A R

T /S

T O

P

O P

E N

/C L

O S

E

E N

A B

L E

/D

IS

A B

L E

S E

T P

O

IN

T A

D J U

S T

P O

S

IT

IO

N

V A

L V

E C

O M

M A

N D

S P

E E

D C

O N

T R

O L

C U

R R

E N

T S

E N

S

IN

G R

E L A

Y

D

IF

F E

R E

N T

IA

L P

R E

S S

U R

E S

W

IT

C H

S T

A R

T /S

T O

P

F L O

W S

W

IT

C H

O P

E N

/C L

O S

E

A L A

R M

P U

S H

B U

T T

O N

O V

E R

R

ID

E

P U

L S

E C

O N

T A

C T

T E

M P

E R

A T

U R

E

E L E

C T

R

IC

A L D

E M

A N

D k W

A M

P E

R A

G E

V F

D F

R E

Q U

E N

C Y

P R

E S

S U

R E

C A

R B

O N

D

IO

X

ID

E

P O

S

IT

IO

N

F L O

W

E N

T H

A L P

Y

H U

M

ID

IT

Y

A N

A L O

G V

A R

IA

B

L E

B

IN

A R

Y V

A R

IA

B

L E

S O

F T

A L A

R M

R U

N T

IM

E

T O

T A

L

IZ

A T

IO

N

R E

S E

T A

V A

IL

A

B L E

S C

H E

D U

L E

C A

L C

U L A

T E

D P

O

IN

T

VAV

VAV DAMPER POSITION X X X

VAV ZONE OCCUPIED/ UNOCCUPIED X X

VAV REHEAT HOT WATER CONTROL VALVE POSITION X X

VAV AIRFLOW (CFM) X X

VAV ZONE TEMPERATURE X X X ALARM PER SEQUENCE

VAV ZONE TEMPERATURE SETPOINT X X

VAV SUPPLY AIR TEMPERATURE X X X ALARM PER SEQUENCE

VAV ZONE SENSOR OVERRIDE STATUS X X

VAV ZONE SENSOR DIAL POSITION X X

UNIT AT END OF RUN SHALL HAVE 3-WAY VALVE

S E

T P

O

IN

T

R A

N G

E

75F

55F

0-100%

0-100%

AI

AI

AO

AI

AO

AO

ROOM THERMOSTAT/SENSOR

WALL MOUNTED

48" [1200mm] AFF.

NO SUPPLEMENTAL HEATING

TU

RHCHWS

HWR

V-1

REHEAT

COIL

AIR

TERMINAL

UNIT

AIR

FLOW

TE

ATU

CONTROLLER

PC

TE

A

IR

F

LO

W

(C F M

ROOM TEMPERATURE

(°F)

HEATING

MINIMUM

SP

VAV BOX CONTROL

SEQUENCE

W/DEADBAND

100%

VA

V

AI

R

FL

O W

R

EH

EAT

FLO

W

FE

A. SETPOINT SHALL BE SET AS

FOLLOWS:

COOLING 75F

(ADJ)

HEATING 70F

(ADJ)

DEADBAND OF 5 F BETWEEN HEATING AND COOLING SET POINTS

WILL BE

MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL

MODULATE TO MINIMUM

POSITION.

C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL

MODULATE TO MAINTAIN SET POINT +/_ 5F. THE ADJUSTABLE

TOLERANCE OF +/_ 5F HAS BEEN SELECTED TO PREVENT VALVE

HUNTING.

D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE

TEMPERATURE.

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

LIFE SAFETY AND FIRE PROTECTION:

STANTON ENGINEERING SERVICES

10280 OLD COLUMBIA RD

STE 275

COLUMBIA, MD 21046

(410) 290-9301

PROFESSIONAL SEAL:

Richmond VA Medical Center (RICVAMC) 1201 Broad Rock Blvd Richmond, VA 23249

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR

SUITE 350

CALVERTON, MD 20705

443-388-7351

ARCHITECTURE & MEP:

RAYMOND ENGINEERING

1601 SUMMIT AVE

RICHMOND, VA 23230

804-726-9540

05/20/2022

652-20121

ANCH

RENOVATION OF OLD DIALYSIS

AREA 2H

CONSTRUCTION BID SET

MECHANICAL CONTROLS

M-801

-2

M -8

/1

/2

.p

Sheets
M-001 - MECHANICAL GENERAL NOTES AND DESIGN CRITERIA
M-002 - MECHANICAL ABBREVIATIONS AND LEGENDS
MD-101 - LEVEL 1 MECHANICAL DEMOLITION PLAN
MP-101 - MECHANICAL PIPING PLAN
M-101 - LEVEL 1 MECHANICAL FLOOR PLAN
M-501 - MECHANICAL DETAILS
M-601 - MECHANICAL SCHEDULES
M-801 - MECHANICAL CONTROLS