This is a specifications document for aquatic pumps related to a pool facility renovation at Kennedy Memorial Park in the Incorporated Village of Hempstead, New York. The scope of work requires the contractor to furnish materials, labor, and equipment for the installation of centrifugal pumps including pool recirculation pumps, spray park recirculation pumps, feature recirculation pumps, motor and pump realignment, and operational verification. The project specifies five pump installations across multiple facilities: a competition pool (SPECK Model 100/250, 624 GPM, 65 feet head), a family pool (SPECK Model 65/250, 172 GPM, 75 feet head), a spray park main system (SPECK Model 100/250, 500 GPM, 40 feet head), a spray park major feature (SPECK Model 100/250, 516 GPM, 60 feet head), and a spray park minor feature (SPECK Model 100/250, 727 GPM, 45 feet head). All pumps must be NSF-listed with cast iron volutes rated for 175 PSIG, bronze impellers suitable for chlorinated water, and carbon/ceramic mechanical seals. Motors must be close-coupled, premium efficient, 208 volts, 60 Hertz, 3-phase units with minimum bearing life of 100,000 average B-10 hours and compliance with NEMA specifications.

The project requires five Variable Frequency Drives (VFDs) in NEMA 12 enclosures, manufactured by Horlick Co. Inc., with PWM output utilizing IGBT inverter technology. VFDs must include internal DC link reactors for harmonic distortion control, Automatic Energy Optimization and Automatic Motor Adaptation functions, and bypass capabilities with overload protection. All pumps must conform to ANSI/HI standards for centrifugal pumps and meet Nassau County Department of Health, New York State Swimming Pool Code, and New York State Sanitary Code requirements. Contractors must provide three copies of pump curves indicating operating points, voltage, and current draw, with one copy laminated and installed in the pump room. All pumps require factory testing and NSF Standard 50 listing. Pump manufacturers must be ISO-9001 certified. The specification document was issued July 2026 and includes requirements for proper product handling, crating, protective measures during transportation, and precise alignment verification post-installation using dial indicators to ensure runout does not exceed manufacturer recommendations.

View the file

Other files

File Type Posted
Appendix B.pdf PDF
BID 9 PROPOSAL PAGES.pdf PDF
addenda #3.pdf PDF
Appendix C.pdf PDF
Table of Contents.pdf PDF
011B.4- Proposal P1D - Contract E.pdf PDF
addenda #2.pdf PDF
2026-27 Bid 9 Notice.doc DOC document
HEMV2602 - Addendum No. 1 - 07.28.2026.pdf PDF
Revised Plans.pdf PDF
Appendix A.pdf PDF
Revised Section 225119 - Aquatic Filtration System.pdf PDF
addenda #2 part 2.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 225116 - AQUATIC PUMPS H2M

HEMV2502 225116 - 1 Issue Date: JULY 2026

07-27-2026 12:27:16 PM

PART 1 - GENERAL

1.01 SCOPE OF WORK

A. Under this section, the Contractor shall furnish all necessary materials, labor and equipment as specified herein and/or as shown on the plans for the installation of centrifugal pumps, as required for a complete operating system. Work shall include, but not necessarily be limited to, the installation and performance of the following:

1. Pool recirculation pumps

2. Spray Park recirculation pumps

3. Feature recirculation pumps

4. Realignment of pumps and motors

5. Checkout and verification of operation

1.02 RELATED WORK SPECIFIED ELSEWHERE

A. Section 033000 - Cast-In-Place Concrete B. Section 130811 - Testing, Adjusting, and Balancing of Aquatic System C. Section 225119 - Aquatic Filtration Systems D. Section 225113 - Aquatic Recirculation Piping

1.03 QUALITY ASSURANCE

A. The Contractor shall check that all labels and identifications are in place. Equipment not possessing such labels shall be rejected and removed from the site.

1. Pumps shall be National Sanitation Foundation (NSF) listed at the time of the bid date.

2. Pumps shall have labels specifying head capacity and speed.

3. Motors shall have labels specifying voltage, full load amperage, speed, horsepower and service factor.

4. Head/capacity curves from the manufacturer shall accompany pumps.

B. Pump Curves

1. Provide three (3) copies of pump curve showing impeller installed and indicating operating point for each pump

2. Provide voltage and current draw at operating point

3. Encapsulate all three (3) pump curves in plastic, frame, install one (1) in pump room of the filter building adjacent to each pump and turnover the others to the Engineer.

C. Standards

1. In addition to complying with pertinent regulations of governmental agencies having jurisdiction, The Contractor shall comply with the following:

a. Nassau County Department of Health

b. New York State Swimming Pool Code

c. US Swimming Rules and Regulations, 1993 edition

d. New York State Sanitary Code, Part 6

e. ACI 347

f. Governmental agencies having jurisdiction

2. In the event of conflict between or among specified requirements and pertinent regulations, the more stringent requirements will govern.

1.04 PRODUCT HANDLING

A. Before pumps are shipped, they shall be crated by manufacturer to withstand rigors of handling and transportation. Crating shall be wood with pumps securely bolted to the frame of the crate to prevent movement.

B. All pump openings shall be closed to prevent entrance of foreign materials and to protect surfaces.

Flanges shall have wooden flange protectors bolted in place. Threaded connections shall be fitted with plugs. Protect seals, shaft, coupling and coupling guard.

HEMV2502 225116 - 2 Issue Date: JULY 2026

C. Provide unloading and handling equipment on-site to unload pumps. Under no circumstances shall the pumps be allowed to drop on the ground or on hard surfaces.

D. Move the pumps to protected areas on the site. Keep the pumps covered and protected from the weather and vandalism at all times.

PART 2 - PRODUCTS

2.01 PUMPS

A. Circulating Pump and Motor

1. Competition Pool - Funish and install horizontal shaft coupled, centrifugal pump, of plastic construction as manufactured by SPECK Pumps, Model 100/250 describe to the following conditions:

a. Design Capacity: 624 GPM

b. Design Total head: 65 feet

c. Maximum RPM: 1,750 RPM

2. Family Pool - Funish and install horizontal shaft coupled, centrifugal pump, of plastic construction as manufactured by SPECK Pumps, Model 65/250 described to the following conditions:

a. Design Capacity: 172 GPM

b. Design Total head: 75 feet

c. Maximum RPM: 1,750 RPM

3. Spray Park - Furnish and install the horizontal shaft coupled, centrifugal pump, of plastic construction as manufactured by SPECK Pumps, Model 100/250 described for the following conditions:

a. Design Capacity: 500 GPM

b. Design Total Head: 40 feet

c. Maximum RPM: 1750

4. Spray Park Major Feature - Furnish and install the horizontal shaft coupled, centrifugal pump, of plastic construction as manufactured by SPECK Pumps, Model 100/250 described for the following conditions:

a. Design Capacity: 516 GPM

b. Design Total Head: 60

c. Maximum RPM:1,750

5. Spray Park Minor Feature - Furnish and install the horizontal shaft coupled, centrifugal pump, of plastic construction as manufactured by SPECK Pumps, Model 100/250 described for the following conditions:

a. Design Capacity: 727 GPM

b. Design Total Head: 45

c. Maximum RPM: 1,750

6. Pump volute shall be of a cast iron design (ASTM 48, Class 30) rated for 175 PSIG with integral cast iron flanges drilled for 125# ANSI companion flanges. Volute shall include gauge ports at nozzles, and vent and drain ports. The pump and motor shall be connected by an ASTM 48, Class 30, cast iron bracket with a slinger to prevent moisture from entering the front motor bearing. Pump shall be of back pull out design to permit removal of the motor and all rotating parts without breaking the suction and discharge connections.

7. The impeller shall be an enclosed, single piece cast bronze casting, completely machined on all outside surfaces and statically balance at time of pump assembly. The impeller shall be keyed to the shaft and securely fastened with a vibration resistant lock screw and washer. The impeller shall be manufactured from Alloy C95800, Aluminum Bronze; suitable for use with chlorinated water. The impeller shall not contact the suction wear ring under any operating load condition.

8. The mechanical shaft seal shall have carbon/ceramic mating faces for leak free operation, with stainless steel internal parts.

9. Competition Pool - The motor shall be close coupled type. It shall be no less than 20 HP at 1,750 RPM, be non-overloading at any point on the pump curve and shall meet NEMA

HEMV2502 225116 - 3 Issue Date: JULY 2026 specifications. Motor supply is 208 volts, 60 Hertz, 3 phase. The motor shall Premium efficient. The motor bearings shall be selected to withstand thrust loads and have a minimum life of 100,000 average B-10 hours. Motors shall meet or exceed the minimum full load efficiencies as per NEMA MG-1, Table 12-11.

10. Family Pool - The motor shall be close coupled type. It shall be no less than 7.5 HP at 1,750 RPM, be non-overloading at any point on the pump curve and shall meet NEMA specifications. Motor supply is 208 volts, 60 Hertz, 3 phase. The motor shall Premium efficient. The motor bearings shall be selected to withstand thrust loads and have a minimum life of 100,000 average B-10 hours. Motors shall meet or exceed the minimum full load efficiencies as per NEMA MG-1, Table 12-11.

11. Spray Park - The motor shall be close coupled type. It shall be no less than 15 HP at 1,750 RPM, be non-overloading at any point on the pump curve and shall meet NEMA specifications. Motor supply is 208 volts, 60 Hertz, 3 phase. The motor shall Premium efficient. The motor bearings shall be selected to withstand thrust loads and have a minimum life of 100,000 average B-10 hours. Motors shall meet or exceed the minimum full load efficiencies as per NEMA MG-1, Table 12-11.

12. The motor shall have a solid SAE1144 steel shaft. A bronze shaft sleeve shall be employed to completely cover the wetted area under the seal.

13. Pumps shall conform to ANSI/HI 9.6.3.1 standard for Preferred Operating Region (POR) unless otherwise approved by the engineer. The pump NPSH shall conform to the ANSI/HI 9.6.1-1997 standards for Centrifugal and Vertical Pumps for NPSH Margin.

14. Pump shall be of maintainable design and for ease of maintenance should use machine fit parts and not press fit parts.

15. Pump manufacturer shall be ISO-9001 certified

16. Each pump shall be factory tested and name-plated before shipment.

17. Pump shall be NSF standard 50 listed.

B. Variable Frequency Drive (VFD)

1. A Variable Frequency Drive (VFD) shall be provided for each set of pumps, five total.

2. The Variable Frequency Drives (VFDs) shall be solid state, with a Pulse Width Modulated

(PWM) output. The VFD package as specified herein shall be enclosed in a NEMA 12 enclosure, completely assembled, programmed and tested by the manufacturer. The VFD shall convert incoming fixed frequency three-phase AC power into a variable frequency and voltage for controlling the speed of three-phase AC induction motors. The VFD shall be a six-pulse input design. The VFD shall be of a PWM output design utilizing current IGBT inverter technology and voltage vector control of the output PWM waveform and shall output a waveform that closely approximates a sine wave.

3. Option for Single Phase input: The VFD shall convert incoming fixed frequency single-phase AC power into a variable frequency and voltage for controlling the speed of three-phase AC induction motors. The VFD shall be UL-listed for Single Phase operation. De-rating the VFD for operation on other than UL-labeled voltages shall not be acceptable. The VFD shall be a six-pulse input design. The VFD shall be of a PWM output design utilizing current IGBT inverter technology and voltage vector control of the output PWM waveform and shall output a waveform that closely approximates a sine wave.

4. The VFD shall utilize VVCPLUS, an output voltage-vector switching algorithm, or equivalent, in both variable and constant torque modes. VVCPLUS provides rated RMS fundamental voltage from the VFD. This allows the motor to operate at a lower temperature rise, extending its thermal life. VFD’s that cannot produce rated RMS fundamental output voltage or require the input voltage to be increased above motor nameplate value to achieve rated RMS fundamental output voltage are not acceptable. VFD’s that utilize Sine-Coded PWM or Look-up tables shall not be acceptable.

5. An Automatic Energy Optimization (AEO) selection feature shall be provided in the VFD to minimize energy consumption in variable torque applications. This feature shall optimize motor magnetization voltage and shall dynamically adjust output voltage in response to

HEMV2502 225116 - 4 Issue Date: JULY 2026 load, independent of speed. Output voltage adjustment based on frequency alone is not acceptable for single motor VT configurations.

6. An Automatic Motor Adaptation (AMA) function shall measure motor stator resistance and reactance to optimize performance and efficiency. It shall not be necessary to spin the motor shaft or de-couple the motor from the load to accomplish this optimization. Additionally, the parameters for motor resistance and motor reactance shall be user-programmable.

7. Run permissive circuit shall be provided to accept a “system ready” signal to ensure that the VFD does not start until isolation valves, seal water pumps or other types of auxiliary equipment are in the proper state for VFD operation. The run permissive circuit shall also be capable of sending an output signal as a start command to actuate external equipment before allowing the VFD to start.

8. All Horlick Co. Inc. VFDs shall be factory programmed per the unique requirements of each job per Neptune Benson specifications. Programming shall include but shall not be limited to filter pump, remote start/stop requirements, run confirm requirements and PID loop requirements.

9. VFDs and options shall be UL, CUL, and CE labeled as a component.

10. Harmonic Distortion Control:

11. The VFD shall provide internal DC link reactors to minimize power line harmonics and to provide near unity power factor. DC Link reactor shall be installed so that power fluctuations to the DC Capacitors shall be reduced to increase Capacitor life. VFDs without a DC link reactor shall provide a 5% impedance line side reactor and provide spare capacitors.

12. Specifications:

a. Input voltage 200-240, 380-480, 575-600 VAC +/- 10%, 3 phase, 48-63 Hz.

b. Voltage tolerance + 10% or - 15% of specified line voltage.

c. Output Frequency 0 to 300 Hz. Operation above 60 Hz shall require

d. programming changes to prevent inadvertent high-speed operation.

e. Environmental operating conditions: -10 to 50?°C, 0 to 1000 meters above sea level, less than 90% humidity, non-condensing.

f. Enclosure shall be rated NEMA 12 or as specifically mentioned elsewhere.

13. The VFD shall be wired into the RMF controller for on/off and run confirm functions. Wiring shall be by electrical contractor.

14. The VFD shall be a Horlick Co. Inc. series.

15. The VFD shall be equipped with a bypass. Bypass option shall send the motor to bypass mode based on an easily accessible door-mounted selector or based on the drive’s programmable relay. A bypass pilot light shall provide indication of the bypass mode. The bypass mode shall provide overload protection. Contactors shall be electrically and mechanically interlocked. An essential services mode shall send the motor to bypass regardless of the selected mode.

16. The bypass enclosure shall be equipped with a circuit breaker/disconnect switch.

PART 3 - EXECUTION

3.01 PUMPS

A. Preliminary

1. Install pump foundations as shown on the Plans. Anchor bolts shall be located using template provided by pump manufacturer. All exposed edges of pump foundation shall have a one half (1/2) inch chamfer.

B. Setting

1. Pumps shall be installed without jolting to avoid misalignment during setting. Provide witness marks to establish manufacturer’s initial alignment. Shim as required to establish baseplate in a level plane. Grout in baseplate after leveling.

C. Alignment

HEMV2502 225116 - 5 Issue Date: JULY 2026

1. Verify alignment of pump, coupling and motor after installation, rotate motor, use dial indicator to check remount both axially and radically, realign motor if runout exceeds manufacturer’s recommendations.

END OF SECTION