PLANS_IFB_R2_2026-02-27.pdf
PDF 7 MB Posted
- Attached to
- 2026 Fall Protection Systems Installation
- Solicitation number
- 26-014-ITB
- Issued by
- Kenton County, Erlanger City, Kentucky
About this file
Summary of Fall Protection Systems Installation Contract Opportunity
This is a competitive bid solicitation issued by the Kenton County Airport Board (KCAB) for fall protection systems installation at Cincinnati/Northern Kentucky International Airport. The project encompasses three separate bid packages: the Storm Water Treatment Plant (SWTP) Fall Protection Components & Confined Space Equipment; the T3 Parking Deck Fall Protection Components; and the Concourse A Roof Fall Protection Components. Work includes providing fall arrest systems at the Sludge Holding Tank, Digesters, Clarifiers, and Splitter Box; fall protection railings, gates, roof markings, and access ladders; and comprehensive fall protection systems for the entire Concourse A Roof. Bidders may submit proposals for any or all three packages. A mandatory pre-bid meeting and site visit will be held on Thursday, March 19, 2026 at 10:00 am at CVG Centre Administrative Offices, 77 Comair Boulevard, Erlanger, Kentucky 41018. Questions must be submitted by 11:59 pm on Friday, April 3, 2026, with answers posted no later than Tuesday, April 7, 2026 at 11:59 pm. Bids are due by Thursday, April 16, 2026 at 2:00 pm, with no late submissions accepted unless extended by addendum.
The fall protection systems are designed by LJB, Inc. in accordance with the current ANSI/ASSP Z359.6 standard and include detailed structural requirements for materials, fabrication, installation, anchoring, and testing. All structural steel must be galvanized per ASTM A123, with mechanical and adhesive anchors installed per manufacturer specifications and proof-tested prior to use. The contract requires 100% inspection and testing of adhesive anchors, mechanical expansion anchors, and wire rope terminations. Design specifications comply with the 2018 Kentucky Building Code and 2015 International Building Code, with wind speeds of 115 mph and seismic design category B. The contractor is responsible for all fabrication, erection, temporary bracing, debris removal, field verification of existing conditions, shop drawings submission, and coordination with the engineer of record throughout the project.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL INFORMATION
G000 COVER SHEET
S T
T E O F K ENT U
C l
O
31511
K
A
C N S O
R P
F
E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
DATEPROJECT NUMBER SHEET NUMBER
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
RELEASES / REVISIONS
DRAWING INDEX
06/02/2025
5/
/2
2:
:3
P
M
0127047A.00 05-01-25 G000
PROJECT TEAM
FALL PROTECTION AND CONFINED SPACE DESIGN
CINCINNATI/NORTHERN KENTUCKY INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH 45275
SWTP
G001 COVER SHEET
S001 GENERAL STRUCTURAL DATA
S002 GENERAL STRUCTURAL DATA
S101 SWTP OVERALL PLAN
S102 SLUDGE HOLDING TANK PLAN
S103 DIGESTER 2 PLAN
S104 DIGESTER 1 PLAN
S105 CLARIFIER PLAN VIEW
S106 SPLITTER BOX PLAN VIEW
S501 SECTIONS & DETAILS
S502 SECTIONS & DETAILS
S503 SECTIONS & DETAILS
PARKING DECK
G001 COVER SHEET
S001 GENERAL STRUCTURAL DATA
S101 PLAN VIEW
S501 SECTIONS & DETAILS
CONCOURSE A
G001 COVER SHEET
S001 GENERAL STRUCTURAL DATA
S101 OVERALL PLAN
S401 ENLARGED PLANS
S402 ENLARGED PLANS
S403 ENLARGED PLANS
S404 ENLARGED PLANS
S501 SECTIONS & DETAILS
S502 SECTIONS & DETAILS
S503 SECTIONS & DETAILS
S504 SECTIONS & DETAILS
S505 SECTIONS & DETAILS
S506 SECTIONS & DETAILS
CONCOURSE A
PARKING DECK
SWTP
REV DATE RELEASED FOR
0 6/02/2025 CONSTRUCTION
0129467A.00
0128276A.00
S504 SECTIONS & DETAILS07
GENERAL STRUCTURAL DATA
CONCOURSE A ROOF PLAN
ENLARGED PLANS
SECTIONS & DETAILS
ROOF FLASHING DETAILS
G001
S001
S101
S501
A101
CONCOURSE A (GUARDRAIL SET)
0127047A.00 0129467A.00
0128276A.00
0129051A.00
S T
T E O F K ENT U
C l
O
31511
K
A
C N S O
R P
F
E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
DATEPROJECT NUMBER SHEET NUMBER
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
RELEASES / REVISIONS
DRAWING INDEX
06/02/2025
5/
/2
2:
:0
P
M
0127047A.00 05-01-25 G001
PROJECT TEAM
FALL PROTECTION AND CONFINED SPACE DESIGN -
SWTP
CINCINNATI/NORTHERN KENTUCKY INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH 45275
SWTP
G001 COVER SHEET
S001 GENERAL STRUCTURAL DATA
S002 GENERAL STRUCTURAL DATA
S101 SWTP OVERALL PLAN
S102 SLUDGE HOLDING TANK PLAN
S103 DIGESTER 2 PLAN
S104 DIGESTER 1 PLAN
S105 CLARIFIER PLAN VIEW
S106 SPLITTER BOX PLAN VIEW
S501 SECTIONS & DETAILS
S502 SECTIONS & DETAILS
S503 SECTIONS & DETAILS
REV DATE RELEASED FOR
0 6/02/2025 CONSTRUCTION
GENERAL INFORMATION
G001 COVER SHEET
STRUCTURAL
SUMMARY OF WORK: Provide confined space and fall arrest improvements at the Sludge Holding Tank, Digesters, Clarifiers, and Splitter Box.
i. Modification and evaluation of existing fall protection components. (Potential Allowance)
ii. Providing the indicated fall protection listed on the equipment list.
iii. Providing steel construction components indicated on the drawings.
iv. X-ray concrete penetrations to ensure minimum 2” clearance between the edge of any cut or Opening and any post-tensions.
v. Provide metal fabrications and foundations, including new access stairs and platforms;
Modifications to existing fabrications and structures for additional fall protection components detailed on the drawings.
2018 KENTUCKY BUILDING CODE
2015 INTERNATIONAL BUILDING CODE
OSHA 29 CFR 1910
ANSI/ASSP Z359.6-2016
DESIGN SPECIFICATIONS
BASIC DESIGN WIND LOAD
BASIC WIND SPEED, V ---------------------------------- 115 MPH
RISK CATEGORY ------------------------------------------ II
EXPOSURE -------------------------------------------------- B
VELOCITY PRESSURE, q ------------------------------- 16 PSF
GEOTECHNICAL DATA
ALLOWABLE SOIL BEARING ---------------- 1,500 PSF (ASSUMED)
FROST DEPTH ----------------------------------- 30 INCHES
EARTHQUAKE DESIGN DATA (ACCESS PLATFORMS)
RISK CATEGORY ------------------------------------------ II
SEISMIC IMPORTANCE FACTOR, le ----------------- 1.00
SS = 0.146
S1 = 0.08
SITE CLASS -----------------------------------------D(DEFAULT)
SDS = 0.156
SD1 = 0.128
SEISMIC DESIGN CATEGORY ------------------------- B
BASIC SEISMIC-FORCE-RESISTING SYSTEM:
STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
SEISMIC RESPONSE COEFFICIENT, CS ------------ 0.052
RESPONSE MODIFICATION COEFFICIENT, R ---- 3
DESIGN BASE SHEAR, CSW ----------------------------- 0.052W
ANALYSIS PROCEDURE:
ELF PROCEDURE
FALL PROTECTION LOAD
FALL ARREST ACTIVE (A) LOAD = 1,350 LBS
• ARREST FORCE - 1,350 LBS
• NUMBER OF USERS - 1
• LUMPING FACTOR - 1.0
DESIGN DATA
WALKING-WORKING SURFACE LOADS
STAIR TREADS & STRINGERS
• LIVE LOAD (CONCENTRATED) ---------------------- 300 LBS
• LIVE LOAD (UNIFORM) --------------------------------- 60 PSF
• DEAD LOAD ------------------------------------------------- SELF-WEIGHT
STAIR HANDRAIL
• LIVE LOAD (CONCENTRATED) ----------------------- 200 LBS
• DEAD LOAD ------------------------------------------------- 3 PLF
GUARDRAIL & STAIR RAILS
• LIVE LOAD TOP RAIL (CONCENTRATED) -------- 200 LBS
• LIVE LOAD MID RAIL ------------------------------------- 150 LBS
• LIVE LOAD TOEBOARD --------------------------------- 50 LBS
• DEAD LOAD ------------------------------------------------- 20 PLF
PLATFORMS
• LIVE LOAD (CONCENTRATED) ----------------------- 300 LBS
• LIVE LOAD (UNIFORM) ---------------------------------- 60 PSF
• DEAD LOAD ------------------------------------------------- SELF-WEIGHT
FALL PROTECTION DATA
FALL PROTECTION SYSTEMS
THE FALL PROTECTION SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE CURRENT ANSI/ASSP Z359.6 STANDARD AND MEET THE
FOLLOWING REQUIREMENTS:
1. DESIGNED AS THE FOLLOWING SYSTEM TYPE:
• FALL ARREST AT SLUDGE HOLDING TANK, DIGESTERS, CLARIFIERS AND SPLITTER BOX
2. ONE USER TO BE ATTACHED PER CONNECTION POINT OR ANCHORAGE CONNECTOR.
3. USER WEIGHT RANGE: 130 LB - 310 LB.
4. THE SYSTEMS ARE DESIGNED TO BE USED ONLY AT THE LOCATION SHOWN ON THE ENGINEERING DRAWINGS.
5. ANY MODIFICATIONS TO THE DESIGN, LAYOUT OR LOCATION OF THE SYSTEMS MUST BE APPROVED BY A QUALIFIED PERSON AND
THE ENGINEER OF RECORD.
6. THE MAXIMUM ARREST FORCE ON EACH USER SHALL NOT EXCEED 1,800 LB.
7. THE SYSTEMS SHALL BE USED IN ACCORDANCE WITH THE WRITTEN USE AND RESCUE PROCEDURES DEVELOPED FOR THE SYSTEMS.
8. THE SYSTEMS SHALL BE INSPECTED BY A COMPETENT PERSON ANNUALLY.
9. THE SYSTEMS SHALL BE RECERTIFIED BY A QUALIFIED PERSON EVERY FIVE YEARS.
PROOF TESTING
THE CONTRACTOR SHALL PERFORM PROOF TESTING ON 100% OF THE FOLLOWING INSTALLATIONS:
1. ADHESIVE ANCHORS INTO CONCRETE OR MASONRY SHALL BE AXIAL TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE
ANCHOR NOTES OR SPECIFICATIONS.
2. MECHANICAL EXPANSION ANCHORS INTO CONCRETE OR MASONRY SHALL BE TORQUE TESTED IN ACCORDANCE WITH THE REQUIREMENTS
OF THE ANCHOR NOTES OR SPECIFICATIONS.
3. WIRE ROPE TERMINATIONS SHALL BE AXIAL TESTED TO 50% OF THE MINIMUM CABLE BREAKING STRENGTH.
FALL PROTECTION EQUIPMENT
THE EQUIPMENT USED WITH THE SYSTEMS SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT ANSI/ASSP FALL PROTECTION STANDARD. CONSULT A FALL PROTECTION COMPETENT PERSON TO DETERMINE IF EXISTING EQUIPMENT NOT CONFORMING
TO THESE REQUIREMENTS IS ACCEPTABLE FOR USE.
1. Z359.3-2019: SAFETY REQUIREMENTS FOR LANYARDS AND POSITIONING LANYARDS.
2. Z359.4-2013 (R2022): SAFETY REQUIREMENTS FOR ASSISTED-RESCUE AND SELF-RESCUE SYSTEMS, SUBSYSTEMS AND COMPONENTS.
3. Z359.9-2021 PERSONAL EQUIPMENT FOR PROTECTION AGAINST FALLS - DESCENT CONTROLLERS.
4. Z359.11-2021: SAFETY REQUIREMENTS FOR FULL BODY HARNESSES.
5. Z359.12-2019: CONNECTING COMPONENTS FOR PERSONAL FALL ARREST SYSTEMS.
6. Z359.13-2013 (R2022): PERSONAL ENERGY ABSORBERS AND ENERGY ABSORBING LANYARDS.
7. Z359.14-2021: SAFETY REQUIREMENTS FOR SELF-RETRACTING DEVICES FOR PERSONAL FALL ARREST AND RESCUE SYSTEMS.
8. Z359.15-2014: SAFETY REQUIREMENTS FOR SINGLE ANCHOR LIFELINES AND FALL ARRESTERS FOR PERSONAL FALL ARREST SYSTEMS.
9. Z359.16-2016: SAFETY REQUIREMENTS FOR CLIMBING LADDER FALL ARREST SYSTEMS.
10. Z359.18-2017: SAFETY REQUIREMENTS FOR ANCHORAGE CONNECTORS FOR ACTIVE FALL PROTECTION SYSTEMS.
REQUIRED FALL PROTECTION EQUIPMENT LIST
DAVIT
NOTES:
1. HARNESSES TO BE PROVIDED BY THE OWNER.
TYPE
SRL-R
DAVIT BASE
MANUFACTURER
3M DBI-SALA
MODEL / DESCRIPTION
CONFINED SPACE WINCH, 190ft
PART NUMBER
8518580
QUANTITY
DAVIT BASE
WINCH
3M DBI-SALA
3M DBI-SALA
3M DBI-SALA
3M DBI-SALA
ULTRA-LOK SELF-RETRACTING LIFELINE, 9m
ADJUSTABLE OFFSET DAVIT
CENTER MOUNT DAVIT BASE
WALL MOUNT DAVIT BASE
3504426
8518001
8512831
8518348
ADD'L.
A.F.F.
ALT.
ALUM.
ARCH.
B/ B.F.F.
BLDG.
C/C C.J.P.
C.L.
C.M.U.
CONT.
DIA.
DIM.
DWG.
ELEV.
EQ.
EQUIP.
E.S.
E.W.
EX.
EXT.
F/ F.S.
F.V.
GA.
GALV.
HORIZ.
I.D.
K
KLF
KSI
LB.
L.F.
ADDITIONAL
ABOVE FINISH FLOOR
ALTERNATE
ALUMINUM
ARCHITECTURAL
BOTTOM OF
BELOW FINISH FLOOR
BUILDING
CENTER TO CENTER
COMPLETE JOINT PENETRATION
CENTERLINE
CONCRETE MASONRY UNIT
CONTINUOUS
DIAMETER
DIMENSION
DRAWING
ELEVATION
EQUAL
EQUIPMENT
EACH SIDE
EACH WAY
EXISTING
EXTERIOR
FACE OF
FAR SIDE
FIELD VERIFY
GAUGE
GALVANIZED
HORIZONTAL
INSIDE DIAMETER
KIP
KIPS PER LINEAR FOOT
KIPS PER SQUARE INCH
POUND
LINEAL FEET
LLH
LLV
MAX.
MECH.
MEMB.
MIN.
MISC.
N.A.
N.S.
N.T.S.
O/O O.C.
O.D.
OPP.
PCF
PL
PLF
PSF
PSI
R.D.
REQ'D.
R.T.U.
SCH.
SIM.
SQ.
S.S.
STL.
STRUCT.
T/ T&B
TYP.
U.N.O.
VERT.
W/ W.P.
LONG LEG HORIZONTAL
LONG LEG VERTICAL
MAXIMUM
MECHANICAL
MEMBRANE
MINIMUM
MISCELLANEOUS
NOT APPLICABLE
NEAR SIDE
NOT TO SCALE
OUT TO OUT
ON CENTER
OUTSIDE DIAMETER
OPPOSITE
POUNDS PER CUBIC FOOT
PLATE
POUNDS PER LINEAL FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
ROOF DRAIN
REQUIRED
ROOF TOP UNIT
SCHEDULE
SIMILAR
SQUARE
STAINLESS STEEL
STEEL
STRUCTURAL
TOP OF
TOP AND BOTTOM
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
WITH
WORK POINT
STRUCTURAL ABBREVIATIONS
FALL PROTECTION ABBREVIATIONS
AAF
CLFAS
EAL
FBH
HLL
MAD
MAF
AVERAGE ARREST FORCE
CLIMBING LADDER FALL ARREST SYSTEM
ENERGY ABSORBING LANYARD
FULL BODY HARNESS
HORIZONTAL LIFELINE
MAXIMUM ARREST DISTANCE
MAXIMUM ARREST FORCE
PPE
SRD
SRL
SRL-LE
SRL-P
SRL-R
VLL
PERSONAL PROTECTIVE EQUIPMENT
SELF-RETRACTING DEVICE
SELF-RETRACTING LANYARD
SELF-RETRACTING LANYARD, LEADING EDGE
SELF-RETRACTING LANYARD, PERSONAL
SELF-RETRACTING LANYARD, RESCUE
VERTICAL LIFELINE
GENERAL NOTES
1. INSTALLER / ERECTOR IS RESPONSIBLE FOR MEANS, METHODS, PROCEDURES, AND SEQUENCES
OF CONSTRUCTION.
2. INSTALLER / ERECTOR IS RESPONSIBLE FOR CONDUCTING OPERATIONS IN ACCORDANCE WITH
THE APPLICABLE OSHA REGULATIONS AS WELL AS SAFETY REQUIREMENTS OF THE OWNER,
SITE, STATE, LOCAL AGENCIES.
3. INSTALLER / ERECTOR IS RESPONSIBLE FOR TEMPORARY BRACING AND SHORING TO ENSURE THE
STRUCTURAL INTEGRITY OF THE NEW AND ANY EXISTING STRUCTURES DURING CONSTRUCTION.
4. INSTALLER / ERECTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL DEBRIS FROM THE OWNER'S
PROPERTY AND DISPOSAL ACCORDING TO OWNER AND LOCAL REGULATIONS.
5. HOLES AND NOTCHES SHALL NOT BE CUT, DRILLED OR BURNED INTO ANY STRUCTURAL MEMBER
IN THE FIELD WITHOUT THE APPROVAL OF THE ENGINEER.
6. ALL DEVIATIONS FROM THE ENGINEERING DRAWINGS SHALL BE SUBMITTED IN WRITTEN FORM
TO THE ENGINEER FOR APPROVAL.
7. INSTALLER / ERECTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN
THE ENGINEERING DRAWINGS AND THE EXISTING CONDITIONS.
8. INSTALLER / ERECTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN
THE GENERAL STRUCTURAL NOTES, SPECIFICATIONS, AND DRAWINGS. THE ENGINEER WILL
DETERMINE WHICH REQUIREMENT WILL GOVERN.
9. DETAILS DESIGNATED AS "TYPICAL DETAILS" APPLY GENERALLY TO THE DRAWINGS IN AREAS
WHERE CONDITIONS ARE SIMILAR TO THOSE SHOWN IN THE DETAILS. CONTACT ENGINEER FOR
INTERPRETATION OF THE APPLICABILITY OF TYPICAL DETAILS.
10. EXISTING BUILDING INFORMATION SHOWN IS BASED UPON EXISTING BUILDING DRAWINGS AND FIELD OBERSVATIONS. THIS INFORMATION MAY NOT CONFORM EXACTLY TO THE CONDITIONS IN THE FIELD. INSTALLER / ERECTOR SHALL FIELD VERIFY ALL EXISTING BUILDING INFORMATION
SHOWN AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO THE FABRICATION OR
INSTALLATION.
11. INSTALLER / ERECTOR IS RESPONSIBLE FOR REPLACING AND REINSTALLING ANY STRUCTURAL MEMBER, ANCHOR OR COMPONENT THAT IS DAMAGED, BROKEN, OR FAILS INSPECTIONS / TESTING.
12. INSTALLER / ERECTOR IS RESPONSIBLE FOR TEMPORARILY REMOVING EXISTING UTILITIES AND OBSTRUCTIONS AS REQUIRED FOR THE INSTALLATION AND REINSTALLING (INCLUDING NECESSARY
MODIFICATIONS) AFTER COMPLETION OF WORK.
13. INSTALLER / ERECTOR IS RESPONSIBLE FOR SUBMITTING SHOP DRAWINGS FOR STRUCTURAL
WORK SHOWING ERECTION PLANS, PIECE DRAWINGS, AND CONNECTION DETAILS TO THE
ENGINEER. SHOP DRAWINGS SHALL BE APPROVED BY THE ENGINEER PRIOR TO FABRICATION.
LEGAL DISCLAIMER
THE DESIGNS AND SPECIFICATIONS CONTAINED HEREIN ARE INTENDED SOLELY FOR USE ON THE SPECIFIC PROJECT FOR WHICH THEY ARE PREPARED. ANY USE OF THESE DESIGNS AND SPECIFICATIONS ON OTHER PROJECTS, OR WITHOUT THE DIRECT INVOLVEMENT OF LJB, IS STRICTLY PROHIBITED. LJB SHALL NOT BE HELD RESPONSIBLE FOR ANY CLAIMS, DAMAGES, OR LIABILITIES ARISING FROM SUCH UNAUTHORIZED USE.
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
GENERAL
STRUCTURAL
DATA
S001
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SPECIAL INSPECTION
WHERE SPECIAL INSPECTION IS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IT SHALL BE PERFORMED BY A REGISTERED DEPUTY INSPECTOR, EMPLOYED BY THE OWNER AND APPROVED BY THE GOVERNING JURISDICTION. COPIES OF THE INSPECTION REPORTS SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT AND "LJB." A LICENSED ENGINEER OR ARCHITECT SHALL SIGN EACH REPORT.
"LJB" SHALL BE NOTIFIED IMMEDIATELY OF ANY TEST WHICH INDICATES NON COMPLIANCE WITH APPLICABLE CODES OR REQUIREMENTS OF THESE PLANS UNLESS NOTED OTHERWISE. UNLESS NOTED OTHERWISE, PROVIDE SPECIAL INSPECTION IN ACCORDANCE WITH SECTION 1705 OF THE 2015
INTERNATIONAL BUILDING CODE ON THE FOLLOWING:
A. STEEL CONSTRUCTION PER SECTION 1705.2.
B. CONCRETE CONSTRUCTION PER SECTION1705.3.
C. SOILS PER SECTION 1705.6.
D. EPOXY ANCHORS
0 6/02/2025 CONSTRUCTION
STRUCTURAL STEEL
FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS WITH THE FOLLOWING SUPPLEMENTAL
REQUIREMENTS, UNLESS NOTED OTHERWISE ON THE DRAWINGS:
1. WIDE FLANGE SHAPES, STRUCTURAL TEES, AND CHANNELS SHALL CONFORM TO ASTM A992.
STRUCTURAL TUBES SHALL CONFORM TO ASTM A500 GRADE C. STRUCTURAL PLATES AND
ANGLES SHALL CONFORM TO ASTM A572 GRADE 50. PIPES SHALL CONFORM TO ASTM A53 GRADE B.
ALL OTHER STRUCTURAL STEEL SHALL CONFORM TO ASTM A572 GRADE 50.
2. BOLTS SHALL CONFORM TO ASTM F3125 GRADE A325, SIZE AS PER PLAN. BOLTED CONNECTIONS SHALL PROVIDE A MINIMUM EDGE DISTANCE OF 1" FOR BOLT DIAMETERS 1/2" THROUGH 5/8" AND 1 1/4"
FOR BOLT DIAMETERS 3/4" THROUGH 1" AND SHALL BE LOCATED PER THE WORKABLE GAGE
ALLOWANCES. BOLT HOLES SHALL BE DRILLED 1/16" LARGER THAN THE BOLT DIAMETER, EXCEPT FOR
GALVANIZED MATERIAL WHICH SHALL BE DRILLED 1/8" LARGER.
3. THREADED RODS SHALL CONFORM TO ASTM A36. ANCHOR RODS SHALL CONFORM TO ASTM F1554 GRADE 36 STEEL WITH COMPOSITIONAL LIMITS OF ASTM A36 STEEL TO ENSURE WELDABITLITY.
4. NUTS SHALL CONFORM TO ASTM A563. WASHERS SHALL CONFORM TO ASTM F436.
5. SPLICING OF STRUCTURAL STEEL IS PROHIBITED EXCEPT AS DETAILED.
6. ALL WELDING SHALL BE DONE BY QUALIFIED WELDERS IN ACCORDANCE WITH THE CURRENT EDITION
OF THE AWS STRUCTURAL WELDING CODE. WELDING ELECTRODES SHALL BE E70SXX.
7. ALL STRUCTURAL STEEL, CONNECTIONS AND BOLTS SHALL BE GALVANIZED. APPLY ZINC COATING BY
THE HOT-DIPPED PROCESS IN ACCORDANCE WITH ASTM A123. GALVANIZING SHALL BE PERFORMED
AFTER FABRICATION. GALVANIZED STEEL SHALL NOT BE PAINTED.
8. BAR GRATING SHALL CONFORM TO ASTM A1011, GRADE 36. GRATING SHALL BE FABRICATED AND
ERECTED IN ACCORDANCE TO THE CURRENT METAL BAR GRATING MANUALS AND BEAR ON THE
SUPPORTING STRUCTURE A MINIMUM OF 1" (2" IF GREATER THAN 2 1/4" BAR HEIGHT) AND BE FASTENED WITH APPROVED WELDS, SCREWS, BOLTS OR CLIPS. TWO OR MORE FASTENERS SHALL BE PROVIDED PER SUPPORTING MEMBER WITH A MINIMUM OF FOUR PER PIECE. GRATING SHALL BE
TYPE 19-W-4 SMOOTH SURFACE WITH 3/16" BEARING BAR THICKNESS.
9. STAIR TREADS SHALL COMPRISE OF BAR GRATING CONFORMING TO ASTM A1011 GRADE 36, CARRIER PLATES ON BOTH ENDS AND A NOSING. GRATING SHALL BE TYPE 19-W-4 SMOOTH SURFACE WITH 3/16" BEARING BAR THICKNESS. TWO 3/8" DIAMETER ASTM A307 BOLTS SHALL BE PROVIDED PER
CARRIER PLATE WITH MINIMUM OF FOUR PER TREAD, UNLESS OTHERWISE REQUIRED BY THE
MANUFACTURER.
10. CLEAN FIELD WELDS AND DAMAGED AREAS FOLLOWING ERECTION. APPLY PAINT ACCORDING TO THE SHOP PAINTING REQUIREMENTS. APPLY GALVANIZING REPAIR PAINT ACCORDING TO ASTM A780.
CONCRETE
CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT ACI 301 SPECIFICATIONS FOR STRUCTURAL CONCRETE, ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, ACI 305 SPECIFICATION FOR HOT WEATHER CONCRETING, ACI 306 SPECIFICATION FOR COLD WEATHER CONCRETING, AND ACI 117 SPECIFICATION FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS WITH THE FOLLOWING
SUPPLEMENTAL REQUIREMENTS, UNLESS NOTED OTHERWISE ON THE DRAWINGS:
1. CONCRETE MIXES SHALL MEET THE REQUIREMENTS SPECIFIED BELOW:
2. CEMENT SHALL CONFORM TO ASTM C50 TYPE I, II, OR III, OR ASTM C595 TYPE IL.
3. CONTRACTOR SHALL PROVIDE SPACERS, CHAIRS, STIRRUPS, TIES, ETC. AS NECESSARY TO SECURELY HOLD
REINFORCING IN PLACE WHILE PLACING CONCRETE.
4. CHLORIDE-BASED ADMIXTURES ARE PROHIBITED IN ALL REINFORCED CONCRETE.
5. REINFORCING STEEL SHALL BE CONFORM TO A615, A706, OR A996, GRADE 60.
6. WELDED WIRE REINFORCMENT SHALL CONFORM TO ASTM A1064.
7. HORIZONTAL REINFORCING SHALL BE CONTINUOUS. REINFORCING STEEL SHALL BE LAPPED AS FOLLOWS
WHERE SPLICES ARE REQUIRED:
BAR SIZE LAP DIMENSION
#4 2'-0" #5 2'-6" #6 3'-0"
8. CONCRETE COVER ON REINFORCEMENT SHALL BE 3".
9. NON-SHRINK, NON-METALLIC, FACTORY PACKAGED GROUT SHALL BE USED BENEATH STEEL BASE PLATES.
GROUT SHALL HAVE A MINUMUM 28-DAY COMPRESSIVE STRENGTH OF 6,000 PSI AND SHALL CONFORM TO
ASTM C1107.
CONCRETE USE
FOUNDATIONS
28-DAY
COMPRESSIVE
STRENGTH
(f'c)
3,000 PSI 1 1/2"
AIR
ENTRAINMENT
NONE
UNIT WEIGHT
145 - 150 PCF
MAX
AGGREGATE
SIZE
0.55
MAX
W/C
RATIO
FOUNDATION NOTES
1. FOUNDATIONS SHALL BEAR ON UNDISTURBED SOIL OR COMPACTED ENGINEERING FILL.
2. EARTHWORK OPERATIONS SHALL BE PERFORMED UNDER THE DIRECTION OF A PROFESSIONAL GEOTECHNICAL
ENGINEER TO ASSURE COMPLIANCE WITH THE RECOMMENDATIONS OF THE SOILS REPORT.
3. CONCRETE SHALL NOT BE PLACED WHERE WATER OR FROST EXISTS IN THE BOTTOM OF THE FOUNDATION
EXCAVATION.
4. GEOTECHNICAL ENGINEER SHALL VERIFY THAT SOIL ON WHICH FOUNDATIONS BEAR MEET THE SOIL BEARING
CAPACITY LISTED IN THE DESIGN DATA.
5. OWNER IS RESPONSIBLE FOR VERIFYING LOCATIONS OF UNDERGROUND UTLITIES PRIOR TO EXCAVATION TO
AVOID DAMAGE.
6. BACKFILL SHALL BE GRANULAR MATERIAL, FREE FROM CLAY, LOAM OR PERISHABLE MATERIAL. THE APPROVED
MATERIAL SHALL BE PROPERLY COMPACTED.
POST-INSTALLED ANCHORS
ADHESIVE ANCHORS AND MECHANICAL EXPANSION ANCHORS INTO CONCRETE OR MASONRY SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT ACI 301 SPECIFICATIONS FOR STRUCTURAL CONCRETE AND ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE WITH THE FOLLOWING SUPPLEMENTAL REQUIREMENTS, UNLESS NOTED OTHERWISE ON THE DRAWINGS:
1. ADHESIVE ANCHORS SHALL MEET THE REQUIREMENTS:
BASE MATERIAL ANCHOR DESCRIPTION
CONCRETE HILTI HIT-HY 200 V3 W/THREADED ROD ASTM F1554 GR. 55
2. MECHANICAL EXPANSION ANCHORS SHALL MEET THE REQUIREMENTS:
BASE MATERIAL ANCHOR DESCRIPTION
CONCRETE HILTI CARBON STEEL KWIK BOLT KB-TZ2
3. ANCHOR DIAMETERS AND EMBEDMENT DEPTHS SHALL BE IN ACCORDANCE WITH THE SECTIONS AND DETAILS.
4. APPROVAL FROM A PROFESSIONAL ENGINEER IS REQUIRED BEFORE USING ANY ANCHOR NOT LISTED.
5. PROVIDE A MESH SCREEN IN UNGROUTED CMU AND BRICKS WITH HOLES OR VOIDS.
6. ANCHORS SHALL BE INSTALLED BY TRAINED PERSONNEL IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. WHEN APPLICABLE, HOLES SHALL BE PROPERLY DRILLED, CLEANED AND DRIED.
7. CONTACT THE ENGINEER OF RECORD IF EXISTING REINFORCING BARS OBSTRUCT THE ANCHOR LOCATION.
DO NOT CUT OR DAMAGE EXISTING REINFORCING BARS.
8. ADHESIVE ANCHORS SHALL BE AXIAL PROOF TESTED TO A LOAD EQUAL TO 67% OF THE MANUFACTURER'S LISTED TENSION CAPACITY OF THE ANCHOR DUE TO BOND AND CONCRETE FAILURE (REFER TO CHART BELOW). EACH ANCHOR SHALL BE TESTED INDIVIDUALLY WITH THE LOAD HELD FOR 1 MINUTE. ANCHORS SHALL BE REJECTED AND REPLACED IF THEY SHOW SIGNS OF SLIPPAGE, DISPLACEMENT, DAMAGE, OR
CONCRETE CRACKING / FAILURE.
BASE MATERIAL ANCHOR DIAMETER EMBEDMENT LOAD (LBS.)
CONCRETE 3/4" 4 3/4" 7,235
CONCRETE 3/4" 6" 7,735
9. MECHANICAL EXPANSION ANCHORS SHALL BE TESTED BY APPLYING THE SPECIFIED INSTALLATION TORQUE
VALUE. ANCHORS SHALL BE REJECTED AND REPLACED IF THEY SHOW SIGNS OF SLIPPAGE, DISPLACEMENT, DAMAGE, OR CONCRETE CRACKING / FAILURE
10. VERIFY REINFORCEMENT LOCATIONS BEFORE CONSTRUCTION TO CONFIRM FINAL ANCHOR POSITIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES TO BE ATTACHED USING MECHANICAL
ANCHORS.
11. CONTRACTOR SHALL LOCATE ALL SLAB PENETRATIONS PRIOR TO CONSTRUCTION BY SCANNING WITH GROUND PENETRATING RADAR (GPR), X-RAY, OR OTHER APPROVED METHOD, ENSURING A MINIMUM 2" CLEARANCE BETWEEN THE EDGE OF ANY CUT OR OPENING AND ANY POST-TENSIONING TENDON OR MILD
REINFORCEMENT.
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05/01/25
GENERAL
STRUCTURAL
DATA
S002
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SPLITTER BOX
DIGESTER 1DIGESTER 2SLUDGE HOLDING TANK
CLARIFIERS
S102
A S103
B
S104
C
S105
D
S106
E
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
SWTP OVERALL
PLAN
S101
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1/32" = 1'-0"
SWTP OVERALL PLANN
26'-8"
ACCESS PLATFORM
ACCESS PLATFORM
EX. ACCESS PLATFORM
S501
1'-0" M
AX.
26'-8"
1'-0" MAX.
3' -0
MODIFY EX. GUARDRAIL
S501
OPP.
S501
LEGEND
- WALL MOUNT DAVIT BASE
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
SLUDGE
HOLDING TANK
PLAN
S102
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1/8" = 1'-0"
A S101
SLUDGE HOLDING TANK PLANN
EX. ACCESS
PLATFORM
EX. SWING GATE TO BE LOCKED
UNLESS FALL PROTECTION SYSTEM
IS BEING USED
ACCESS PLATFORM
1'-0" MAX.
S501
EX. ACCESS
PLATFORM
S501
MODIFY EX. GUARDRAIL
1' -0
M
A X
ACCESS PLATFORM
1'-0" M
AX.
S501
OPP.
1' -0
" M
AX
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
DIGESTER 2
PLAN
S103
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1/8" = 1'-0"
B S101
DIGESTER 2 PLANN
EX. ACCESS
PLATFORM
EX. ACCESS
PLATFORM
S501
EX. SWING GATE TO BE LOCKED
UNLESS FALL PROTECTION
SYSTEM IS BEING USED
MODIFY EX. GUARDRAIL
ACCESS PLATFORM
1'-0" MAX.
1' -0
M
A X
S501
ACCESS PLATFORM
1'-0" M
AX.
S501
OPP.
1'-0" M
AX.
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
DIGESTER 1
PLAN
S104
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1/8" = 1'-0"
C S101
DIGESTER 1 PLANN
5'-8" 8'-0" 7'-8"
℄ EX. SWING GATE ℄ EX. SWING GATE ℄ EX. SWING GATE
3'-0" 3'-0" 3'-0"
S502
TYP.
- CENTER MOUNT DAVIT BASE
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
CLARIFIER PLAN
VIEW
S105
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1/8" = 1'-0"
D S101
CLARIFIER PLANN
UP
6'-0"
3' -0
3'
-0
5'-0"
7' -0
5'-0" 6'-0"
8' -6
MODIFY GRATING TO PROVIDE 6"x6"
OPENING FOR DAVIT AND INSTALL
REMOVABLE HATCH OR COVER
2'-6"
2' -0
8' -6
2'-6"
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
SPLITTER BOX
PLAN VIEW
S106
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1/4" = 1'-0"
E S101
SPLITTER BOX PLANN
BOLT-ON GUARDRAIL -
1 1/2"Ø SCH 40 PIPE
3' -6
M
A X
3' -3
M
IN
4'-6"
SWING GATE
2'-2"
1' -7
M
A X
GUARDRAIL POST -
1 1/2"Ø SCH 80
PIPE
T/GRATING
SEE TYPICAL GUARDRAIL
POST TO CHANNEL DETAIL
EX. 2"Ø ALUMINUM
GUARDRAIL
3'-2"
1' -7
3' -6
M
A X
3' -3
M
IN
BOLT-ON GUARDRAIL -
1 1/2"Ø SCH 40 PIPE
2'-2"
DEMO EX. RAIL
SWING GATE
GUARDRAIL
POST - 1 1/2"Ø
SCH 80 PIPE
EX. WINCH
T/CONC
SEE TYPICAL GUARDRAIL
POST TO CONCRETE DETAIL
3'-6"
LANDING LENGTH
2'-6" MIN.
C12X20.7
10" TYP.
10" TREADS TYP.
1" BAR GRATING
(GALVANIZED)
HSS3X3X1/4
HSS3X3X1/4
(1 5)
E Q
. S P
A C
E S
8' -9
1" BAR GRATING
(GALVANIZED)
T/FOUNDATION
T/TANK
2'-0" MAX. 4'-6" MAX, 4'-6" MAX. 4'-6" MAX.
SWING GATE
S501
3'-3"
0' -0
M
IN
1' -0
M
A X
C12X20.7 WELDMENT
3'-0"
EX. TANK WALL
3' -6
M
A X
3' -3
M
IN
1' -7
M
A X
C12X20.7 WELDMENT
W.P.
1'-0"
W.P.
W.P.
M A
X
6" E
Q
E Q
M A
X
6"
L3X3X3/16
L3X3X3/16
1 1/2" SCH 80 PIPE
1/2" GUSSET
PLATE - TYP.
TYP. BRACING
(2) LOCATIONS
TOE PL1/4X4
3'-3"
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
SECTIONS &
DETAILS
S501
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 3/4" = 1'-0"
S103 S104
SECTION
SCALE: 3/4" = 1'-0"
S102
SECTION
SCALE: 3/4" = 1'-0"
S102, S103, S104
SECTION
SCALE: 3/4" = 1'-0"
S501
SECTION
NOTE: SEE SHEET S502 FOR FOUNDATION REQUIREMENTS NOTE: SEE SHEET S502 FOR FOUNDATION REQUIREMENTS
2' -0
DAVIT BASE
BOLT D-RING W/ 5/8"Ø EXPANSION
ANCHOR (ALL STAINLESS STEEL)
EX. GUARDRAIL
T/CONC
ELEV = 840'-7"
T/CONC
ELEV = 823'-7"
#4 TIES EQ. SPACED AT
1'-0"
(4) #6 BARS
GRADE
2' -6
3"
3" C
LR
#4 TIES EQ. SPACED AT
1'-0"
(4) #6 BARS
1'-8" SQ.
T Y
P
IC
A L
3" C
LR
3" C
LR
WIRE MESH CENTERED IN SLAB
GRADE
COMPACTED GRAVEL
4'-0"
3" 1/
2"
1/
2"
1"
COMPACTED
2' -6
3" C
LR
T Y
P
1'-2" (x4'-0") STAIR LANDING
(2) #4 CONT.
(2) #4 CONT.
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
SECTIONS &
DETAILS
S502
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 3/4" = 1'-0"
S105
SECTION
SCALE: 1" = 1'-0"
TYP. FOOTING AT STAIR POST
SCALE: 1" = 1'-0"
TYP. STAIR LANDING SECTION
SCALE: 1" = 1'-0"
TYP. STAIR STRINGER FOOTING
1' -9
1'
-9
3' -0
1 1/2" SCH 40 PIPE TOP RAIL
1 1/4" SCH 40 PIPE
HANDRAIL
1 1/2" SCH 80 PIPE POST TYP
1 1/2" SCH 40 PIPE MID-RAIL
5"
2 1/4" MIN.
C12 STRINGER
T/LANDING OR
TREAD AT NOSING
3'-6" MAX
2'-6" CLEAR
1'-10" MIN.
CL POST
3/16
C12 STRINGER
PL 3/8X2 1/2X0'-8" W/ (2) 5/8"Ø BOLTS
1"
1"
1/
2"
4" 4"2" 2"
C12
1/4" CLOSURE PL
3/16
PL 3/8X4X0'-8"
W/(1) 13/16"⌀ HOLE
1/4" PL TO C12
C
PL 3/8"
CENTERED
℄ (1) 5/8"⌀ EXPANSION
ANCHOR W/ 3 1/4"
EMBEDMENT
1/4" CLOSURE PL
1" NON-SHRINK
GROUT
FOOTING
4"
9"
1/4"
4 SIDES
HSS3X3
PL1/2X4X0'-9"
1 1/2" TYP.
℄ (2) 5/8"Ø EXPANSION ANCHORS
W/ 3 1/4" EMBEDMENT
1" NON-SHRINK
GROUT
FOOTING
9"
4"
(2) 5/8"Ø BOLTS
1/4"
4 SIDES
1 1/2" TYP.
PL3/8X4X0'-9"
HSS3X3
℄ (2) 1/2"Ø EXPANSION
ANCHORS W/ 3 1/4"
EMBEDMENT
CONCRETE
GUARDRAIL POST
PL 3/8X6X0'-6"
3/16
1" 4" 1"
1" 4"
1"
PL 3/8X6X0'-6"
6"
6"
NOTE:
1)SWING GATE ATTACHED TO GUARDRAIL PER
MANUFACTURER SPECIFICATIONS.
2)SWING GATE TO BE LOCKED UNLESS FALL
PROTECTION SYSTEM IS BEING USED.
1' -7
M
A X
1' -7
M
A X
3' -6
(3
'-3
M
IN
T/GRATING
SWING GATE -
GARLOCK PN: 56HH74
(OR APPROVED EQUAL)
CL POST
3/16
CHANNEL
PL 3/8X2 1/2X0'-8" W/ (2) 5/8"Ø BOLTS
1/
2"
9"
4"
EDGE OF CONC.
6" M
IN
(4) 3/4"Ø ADHESIVE ANCHORS
W/ 6" EMBEDMENT
1/
2" M
IN
EX. CONC. WALL
8 1/2"
1/
4"
M
IN
(4) 3/4"Ø ADHESIVE ANCHORS
W/ 4 3/4" EMBEDMENT
T/CONC
(2) 5/8"Ø BOLTS
C12
PL3/8X4X0'-6"
C12 STRINGER
1/4"
1/4"
TYP.
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
2:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
SECTIONS &
DETAILS
S503
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE DESIGN -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1" = 1'-0"
TYP. STAIR RAIL DETAIL
SCALE: 1 1/2" = 1'-0"
TYP. GUARDRAIL POST TO STRINGER
SCALE: 1 1/2" = 1'-0"
TYP. STRINGER BOTTOM CONNECTON
SCALE: 1 1/2" = 1'-0"
TYP. BASE PLATE CONNECTION
SCALE: 1" = 1'-0"
TYP. CAP PLATE CONNECTION
SCALE: 1" = 1'-0"
TYP. GUARDRAIL TO CONCRETE
SCALE: 1" = 1'-0"
TYP. SWING GATE SECTION
SCALE: 1 1/2" = 1'-0"
TYP. GUARDRAIL POST TO CHANNEL
SCALE: 1 1/2" = 1'-0"
TYP. CENTER MOUNT DAVIT BASE
SCALE: 1 1/2" = 1'-0"
TYP. WALL MOUNT DAVIT BASE
SCALE: 1 1/2" = 1'-0"
TYP. STRINGER TOP CONNECTION
NOTE: 4" MINIMUM EDGE DISTANCE FOR EXPANSION ANCHORS
SPLITTER BOX
DIGESTER 1DIGESTER 2SLUDGE HOLDING TANK
CLARIFIERS
S102
A S103
B
S104
C
S105
D
S106
E
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
1:
:0
P
M
OAZ
RDS
ZEP
0127047A.00
05-01-25
SWTP OVERALL
PLAN
S101
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
FALL PROTECTION
AND CONFINED
SPACE RETRIEVAL -
SWTP
KENTON COUNTY
AIRPORT BOARD
P.O. BOX 75200 CINCINNATI, OH
45275
SCALE: 1/32" = 1'-0"
SWTP OVERALL PLANN
0 6/02/2025 CONSTRUCTION
P3
P4
P5
P6
P7 P8
P9
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
REVISED JULY 15, 2025
P101
P3
ADD GUARDRAIL ADD SWING GATE
ADD DAVIT BASE
ON OUTSIDE OF
CONCRETE WALL
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
P102
P4
NEW GROUND SUPPORTED
ACCESS PLATFORM WITH
STAIRS AND SWING GATE
INSTALL DAVIT
BASE ON WALL
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
P103
P5
ADD GUARDRAIL
WITH SWING GATE
INSTALL DAVIT
BASE ON WALL
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
P104
ADD GUARDRAIL
WITH SWING GATE
INSTALL DAVIT
BASE ON WALL
P6
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
P105
P7
INSTALL DAVIT BASES
ON WALL AT EACH
SWING GATE LOCATION
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
P106
P8
INSTALL D-RINGS
ON WALL BELOW
EACH SWING GATE
LOCATION
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
P107
P9
INSTALL SEVERAL DAVIT
BASES TO SIDE ON WALL
AROUND SPLITTER BOX
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
LJB INC.
CVG FALL PROTECTION AND
CONFINED SPACE DESIGN
JUNE 2, 2025
P108
G001 COVER SHEET
S T
T E O F K ENT U
C l
O
31511
K
A
C N S O
R P
F
E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
DATEPROJECT NUMBER SHEET NUMBER
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
RELEASES / REVISIONS
DRAWING INDEX
06/02/2025
5/
/2
5:
:5
P
M
0128276A.00 05-01-25 G001
PROJECT TEAM
ROOF FALL PROTECTION - PARKING DECK
CINCINNATI/NORTHERN KENTUCKY INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
PO BOX 75200 CINCINNATI, OH 45275
STRUCTURAL
S001 GENERAL STRUCTURAL DATA
S101 PLAN VIEW
S501 SECTIONS & DETAILS
REV DATE RELEASED FOR
0 06-02-2025 CONSTRUCTION
SUMMARY OF WORK: Providing fall protection railings, roof markings, access ladder and gate, etc. as indicated on the drawings.
i. Locate and avoid existing reinforcing and or post tensioning tendons via X-Ray or approved methods.
ii. Provide 160’ +/- steel railing, access ladder, (70 +/-) roof marking.
OSHA 29 CFR 1910
DESIGN SPECIFICATIONS
DESIGN DATA
ROOF LOADS
ROOF SNOW LOAD
GROUND SNOW LOAD, pg ------------------------- 20 PSF FLAT ROOF SNOW LOAD, pf --------------------- 20 PSF SNOW EXPOSURE FACTOR, Ce ----------------- 0.9 SNOW LOAD IMPORTANCE FACTOR, ls ------ 1.0 THERMAL FACTOR, Ct ------------------------------ 1.2
BASIC DESIGN WIND LOAD
BASIC WIND SPEED, V ---------------------------------- 115 MPH
RISK CATEGORY ------------------------------------------ II
EXPOSURE -------------------------------------------------- B
VELOCITY PRESSURE, q ------------------------------- 16 PSF
LIVE LOAD (UNIFORM) ------------------------ 25 PSF
DEAD LOAD (TOTAL) --------------------------- SELF-WEIGHT
EARTHQUAKE DESIGN DATA
RISK CATEGORY ------------------------------------------ II
SEISMIC IMPORTANCE FACTOR, le ----------------- 1.00
SS = 0.146
S1 = 0.08
SITE CLASS -------------------------------------------------- D (DEFAULT)
SDS = 0.156
SD1 = 0.128
SEISMIC DESIGN CATEGORY ------------------------- B
BASIC SEISMIC-FORCE-RESISTING SYSTEM:
STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
SEISMIC RESPONSE COEFFICIENT, CS ------------ 0.052
RESPONSE MODIFICATION COEFFICIENT, R ---- 3
DESIGN BASE SHEAR, CSW ----------------------------- 0.052W
ANALYSIS PROCEDURE:
ELF PROCEDURE
WALKING-WORKING SURFACE LOADS
LADDER
• LIVE LOAD ------------------------------------------------- 300 LBS
• DEAD LOAD LADDER ---------------------------------- 10 PLF
GUARDRAIL & STAIR RAILS
• LIVE LOAD TOP RAIL (CONCENTRATED) -------- 200 LBS
• LIVE LOAD MID RAIL ------------------------------------- 150 LBS
• LIVE LOAD TOEBOARD --------------------------------- 50 LBS
• DEAD LOAD ------------------------------------------------- 20 PLF
ADD'L.
A.F.F.
ALT.
ALUM.
ARCH.
B/ B.F.F.
BLDG.
C/C C.J.P.
C.L.
C.M.U.
CONT.
DIA.
DIM.
DWG.
ELEV.
EQ.
EQUIP.
E.S.
E.W.
EX.
EXT.
F/ F.S.
F.V.
GA.
GALV.
HORIZ.
I.D.
K
KLF
KSI
LB.
L.F.
ADDITIONAL
ABOVE FINISH FLOOR
ALTERNATE
ALUMINUM
ARCHITECTURAL
BOTTOM OF
BELOW FINISH FLOOR
BUILDING
CENTER TO CENTER
COMPLETE JOINT PENETRATION
CENTERLINE
CONCRETE MASONRY UNIT
CONTINUOUS
DIAMETER
DIMENSION
DRAWING
ELEVATION
EQUAL
EQUIPMENT
EACH SIDE
EACH WAY
EXISTING
EXTERIOR
FACE OF
FAR SIDE
FIELD VERIFY
GAUGE
GALVANIZED
HORIZONTAL
INSIDE DIAMETER
KIP
KIPS PER LINEAR FOOT
KIPS PER SQUARE INCH
POUND
LINEAL FEET
LLH
LLV
MAX.
MECH.
MEMB.
MIN.
MISC.
N.A.
N.S.
N.T.S.
O/O O.C.
O.D.
OPP.
PCF
PL
PLF
PSF
PSI
R.D.
REQ'D.
R.T.U.
SCH.
SIM.
SQ.
S.S.
STL.
STRUCT.
T/ T&B
TYP.
U.N.O.
VERT.
W/ W.P.
LONG LEG HORIZONTAL
LONG LEG VERTICAL
MAXIMUM
MECHANICAL
MEMBRANE
MINIMUM
MISCELLANEOUS
NOT APPLICABLE
NEAR SIDE
NOT TO SCALE
OUT TO OUT
ON CENTER
OUTSIDE DIAMETER
OPPOSITE
POUNDS PER CUBIC FOOT
PLATE
POUNDS PER LINEAL FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
ROOF DRAIN
REQUIRED
ROOF TOP UNIT
SCHEDULE
SIMILAR
SQUARE
STAINLESS STEEL
STEEL
STRUCTURAL
TOP OF
TOP AND BOTTOM
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
WITH
WORK POINT
STRUCTURAL ABBREVIATIONS
FALL PROTECTION ABBREVIATIONS
AAF
CLFAS
EAL
FBH
HLL
MAD
MAF
AVERAGE ARREST FORCE
CLIMBING LADDER FALL ARREST SYSTEM
ENERGY ABSORBING LANYARD
FULL BODY HARNESS
HORIZONTAL LIFELINE
MAXIMUM ARREST DISTANCE
MAXIMUM ARREST FORCE
PPE
SRD
SRL
SRL-LE
SRL-P
SRL-R
VLL
PERSONAL PROTECTIVE EQUIPMENT
SELF-RETRACTING DEVICE
SELF-RETRACTING LANYARD
SELF-RETRACTING LANYARD, LEADING EDGE
SELF-RETRACTING LANYARD, PERSONAL
SELF-RETRACTING LANYARD, RESCUE
VERTICAL LIFELINE
GENERAL NOTES
1. INSTALLER / ERECTOR IS RESPONSIBLE FOR MEANS, METHODS, PROCEDURES, AND SEQUENCES
OF CONSTRUCTION.
2. INSTALLER / ERECTOR IS RESPONSIBLE FOR CONDUCTING OPERATIONS IN ACCORDANCE WITH
THE APPLICABLE OSHA REGULATIONS AS WELL AS SAFETY REQUIREMENTS OF THE OWNER,
SITE, STATE, LOCAL AGENCIES.
3. INSTALLER / ERECTOR IS RESPONSIBLE FOR TEMPORARY BRACING AND SHORING TO ENSURE THE
STRUCTURAL INTEGRITY OF THE NEW AND ANY EXISTING STRUCTURES DURING CONSTRUCTION.
4. INSTALLER / ERECTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL DEBRIS FROM THE OWNER'S
PROPERTY AND DISPOSAL ACCORDING TO OWNER AND LOCAL REGULATIONS.
5. HOLES AND NOTCHES SHALL NOT BE CUT, DRILLED OR BURNED INTO ANY STRUCTURAL MEMBER
IN THE FIELD WITHOUT THE APPROVAL OF THE ENGINEER.
6. ALL DEVIATIONS FROM THE ENGINEERING DRAWINGS SHALL BE SUBMITTED IN WRITTEN FORM
TO THE ENGINEER FOR APPROVAL.
7. INSTALLER / ERECTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN
THE ENGINEERING DRAWINGS AND THE EXISTING CONDITIONS.
8. INSTALLER / ERECTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN
THE GENERAL STRUCTURAL NOTES, SPECIFICATIONS, AND DRAWINGS. THE ENGINEER WILL
DETERMINE WHICH REQUIREMENT WILL GOVERN.
9. DETAILS DESIGNATED AS "TYPICAL DETAILS" APPLY GENERALLY TO THE DRAWINGS IN AREAS
WHERE CONDITIONS ARE SIMILAR TO THOSE SHOWN IN THE DETAILS. CONTACT ENGINEER FOR
INTERPRETATION OF THE APPLICABILITY OF TYPICAL DETAILS.
10. EXISTING BUILDING INFORMATION SHOWN IS BASED UPON EXISTING BUILDING DRAWINGS AND FIELD OBERSVATIONS. THIS INFORMATION MAY NOT CONFORM EXACTLY TO THE CONDITIONS IN THE FIELD. INSTALLER / ERECTOR SHALL FIELD VERIFY ALL EXISTING BUILDING INFORMATION
SHOWN AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO THE FABRICATION OR
INSTALLATION.
11. INSTALLER / ERECTOR IS RESPONSIBLE FOR REPLACING AND REINSTALLING ANY STRUCTURAL MEMBER, ANCHOR OR COMPONENT THAT IS DAMAGED, BROKEN, OR FAILS INSPECTIONS / TESTING.
12. INSTALLER / ERECTOR IS RESPONSIBLE FOR TEMPORARILY REMOVING EXISTING UTILITIES AND OBSTRUCTIONS AS REQUIRED FOR THE INSTALLATION AND REINSTALLING (INCLUDING NECESSARY
MODIFICATIONS) AFTER COMPLETION OF WORK.
13. INSTALLER / ERECTOR IS RESPONSIBLE FOR SUBMITTING SHOP DRAWINGS FOR STRUCTURAL
WORK SHOWING ERECTION PLANS, PIECE DRAWINGS, AND CONNECTION DETAILS TO THE
ENGINEER. SHOP DRAWINGS SHALL BE APPROVED BY THE ENGINEER PRIOR TO FABRICATION.
14. ROOF MARKINGS TO BE MINIMUM 6" WIDE AND SAFETY YELLOW. ROOF MARKINGS TO BE
ADHERED TO ROOF WITH APPROPRIATE ROOFING ADHEISIVE.
LEGAL DISCLAIMER
THE DESIGNS AND SPECIFICATIONS CONTAINED HEREIN ARE INTENDED SOLELY FOR USE ON THE SPECIFIC PROJECT FOR WHICH THEY ARE PREPARED. ANY USE OF THESE DESIGNS AND SPECIFICATIONS ON OTHER PROJECTS, OR WITHOUT THE DIRECT INVOLVEMENT OF LJB, IS STRICTLY PROHIBITED. LJB SHALL NOT BE HELD RESPONSIBLE FOR ANY CLAIMS, DAMAGES, OR LIABILITIES ARISING FROM SUCH UNAUTHORIZED USE.
STRUCTURAL STEEL
FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS WITH THE FOLLOWING SUPPLEMENTAL
REQUIREMENTS, UNLESS NOTED OTHERWISE ON THE DRAWINGS:
1. WIDE FLANGE SHAPES, STRUCTURAL TEES, AND CHANNELS SHALL CONFORM TO ASTM A992.
STRUCTURAL TUBES SHALL CONFORM TO ASTM A500 GRADE C. STRUCTURAL PLATES AND
ANGLES SHALL CONFORM TO ASTM A572 GRADE 50. PIPES SHALL CONFORM TO ASTM A53 GRADE B.
ALL OTHER STRUCTURAL STEEL SHALL CONFORM TO ASTM A572 GRADE 50.
2. BOLTS SHALL CONFORM TO ASTM F3125 GRADE A325, SIZE AS PER PLAN. BOLTED CONNECTIONS SHALL PROVIDE A MINIMUM EDGE DISTANCE OF 1" FOR BOLT DIAMETERS 1/2" THROUGH 5/8" AND 1 1/4"
FOR BOLT DIAMETERS 3/4" THROUGH 1" AND SHALL BE LOCATED PER THE WORKABLE GAGE
ALLOWANCES. BOLT HOLES SHALL BE DRILLED 1/16" LARGER THAN THE BOLT DIAMETER, EXCEPT FOR
GALVANIZED MATERIAL WHICH SHALL BE DRILLED 1/8" LARGER.
3. THREADED RODS SHALL CONFORM TO ASTM A36. ANCHOR RODS SHALL CONFORM TO ASTM F1554 GRADE 36 STEEL WITH COMPOSITIONAL LIMITS OF ASTM A36 STEEL TO ENSURE WELDABITLITY.
4. NUTS SHALL CONFORM TO ASTM A563. WASHERS SHALL CONFORM TO ASTM F436.
5. SPLICING OF STRUCTURAL STEEL IS PROHIBITED EXCEPT AS DETAILED.
6. ALL WELDING SHALL BE DONE BY QUALIFIED WELDERS IN ACCORDANCE WITH THE CURRENT EDITION
OF THE AWS STRUCTURAL WELDING CODE. WELDING ELECTRODES SHALL BE E70SXX.
7. ALL STRUCTURAL STEEL, CONNECTIONS AND BOLTS SHALL BE GALVANIZED. APPLY ZINC COATING BY THE HOT-DIPPED PROCESS IN ACCORDANCE WITH ASTM A123. GALVANIZING SHALL BE PERFORMED
AFTER FABRICATION. GALVANIZED STEEL SHALL NOT BE PAINTED.
8. CLEAN FIELD WELDS AND DAMAGED AREAS FOLLOWING ERECTION. APPLY PAINT ACCORDING TO THE SHOP PAINTING REQUIREMENTS. APPLY GALVANIZING REPAIR PAINT ACCORDING TO ASTM A780.
POST-INSTALLED ANCHORS
ADHESIVE ANCHORS AND MECHANICAL EXPANSION ANCHORS INTO CONCRETE OR MASONRY SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT ACI 301 SPECIFICATIONS FOR STRUCTURAL CONCRETE AND ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE WITH THE FOLLOWING SUPPLEMENTAL REQUIREMENTS, UNLESS NOTED OTHERWISE ON THE DRAWINGS:
1. MECHANICAL EXPANSION ANCHORS SHALL MEET THE REQUIREMENTS:
BASE MATERIAL ANCHOR DESCRIPTION (BRAND, ADHESIVE, ROD, MATERIAL)
CONCRETE HILTI CARBON STEEL KWIK BOLT KB-TZ2
2. ANCHOR DIAMETERS AND EMBEDMENT DEPTHS SHALL BE IN ACCORDANCE WITH THE SECTIONS AND DETAILS.
3. APPROVAL FROM A PROFESSIONAL ENGINEER IS REQUIRED BEFORE USING ANY ANCHOR NOT LISTED.
4. ANCHORS SHALL BE INSTALLED BY TRAINED PERSONNEL IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. WHEN APPLICABLE, HOLES SHALL BE PROPERLY DRILLED, CLEANED AND DRIED.
5. CONTACT THE ENGINEER OF RECORD IF EXISTING REINFORCING BARS OBSTRUCT THE ANCHOR LOCATION.
DO NOT CUT OR DAMAGE EXISTING REINFORCING BARS.
6. MECHANICAL EXPANSION ANCHORS SHALL BE TESTED BY APPLYING THE SPECIFIED INSTALLATION TORQUE
DAMAGE, OR CONCRETE CRACKING / FAILURE.
7. VERIFY REINFORCEMENT LOCATIONS BEFORE CONSTRUCTION TO CONFIRM FINAL ANCHOR POSITIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES TO BE ATTACHED USING MECHANICAL
ANCHORS.
8. CONTRACTOR SHALL LOCATE ALL SLAB PENETRATIONS PRIOR TO CONSTRUCTION BY SCANNING WITH GROUND PENETRATING RADAR (GPR), X-RAY, OR OTHER APPROVED METHOD, ENSURING A MINIMUM 2" CLEARANCE BETWEEN THE EDGE OF ANY CUT OR OPENING AND ANY POST-TENSIONING TENDON OR MILD
REINFORCEMENT.
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
5:
:5
P
M
OAZ
TVT
ZEP
0128276A.00
05-01-25
GENERAL
STRUCTURAL
DATA
S001
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
ROOF FALL
PROTECTION -
PARKING DECK
KENTON COUNTY
AIRPORT BOARD
PO BOX 75200 CINCINNATI, OH
45275
0 06-02-2025 CONSTRUCTION
EX. BEACON
ROOF MOUNTED
GUARDRAIL
ROOF MARKING
'-0
'-0
SWING
GATE
LADDER
70'-0"
'-0
'-0
S501
PARKING GARAGE ROOF
PARKING DECK ROOF
ELEV. = 936'-7"
S501
1'-0"
C.L. LADDER
S T
T E O F K ENTU
C l
O
31511
K
A
C N S O
R P
F E
SSI LN E NG IN
E E
R
EE DL
A
YDR. JAMES
GRIFFIN
JEFFREY
LJBinc.com
(866) 552-3536 info@LJBinc.com
CHECKED
DATE
PROJECT NUMBER
SHEET TITLE
SHEET NUMBER
DRAWN
DESIGNED
RELEASED FORREV DATE
© 1985-2025 LJB Inc. This drawing contains information that is proprietary to and property of LJB Inc. and shall be kept confidential. No publication or distribution of this drawing may be made without the express written consent of LJB Inc. except for the limited purposes set forth in the contract between LJB Inc. and party for whom this drawing was made.
06/02/2025
5/
/2
5:
:5
P
M
OAZ
TVT
ZEP
0128276A.00
05-01-25
PLAN VIEW
S101
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
ROOF FALL
PROTECTION -
PARKING DECK
KENTON COUNTY
AIRPORT BOARD
PO BOX 75200 CINCINNATI, OH
45275
N SCALE: 3/16" = 1'-0"
PARKING DECK ROOF PLAN
0 06-02-2025 CONSTRUCTION
1' -8
5' -9
GUARDRAIL
BEACON BEAM
PARKING DECK ROOF
3' -6
23'-9"
LADDER SIDERAIL
LADDER RUNG
3/16
3/8" 1/8"
LEVEL 5
ELEV = 924'-7"
'-6
4' -6
7'
-0
3"
3"
1/ 2"
LEVEL 5
ELEV = 924'-7"
T/RUNG & ROOF
ELEV = 936'-7"
'-6
S P
A C
E S
'-0
2' -0
T/RUNG & ROOF
ELEV = 936'-7"
1'-0" 1'-0"
3/4"Ø NON-SLIP RUNGS
(NOT REBAR)
1/2X2 1/2" PL. SIDERAIL
BRACKETS @ 7'-0" O.C.
MAX. (SEE LADDER
CONNECTION DETAIL)
1'-6"
(M A
X
1' -0
INSTALL LADDER
SECURITY GUARD
NOTE:
SWING GATE ATTACHED TO GUARDRAIL PER
MANUFACTURER SPECIFICATIONS
1' -7
M
A X
1' -7
M
A X
3' -6
(3
'-3
M
IN
T/ DECK
SWING GATE
GARLOCK PN 56HH74
(OR APPROVED EQUAL)
1/2" ⌀ EXPANSION ANCHOR
W/ 3 1/4" EMBEDMENT
BENT PL 3/8X3
3/16
3 SIDES
PL 1/2" X 2 1/2"
1/2"
CONCRETE
12" MAX.
9 1/2" MIN.
1"
1/ 2"
LADDER SIDERAIL
LADDER RUNG
C.L. 1/2"Ø EXPANSION ANCHOR
W/ 3 1/4" EMBEDMENT, CENTERED
L4X3X3/8X0'-2 1/2" (LLV)
CENTER ON SIDERAIL
C.L.