This technical specification outlines requirements for a high density storage system for Portsmouth Naval Shipyard in Kittery, Maine. The scope includes design, procurement, and installation of two narrow aisle forklifts, forklift chargers, in-floor wire guide systems, and storage rack systems. Additional optional items include one additional narrow aisle forklift and one standard forklift. Submittals require drawings, product data, design data, manufacturer instructions, and operation and maintenance documentation. Performance criteria specify lift truck and reach truck capacity ratings of 3,500 to 4,500 pounds at specified load centers and lift heights. Storage racks require load support decks and vertical supports spaced at approximately 9 feet 4 inches with welded base plates and gray powder coated finish. The Navy Facilities Engineering Command is the contracting agency.

View the file

Other files for this federal contract opportunity

Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B178, HIGH DENSITY STORAGE SYSTEM

PORTSMOUTH NAVAL SHIPYARD, KITTERY, MAINE

SECTION 11 54 01

SHOP EQUIPMENT

11/08

PART 1 GENERAL

1.1 REFERENCES

All applicable Governmental manufacturing, safety, testing, and certifying reference publications shall be provided with each submittal. These publications shall include, but not necessarily be limited to, ASTM (International), NFPA, OSHA, and UL.

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM E84 (2014) Standard Test Method for Surface Burning Characteristics of Building Materials

1.2 SUMMARY

The equipment described in this technical specification are to be included in the following project:

High Rack Shelving/Lift Trucks System

Refer to the attachment at the end of this section for industrial equipment basis-of-design product cut sheets (for reference only).

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33

SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Narrow Aisle Lift Truck; G Narrow Aisle Lift Truck Charging Station; G Narrow Aisle Lift Truck In-Floor Wire Guide System; G Narrow Aisle Storage Rack System; G Lift Truck; G Lift Truck Charging Station; G Storage Rack System; G

SD-03 Product Data

Narrow Aisle Lift Truck; G Narrow Aisle Lift Truck Charging Station; G Narrow Aisle Lift Truck In-Floor Wire Guide System; G Narrow Aisle Storage Rack System; G

Lift Truck; G

SD-05 Design Data

Narrow Aisle Lift Truck In-Floor Wire Guide System; G Narrow Aisle Storage Rack System; G

SD-08 Manufacturer's Instructions

Narrow Aisle Lift Truck Charging Station; G Narrow Aisle Lift Truck In-Floor Wire Guide System; G Narrow Aisle Storage Rack System; G Lift Truck; G

SD-10 Operation and Maintenance Data

Narrow Aisle Lift Truck Charging Station; G Narrow Aisle Lift Truck In-Floor Wire Guide System; G Narrow Aisle Storage Rack System; G Lift Truck; G

Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.

Refer to Section 01 78 24.00 20 FACILITY ELECTRONIC OPERATION AND MAINTENANCE SUPPORT INFORMATION (eOMSI) for additional requirements.

PART 2 PRODUCTS

2.1 WARRANTY

All equipment specified shall include the standard manufacturer's warranty unless an extended warranty period is specifically indicated.

2.2 PERFORMANCE CRITERIA FOR PRODUCTS

2.2.1 Narrow Aisle Material Handling System

2.2.1.1 Narrow Aisle Turret Truck

Each electric narrow aisle turret truck shall have a 3,500 pound rated capacity at a 24-inch load center and at least 3,000 pound capacity at maximum lift height. The truck shall have enough lift height to reach all storage levels of the designed narrow aisle storage racking system.

The truck must have extended load-handling capability 48” deep X 108” wide. This extended capability is intended to support loads of this size stored on the racking endcaps and in other specially–constructed shelves, and is not reflective of the average 48” x 40” stacker loads. Truck must have in-aisle detection and end-of-aisle slow down capability. The carriage shall be equipped with 42" forks and must be able to pivot 180 degrees to pick up and deposit loads from either side or the front. The turret truck must be UL or FM certified with an NFPA rating of EE. The certification plate shall contain the lift truck's serial number, the accredited laboratory's identification, and the type designation EE. Service braking may be accomplished by plugging or other methods that allow for a smooth controlled stop. The truck shall be turret/stock picker type with sit and stand operation available. The cab shall be equipped with OSHA-approved front guard rail with side gates such that a fall protection harness need not be worn during operation. The operator cab shall have a full suspension seat with vertical adjustments for operation either sitting or standing and a cushioned floor mat.

Steering shall be multi-turn power steer with a three-wheel configuration to optimize maneuverability and stability.

All motors and controllers shall be easily accessible. Included shall be a body harness with retractable tether, mirrors, clipboard bracket, two copies of manuals (service and parts), operations training, transportation and set up. The turret truck shall be painted yellow (FED-STD-595, No. 13538 or equivalent). The truck shall feature an amber strobe light, an audible back-up alarm, an hour meter, work lights, a horn, battery discharge indicator, blue LED forklift pedestrian safety spotlight (front and Rear), and safety markings as detailed in Attachment (XX). The truck battery shall be maintenance-free, sealed, gel-type, equipped with a Battery ID Module (BID), with sufficient amp-hour capacity to provide a minimum of 8 hours runtime before charging. The truck and operational dimensions and weight lift capabilities shall be within the dimensional parameters indicated on the plans.

2.2.1.2 Narrow Aisle Turret Truck Battery Charging Station

A vehicle impact safety barrier shall be installed around the battery charger to ensure it is protected from physical damage. The Charger shall be a compatible smart charger with matching amp-hour charging capacity and BID capability, wired to receive 480V, 3 phase, 60 hertz.

2.2.1.3 Narrow Aisle Lift Truck In-Floor Wire Guide System

The electric lift truck traveling in rack aisles shall be guided by a wire installed within the concrete floor. Each wire guide shall be 16-gauge copper laid within a slot in the concrete floor sealed with two-part epoxy installed as part of this system. The wire guide system shall include all wire, end stops, line drives and other accessories required for a complete system. Coordinate with the storage rack system. The system shall utilize a 6.25 kHz signal.

2.2.1.4 Narrow Aisle Storage Rack System

a. General Calculations: Submit storage rack system calculations stamped by a registered design professional in the project jurisdiction to verify sizes, spacing of members, connections, and bracing. The storage rack system includes all components necessary to support the rack loads including the base plates, anchorage to the structural concrete slab, and seismic bracing of the rack system.

1) The minimum base plate size shall be based upon the maximum vertical leg (column) load used to account for the punching shear in the slab design.

2) Submit drawings showing sizes, thicknesses, layout, material designation, methods of installation, and accessories.

b. Storage rack framing system shall provide horizontal and vertical spacing as indicated on the plans and elevations. Load support wire decks shall be installed and mechanically fastened to storage rack horizontal frame members. Load carrying capacity of each deck and member shall not be less than that indicated on the elevations.

Vertical support systems shall be provided with support centerline dimension of approximately 9-feet 4-inches in length. Each horizontal member shall rest in vertical support notches or slots so that all applied weight is transferred from the horizontal member to the support vertically. Pre-drilled holes shall contain mechanical fasteners to eliminate horizontal member shift or lift during loading and unloading. No rack weight shall bear on these fasteners. Vertical supports shall be all welded construction with welded base plates and shall have a gray powder coated factory finish.

2.2.2 Narrow Aisle Reach Truck

Electric narrow aisle reach truck shall have a rated load capacity of 4500 pounds at a 24-inch load center and at least 3,500 pound load capacity at full lifting height. The Lifting height must be at least 300 inches and a maximum collapsed height must be 140 inches or less.

Carriage must be equipped with hydraulic side-shift, fork positioners, and fork tilt with tilt position indicator. Fork length shall be 45”.

Inside straddle width shall be at least 48 inches. The operator compartment shall come with an adjustable suspended seat and configured to allow stand up or sit down operation. The truck must be UL or FM certified with an NFPA rating of EE. The certification plate shall contain the lift truck's serial number, the accredited laboratory's identification, and the type designation EE. Service braking may be accomplished by plugging or other methods that allow for a smooth controlled stop. Truck shall be equipped with camera/s and a colored monitor capable of viewing all corners of the load.

All motors and controllers shall be easily accessed for maintenance.

Included shall be mirrors, clipboard bracket, two copies of manuals (service and parts), operations training, transportation and set up.

The truck shall be painted yellow (FED-STD-595, No. 13538 or equivalent). The truck shall feature an amber strobe light, an audible back-up alarm, an hour meter, work lights, a horn, battery discharge indicator, blue LED forklift pedestrian safety spotlight (front and Rear), and safety markings as detailed in Attachment (XX). The truck battery shall be maintenance-free, sealed, gel-type, equipped with a Battery ID Module (BID), with sufficient amp-hour capacity to provide a minimum of 8 hours runtime before charging.

2.2.3 Lift Truck Charging Station

A vehicle impact safety barrier shall be installed around the battery charger to ensure it is protected from physical damage. The Charger shall be a compatible smart charger with matching amp-hour charging capacity and BID capability, wired to receive 480V, 3 phase, 60 hertz.

PART 3 EXECUTION

3.1 INSTALLATION

Install shop handling equipment at locations indicated. Conform to manufacturers installation provisions. Bolt equipment to the floor where required and place equipment in the finished space where indicated.

3.2 POSTED OPERATING INSTRUCTIONS

Provide in accordance with the manufacturer's instructions.

3.3 FIELD QUALITY CONTROL

3.3.1 Inspection

Examine each unit for visual defects, operation and conformance to specifications.

3.3.2 Tests

Test each unit to ensure that the equipment is operational and conforms to specification requirements.

-- End of Section --

NAVSUP WSS PD-41206

14 January 2013

SUPERSEDING

NAVSUP WSS PD-41206

29 February 2012

MHE SHOREBASE FORKLIFTS - REQUIRED SAFETY MARKINGS

1. Identification Plate / Label – A manufacturer’s identification plate shall be furnished and installed, by the manufacturer, on the MHE in accordance with ANSI/ITSDF B56.1. In addition to this requirement, the identification plate shall contain, at a minimum, the manufacturer’s make, model, unit serial number, nomenclature, contract number, lifting capacity, lift height, fork and mast type, USN registration number, shipping weight, cube dimension, name or stamp of government inspector, date shipped, technical manual stock number, warranty expiration date and manufacturer’s name and address.

2. Weight Test Label / Stencil – Label or stencil “STRUCTURALLY TESTED by

(MANUFACTURER or FACILITY) on (DATE)” on each side of MHE.

3. Accredited Laboratory Certification – An Underwriters’ Laboratory (UL) or Factory Mutual (FM) identification plate or label with type designation (e.g., DS, D, EE, E) shall be affixed to the MHE. In addition a 3-inch block alphabetical type designator (e.g., DS, D, EE, E) shall be visually centered and applied on each side and rear of the MHE. The type designators shall consist of black borders and lettering on a yellow background.

4. Operator Controls - All operator controls shall be properly and clearly marked.

5. Battery Identification Plate - For electrically powered MHE a battery plate is required to identify the weight, specific gravity, manufacturer, etc. The plate shall be installed in an area visible from the outside of the equipment.

6. Warning Decals and Labels – Warning decals and labels shall be affixed onto the MHE to identify potential pinch points or other operator hazards.

7. Safe Working Load and Vehicle Weight – The safe working load (SWL) and vehicle weight (VW) shall be clearly printed, in 2-inch minimum high black block painted or vinyl letters, on both sides of the MHE body. Also, the safe working load (SWL) shall be clearly printed, in 1-inch minimum high black block painted or vinyl letters, on each side of the mast. In addition, these markings must be clearly in view of the operator, normally on the mast crossbar, using the largest lettering size that will fit on the area. (Example: SWL 6,000 LBS. VW 10,000LBS.)

8. USN Numbers – The seven digit USN number (example: 13-54321), assigned by NAVSUP WSS, shall be marked on each side and rear of the MHE with 3-inch high black block painted or vinyl letters.

9. Lift and Tie-down Provisions – All lift and tie-down points shall be identified with ¾-inch minimum high black block painted or vinyl letters.

NAVSUP WSS PD-41206

14 January 2013

SUPERSEDING

NAVSUP WSS PD-41206

29 February 2012

10. Tire Pressure - The tire pressure (pneumatic tires only) for each tire shall be marked with ¾-inch minimum high painted or vinyl letters on each side of the MHE near the applicable tire. (Example;

TP 80 PSI).

11. Fuel Cap – All fuel caps shall be color coded to properly identify the required fuel type. (Example:

DIESEL = Green or GAS = Red).