B178 stacker RFI Set 3.pdf

PDF 178 KB Posted

Attached to
Building 178 High Density Storage Stacker Federal contract opportunity
Solicitation number
N40085-20-B-2540
Issued by
Department of the Navy Naval Facilities Engineering Command

About this file

This request for information document pertains to a federal contract opportunity for the design, procurement, and installation of high density storage systems and equipment for Building 178 at a Naval Facilities Engineering Command site. The contractor questions whether existing slabs have been analyzed to support new forklifts weighing 20,000 to 30,000 pounds and if 3-inch inlay slabs will adequately support this weight at sawcut control joints. The government response indicates no specific analysis has been completed but the floors are intended for and routinely subjected to heavy industrial traffic. The contractor's designer must confirm floor strength is sufficient. The related federal contract opportunity involves solicitation N40085-20-B-2540 for high density storage stacker systems, including narrow aisle forklifts, chargers, guide wire systems, rack systems, fire suppression, alarm modifications, and electrical and concrete work. The agency is the Department of the Navy Naval Facilities Engineering Command.

View the file

Other files for this federal contract opportunity

Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION DATE

Jun 17, 2020

ACTIVITY ID

B178 HIGH DENSITY STORAGE STACKER, PNSY

CONTRACT TITLECONTRACT NO

N40085-20-B-2540

RFI NO

MISCELLANEOUS

RFI SUBJECT DWG NO

DWG DETAIL

DWG SHEET NO

VARIOUS

SPEC SECTION

SPEC PARAGRAPH

SPEC PAGE NO

RFI PRIORITY?

POTENTIAL TIME/COST?

SCHEDULE REFERENCED?

CRITICAL PATH?

HIGH NORMAL

YES NO

YES NO

YES NO

4296/2C (9/98) SHEET of

CONTRACTOR QUESTION AND PROPOSED SOLUTION

RFI QUESTION/ISSUE:

1. Have existing slabs been analyzed by a structural engineer to determine adequate support for a new fork truck 20,000-30,000 pounds?

2. Is 3 ½” inlay slab adequate to support this weight especially at sawcut control joints? Our subcontractor has seen control joints fail which affect the functionality of the guide wire system.

3. Can the bid due date be extended ?

CONTRACTOR PROPOSED SOLUTION:

Jun 17, 2020

DATECONTRACTOR/PROJECT MANAGER

NOTE: If the determination of this RFI is "Answered - No Cost" then this reply is given with the expressed understanding that it does not constitute a basis for any change in the amount or time of subject contract. Information provided in this response does not authorize work not currently included in the contract. If determination of this RFI is "Answered - Pending PCO" then this response may require a change to the contract.

ANSWERS AND COMMENTS

RFI REASON CODE

RFI ACTION

COMMENTS FOR DETAILED REVIEWER:

DETAILED REVIEWER 1 RECOMMENDED RFI SOLUTION:

DETAILED REVIEWER 1 NAME/SIGNATURE TITLE RESPONSE DATE

DETAILED REVIEWER 2 RECOMMENDED RFI SOLUTION:

DETAILED REVIEWER 2 NAME/SIGNATURE TITLE RESPONSE DATE

RFI RESPONSE:

DATEGOVERNMENT CONSTRUCTION MANAGER

jon.reaves Typewritten Text No specific analysis has been completed by the Government for this project to verify floor strength, however these floors are intended for and are routinely subjected to industrial traffic which applies heavy loads as shown on the included drawing 178-13-362. The contractor's designer is to confirm (as needed) that the building and its floors have the required strength to support the contractor's specific design loads.

jon.reaves Typewritten Text Structural Engineer jon.reaves Typewritten Text 6/22/20