This is a fire alarm system documentation file for Building C, detailing the complete alarm node configuration and monitoring system as of November 18, 2025. The document provides a comprehensive inventory of all detection devices, control modules, and monitoring equipment integrated into Node 3 of the facility's fire safety infrastructure.
The file catalogs 359 individual alarm devices organized across six loops (L01 through L06), including smoke detectors (both ionization and photoelectric types), heat detectors, water flow monitors, sprinkler tamper switches, elevator controls, air handling unit (PAHU) monitoring systems, roll-up door relays, strobe light controls, and emergency communication systems. Devices are distributed throughout Building C across multiple levels and locations, including exhibit halls (C-1 through C-4), restrooms, mechanical rooms, elevator shafts, stairwells, storage areas, and rooftop equipment. The system monitors critical infrastructure including 29 penthouse units, 41 separate PAHU units with damper controls, 14 elevator and stairwell systems, and multiple Ansul fire suppression systems in food service areas. All detectors display "NORMAL" or operational status, with modules indicating various states including shutdown mode, purge mode, damper activation, and communications faults. The documentation serves as the master reference record for the facility's integrated fire detection and alarm management system.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NODE 3
11/18/2025 1
Alarm No. 101: Node 3: L01D01: Loop: 1 Device: 1
Display: NORMAL SMOKE (ION) C-4 MENS RESTROOM W Building: C Location: In housekeeping storage closet inside C-4 mens restroom west wall Description: A Smoke Detector has gone off in this area.
Alarm No. 102: Node 3: L01D02: Loop: 1 Device: 2
Display: NORMAL SMOKE(PHOTO) C-4 WOMENS RESTRM W
Location: Housekeeping storage closet inside C-4 womens restroom west wall Description: A Smoke Detector has gone off in this area.
Alarm No. 103: Node 3: L01D03: Loop: 1 Device: 3
Display: NORMAL SMOKE (ION) C-4 SHOW OFFICE WEST
Location: Inside the show managers office for C-4 hall on the west wall enter from the point lobby Description: A Smoke Detector has gone off in this area.
Alarm No. 104: Node 3: L01D04: Loop: 1 Device: 4
Display: NORMAL SMOKE (ION) C-3 W ENGINEERING
Location: Engineering shop on west wall of C-3 hall near the C-3/C-4 point lobby Description: A Smoke Detector has gone off in this area.
Alarm No. 105: Node 3: L01D05: Loop: 1 Device: 5
Display: NORMAL SMOKE(PHOTO) BC-E-1 SUPPLY DUCT
Location: This detector is located inside the air handler in the ceiling above Starbucks in the C-Bldg main entrance Description: A Smoke Detector has gone off in this area.
Alarm No. 106: Node 3: L01D06: Loop: 1 Device: 6
Display: NORMAL SMOKE (ION) C-3 W ENGINEERING
Location: Engineering shop on the west wall of C-3 hall near the C-3/C4 point lobby Description: A Smoke Detector has gone off in this area.
11/18/2025 2
Alarm No. 107: Node 3: L01D07: Loop: 1 Device: 7
Display: NORMAL HEAT(ANALOG) ELEV 14 PIT HEAT
Location: This detector is located in the pit of elevator 14 on level 1 C-Bldg Description: A Heat Detector has gone off in this area.
Alarm No. 109: Node 3: L01D09: Loop: 1 Device: 9
Display: NORMAL SMOKE (ION) ELEV 14 LVL 1 LOBBY
Location: This detector is located outside the elevator 14 on level 1 C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 111: Node 3: L01D11: Loop: 1 Device: 11
Display: NORMAL SMOKE (ION) ELEV 14 MACHINE ROOM
Location: This detector is located in the elevator 14 mecanical room on level 1 C-Bldg next to the elevator Description: A Smoke Detector has gone off in this area.
Alarm No. 114: Node 3: L01D14: Loop: 1 Device: 14
Display: NORMAL SMOKE (ION) C-3 WOMENS RESTRM W
Location: Housekeeping storage closet inside C-3 womens restroom west wall Description: A Smoke Detector has gone off in this area.
Alarm No. 115: Node 3: L01D15: Loop: 1 Device: 15
Display: NORMAL SMOKE (ION) C-3 MENS RESTROOM W
Location: Housekeeping storage closet inside C-3 mens restroom west wall Description: A Smoke Detector has gone off in this area.
Alarm No. 116: Node 3: L01D16: Loop: 1 Device: 16
Display: NORMAL SMOKE (ION) WC WOMENS RESTROOM N
Location: Housekeeping storage closet inside womens restroom in C-Bldg main entrance
11/18/2025 3
Description: A Smoke Detector has gone off in this area.
Alarm No. 117: Node 3: L01D17: Loop: 1 Device: 17
Display: NORMAL SMOKE (ION) WC MENS RESTROOM N
Location: Housekeeping storage closet inside mens restroom in C-Bldg main entrance Description: A Smoke Detector has gone off in this area.
Alarm No. 118: Node 3: L01D18: Loop: 1 Device: 18
Display: NORMAL SMOKE (ION) C-2 MENS RESTROOM W
Location: In housekeeping storage closet inside mens restroom on west wall of C-2 hall Description: A Smoke Detector has gone off in this area.
Alarm No. 119: Node 3: L01D19: Loop: 1 Device: 19
Display: NORMAL SMOKE (ION) C-2 WOMENS RESTRM W
Location: In housekeeping storage closet inside womens restroom on west wall of C-2 hall Description: A Smoke Detector has gone off in this area.
Alarm No. 120: Node 3: L01D20: Loop: 1 Device: 20
Display: NORMAL SMOKE (ION) ELEV 15 MACHINE RM
Location: This detector is located in the elevator 15 mecanical room on level 1 C-Bldg next to the elevator Description: A Smoke Detector has gone off in this area.
Alarm No. 122: Node 3: L01D22: Loop: 1 Device: 22
Display: NORMAL SMOKE (ION) ELEV 15 LVL 1 LOBBY
Location: This detector is located outside the elevator 15 on level 1 C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 124: Node 3: L01D24: Loop: 1 Device: 24
Display: NORMAL HEAT(ANALOG) ELEV 15 PIT HEAT
11/18/2025 4
Location: This detector is located in the pit of elevator 15 on level 1 C-Bldg Description: A Heat Detector has gone off in this area.
Alarm No. 125: Node 3: L01D25: Loop: 1 Device: 25
Display: NORMAL SMOKE (ION) WC NEAR ELEV 15
Location: Inside setup storage room west concourse C Bldg. Main entrance next to elevator 15.
Description: A Smoke Detector has gone off in this area.
Alarm No. 126: Node 3: L01D26: Loop: 1 Device: 26
Display: NORMAL SMOKE (ION) WC NEAR ELEV 15
Location: Inside setup storage room west concourse C Bldg. Main entrance next to elevator 15.
Description: A Smoke Detector has gone off in this area.
Alarm No. 127: Node 3: L01D27: Loop: 1 Device: 27
Display: NORMAL SMOKE (ION) C-4 EXHIBIT HALL W
Location: Engineering panel storage room with the blow open door controllers inside C-4 hall west wall Description: A Smoke Detector has gone off in this area.
Alarm No. 128: Node 3: L01D28: Loop: 1 Device: 28
Display: NORMAL SMOKE (ION) C-4 EXHIBIT HALL W
Location: Housekeeping storage room on west wall C-4 hall
11/18/2025 5
Alarm No. 201: Node 3: L02D01: Loop: 2 Device: 1
Display: NORMAL SMOKE (ION) POWERHOUSE 32
Location: 1st penthouse on C-Bldg roof west side Description: A Smoke Detector has gone off in this area.
Alarm No. 203: Node 3: L02D03: Loop: 2 Device: 3
Display: NORMAL SMOKE(PHOTO) PAHU 4-4 SUPPLY
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 204: Node 3: L02D04: Loop: 2 Device: 4
Display: NORMAL SMOKE(PHOTO) PAHU 4-4 RETURN
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 205: Node 3: L02D05: Loop: 2 Device: 5
Display: NORMAL SMOKE(PHOTO) PAHU 4-2 SUPPLY
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 206: Node 3: L02D06: Loop: 2 Device: 6
Display: NORMAL SMOKE(PHOTO) PAHU 4-2 RETURN
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 207: Node 3: L02D07: Loop: 2 Device: 7
Display: NORMAL SMOKE(PHOTO) PAHU 4-3 SUPPLY
Location: This detector is located inside the air handler on C1 hall roof
11/18/2025 6
Alarm No. 208: Node 3: L02D08: Loop: 2 Device: 8
Display: NORMAL SMOKE(PHOTO) PAHU 4-3 RETURN
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 209: Node 3: L02D09: Loop: 2 Device: 9
Display: NORMAL SMOKE(PHOTO) PAHU 4-1 SUPPLY
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 210: Node 3: L02D10: Loop: 2 Device: 10
Display: NORMAL SMOKE(PHOTO) PAHU 4-1 RETURN
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 211: Node 3: L02D11: Loop: 2 Device: 11
Display: NORMAL SMOKE (ION) POWERHOUSE 31
Location: 1st penthouse on C-Bldg roof east side Description: A Smoke Detector has gone off in this area.
Alarm No. 213: Node 3: L02D13: Loop: 2 Device: 13
Display: NORMAL SMOKE(PHOTO) PAHU 4-28 SUPPLY
Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 214: Node 3: L02D14: Loop: 2 Device: 14
Display: NORMAL SMOKE(PHOTO) PAHU 4-28 RETURN
Location: This detector is located inside the air handler on C1 hall roof
11/18/2025 7
Description: A Smoke Detector has gone off in this area.
Alarm No. 215: Node 3: L02D15: Loop: 2 Device: 15
Display: NORMAL SMOKE(PHOTO) BC-P-1 SUPPLY
Location: This detector is located in the air handler in the ceiling of the electrical mechanical room behind the american grill in Foodworld in C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 216: Node 3: L02D16: Loop: 2 Device: 16
Display: NORMAL SMOKE (ION) LVL 2 FOODWORLD NW
Location: North west end in electrical room past American grill Description: A Smoke Detector has gone off in this area.
Alarm No. 217: Node 3: L02D17: Loop: 2 Device: 17
Display: NORMAL SMOKE (ION) LVL 2 SW FOOD COURT
Location: In ceiling as you walk in front door of Foodworld
11/18/2025 8
11/18/2025 9
Alarm No. 301: Node 3: L03D01: Loop: 3 Device: 1
Display: NORMAL SMOKE (ION) FACP 3 ROOM LEVEL 3
Location: In room back hallway where Node 3 is located Description: A Smoke Detector has gone off in this area.
Alarm No. 302: Node 3: L03D02: Loop: 3 Device: 2
Display: NORMAL SMOKE (ION) LEVEL 3 NORTHWEST
Location: Set up store room level 3 C-Bldg northwest end of back hallway Description: A Smoke Detector has gone off in this area.
Alarm No. 303: Node 3: L03D03: Loop: 3 Device: 3
Display: NORMAL SMOKE (ION) LEVEL 3 NORTHWEST
Location: Set up store room level 3 C-Bldg northwest end of back hallway Description: A Smoke Detector has gone off in this area.
Alarm No. 304: Node 3: L03D04: Loop: 3 Device: 4
Display: NORMAL SMOKE (ION) ELEV 14 LVL 3 LOBBY
Location: This detector is located outside the elevator 14 on level 3 C-Bldg nothrthend Description: A Smoke Detector has gone off in this area.
Alarm No. 305: Node 3: L03D05: Loop: 3 Device: 5
Display: NORMAL SMOKE (ION) C308 CHAIR STORAGE
Location: Chair storage room in room C308 level 3 C-Bldg northend Description: A Smoke Detector has gone off in this area.
Alarm No. 306: Node 3: L03D06: Loop: 3 Device: 6
Display: NORMAL SMOKE (ION) C308 PARTITION WALL
Location: Inside wall storage room in C308 level 3 C-Bldg
11/18/2025 10
Alarm No. 307: Node 3: L03D07: Loop: 3 Device: 7
Display: NORMAL SMOKE (ION) C306 PARTITION WALL
Location: Inside wall storage in C307 level 3 C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 308: Node 3: L03D08: Loop: 3 Device: 8
Display: NORMAL SMOKE (ION) C306 CHAIR STORAGE
Location: Chair storage room in room C306 level 3 C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 309: Node 3: L03D09: Loop: 3 Device: 9
Display: NORMAL SMOKE (ION) LVL 3 WC SRVICE HALL
Location: Northend housekeeping storage room level 3 back hallway C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 310: Node 3: L03D10: Loop: 3 Device: 10
Display: NORMAL SMOKE (ION) WC LVL 3 MENS RESTRM
Location: Housekeeping storage room inside restroom next to room C306 Description: A Smoke Detector has gone off in this area.
Alarm No. 311: Node 3: L03D11: Loop: 3 Device: 11
Display: NORMAL SMOKE (ION) C305 CHAIR STORAGE
Location: Chair storage room inside room C305 level 3 Bldg C Description: A Smoke Detector has gone off in this area.
Alarm No. 312: Node 3: L03D12: Loop: 3 Device: 12
Display: NORMAL SMOKE (ION) C305 PARTITION WALL
Location: Air wall storage room inside room C304 level 3 Bldg C
11/18/2025 11
Description: A Smoke Detector has gone off in this area.
Alarm No. 313: Node 3: L03D13: Loop: 3 Device: 13
Display: NORMAL SMOKE (ION) C303 PARTITION WALL
Location: Air wall storage room inside room C304 level 3 Bldg C Description: A Smoke Detector has gone off in this area.
Alarm No. 314: Node 3: L03D14: Loop: 3 Device: 14
Display: NORMAL SMOKE (ION) C303 CHAIR STORAGE
Location: Chair storage room inside room C303 level 3 Bldg C Description: A Smoke Detector has gone off in this area.
Alarm No. 315: Node 3: L03D15: Loop: 3 Device: 15
Display: NORMAL SMOKE (ION) WC LV3 WOMENS RESTRM
Location: Housekeeping storage room inside mens restroom next to room C305 level 3 C-bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 316: Node 3: L03D16: Loop: 3 Device: 16
Display: NORMAL SMOKE (ION) WC LV3 WOMENS RESTRM
Location: Housekeeping storage room inside womens restroom next to room C303 level 3 Bldg C Description: A Smoke Detector has gone off in this area.
Alarm No. 317: Node 3: L03D17: Loop: 3 Device: 17
Display: NORMAL SMOKE (ION) WC LVL 3 MENS RESTRM
Location: Housekeeping storage room inside mens restroom next to room C303 level 3 Bldg C Description: A Smoke Detector has gone off in this area.
Alarm No. 318: Node 3: L03D18: Loop: 3 Device: 18
Display: NORMAL SMOKE (ION) ELEV 15 LVL 3 LOBBY
11/18/2025 12
Location: This detector is located outside the elevator 15 on level 3 C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 319: Node 3: L03D19: Loop: 3 Device: 19
Display: NORMAL SMOKE (ION) ELEV 15 TOP OF SHAFT
Location: This detector is located at the top of the shaft of elevator 15 C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 320: Node 3: L03D20: Loop: 3 Device: 20
Display: NORMAL SMOKE(PHOTO) PAHU 4-17 SUPPLY
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 321: Node 3: L03D21: Loop: 3 Device: 21
Display: NORMAL SMOKE(PHOTO) PAHU 4-17 RETURN
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 322: Node 3: L03D22: Loop: 3 Device: 22
Display: NORMAL SMOKE(PHOTO) PAHU 4-14 SUPPLY
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 323: Node 3: L03D23: Loop: 3 Device: 23
Display: NORMAL SMOKE(PHOTO) PAHU 4-14 RETURN
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 324: Node 3: L03D24: Loop: 3 Device: 24
Display: NORMAL SMOKE (ION) POWERHOUSE 26
11/18/2025 13
Building: C Location: 4th penthouse on west side of C-Bldg roof Description: A Smoke Detector has gone off in this area.
Alarm No. 325: Node 3: L03D25: Loop: 3 Device: 25
Display: NORMAL SMOKE(PHOTO) PAHU 4-16 SUPPLY
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 326: Node 3: L03D26: Loop: 3 Device: 26
Display: NORMAL SMOKE(PHOTO) PAHU 4-16 RETURN
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 327: Node 3: L03D27: Loop: 3 Device: 27
Display: NORMAL SMOKE(PHOTO) PAHU 4-15 SUPPLY
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 328: Node 3: L03D28: Loop: 3 Device: 28
Display: NORMAL SMOKE(PHOTO) PAHU 4-15 RETURN
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 329: Node 3: L03D29: Loop: 3 Device: 29
Display: NORMAL SMOKE (ION) POWERHOUSE 25
Location: 4th penthouse on east side C-Bldg roof Description: A Smoke Detector has gone off in this area.
Alarm No. 330: Node 3: L03D30: Loop: 3 Device: 30
11/18/2025 14
Display: NORMAL SMOKE(PHOTO) PAHU 4-13 SUPPLY Building: C Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 331: Node 3: L03D31: Loop: 3 Device: 31
Display: NORMAL SMOKE(PHOTO) PAHU 4-13 RETURN
Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 332: Node 3: L03D32: Loop: 3 Device: 32
Display: NORMAL SMOKE (ION) ELEV 14 TOP OF SHAFT
Location: This detector is located at the top of the shaft of elevator 14 C-Bldg northend Description: A Smoke Detector has gone off in this area.
Alarm No. 333: Node 3: L03D33: Loop: 3 Device: 33
Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE
Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 334: Node 3: L03D34: Loop: 3 Device: 34
Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 335: Node 3: L03D35: Loop: 3 Device: 35
Location: Southend of back hallway 3rd level tech services store room in C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 336: Node 3: L03D36: Loop: 3 Device: 36
11/18/2025 15
Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE V000 M 051 L03D36
Location: Southend of back hallway 3rd level setup store room in C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 337: Node 3: L03D37: Loop: 3 Device: 37
Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE V000 M 042 L03D37
Location: Southend of back hallway 3rd level setup store room in C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 338: Node 3: L03D38: Loop: 3 Device: 38
Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE V000 M 030 L03D38
Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 339: Node 3: L03D39: Loop: 3 Device: 39
Display: NORMAL SMOKE(PHOTO) PAHU 4-41 SUPPLY V000 M 037 L03D39
Location: This detector is located inside the air handler on the roof accessed by the roof hatch in the #16/17 elevator mecanical room on level 4 back hallway Description: A Smoke Detector has gone off in this area.
Alarm No. 340: Node 3: L03D40: Loop: 3 Device: 40
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D40
Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 341: Node 3: L03D41: Loop: 3 Device: 41
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D41
Location: Southend of back hallway 3rd level C-Bldg
11/18/2025 16
Alarm No. 342: Node 3: L03D42: Loop: 3 Device: 42
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D42
Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 343: Node 3: L03D43: Loop: 3 Device: 43
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D43
Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 344: Node 3: L03D44: Loop: 3 Device: 44
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D44
Location: Center section of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 345: Node 3: L03D45: Loop: 3 Device: 45
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 032 L03D45
Location: Center section of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 346: Node 3: L03D46: Loop: 3 Device: 46
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 048 L03D46
Location: Center section of the back hallway 3rd level C-Bldg behind room C303 Description: A Smoke Detector has gone off in this area.
Alarm No. 347: Node 3: L03D47: Loop: 3 Device: 47
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 045 L03D47
Location: Center section of the back hallway 3rd level C-Bldg behind room C304
11/18/2025 17
Alarm No. 348: Node 3: L03D48: Loop: 3 Device: 48
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 048 L03D48
Location: Center section of the back hallway 3rd level C-Bldg behind room C305 Description: A Smoke Detector has gone off in this area.
Alarm No. 349: Node 3: L03D49: Loop: 3 Device: 49
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 045 L03D49
Location: Center section of the back hallway 3rd level C-Bldg behind room C305 Description: A Smoke Detector has gone off in this area.
Alarm No. 350: Node 3: L03D50: Loop: 3 Device: 50
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 046 L03D50
Location: Center section of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 351: Node 3: L03D51: Loop: 3 Device: 51
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D51
Location: Center section of the back hallway 3rd level C-Bldg behind room C306 Description: A Smoke Detector has gone off in this area.
Alarm No. 352: Node 3: L03D52: Loop: 3 Device: 52
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 044 L03D52
Location: Center section of the back hallway 3rd level C-Bldg behind room C307 Description: A Smoke Detector has gone off in this area.
Alarm No. 353: Node 3: L03D53: Loop: 3 Device: 53
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 044 L03D53
Location: Center section of the back hallway 3rd level C-Bldg behind room C308
11/18/2025 18
Description: A Smoke Detector has gone off in this area.
Alarm No. 354: Node 3: L03D54: Loop: 3 Device: 54
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 036 L03D54
Location: Center section of the back hallway 3rd level C-Bldg behind room C308 Description: A Smoke Detector has gone off in this area.
Alarm No. 355: Node 3: L03D55: Loop: 3 Device: 55
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 051 L03D55
Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 356: Node 3: L03D56: Loop: 3 Device: 56
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D56
Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 357: Node 3: L03D57: Loop: 3 Device: 57
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D57
Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 358: Node 3: L03D58: Loop: 3 Device: 58
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D58
Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.
Alarm No. 359: Node 3: L03D59: Loop: 3 Device: 59
Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 036 L03D59
11/18/2025 19
Location: Northend of the back hallway 3rd level C-Bldg
11/18/2025 20
11/18/2025 21
Alarm No. 401: Node 3: L04D01: Loop: 4 Device: 1
Display: NORMAL SMOKE(PHOTO) PAHU 4-12 SUPPLY V000 M 038 L04D01
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 402: Node 3: L04D02: Loop: 4 Device: 2
Display: NORMAL SMOKE(PHOTO) PAHU 4-12 RETURN V000 M 042 L04D02
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 403: Node 3: L04D03: Loop: 4 Device: 3
Display: NORMAL SMOKE (ION) POWERHOUSE 28 V000 M 065 L04D03
Location: 3rd penthouse on C-Bldg roof westside Description: A Smoke Detector has gone off in this area.
Alarm No. 404: Node 3: L04D04: Loop: 4 Device: 4
Display: NORMAL SMOKE(PHOTO) PAHU 4-19 SUPPLY V000 M 038 L04D04
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 405: Node 3: L04D05: Loop: 4 Device: 5
Display: NORMAL SMOKE(PHOTO) PAHU 4-19 RETURN V000 M 043 L04D05
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 406: Node 3: L04D06: Loop: 4 Device: 6
Display: NORMAL SMOKE(PHOTO) PAHU 4-18 SUPPLY V000 M 034 L04D06
Location: This detector is located inside the air handler on C3 hall roof
11/18/2025 22
Alarm No. 407: Node 3: L04D07: Loop: 4 Device: 7
Display: NORMAL SMOKE(PHOTO) PAHU 4-10 SUPPLY V000 M 036 L04D07
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 408: Node 3: L04D08: Loop: 4 Device: 8
Display: NORMAL SMOKE(PHOTO) PAHU 4-10 RETURN V000 M 043 L04D08
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 409: Node 3: L04D09: Loop: 4 Device: 9
Display: NORMAL SMOKE(PHOTO) PAHU 4-9 SUPPLY V000 M 039 L04D09
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 410: Node 3: L04D10: Loop: 4 Device: 10
Display: NORMAL SMOKE(PHOTO) PAHU 4-9 RETURN V000 M 050 L04D10
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 411: Node 3: L04D11: Loop: 4 Device: 11
Display: NORMAL SMOKE (ION) POWERHOUSE 27 V000 M 060 L04D11
Location: 3rd penthouse on C-Bldg roof eastside Description: A Smoke Detector has gone off in this area.
Alarm No. 412: Node 3: L04D12: Loop: 4 Device: 12
Display: NORMAL SMOKE(PHOTO) PAHU 4-11 SUPPLY V000 M 037 L04D12
Location: This detector is located inside the air handler on C3 hall roof
11/18/2025 23
Description: A Smoke Detector has gone off in this area.
Alarm No. 413: Node 3: L04D13: Loop: 4 Device: 13
Display: NORMAL SMOKE(PHOTO) PAHU 4-11 RETURN V000 M 039 L04D13
Location: This detector is located inside the air handler on C3 hall roof
11/18/2025 24
11/18/2025 25
Alarm No. 501: Node 3: L05D01: Loop: 5 Device: 1
Display: NORMAL SMOKE(PHOTO) PAHU 4-22 SUPPLY V000 M 038 L05D01
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 502: Node 3: L05D02: Loop: 5 Device: 2
Display: NORMAL SMOKE(PHOTO) PAHU 4-22 RETURN V000 M 044 L05D02
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 503: Node 3: L05D03: Loop: 5 Device: 3
Display: NORMAL SMOKE(PHOTO) PAHU 4-21 SUPPLY V000 M 039 L05D03
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 504: Node 3: L05D04: Loop: 5 Device: 4
Display: NORMAL SMOKE(PHOTO) PAHU 4-20 SUPPLY V000 M 038 L05D04
Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 505: Node 3: L05D05: Loop: 5 Device: 5
Display: NORMAL SMOKE(PHOTO) PAHU 4-7 SUPPLY V000 M 037 L05D05
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 506: Node 3: L05D06: Loop: 5 Device: 6
Display: NORMAL SMOKE(PHOTO) PAHU 4-7 RETURN V000 M 043 L05D06
Location: This detector is located inside the air handler on C2 hall roof
11/18/2025 26
Alarm No. 507: Node 3: L05D07: Loop: 5 Device: 7
Display: NORMAL SMOKE (ION) POWERHOUSE 29 V000 M 063 L05D07
Location: 2nd penthouse on C-Bldg roof eastside Description: A Smoke Detector has gone off in this area.
Alarm No. 508: Node 3: L05D08: Loop: 5 Device: 8
Display: NORMAL SMOKE(PHOTO) PAHU 4-5 SUPPLY V000 M 039 L05D08
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 509: Node 3: L05D09: Loop: 5 Device: 9
Display: NORMAL SMOKE(PHOTO) PAHU 4-5 RETURN V000 M 055 L05D09
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 510: Node 3: L05D10: Loop: 5 Device: 10
Display: NORMAL SMOKE(PHOTO) PAHU 4-8 SUPPLY V000 M 038 L05D10
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 511: Node 3: L05D11: Loop: 5 Device: 11
Display: NORMAL SMOKE(PHOTO) PAHU 4-8 RETURN V000 M 042 L05D11
Location: This detector is located inside the air handler on C2 hall roof
11/18/2025 27
Alarm No. 601: Node 3: L06D01: Loop: 6 Device: 1
Display: NORMAL SMOKE(PHOTO) PAHU 4-23 SUPPLY V000 M 038 L06D01
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 602: Node 3: L06D02: Loop: 6 Device: 2
Display: NORMAL SMOKE(PHOTO) PAHU 4-23 RETURN V000 M 049 L06D02
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 603: Node 3: L06D03: Loop: 6 Device: 3
Display: NORMAL SMOKE(PHOTO) PAHU 4-24 SUPPLY V000 M 039 L06D03
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 604: Node 3: L06D04: Loop: 6 Device: 4
Display: NORMAL SMOKE(PHOTO) PAHU 4-25 SUPPLY V000 M 037 L06D04
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 605: Node 3: L06D05: Loop: 6 Device: 5
Display: NORMAL SMOKE (ION) POWERHOUSE 30 V000 M 066 L06D05
Location: 2nd penthouse on C-Bldg roof westside Description: A Smoke Detector has gone off in this area.
Alarm No. 606: Node 3: L06D06: Loop: 6 Device: 6
Display: NORMAL SMOKE(PHOTO) PAHU 4-26 SUPPLY V000 M 037 L06D06
11/18/2025 28
Alarm No. 607: Node 3: L06D07: Loop: 6 Device: 7
Display: NORMAL SMOKE(PHOTO) PAHU 4-26 RETURN V000 M 067 L06D07
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 613: Node 3: L06D13: Loop: 6 Device: 13
Display: NORMAL SMOKE(PHOTO) PAHU 4-6 SUPPLY V000 M 042 L06D13
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 614: Node 3: L06D14: Loop: 6 Device: 14
Display: NORMAL SMOKE(PHOTO) PAHU 4-6 RETURN V000 M 045 L06D14
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 615: Node 3: L06D15: Loop: 6 Device: 15
Display: NORMAL SMOKE(PHOTO) PAHU 4-29 SUPPLY V000 M 032 L06D15
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 616: Node 3: L06D16: Loop: 6 Device: 16
Display: NORMAL SMOKE(PHOTO) PAHU 4-29 RETURN V000 M 056 L06D16
Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.
Alarm No. 617: Node 3: L06D17: Loop: 6 Device: 17
Display: NORMAL SMOKE(PHOTO) PAHU 4-27 SUPPLY V000 M 038 L06D17
11/18/2025 29
11/18/2025 30
11/18/2025 31
Alarm No. 101: Node 3: L01M01: Loop: 1 Module: 1
Display: OFF SPRNKLR MNTR STAIR 41 STANDPIPE K L01M01
Location: Module is located in the stairwell north end level 3 Description: Tamper switch has been activated
Alarm No. 102: Node 3: L01M02: Loop: 1 Module: 2
Display: OFF CONTROL RPS 32 C-3 HALL STRB CF L01M02
Location: RPS located in the electrical store room on the west wall of C4 hall Description: Strobes have been activated
Alarm No. 103: Node 3: L01M03: Loop: 1 Module: 3
Display: OFF SPRNKLR MNTR SYSTEM 10 STAIR 41 K L01M03
Location: Module is located in the stairwell north end level 3 Description: Tamper switch has been activated
Alarm No. 104: Node 3: L01M04: Loop: 1 Module: 4
Display: NORMAL WATER FLOW SYSTEM 10 STAIR 41 L01M04
Location: Module is located in the stairwell north end level 3 Description: Water Flow has been activated
Alarm No. 105: Node 3: L01M05: Loop: 1 Module: 5
Display: OFF SPRNKLR MNTR C-4 FHV TAMPER K L01M05
Location: In ceiling C-4 hall near center of west wall about 30-40 feet off the wall lobby side Description: Tamper switch has been activated
Alarm No. 106: Node 3: L01M06: Loop: 1 Module: 6
Display: OFF SPRNKLR MNTR C-4 FHV TAMPER K L01M06
Location: In ceiling C-4 hall at the fire exit doors at C3/4 point lobby Description: Tamper switch has been activated
11/18/2025 32
Alarm No. 107: Node 3: L01M07: Loop: 1 Module: 7
Display: OFF FORM C RELAY C-4 O-H DOOR RELAY S CF L01M07
Location: Module located at the rollup door leading out the C3/4 point lobby side in C4 hall Description: Roll-Up Doors have been closed
Alarm No. 108: Node 3: L01M08: Loop: 1 Module: 8
Display: OFF FORM C RELAY C-3 O-H DOOR RELAY N CF L01M08
Location: Module located at the rollup door leading out the C3/4 point lobby side in C3 hall Description: Roll-Up Doors have been closed
Alarm No. 110: Node 3: L01M10: Loop: 1 Module: 10
Display: OFF SPRNKLR MNTR SYSTEM 11 STAIR 39 K L01M10
Location: Module is located in stairwell 39 which is right across from elevator 14 the last elevator heading north in the C-Bldg main entrance Description: Tamper switch has been activated
Alarm No. 111: Node 3: L01M11: Loop: 1 Module: 11
Display: NORMAL WATER FLOW SYSTEM 11 STAIR 39 L01M11
Location: Module is located in stairwell 39 which is right across from elevator 14 the last elevator heading north in the C-Bldg main entrance Description: Water Flow has been activated
Alarm No. 114: Node 3: L01M14: Loop: 1 Module: 14
Display: OFF SPRNKLR MNTR C-2 FHV TAMPER SW K L01M14
Location: In ceiling center of the southwest wall in C-2 hall Description: Tamper switch has been activated
Alarm No. 118: Node 3: L01M18: Loop: 1 Module: 18
Display: OFF CONTROL RPS 6 C-3 HALL STRBS CF L01M18
11/18/2025 33
Building: C Location: RPS located in the C3 engineering shop on the west wall of C3 hall Description: Strobes have been activated
Alarm No. 119: Node 3: L01M19: Loop: 1 Module: 19
Display: OFF CONTROL RPS 7 C-3 HALL STRBS CF L01M19
Location: RPS located in the C3 engineering shop on the west wall of C3 hall Description: Strobes have been activated
Alarm No. 120: Node 3: L01M20: Loop: 1 Module: 20
Display: OFF FORM C RELAY ELEV 14 PRIM RECALL CF L01M20
Location: Module is in the elevator macine room located next to the elevator on level 1 C-Bldg main entrance last elevator heading north Description: Elevator has been sent to the Primary Level
Alarm No. 121: Node 3: L01M21: Loop: 1 Module: 21
Display: OFF FORM C RELAY ELEV 14 ALT RECALL CF L01M21
Location: Module is in the elevator macine room located next to the elevator on level 1 C-Bldg main entrance last elevator heading north Description: Elevator has been sent to the Alternate Level
Alarm No. 122: Node 3: L01M22: Loop: 1 Module: 22
Display: OFF FORM C RELAY ELEV 14 WARNING LITE CF L01M22
Location: Module is in the elevator macine room located next to the elevator on level 1 C-Bldg main entrance last elevator heading north Description: Elevator has been shut down
Alarm No. 123: Node 3: L01M23: Loop: 1 Module: 23
Display: OFF SPRNKLR MNTR C-2 W FHV TAMPER K L01M23
Location: In ceiling center of the west wall in C-2 hall Description: Tamper switch has been activated
11/18/2025 34
Alarm No. 124: Node 3: L01M24: Loop: 1 Module: 24
Display: OFF SPRNKLR MNTR C-2 W FHV TAMPER K L01M24
Location: In ceiling center of the west wall in C-2 hall Description: Tamper switch has been activated
Alarm No. 125: Node 3: L01M25: Loop: 1 Module: 25
Display: OFF FORM C RELAY C-3 O-H DOOR RELAY S CF L01M25
Location: Module located at the rollup door leading out the C2/3 point lobby side in C3 hall Description: Roll-Up Doors have been closed
Alarm No. 126: Node 3: L01M26: Loop: 1 Module: 26
Display: OFF SPRNKLR MNTR STAIR 38 FHV TAMPER K L01M26
Location: Module located in the stairwell across from room C308 Description: Tamper switch has been activated
Alarm No. 127: Node 3: L01M27: Loop: 1 Module: 27
Display: OFF FORM C RELAY BC-E-1 SHUTDOWN RLY CF L01M27
Location: Module located in the air handler above the ceiling soffit at the Starbucks in C-Bldg main entrance far northend Description: Unit in Shutdown Mode
Alarm No. 128: Node 3: L01M28: Loop: 1 Module: 28
Display: OFF SPRNKLR MNTR STAIR 37 FHV TAMPER K L01M28
Location: Module located in the stairwell across from room C306 Description: Tamper switch has been activated
Alarm No. 129: Node 3: L01M29: Loop: 1 Module: 29
Display: OFF FORM C RELAY BC-E-2 SHUTDOWN RLY CF L01M29
11/18/2025 35
Location: Module located in the air handler above the ceiling soffit at the Starbucks in C-Bldg main entrance far northend Description: Elevator has been shut down
Alarm No. 130: Node 3: L01M30: Loop: 1 Module: 30
Display: OFF FORM C RELAY C-2 O-H DOOR RELAY N CF L01M30
Location: Module located at the rollup door leading out the C2/3 point lobby side in C2 hall Description: Roll-Up Doors have been closed
Alarm No. 131: Node 3: L01M31: Loop: 1 Module: 31
Display: NORMAL WATER FLOW SYSTEM 12 STAIR 34 L01M31
Location: Module is located in stairwell 34 locatedi C-Bldg main lobby just to the right as you walk out the C1/2 point lobby Description: Water Flow has been activated
Alarm No. 133: Node 3: L01M33: Loop: 1 Module: 33
Display: OFF SPRNKLR MNTR STAIR 35 TAMPER TOP K L01M33
Location: Module located in the stairwell across from room C303 Description: Tamper switch has been activated
Alarm No. 134: Node 3: L01M34: Loop: 1 Module: 34
Display: OFF SPRNKLR MNTR STAIR 36 TAMPER TOP K L01M34
Location: Module located in the stairwell across from room C305 Description: Tamper switch has been activated
Alarm No. 135: Node 3: L01M35: Loop: 1 Module: 35
Display: OFF SPRNKLR MNTR STAIR 35 FHV TAMPER K L01M35
Location: Module located in the stairwell across from room C303 Description: Tamper switch has been activated
Alarm No. 136: Node 3: L01M36: Loop: 1 Module: 36
11/18/2025 36
Display: OFF SPRNKLR MNTR STAIR 36 FHV TAMPER K L01M36
Location: Module located in the stairwell across from room C305 Description: Tamper switch has been activated
Alarm No. 137: Node 3: L01M37: Loop: 1 Module: 37
Display: OFF SPRNKLR MNTR STAIR 37 TAMPER TOP K L01M37
Location: Module located in the stairwell across from room C306 Description: Tamper switch has been activated
Alarm No. 138: Node 3: L01M38: Loop: 1 Module: 38
Display: OFF SPRNKLR MNTR STAIR 38 TAMPER TOP K L01M38
Location: Module located in the stairwell across from room C308 Description: Tamper switch has been activated
Alarm No. 139: Node 3: L01M39: Loop: 1 Module: 39
Display: OFF SPRNKLR MNTR ELEV 14 PIT TAMPER K L01M39
Location: Valve located in the pit of elevator 14 C-Bldg main entrance last elevator heading north Description: Tamper switch has been activated
Alarm No. 140: Node 3: L01M40: Loop: 1 Module: 40
Display: OFF SPRNKLR MNTR ELEV 15 PIT TAMPER K L01M40
Location: Valve located in the pit of elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Tamper switch has been activated
Alarm No. 141: Node 3: L01M41: Loop: 1 Module: 41
Display: OFF FORM C RELAY ELEV 15 PRIM RECALL CF L01M41
Location: Module located in the machine room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Elevator has been sent to the Primary Level
11/18/2025 37
Alarm No. 142: Node 3: L01M42: Loop: 1 Module: 42
Display: OFF FORM C RELAY ELEV 15 ALT RECALL CF L01M42
Location: Module located in the machine room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Elevator has been sent to the Alternate Level
Alarm No. 143: Node 3: L01M43: Loop: 1 Module: 43
Display: OFF FORM C RELAY ELEV 15 WARNING LITE CF L01M43
Location: Module located in the machine room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Elevator has been shut down
Alarm No. 144: Node 3: L01M44: Loop: 1 Module: 44
Display: OFF CONTROL RPS 4 WC STROBES CF L01M44
Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated
Alarm No. 145: Node 3: L01M45: Loop: 1 Module: 45
Display: OFF CONTROL RPS 5 WC STROBES CF L01M45
Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated
Alarm No. 146: Node 3: L01M46: Loop: 1 Module: 46
Display: OFF SPRNKLR MNTR SYSTEM 12 STAIR 34 K L01M46
Location: Module is located in stairwell 34 locatedi C-Bldg main lobby just to the right as you walk out the C1/2 point lobby Description: Tamper switch has been activated
Alarm No. 147: Node 3: L01M47: Loop: 1 Module: 47
11/18/2025 38
Display: OFF FORM C RELAY C-2 O-H DOOR RELAY S CF L01M47
Location: Module located at the rollup door leading out the C1/2 point lobby side in C2 hall Description: Roll-Up Doors have been closed
Alarm No. 148: Node 3: L01M48: Loop: 1 Module: 48
Display: OFF FORM C RELAY C-1 O-H DOOR RELAY N CF L01M48
Location: Module located at the rollup door leading out the C1/2 point lobby side in C1 hall Description: Roll-Up Doors have been closed
Alarm No. 149: Node 3: L01M49: Loop: 1 Module: 49
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M49
Location: Module located in the electrical store room on the west wall of C4 hall Description: Blow Open Doors have been opened
Alarm No. 150: Node 3: L01M50: Loop: 1 Module: 50
Display: OFF NON ALM MON C-3 INTERFACE NODE 2 K L01M50
Location: Module located at the C3/4 point lobby side in C3 hall ceiling at overhead door Description: Communications fault
Alarm No. 151: Node 3: L01M51: Loop: 1 Module: 51
Display: OFF NON ALM MON C-4 INTERFACE NODE 2 K L01M51
Location: Module located at the C3/4 point lobby side in C4 hall ceiling at overhead door Description: Communications fault
Alarm No. 152: Node 3: L01M52: Loop: 1 Module: 52
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M52
Location: Module located in the electrical store room on the west wall of C4 hall Description: Blow Open Doors have been opened
11/18/2025 39
Alarm No. 153: Node 3: L01M53: Loop: 1 Module: 53
Display: OFF CONTROL RPS 4 C-2 HALL STRBS CF L01M53
Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated
Alarm No. 154: Node 3: L01M54: Loop: 1 Module: 54
Display: OFF CONTROL RPS 5 C-2 HALL STRBS CF L01M54
Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated
Alarm No. 155: Node 3: L01M55: Loop: 1 Module: 55
Display: OFF CONTROL RPS 6 WC STROBES CF L01M55
Location: RPS located in the C3 engineering shop on the west wall of C3 hall Description: Strobes have been activated
Alarm No. 156: Node 3: L01M56: Loop: 1 Module: 56
Display: OFF CONTROL RPS 8 C-4 HALL STRBS CF L01M56
Location: RPS located in the electrical store room on the west wall of C4 hall Description: Strobes have been activated
Alarm No. 157: Node 3: L01M57: Loop: 1 Module: 57
Display: OFF CONTROL RPS 32 WC STROBES CF L01M57
Location: RPS located in the electrical store room on the west wall of C4 hall Description: Strobes have been activated
Alarm No. 158: Node 3: L01M58: Loop: 1 Module: 58
Display: OFF NON ALM MON C-2 INTERFACE NODE 2 K L01M58
Location: Module located at the C1/2 point lobby side in C2 hall ceiling at overhead door
11/18/2025 40
Description: Communications fault
Alarm No. 159: Node 3: L01M59: Loop: 1 Module: 59
Display: OFF NON ALM MON C-1 INTERFACE NODE 2 K L01M59
Location: Module located at the C1/2 point lobby side in C1 hall ceiling at overhead door Description: Communications fault
Alarm No. 160: Node 3: L01M60: Loop: 1 Module: 60
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M60
Location: Module is located behind the information desk in the C-Bldg main entrance south of the C3/4 point Description: Blow Open Doors have been opened
Alarm No. 161: Node 3: L01M61: Loop: 1 Module: 61
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M61
Location: Module is located behind the information desk in the C-Bldg main entrance south of the C3/4 point Description: Blow Open Doors have been opened
Alarm No. 162: Node 3: L01M62: Loop: 1 Module: 62
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M62
Location: Module is located behind the information desk in the C-Bldg main entrance south of the C3/4 point Description: Blow Open Doors have been opened
Alarm No. 163: Node 3: L01M63: Loop: 1 Module: 63
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M63
Location: Module located on the left wall heading north just before Starbucks in the C-Bldg main entrance Description: Blow Open Doors have been opened
Alarm No. 164: Node 3: L01M64: Loop: 1 Module: 64
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M64
11/18/2025 41
Location: Module located on the left wall heading north just before Starbucks in the C-Bldg main entrance Description: Blow Open Doors have been opened
Alarm No. 165: Node 3: L01M65: Loop: 1 Module: 65
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M65
Location: Module located on the left wall heading north just before Starbucks in the C-Bldg main entrance Description: Blow Open Doors have been opened
Alarm No. 166: Node 3: L01M66: Loop: 1 Module: 66
Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M66
Location: Module located in the electrical store room on the west wall of C4 hall Description: Blow Open Doors have been opened
11/18/2025 42
11/18/2025 43
Alarm No. 201: Node 3: L02M01: Loop: 2 Module: 1
Display: NORMAL MONITOR POWERHOUSE 32 HEAT L02M01
Location: Heat detector located in power center 32 located on the northwest end of the C1 roof Description: A Heat Detector has gone off in this area.
Alarm No. 202: Node 3: L02M02: Loop: 2 Module: 2
Display: OFF FORM C RELAY WC INTERFACE NODE 2 CF L02M02
Location: Module located in the panel next to the Node 3 panel in the Node 3 room at the northend level 3 C- Bldg Description: Communications fault
Alarm No. 204: Node 3: L02M04: Loop: 2 Module: 4
Display: OFF FORM C RELAY PAHU 4-4 SHUTDOWN CF L02M04
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Unit in Shutdown Mode
Alarm No. 205: Node 3: L02M05: Loop: 2 Module: 5
Display: OFF FORM C RELAY PAHU 4-4 PURGE CF L02M05
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Unit in Purge Mode
Alarm No. 206: Node 3: L02M06: Loop: 2 Module: 6
Display: OFF NON ALM MON PAHU 4-4 OAD OPENED K L02M06
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Outside Air Damper is Opened
Alarm No. 207: Node 3: L02M07: Loop: 2 Module: 7
Display: ON NON ALM MON PAHU 4-4 OAD CLOSED MO K L02M07
Location: Module is located in the air handler on the northwest side of C1 hall roof
11/18/2025 44
Description: Outside Air Damper is Closed
Alarm No. 208: Node 3: L02M08: Loop: 2 Module: 8
Display: ON NON ALM MON PAHU 4-4 RAD OPENED MO K L02M08
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Return Air Damper is Opened
Alarm No. 209: Node 3: L02M09: Loop: 2 Module: 9
Display: OFF NON ALM MON PAHU 4-4 RAD CLOSED K L02M09
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Return Air Damper is Closed
Alarm No. 210: Node 3: L02M10: Loop: 2 Module: 10
Display: OFF NON ALM MON PAHU 4-4 EAD OPENED K L02M10
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Exhaust Air Damper is Opened
Alarm No. 211: Node 3: L02M11: Loop: 2 Module: 11
Display: ON NON ALM MON PAHU 4-4 EAD CLOSED MO K L02M11
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Exhaust Air Damper is Closed
Alarm No. 212: Node 3: L02M12: Loop: 2 Module: 12
Display: OFF NON ALM MON PAHU 4-4 SUPPLY FAN K L02M12
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Fan is active
Alarm No. 213: Node 3: L02M13: Loop: 2 Module: 13
Display: OFF NON ALM MON PAHU 4-4 RETURN FAN K L02M13
11/18/2025 45
Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Fan is active
Alarm No. 214: Node 3: L02M14: Loop: 2 Module: 14
Display: OFF FORM C RELAY PAHU 4-2 SHUTDOWN CF L02M14
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Unit in Shutdown Mode
Alarm No. 215: Node 3: L02M15: Loop: 2 Module: 15
Display: OFF FORM C RELAY PAHU 4-2 PURGE CF L02M15
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Unit in Purge Mode
Alarm No. 216: Node 3: L02M16: Loop: 2 Module: 16
Display: OFF NON ALM MON PAHU 4-2 OAD OPENED K L02M16
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Outside Air Damper is Opened
Alarm No. 217: Node 3: L02M17: Loop: 2 Module: 17
Display: ON NON ALM MON PAHU 4-2 OAD CLOSED MO K L02M17
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Outside Air Damper is Closed
Alarm No. 218: Node 3: L02M18: Loop: 2 Module: 18
Display: ON NON ALM MON PAHU 4-2 RAD OPENED MO K L02M18
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Return Air Damper is Opened
Alarm No. 219: Node 3: L02M19: Loop: 2 Module: 19
Display: OFF NON ALM MON PAHU 4-2 RAD CLOSED K L02M19
11/18/2025 46
Building: C Location: Module is located in the air handler in the center west side of C1 hall roof Description: Return Air Damper is Closed
Alarm No. 220: Node 3: L02M20: Loop: 2 Module: 20
Display: OFF NON ALM MON PAHU 4-2 EAD OPENED K L02M20
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Exhaust Air Damper is Opened
Alarm No. 221: Node 3: L02M21: Loop: 2 Module: 21
Display: ON NON ALM MON PAHU 4-2 EAD CLOSED MO K L02M21
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Exhaust Air Damper is Closed
Alarm No. 222: Node 3: L02M22: Loop: 2 Module: 22
Display: OFF NON ALM MON PAHU 4-2 SUPPLY FAN K L02M22
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Fan is active
Alarm No. 223: Node 3: L02M23: Loop: 2 Module: 23
Display: OFF NON ALM MON PAHU 4-2 RETURN FAN K L02M23
Location: Module is located in the air handler in the center west side of C1 hall roof Description: Fan is active
Alarm No. 224: Node 3: L02M24: Loop: 2 Module: 24
Display: OFF FORM C RELAY PAHU 4-3 SHUTDOWN CF L02M24
Location: Module is located in the air handler in the center east side of C1 hall roof Description: Unit in Shutdown Mode
Alarm No. 225: Node 3: L02M25: Loop: 2 Module: 25
11/18/2025 47
Display: OFF FORM C RELAY PAHU 4-3 PURGE CF L02M25 Building: C Location: Module is located in the air handler in the center east side of C1 hall roof Description: Unit in Purge Mode
Alarm No. 226: Node 3: L02M26: Loop: 2 Module: 26
Display: OFF NON ALM MON PAHU 4-3 OAD OPENED K L02M26
Location:…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .