This is a fire alarm system documentation file for Building C, detailing the complete alarm node configuration and monitoring system as of November 18, 2025. The document provides a comprehensive inventory of all detection devices, control modules, and monitoring equipment integrated into Node 3 of the facility's fire safety infrastructure.

The file catalogs 359 individual alarm devices organized across six loops (L01 through L06), including smoke detectors (both ionization and photoelectric types), heat detectors, water flow monitors, sprinkler tamper switches, elevator controls, air handling unit (PAHU) monitoring systems, roll-up door relays, strobe light controls, and emergency communication systems. Devices are distributed throughout Building C across multiple levels and locations, including exhibit halls (C-1 through C-4), restrooms, mechanical rooms, elevator shafts, stairwells, storage areas, and rooftop equipment. The system monitors critical infrastructure including 29 penthouse units, 41 separate PAHU units with damper controls, 14 elevator and stairwell systems, and multiple Ansul fire suppression systems in food service areas. All detectors display "NORMAL" or operational status, with modules indicating various states including shutdown mode, purge mode, damper activation, and communications faults. The documentation serves as the master reference record for the facility's integrated fire detection and alarm management system.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NODE 3

11/18/2025 1

Alarm No. 101: Node 3: L01D01: Loop: 1 Device: 1

Display: NORMAL SMOKE (ION) C-4 MENS RESTROOM W Building: C Location: In housekeeping storage closet inside C-4 mens restroom west wall Description: A Smoke Detector has gone off in this area.

Alarm No. 102: Node 3: L01D02: Loop: 1 Device: 2

Display: NORMAL SMOKE(PHOTO) C-4 WOMENS RESTRM W

Location: Housekeeping storage closet inside C-4 womens restroom west wall Description: A Smoke Detector has gone off in this area.

Alarm No. 103: Node 3: L01D03: Loop: 1 Device: 3

Display: NORMAL SMOKE (ION) C-4 SHOW OFFICE WEST

Location: Inside the show managers office for C-4 hall on the west wall enter from the point lobby Description: A Smoke Detector has gone off in this area.

Alarm No. 104: Node 3: L01D04: Loop: 1 Device: 4

Display: NORMAL SMOKE (ION) C-3 W ENGINEERING

Location: Engineering shop on west wall of C-3 hall near the C-3/C-4 point lobby Description: A Smoke Detector has gone off in this area.

Alarm No. 105: Node 3: L01D05: Loop: 1 Device: 5

Display: NORMAL SMOKE(PHOTO) BC-E-1 SUPPLY DUCT

Location: This detector is located inside the air handler in the ceiling above Starbucks in the C-Bldg main entrance Description: A Smoke Detector has gone off in this area.

Alarm No. 106: Node 3: L01D06: Loop: 1 Device: 6

Display: NORMAL SMOKE (ION) C-3 W ENGINEERING

Location: Engineering shop on the west wall of C-3 hall near the C-3/C4 point lobby Description: A Smoke Detector has gone off in this area.

11/18/2025 2

Alarm No. 107: Node 3: L01D07: Loop: 1 Device: 7

Display: NORMAL HEAT(ANALOG) ELEV 14 PIT HEAT

Location: This detector is located in the pit of elevator 14 on level 1 C-Bldg Description: A Heat Detector has gone off in this area.

Alarm No. 109: Node 3: L01D09: Loop: 1 Device: 9

Display: NORMAL SMOKE (ION) ELEV 14 LVL 1 LOBBY

Location: This detector is located outside the elevator 14 on level 1 C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 111: Node 3: L01D11: Loop: 1 Device: 11

Display: NORMAL SMOKE (ION) ELEV 14 MACHINE ROOM

Location: This detector is located in the elevator 14 mecanical room on level 1 C-Bldg next to the elevator Description: A Smoke Detector has gone off in this area.

Alarm No. 114: Node 3: L01D14: Loop: 1 Device: 14

Display: NORMAL SMOKE (ION) C-3 WOMENS RESTRM W

Location: Housekeeping storage closet inside C-3 womens restroom west wall Description: A Smoke Detector has gone off in this area.

Alarm No. 115: Node 3: L01D15: Loop: 1 Device: 15

Display: NORMAL SMOKE (ION) C-3 MENS RESTROOM W

Location: Housekeeping storage closet inside C-3 mens restroom west wall Description: A Smoke Detector has gone off in this area.

Alarm No. 116: Node 3: L01D16: Loop: 1 Device: 16

Display: NORMAL SMOKE (ION) WC WOMENS RESTROOM N

Location: Housekeeping storage closet inside womens restroom in C-Bldg main entrance

11/18/2025 3

Description: A Smoke Detector has gone off in this area.

Alarm No. 117: Node 3: L01D17: Loop: 1 Device: 17

Display: NORMAL SMOKE (ION) WC MENS RESTROOM N

Location: Housekeeping storage closet inside mens restroom in C-Bldg main entrance Description: A Smoke Detector has gone off in this area.

Alarm No. 118: Node 3: L01D18: Loop: 1 Device: 18

Display: NORMAL SMOKE (ION) C-2 MENS RESTROOM W

Location: In housekeeping storage closet inside mens restroom on west wall of C-2 hall Description: A Smoke Detector has gone off in this area.

Alarm No. 119: Node 3: L01D19: Loop: 1 Device: 19

Display: NORMAL SMOKE (ION) C-2 WOMENS RESTRM W

Location: In housekeeping storage closet inside womens restroom on west wall of C-2 hall Description: A Smoke Detector has gone off in this area.

Alarm No. 120: Node 3: L01D20: Loop: 1 Device: 20

Display: NORMAL SMOKE (ION) ELEV 15 MACHINE RM

Location: This detector is located in the elevator 15 mecanical room on level 1 C-Bldg next to the elevator Description: A Smoke Detector has gone off in this area.

Alarm No. 122: Node 3: L01D22: Loop: 1 Device: 22

Display: NORMAL SMOKE (ION) ELEV 15 LVL 1 LOBBY

Location: This detector is located outside the elevator 15 on level 1 C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 124: Node 3: L01D24: Loop: 1 Device: 24

Display: NORMAL HEAT(ANALOG) ELEV 15 PIT HEAT

11/18/2025 4

Location: This detector is located in the pit of elevator 15 on level 1 C-Bldg Description: A Heat Detector has gone off in this area.

Alarm No. 125: Node 3: L01D25: Loop: 1 Device: 25

Display: NORMAL SMOKE (ION) WC NEAR ELEV 15

Location: Inside setup storage room west concourse C Bldg. Main entrance next to elevator 15.

Description: A Smoke Detector has gone off in this area.

Alarm No. 126: Node 3: L01D26: Loop: 1 Device: 26

Display: NORMAL SMOKE (ION) WC NEAR ELEV 15

Location: Inside setup storage room west concourse C Bldg. Main entrance next to elevator 15.

Description: A Smoke Detector has gone off in this area.

Alarm No. 127: Node 3: L01D27: Loop: 1 Device: 27

Display: NORMAL SMOKE (ION) C-4 EXHIBIT HALL W

Location: Engineering panel storage room with the blow open door controllers inside C-4 hall west wall Description: A Smoke Detector has gone off in this area.

Alarm No. 128: Node 3: L01D28: Loop: 1 Device: 28

Display: NORMAL SMOKE (ION) C-4 EXHIBIT HALL W

Location: Housekeeping storage room on west wall C-4 hall

11/18/2025 5

Alarm No. 201: Node 3: L02D01: Loop: 2 Device: 1

Display: NORMAL SMOKE (ION) POWERHOUSE 32

Location: 1st penthouse on C-Bldg roof west side Description: A Smoke Detector has gone off in this area.

Alarm No. 203: Node 3: L02D03: Loop: 2 Device: 3

Display: NORMAL SMOKE(PHOTO) PAHU 4-4 SUPPLY

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 204: Node 3: L02D04: Loop: 2 Device: 4

Display: NORMAL SMOKE(PHOTO) PAHU 4-4 RETURN

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 205: Node 3: L02D05: Loop: 2 Device: 5

Display: NORMAL SMOKE(PHOTO) PAHU 4-2 SUPPLY

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 206: Node 3: L02D06: Loop: 2 Device: 6

Display: NORMAL SMOKE(PHOTO) PAHU 4-2 RETURN

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 207: Node 3: L02D07: Loop: 2 Device: 7

Display: NORMAL SMOKE(PHOTO) PAHU 4-3 SUPPLY

Location: This detector is located inside the air handler on C1 hall roof

11/18/2025 6

Alarm No. 208: Node 3: L02D08: Loop: 2 Device: 8

Display: NORMAL SMOKE(PHOTO) PAHU 4-3 RETURN

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 209: Node 3: L02D09: Loop: 2 Device: 9

Display: NORMAL SMOKE(PHOTO) PAHU 4-1 SUPPLY

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 210: Node 3: L02D10: Loop: 2 Device: 10

Display: NORMAL SMOKE(PHOTO) PAHU 4-1 RETURN

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 211: Node 3: L02D11: Loop: 2 Device: 11

Display: NORMAL SMOKE (ION) POWERHOUSE 31

Location: 1st penthouse on C-Bldg roof east side Description: A Smoke Detector has gone off in this area.

Alarm No. 213: Node 3: L02D13: Loop: 2 Device: 13

Display: NORMAL SMOKE(PHOTO) PAHU 4-28 SUPPLY

Location: This detector is located inside the air handler on C1 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 214: Node 3: L02D14: Loop: 2 Device: 14

Display: NORMAL SMOKE(PHOTO) PAHU 4-28 RETURN

Location: This detector is located inside the air handler on C1 hall roof

11/18/2025 7

Description: A Smoke Detector has gone off in this area.

Alarm No. 215: Node 3: L02D15: Loop: 2 Device: 15

Display: NORMAL SMOKE(PHOTO) BC-P-1 SUPPLY

Location: This detector is located in the air handler in the ceiling of the electrical mechanical room behind the american grill in Foodworld in C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 216: Node 3: L02D16: Loop: 2 Device: 16

Display: NORMAL SMOKE (ION) LVL 2 FOODWORLD NW

Location: North west end in electrical room past American grill Description: A Smoke Detector has gone off in this area.

Alarm No. 217: Node 3: L02D17: Loop: 2 Device: 17

Display: NORMAL SMOKE (ION) LVL 2 SW FOOD COURT

Location: In ceiling as you walk in front door of Foodworld

11/18/2025 8

11/18/2025 9

Alarm No. 301: Node 3: L03D01: Loop: 3 Device: 1

Display: NORMAL SMOKE (ION) FACP 3 ROOM LEVEL 3

Location: In room back hallway where Node 3 is located Description: A Smoke Detector has gone off in this area.

Alarm No. 302: Node 3: L03D02: Loop: 3 Device: 2

Display: NORMAL SMOKE (ION) LEVEL 3 NORTHWEST

Location: Set up store room level 3 C-Bldg northwest end of back hallway Description: A Smoke Detector has gone off in this area.

Alarm No. 303: Node 3: L03D03: Loop: 3 Device: 3

Display: NORMAL SMOKE (ION) LEVEL 3 NORTHWEST

Location: Set up store room level 3 C-Bldg northwest end of back hallway Description: A Smoke Detector has gone off in this area.

Alarm No. 304: Node 3: L03D04: Loop: 3 Device: 4

Display: NORMAL SMOKE (ION) ELEV 14 LVL 3 LOBBY

Location: This detector is located outside the elevator 14 on level 3 C-Bldg nothrthend Description: A Smoke Detector has gone off in this area.

Alarm No. 305: Node 3: L03D05: Loop: 3 Device: 5

Display: NORMAL SMOKE (ION) C308 CHAIR STORAGE

Location: Chair storage room in room C308 level 3 C-Bldg northend Description: A Smoke Detector has gone off in this area.

Alarm No. 306: Node 3: L03D06: Loop: 3 Device: 6

Display: NORMAL SMOKE (ION) C308 PARTITION WALL

Location: Inside wall storage room in C308 level 3 C-Bldg

11/18/2025 10

Alarm No. 307: Node 3: L03D07: Loop: 3 Device: 7

Display: NORMAL SMOKE (ION) C306 PARTITION WALL

Location: Inside wall storage in C307 level 3 C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 308: Node 3: L03D08: Loop: 3 Device: 8

Display: NORMAL SMOKE (ION) C306 CHAIR STORAGE

Location: Chair storage room in room C306 level 3 C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 309: Node 3: L03D09: Loop: 3 Device: 9

Display: NORMAL SMOKE (ION) LVL 3 WC SRVICE HALL

Location: Northend housekeeping storage room level 3 back hallway C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 310: Node 3: L03D10: Loop: 3 Device: 10

Display: NORMAL SMOKE (ION) WC LVL 3 MENS RESTRM

Location: Housekeeping storage room inside restroom next to room C306 Description: A Smoke Detector has gone off in this area.

Alarm No. 311: Node 3: L03D11: Loop: 3 Device: 11

Display: NORMAL SMOKE (ION) C305 CHAIR STORAGE

Location: Chair storage room inside room C305 level 3 Bldg C Description: A Smoke Detector has gone off in this area.

Alarm No. 312: Node 3: L03D12: Loop: 3 Device: 12

Display: NORMAL SMOKE (ION) C305 PARTITION WALL

Location: Air wall storage room inside room C304 level 3 Bldg C

11/18/2025 11

Description: A Smoke Detector has gone off in this area.

Alarm No. 313: Node 3: L03D13: Loop: 3 Device: 13

Display: NORMAL SMOKE (ION) C303 PARTITION WALL

Location: Air wall storage room inside room C304 level 3 Bldg C Description: A Smoke Detector has gone off in this area.

Alarm No. 314: Node 3: L03D14: Loop: 3 Device: 14

Display: NORMAL SMOKE (ION) C303 CHAIR STORAGE

Location: Chair storage room inside room C303 level 3 Bldg C Description: A Smoke Detector has gone off in this area.

Alarm No. 315: Node 3: L03D15: Loop: 3 Device: 15

Display: NORMAL SMOKE (ION) WC LV3 WOMENS RESTRM

Location: Housekeeping storage room inside mens restroom next to room C305 level 3 C-bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 316: Node 3: L03D16: Loop: 3 Device: 16

Display: NORMAL SMOKE (ION) WC LV3 WOMENS RESTRM

Location: Housekeeping storage room inside womens restroom next to room C303 level 3 Bldg C Description: A Smoke Detector has gone off in this area.

Alarm No. 317: Node 3: L03D17: Loop: 3 Device: 17

Display: NORMAL SMOKE (ION) WC LVL 3 MENS RESTRM

Location: Housekeeping storage room inside mens restroom next to room C303 level 3 Bldg C Description: A Smoke Detector has gone off in this area.

Alarm No. 318: Node 3: L03D18: Loop: 3 Device: 18

Display: NORMAL SMOKE (ION) ELEV 15 LVL 3 LOBBY

11/18/2025 12

Location: This detector is located outside the elevator 15 on level 3 C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 319: Node 3: L03D19: Loop: 3 Device: 19

Display: NORMAL SMOKE (ION) ELEV 15 TOP OF SHAFT

Location: This detector is located at the top of the shaft of elevator 15 C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 320: Node 3: L03D20: Loop: 3 Device: 20

Display: NORMAL SMOKE(PHOTO) PAHU 4-17 SUPPLY

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 321: Node 3: L03D21: Loop: 3 Device: 21

Display: NORMAL SMOKE(PHOTO) PAHU 4-17 RETURN

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 322: Node 3: L03D22: Loop: 3 Device: 22

Display: NORMAL SMOKE(PHOTO) PAHU 4-14 SUPPLY

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 323: Node 3: L03D23: Loop: 3 Device: 23

Display: NORMAL SMOKE(PHOTO) PAHU 4-14 RETURN

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 324: Node 3: L03D24: Loop: 3 Device: 24

Display: NORMAL SMOKE (ION) POWERHOUSE 26

11/18/2025 13

Building: C Location: 4th penthouse on west side of C-Bldg roof Description: A Smoke Detector has gone off in this area.

Alarm No. 325: Node 3: L03D25: Loop: 3 Device: 25

Display: NORMAL SMOKE(PHOTO) PAHU 4-16 SUPPLY

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 326: Node 3: L03D26: Loop: 3 Device: 26

Display: NORMAL SMOKE(PHOTO) PAHU 4-16 RETURN

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 327: Node 3: L03D27: Loop: 3 Device: 27

Display: NORMAL SMOKE(PHOTO) PAHU 4-15 SUPPLY

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 328: Node 3: L03D28: Loop: 3 Device: 28

Display: NORMAL SMOKE(PHOTO) PAHU 4-15 RETURN

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 329: Node 3: L03D29: Loop: 3 Device: 29

Display: NORMAL SMOKE (ION) POWERHOUSE 25

Location: 4th penthouse on east side C-Bldg roof Description: A Smoke Detector has gone off in this area.

Alarm No. 330: Node 3: L03D30: Loop: 3 Device: 30

11/18/2025 14

Display: NORMAL SMOKE(PHOTO) PAHU 4-13 SUPPLY Building: C Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 331: Node 3: L03D31: Loop: 3 Device: 31

Display: NORMAL SMOKE(PHOTO) PAHU 4-13 RETURN

Location: This detector is located inside the air handler on C4 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 332: Node 3: L03D32: Loop: 3 Device: 32

Display: NORMAL SMOKE (ION) ELEV 14 TOP OF SHAFT

Location: This detector is located at the top of the shaft of elevator 14 C-Bldg northend Description: A Smoke Detector has gone off in this area.

Alarm No. 333: Node 3: L03D33: Loop: 3 Device: 33

Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE

Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 334: Node 3: L03D34: Loop: 3 Device: 34

Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 335: Node 3: L03D35: Loop: 3 Device: 35

Location: Southend of back hallway 3rd level tech services store room in C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 336: Node 3: L03D36: Loop: 3 Device: 36

11/18/2025 15

Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE V000 M 051 L03D36

Location: Southend of back hallway 3rd level setup store room in C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 337: Node 3: L03D37: Loop: 3 Device: 37

Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE V000 M 042 L03D37

Location: Southend of back hallway 3rd level setup store room in C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 338: Node 3: L03D38: Loop: 3 Device: 38

Display: NORMAL SMOKE (ION) LVL 3 SW W CONCOURSE V000 M 030 L03D38

Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 339: Node 3: L03D39: Loop: 3 Device: 39

Display: NORMAL SMOKE(PHOTO) PAHU 4-41 SUPPLY V000 M 037 L03D39

Location: This detector is located inside the air handler on the roof accessed by the roof hatch in the #16/17 elevator mecanical room on level 4 back hallway Description: A Smoke Detector has gone off in this area.

Alarm No. 340: Node 3: L03D40: Loop: 3 Device: 40

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D40

Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 341: Node 3: L03D41: Loop: 3 Device: 41

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D41

Location: Southend of back hallway 3rd level C-Bldg

11/18/2025 16

Alarm No. 342: Node 3: L03D42: Loop: 3 Device: 42

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D42

Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 343: Node 3: L03D43: Loop: 3 Device: 43

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D43

Location: Southend of back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 344: Node 3: L03D44: Loop: 3 Device: 44

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D44

Location: Center section of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 345: Node 3: L03D45: Loop: 3 Device: 45

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 032 L03D45

Location: Center section of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 346: Node 3: L03D46: Loop: 3 Device: 46

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 048 L03D46

Location: Center section of the back hallway 3rd level C-Bldg behind room C303 Description: A Smoke Detector has gone off in this area.

Alarm No. 347: Node 3: L03D47: Loop: 3 Device: 47

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 045 L03D47

Location: Center section of the back hallway 3rd level C-Bldg behind room C304

11/18/2025 17

Alarm No. 348: Node 3: L03D48: Loop: 3 Device: 48

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 048 L03D48

Location: Center section of the back hallway 3rd level C-Bldg behind room C305 Description: A Smoke Detector has gone off in this area.

Alarm No. 349: Node 3: L03D49: Loop: 3 Device: 49

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 045 L03D49

Location: Center section of the back hallway 3rd level C-Bldg behind room C305 Description: A Smoke Detector has gone off in this area.

Alarm No. 350: Node 3: L03D50: Loop: 3 Device: 50

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 046 L03D50

Location: Center section of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 351: Node 3: L03D51: Loop: 3 Device: 51

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D51

Location: Center section of the back hallway 3rd level C-Bldg behind room C306 Description: A Smoke Detector has gone off in this area.

Alarm No. 352: Node 3: L03D52: Loop: 3 Device: 52

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 044 L03D52

Location: Center section of the back hallway 3rd level C-Bldg behind room C307 Description: A Smoke Detector has gone off in this area.

Alarm No. 353: Node 3: L03D53: Loop: 3 Device: 53

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 044 L03D53

Location: Center section of the back hallway 3rd level C-Bldg behind room C308

11/18/2025 18

Description: A Smoke Detector has gone off in this area.

Alarm No. 354: Node 3: L03D54: Loop: 3 Device: 54

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 036 L03D54

Location: Center section of the back hallway 3rd level C-Bldg behind room C308 Description: A Smoke Detector has gone off in this area.

Alarm No. 355: Node 3: L03D55: Loop: 3 Device: 55

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 051 L03D55

Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 356: Node 3: L03D56: Loop: 3 Device: 56

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D56

Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 357: Node 3: L03D57: Loop: 3 Device: 57

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D57

Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 358: Node 3: L03D58: Loop: 3 Device: 58

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 039 L03D58

Location: Northend of the back hallway 3rd level C-Bldg Description: A Smoke Detector has gone off in this area.

Alarm No. 359: Node 3: L03D59: Loop: 3 Device: 59

Display: NORMAL SMOKE (ION) LVL 3 W CON SERVICE V000 M 036 L03D59

11/18/2025 19

Location: Northend of the back hallway 3rd level C-Bldg

11/18/2025 20

11/18/2025 21

Alarm No. 401: Node 3: L04D01: Loop: 4 Device: 1

Display: NORMAL SMOKE(PHOTO) PAHU 4-12 SUPPLY V000 M 038 L04D01

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 402: Node 3: L04D02: Loop: 4 Device: 2

Display: NORMAL SMOKE(PHOTO) PAHU 4-12 RETURN V000 M 042 L04D02

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 403: Node 3: L04D03: Loop: 4 Device: 3

Display: NORMAL SMOKE (ION) POWERHOUSE 28 V000 M 065 L04D03

Location: 3rd penthouse on C-Bldg roof westside Description: A Smoke Detector has gone off in this area.

Alarm No. 404: Node 3: L04D04: Loop: 4 Device: 4

Display: NORMAL SMOKE(PHOTO) PAHU 4-19 SUPPLY V000 M 038 L04D04

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 405: Node 3: L04D05: Loop: 4 Device: 5

Display: NORMAL SMOKE(PHOTO) PAHU 4-19 RETURN V000 M 043 L04D05

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 406: Node 3: L04D06: Loop: 4 Device: 6

Display: NORMAL SMOKE(PHOTO) PAHU 4-18 SUPPLY V000 M 034 L04D06

Location: This detector is located inside the air handler on C3 hall roof

11/18/2025 22

Alarm No. 407: Node 3: L04D07: Loop: 4 Device: 7

Display: NORMAL SMOKE(PHOTO) PAHU 4-10 SUPPLY V000 M 036 L04D07

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 408: Node 3: L04D08: Loop: 4 Device: 8

Display: NORMAL SMOKE(PHOTO) PAHU 4-10 RETURN V000 M 043 L04D08

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 409: Node 3: L04D09: Loop: 4 Device: 9

Display: NORMAL SMOKE(PHOTO) PAHU 4-9 SUPPLY V000 M 039 L04D09

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 410: Node 3: L04D10: Loop: 4 Device: 10

Display: NORMAL SMOKE(PHOTO) PAHU 4-9 RETURN V000 M 050 L04D10

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 411: Node 3: L04D11: Loop: 4 Device: 11

Display: NORMAL SMOKE (ION) POWERHOUSE 27 V000 M 060 L04D11

Location: 3rd penthouse on C-Bldg roof eastside Description: A Smoke Detector has gone off in this area.

Alarm No. 412: Node 3: L04D12: Loop: 4 Device: 12

Display: NORMAL SMOKE(PHOTO) PAHU 4-11 SUPPLY V000 M 037 L04D12

Location: This detector is located inside the air handler on C3 hall roof

11/18/2025 23

Description: A Smoke Detector has gone off in this area.

Alarm No. 413: Node 3: L04D13: Loop: 4 Device: 13

Display: NORMAL SMOKE(PHOTO) PAHU 4-11 RETURN V000 M 039 L04D13

Location: This detector is located inside the air handler on C3 hall roof

11/18/2025 24

11/18/2025 25

Alarm No. 501: Node 3: L05D01: Loop: 5 Device: 1

Display: NORMAL SMOKE(PHOTO) PAHU 4-22 SUPPLY V000 M 038 L05D01

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 502: Node 3: L05D02: Loop: 5 Device: 2

Display: NORMAL SMOKE(PHOTO) PAHU 4-22 RETURN V000 M 044 L05D02

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 503: Node 3: L05D03: Loop: 5 Device: 3

Display: NORMAL SMOKE(PHOTO) PAHU 4-21 SUPPLY V000 M 039 L05D03

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 504: Node 3: L05D04: Loop: 5 Device: 4

Display: NORMAL SMOKE(PHOTO) PAHU 4-20 SUPPLY V000 M 038 L05D04

Location: This detector is located inside the air handler on C3 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 505: Node 3: L05D05: Loop: 5 Device: 5

Display: NORMAL SMOKE(PHOTO) PAHU 4-7 SUPPLY V000 M 037 L05D05

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 506: Node 3: L05D06: Loop: 5 Device: 6

Display: NORMAL SMOKE(PHOTO) PAHU 4-7 RETURN V000 M 043 L05D06

Location: This detector is located inside the air handler on C2 hall roof

11/18/2025 26

Alarm No. 507: Node 3: L05D07: Loop: 5 Device: 7

Display: NORMAL SMOKE (ION) POWERHOUSE 29 V000 M 063 L05D07

Location: 2nd penthouse on C-Bldg roof eastside Description: A Smoke Detector has gone off in this area.

Alarm No. 508: Node 3: L05D08: Loop: 5 Device: 8

Display: NORMAL SMOKE(PHOTO) PAHU 4-5 SUPPLY V000 M 039 L05D08

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 509: Node 3: L05D09: Loop: 5 Device: 9

Display: NORMAL SMOKE(PHOTO) PAHU 4-5 RETURN V000 M 055 L05D09

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 510: Node 3: L05D10: Loop: 5 Device: 10

Display: NORMAL SMOKE(PHOTO) PAHU 4-8 SUPPLY V000 M 038 L05D10

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 511: Node 3: L05D11: Loop: 5 Device: 11

Display: NORMAL SMOKE(PHOTO) PAHU 4-8 RETURN V000 M 042 L05D11

Location: This detector is located inside the air handler on C2 hall roof

11/18/2025 27

Alarm No. 601: Node 3: L06D01: Loop: 6 Device: 1

Display: NORMAL SMOKE(PHOTO) PAHU 4-23 SUPPLY V000 M 038 L06D01

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 602: Node 3: L06D02: Loop: 6 Device: 2

Display: NORMAL SMOKE(PHOTO) PAHU 4-23 RETURN V000 M 049 L06D02

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 603: Node 3: L06D03: Loop: 6 Device: 3

Display: NORMAL SMOKE(PHOTO) PAHU 4-24 SUPPLY V000 M 039 L06D03

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 604: Node 3: L06D04: Loop: 6 Device: 4

Display: NORMAL SMOKE(PHOTO) PAHU 4-25 SUPPLY V000 M 037 L06D04

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 605: Node 3: L06D05: Loop: 6 Device: 5

Display: NORMAL SMOKE (ION) POWERHOUSE 30 V000 M 066 L06D05

Location: 2nd penthouse on C-Bldg roof westside Description: A Smoke Detector has gone off in this area.

Alarm No. 606: Node 3: L06D06: Loop: 6 Device: 6

Display: NORMAL SMOKE(PHOTO) PAHU 4-26 SUPPLY V000 M 037 L06D06

11/18/2025 28

Alarm No. 607: Node 3: L06D07: Loop: 6 Device: 7

Display: NORMAL SMOKE(PHOTO) PAHU 4-26 RETURN V000 M 067 L06D07

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 613: Node 3: L06D13: Loop: 6 Device: 13

Display: NORMAL SMOKE(PHOTO) PAHU 4-6 SUPPLY V000 M 042 L06D13

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 614: Node 3: L06D14: Loop: 6 Device: 14

Display: NORMAL SMOKE(PHOTO) PAHU 4-6 RETURN V000 M 045 L06D14

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 615: Node 3: L06D15: Loop: 6 Device: 15

Display: NORMAL SMOKE(PHOTO) PAHU 4-29 SUPPLY V000 M 032 L06D15

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 616: Node 3: L06D16: Loop: 6 Device: 16

Display: NORMAL SMOKE(PHOTO) PAHU 4-29 RETURN V000 M 056 L06D16

Location: This detector is located inside the air handler on C2 hall roof Description: A Smoke Detector has gone off in this area.

Alarm No. 617: Node 3: L06D17: Loop: 6 Device: 17

Display: NORMAL SMOKE(PHOTO) PAHU 4-27 SUPPLY V000 M 038 L06D17

11/18/2025 29

11/18/2025 30

11/18/2025 31

Alarm No. 101: Node 3: L01M01: Loop: 1 Module: 1

Display: OFF SPRNKLR MNTR STAIR 41 STANDPIPE K L01M01

Location: Module is located in the stairwell north end level 3 Description: Tamper switch has been activated

Alarm No. 102: Node 3: L01M02: Loop: 1 Module: 2

Display: OFF CONTROL RPS 32 C-3 HALL STRB CF L01M02

Location: RPS located in the electrical store room on the west wall of C4 hall Description: Strobes have been activated

Alarm No. 103: Node 3: L01M03: Loop: 1 Module: 3

Display: OFF SPRNKLR MNTR SYSTEM 10 STAIR 41 K L01M03

Location: Module is located in the stairwell north end level 3 Description: Tamper switch has been activated

Alarm No. 104: Node 3: L01M04: Loop: 1 Module: 4

Display: NORMAL WATER FLOW SYSTEM 10 STAIR 41 L01M04

Location: Module is located in the stairwell north end level 3 Description: Water Flow has been activated

Alarm No. 105: Node 3: L01M05: Loop: 1 Module: 5

Display: OFF SPRNKLR MNTR C-4 FHV TAMPER K L01M05

Location: In ceiling C-4 hall near center of west wall about 30-40 feet off the wall lobby side Description: Tamper switch has been activated

Alarm No. 106: Node 3: L01M06: Loop: 1 Module: 6

Display: OFF SPRNKLR MNTR C-4 FHV TAMPER K L01M06

Location: In ceiling C-4 hall at the fire exit doors at C3/4 point lobby Description: Tamper switch has been activated

11/18/2025 32

Alarm No. 107: Node 3: L01M07: Loop: 1 Module: 7

Display: OFF FORM C RELAY C-4 O-H DOOR RELAY S CF L01M07

Location: Module located at the rollup door leading out the C3/4 point lobby side in C4 hall Description: Roll-Up Doors have been closed

Alarm No. 108: Node 3: L01M08: Loop: 1 Module: 8

Display: OFF FORM C RELAY C-3 O-H DOOR RELAY N CF L01M08

Location: Module located at the rollup door leading out the C3/4 point lobby side in C3 hall Description: Roll-Up Doors have been closed

Alarm No. 110: Node 3: L01M10: Loop: 1 Module: 10

Display: OFF SPRNKLR MNTR SYSTEM 11 STAIR 39 K L01M10

Location: Module is located in stairwell 39 which is right across from elevator 14 the last elevator heading north in the C-Bldg main entrance Description: Tamper switch has been activated

Alarm No. 111: Node 3: L01M11: Loop: 1 Module: 11

Display: NORMAL WATER FLOW SYSTEM 11 STAIR 39 L01M11

Location: Module is located in stairwell 39 which is right across from elevator 14 the last elevator heading north in the C-Bldg main entrance Description: Water Flow has been activated

Alarm No. 114: Node 3: L01M14: Loop: 1 Module: 14

Display: OFF SPRNKLR MNTR C-2 FHV TAMPER SW K L01M14

Location: In ceiling center of the southwest wall in C-2 hall Description: Tamper switch has been activated

Alarm No. 118: Node 3: L01M18: Loop: 1 Module: 18

Display: OFF CONTROL RPS 6 C-3 HALL STRBS CF L01M18

11/18/2025 33

Building: C Location: RPS located in the C3 engineering shop on the west wall of C3 hall Description: Strobes have been activated

Alarm No. 119: Node 3: L01M19: Loop: 1 Module: 19

Display: OFF CONTROL RPS 7 C-3 HALL STRBS CF L01M19

Location: RPS located in the C3 engineering shop on the west wall of C3 hall Description: Strobes have been activated

Alarm No. 120: Node 3: L01M20: Loop: 1 Module: 20

Display: OFF FORM C RELAY ELEV 14 PRIM RECALL CF L01M20

Location: Module is in the elevator macine room located next to the elevator on level 1 C-Bldg main entrance last elevator heading north Description: Elevator has been sent to the Primary Level

Alarm No. 121: Node 3: L01M21: Loop: 1 Module: 21

Display: OFF FORM C RELAY ELEV 14 ALT RECALL CF L01M21

Location: Module is in the elevator macine room located next to the elevator on level 1 C-Bldg main entrance last elevator heading north Description: Elevator has been sent to the Alternate Level

Alarm No. 122: Node 3: L01M22: Loop: 1 Module: 22

Display: OFF FORM C RELAY ELEV 14 WARNING LITE CF L01M22

Location: Module is in the elevator macine room located next to the elevator on level 1 C-Bldg main entrance last elevator heading north Description: Elevator has been shut down

Alarm No. 123: Node 3: L01M23: Loop: 1 Module: 23

Display: OFF SPRNKLR MNTR C-2 W FHV TAMPER K L01M23

Location: In ceiling center of the west wall in C-2 hall Description: Tamper switch has been activated

11/18/2025 34

Alarm No. 124: Node 3: L01M24: Loop: 1 Module: 24

Display: OFF SPRNKLR MNTR C-2 W FHV TAMPER K L01M24

Location: In ceiling center of the west wall in C-2 hall Description: Tamper switch has been activated

Alarm No. 125: Node 3: L01M25: Loop: 1 Module: 25

Display: OFF FORM C RELAY C-3 O-H DOOR RELAY S CF L01M25

Location: Module located at the rollup door leading out the C2/3 point lobby side in C3 hall Description: Roll-Up Doors have been closed

Alarm No. 126: Node 3: L01M26: Loop: 1 Module: 26

Display: OFF SPRNKLR MNTR STAIR 38 FHV TAMPER K L01M26

Location: Module located in the stairwell across from room C308 Description: Tamper switch has been activated

Alarm No. 127: Node 3: L01M27: Loop: 1 Module: 27

Display: OFF FORM C RELAY BC-E-1 SHUTDOWN RLY CF L01M27

Location: Module located in the air handler above the ceiling soffit at the Starbucks in C-Bldg main entrance far northend Description: Unit in Shutdown Mode

Alarm No. 128: Node 3: L01M28: Loop: 1 Module: 28

Display: OFF SPRNKLR MNTR STAIR 37 FHV TAMPER K L01M28

Location: Module located in the stairwell across from room C306 Description: Tamper switch has been activated

Alarm No. 129: Node 3: L01M29: Loop: 1 Module: 29

Display: OFF FORM C RELAY BC-E-2 SHUTDOWN RLY CF L01M29

11/18/2025 35

Location: Module located in the air handler above the ceiling soffit at the Starbucks in C-Bldg main entrance far northend Description: Elevator has been shut down

Alarm No. 130: Node 3: L01M30: Loop: 1 Module: 30

Display: OFF FORM C RELAY C-2 O-H DOOR RELAY N CF L01M30

Location: Module located at the rollup door leading out the C2/3 point lobby side in C2 hall Description: Roll-Up Doors have been closed

Alarm No. 131: Node 3: L01M31: Loop: 1 Module: 31

Display: NORMAL WATER FLOW SYSTEM 12 STAIR 34 L01M31

Location: Module is located in stairwell 34 locatedi C-Bldg main lobby just to the right as you walk out the C1/2 point lobby Description: Water Flow has been activated

Alarm No. 133: Node 3: L01M33: Loop: 1 Module: 33

Display: OFF SPRNKLR MNTR STAIR 35 TAMPER TOP K L01M33

Location: Module located in the stairwell across from room C303 Description: Tamper switch has been activated

Alarm No. 134: Node 3: L01M34: Loop: 1 Module: 34

Display: OFF SPRNKLR MNTR STAIR 36 TAMPER TOP K L01M34

Location: Module located in the stairwell across from room C305 Description: Tamper switch has been activated

Alarm No. 135: Node 3: L01M35: Loop: 1 Module: 35

Display: OFF SPRNKLR MNTR STAIR 35 FHV TAMPER K L01M35

Location: Module located in the stairwell across from room C303 Description: Tamper switch has been activated

Alarm No. 136: Node 3: L01M36: Loop: 1 Module: 36

11/18/2025 36

Display: OFF SPRNKLR MNTR STAIR 36 FHV TAMPER K L01M36

Location: Module located in the stairwell across from room C305 Description: Tamper switch has been activated

Alarm No. 137: Node 3: L01M37: Loop: 1 Module: 37

Display: OFF SPRNKLR MNTR STAIR 37 TAMPER TOP K L01M37

Location: Module located in the stairwell across from room C306 Description: Tamper switch has been activated

Alarm No. 138: Node 3: L01M38: Loop: 1 Module: 38

Display: OFF SPRNKLR MNTR STAIR 38 TAMPER TOP K L01M38

Location: Module located in the stairwell across from room C308 Description: Tamper switch has been activated

Alarm No. 139: Node 3: L01M39: Loop: 1 Module: 39

Display: OFF SPRNKLR MNTR ELEV 14 PIT TAMPER K L01M39

Location: Valve located in the pit of elevator 14 C-Bldg main entrance last elevator heading north Description: Tamper switch has been activated

Alarm No. 140: Node 3: L01M40: Loop: 1 Module: 40

Display: OFF SPRNKLR MNTR ELEV 15 PIT TAMPER K L01M40

Location: Valve located in the pit of elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Tamper switch has been activated

Alarm No. 141: Node 3: L01M41: Loop: 1 Module: 41

Display: OFF FORM C RELAY ELEV 15 PRIM RECALL CF L01M41

Location: Module located in the machine room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Elevator has been sent to the Primary Level

11/18/2025 37

Alarm No. 142: Node 3: L01M42: Loop: 1 Module: 42

Display: OFF FORM C RELAY ELEV 15 ALT RECALL CF L01M42

Location: Module located in the machine room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Elevator has been sent to the Alternate Level

Alarm No. 143: Node 3: L01M43: Loop: 1 Module: 43

Display: OFF FORM C RELAY ELEV 15 WARNING LITE CF L01M43

Location: Module located in the machine room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Elevator has been shut down

Alarm No. 144: Node 3: L01M44: Loop: 1 Module: 44

Display: OFF CONTROL RPS 4 WC STROBES CF L01M44

Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated

Alarm No. 145: Node 3: L01M45: Loop: 1 Module: 45

Display: OFF CONTROL RPS 5 WC STROBES CF L01M45

Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated

Alarm No. 146: Node 3: L01M46: Loop: 1 Module: 46

Display: OFF SPRNKLR MNTR SYSTEM 12 STAIR 34 K L01M46

Location: Module is located in stairwell 34 locatedi C-Bldg main lobby just to the right as you walk out the C1/2 point lobby Description: Tamper switch has been activated

Alarm No. 147: Node 3: L01M47: Loop: 1 Module: 47

11/18/2025 38

Display: OFF FORM C RELAY C-2 O-H DOOR RELAY S CF L01M47

Location: Module located at the rollup door leading out the C1/2 point lobby side in C2 hall Description: Roll-Up Doors have been closed

Alarm No. 148: Node 3: L01M48: Loop: 1 Module: 48

Display: OFF FORM C RELAY C-1 O-H DOOR RELAY N CF L01M48

Location: Module located at the rollup door leading out the C1/2 point lobby side in C1 hall Description: Roll-Up Doors have been closed

Alarm No. 149: Node 3: L01M49: Loop: 1 Module: 49

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M49

Location: Module located in the electrical store room on the west wall of C4 hall Description: Blow Open Doors have been opened

Alarm No. 150: Node 3: L01M50: Loop: 1 Module: 50

Display: OFF NON ALM MON C-3 INTERFACE NODE 2 K L01M50

Location: Module located at the C3/4 point lobby side in C3 hall ceiling at overhead door Description: Communications fault

Alarm No. 151: Node 3: L01M51: Loop: 1 Module: 51

Display: OFF NON ALM MON C-4 INTERFACE NODE 2 K L01M51

Location: Module located at the C3/4 point lobby side in C4 hall ceiling at overhead door Description: Communications fault

Alarm No. 152: Node 3: L01M52: Loop: 1 Module: 52

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M52

Location: Module located in the electrical store room on the west wall of C4 hall Description: Blow Open Doors have been opened

11/18/2025 39

Alarm No. 153: Node 3: L01M53: Loop: 1 Module: 53

Display: OFF CONTROL RPS 4 C-2 HALL STRBS CF L01M53

Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated

Alarm No. 154: Node 3: L01M54: Loop: 1 Module: 54

Display: OFF CONTROL RPS 5 C-2 HALL STRBS CF L01M54

Location: RPS located in the store room next to elevator 15 C-Bldg main entrance to the right as you exit the C1/2 point Description: Strobes have been activated

Alarm No. 155: Node 3: L01M55: Loop: 1 Module: 55

Display: OFF CONTROL RPS 6 WC STROBES CF L01M55

Location: RPS located in the C3 engineering shop on the west wall of C3 hall Description: Strobes have been activated

Alarm No. 156: Node 3: L01M56: Loop: 1 Module: 56

Display: OFF CONTROL RPS 8 C-4 HALL STRBS CF L01M56

Location: RPS located in the electrical store room on the west wall of C4 hall Description: Strobes have been activated

Alarm No. 157: Node 3: L01M57: Loop: 1 Module: 57

Display: OFF CONTROL RPS 32 WC STROBES CF L01M57

Location: RPS located in the electrical store room on the west wall of C4 hall Description: Strobes have been activated

Alarm No. 158: Node 3: L01M58: Loop: 1 Module: 58

Display: OFF NON ALM MON C-2 INTERFACE NODE 2 K L01M58

Location: Module located at the C1/2 point lobby side in C2 hall ceiling at overhead door

11/18/2025 40

Description: Communications fault

Alarm No. 159: Node 3: L01M59: Loop: 1 Module: 59

Display: OFF NON ALM MON C-1 INTERFACE NODE 2 K L01M59

Location: Module located at the C1/2 point lobby side in C1 hall ceiling at overhead door Description: Communications fault

Alarm No. 160: Node 3: L01M60: Loop: 1 Module: 60

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M60

Location: Module is located behind the information desk in the C-Bldg main entrance south of the C3/4 point Description: Blow Open Doors have been opened

Alarm No. 161: Node 3: L01M61: Loop: 1 Module: 61

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M61

Location: Module is located behind the information desk in the C-Bldg main entrance south of the C3/4 point Description: Blow Open Doors have been opened

Alarm No. 162: Node 3: L01M62: Loop: 1 Module: 62

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M62

Location: Module is located behind the information desk in the C-Bldg main entrance south of the C3/4 point Description: Blow Open Doors have been opened

Alarm No. 163: Node 3: L01M63: Loop: 1 Module: 63

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M63

Location: Module located on the left wall heading north just before Starbucks in the C-Bldg main entrance Description: Blow Open Doors have been opened

Alarm No. 164: Node 3: L01M64: Loop: 1 Module: 64

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M64

11/18/2025 41

Location: Module located on the left wall heading north just before Starbucks in the C-Bldg main entrance Description: Blow Open Doors have been opened

Alarm No. 165: Node 3: L01M65: Loop: 1 Module: 65

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M65

Location: Module located on the left wall heading north just before Starbucks in the C-Bldg main entrance Description: Blow Open Doors have been opened

Alarm No. 166: Node 3: L01M66: Loop: 1 Module: 66

Display: OFF FORM C RELAY WC ADA BLOW OPEN RLY CF L01M66

Location: Module located in the electrical store room on the west wall of C4 hall Description: Blow Open Doors have been opened

11/18/2025 42

11/18/2025 43

Alarm No. 201: Node 3: L02M01: Loop: 2 Module: 1

Display: NORMAL MONITOR POWERHOUSE 32 HEAT L02M01

Location: Heat detector located in power center 32 located on the northwest end of the C1 roof Description: A Heat Detector has gone off in this area.

Alarm No. 202: Node 3: L02M02: Loop: 2 Module: 2

Display: OFF FORM C RELAY WC INTERFACE NODE 2 CF L02M02

Location: Module located in the panel next to the Node 3 panel in the Node 3 room at the northend level 3 C- Bldg Description: Communications fault

Alarm No. 204: Node 3: L02M04: Loop: 2 Module: 4

Display: OFF FORM C RELAY PAHU 4-4 SHUTDOWN CF L02M04

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Unit in Shutdown Mode

Alarm No. 205: Node 3: L02M05: Loop: 2 Module: 5

Display: OFF FORM C RELAY PAHU 4-4 PURGE CF L02M05

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Unit in Purge Mode

Alarm No. 206: Node 3: L02M06: Loop: 2 Module: 6

Display: OFF NON ALM MON PAHU 4-4 OAD OPENED K L02M06

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Outside Air Damper is Opened

Alarm No. 207: Node 3: L02M07: Loop: 2 Module: 7

Display: ON NON ALM MON PAHU 4-4 OAD CLOSED MO K L02M07

Location: Module is located in the air handler on the northwest side of C1 hall roof

11/18/2025 44

Description: Outside Air Damper is Closed

Alarm No. 208: Node 3: L02M08: Loop: 2 Module: 8

Display: ON NON ALM MON PAHU 4-4 RAD OPENED MO K L02M08

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Return Air Damper is Opened

Alarm No. 209: Node 3: L02M09: Loop: 2 Module: 9

Display: OFF NON ALM MON PAHU 4-4 RAD CLOSED K L02M09

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Return Air Damper is Closed

Alarm No. 210: Node 3: L02M10: Loop: 2 Module: 10

Display: OFF NON ALM MON PAHU 4-4 EAD OPENED K L02M10

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Exhaust Air Damper is Opened

Alarm No. 211: Node 3: L02M11: Loop: 2 Module: 11

Display: ON NON ALM MON PAHU 4-4 EAD CLOSED MO K L02M11

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Exhaust Air Damper is Closed

Alarm No. 212: Node 3: L02M12: Loop: 2 Module: 12

Display: OFF NON ALM MON PAHU 4-4 SUPPLY FAN K L02M12

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Fan is active

Alarm No. 213: Node 3: L02M13: Loop: 2 Module: 13

Display: OFF NON ALM MON PAHU 4-4 RETURN FAN K L02M13

11/18/2025 45

Location: Module is located in the air handler on the northwest side of C1 hall roof Description: Fan is active

Alarm No. 214: Node 3: L02M14: Loop: 2 Module: 14

Display: OFF FORM C RELAY PAHU 4-2 SHUTDOWN CF L02M14

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Unit in Shutdown Mode

Alarm No. 215: Node 3: L02M15: Loop: 2 Module: 15

Display: OFF FORM C RELAY PAHU 4-2 PURGE CF L02M15

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Unit in Purge Mode

Alarm No. 216: Node 3: L02M16: Loop: 2 Module: 16

Display: OFF NON ALM MON PAHU 4-2 OAD OPENED K L02M16

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Outside Air Damper is Opened

Alarm No. 217: Node 3: L02M17: Loop: 2 Module: 17

Display: ON NON ALM MON PAHU 4-2 OAD CLOSED MO K L02M17

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Outside Air Damper is Closed

Alarm No. 218: Node 3: L02M18: Loop: 2 Module: 18

Display: ON NON ALM MON PAHU 4-2 RAD OPENED MO K L02M18

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Return Air Damper is Opened

Alarm No. 219: Node 3: L02M19: Loop: 2 Module: 19

Display: OFF NON ALM MON PAHU 4-2 RAD CLOSED K L02M19

11/18/2025 46

Building: C Location: Module is located in the air handler in the center west side of C1 hall roof Description: Return Air Damper is Closed

Alarm No. 220: Node 3: L02M20: Loop: 2 Module: 20

Display: OFF NON ALM MON PAHU 4-2 EAD OPENED K L02M20

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Exhaust Air Damper is Opened

Alarm No. 221: Node 3: L02M21: Loop: 2 Module: 21

Display: ON NON ALM MON PAHU 4-2 EAD CLOSED MO K L02M21

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Exhaust Air Damper is Closed

Alarm No. 222: Node 3: L02M22: Loop: 2 Module: 22

Display: OFF NON ALM MON PAHU 4-2 SUPPLY FAN K L02M22

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Fan is active

Alarm No. 223: Node 3: L02M23: Loop: 2 Module: 23

Display: OFF NON ALM MON PAHU 4-2 RETURN FAN K L02M23

Location: Module is located in the air handler in the center west side of C1 hall roof Description: Fan is active

Alarm No. 224: Node 3: L02M24: Loop: 2 Module: 24

Display: OFF FORM C RELAY PAHU 4-3 SHUTDOWN CF L02M24

Location: Module is located in the air handler in the center east side of C1 hall roof Description: Unit in Shutdown Mode

Alarm No. 225: Node 3: L02M25: Loop: 2 Module: 25

11/18/2025 47

Display: OFF FORM C RELAY PAHU 4-3 PURGE CF L02M25 Building: C Location: Module is located in the air handler in the center east side of C1 hall roof Description: Unit in Purge Mode

Alarm No. 226: Node 3: L02M26: Loop: 2 Module: 26

Display: OFF NON ALM MON PAHU 4-3 OAD OPENED K L02M26

Location:…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .